Documente Academic
Documente Profesional
Documente Cultură
Where fck is the characteristic 28 days cube compressive strength of concrete in N/mm2.
Modulus of elasticity of concrete
The modulus of elasticity of concrete can be assumed as follows:
Actual measured values may differ by +/- 20 percent from the values obtained from the above
expression.
The unit weights of plain concrete and reinforced concrete made with sand and gravel or crushed
natural stone aggregate may be taken as 24 kN/m3 and 25 kN/m3 respectively.
In ordinary buildings, such as low rise dwellings whose lateral dimension do not exceed 45 m,
the effects due to temperature fluctuations and shrinkage and creep can be ignored in &sign
calculations.
STABILITY OF THE STRUCTURE
The stability of a structure as a whole against overturning shall be ensured so that the restoring
moment shall be
Restoring moment ¿ sum of 1.2 times the maximum overturning moment (dead load)
Restoring moment ¿ sum of 1.4 times the maximum overturning moment (imposed loads)
Restoring moment due to imposed loads shall be ignored.
Sliding
Factor against sliding not less than 1.4 times under most under adverse combination of forces.
Variation dead load
Wind and seismic load shall be treat as imposed load.
Lateral Sway
Under transient wind load
Lateral sway < H/500
Where H total height of building
For seismic load reference should be from IS 1893
FIRE RESISTANCE
General requirement of fire protection is given in IS 1641 and IS 1642
Analysis
Effective span
Simply supported beam or slab
Effective span=clear span effective + depth of slab or beam
Effective span = center to center distance of supports whichever is less
Continuous beam or slab
If width of support is < 1/12 of clear span than effective span as per simply supported beam or
slab
NOTES ON IS 456:2000
If width of supports is > 1/12 of clear span or 600 mm than effective span will be
1) End span with one fixed and other continuous or intermediate than
Effective span =clear span between supports
2) for End span one end free and other is continuous than
Effective span =clear span +1/2 the effective depth of beam or slab whichever is less
Effective span =clear span +1/2the width of discontinues supports
3) span with roller or rocket bearing
Effective span =distance between the canters of bearings
Cantilever beam or slab
Effective length = length of face to face distance + ½ effective depth
Arrangement of Imposed load
The load arrangement may be design dead load and design imposed load on all the spans.
For lateral loads, simplified methods may be used to obtain the moments and shears for
structures that are symmetrical. For unsymmetrical or very tall structures, more rigorous methods
should be used.
Where a member is built into a masonry wall which develops only partial restraint, the member
shall be designed to resist a negative moment at the face of the support of WL2/24 where W is
the total design load and L is the effective span, or such other restraining moment as may be
shown to be applicable. For such condition shear coefficient given in Table 13 at the end support
may be increased by 0.05
NOTES ON IS 456:2000
Control deflection
For cantilever
Clear distance between lateral restrains < 25b or 100b2/d whichever is less
.d – effective depth of beam
.b – breath of compression face
Solid Slab
Beam apply to slabs also
For slab spanning in two directions the shorter of the two spans should be used in span to
effective depth ratio.
For two way slab of shorter spans (up to 3.5 m) with mild steel
Simply supported slabs 35
Continuous slab 40
For high strength deformed bars the above values should multiply by 0.80.
Compression member consider short when Lex/D and Ley are less than 12.
Unsupported length
In flat slab clear distance between floor and drop panel or slab whichever is less
Unsupported length should not exceed 60 times least lateral dimension of column
Bars may arrange in singly, pairs in contact, or group 0f 3 or 4 bar bundles in contact.
Bundled bars enclosed in stirrups or ties.
Bar larger than 32mm shall not be bundled except in column.
In Compression
Length of anchorages = development length
Stirrups
Development Length = 8 times the dia of baar when bar bent through an angle of 90o
Development Length = 6 times the dia of baar when bar bent through an angle of 135o
Development Length = 4 times the dia of baar when bar bent through an angle of 180o
NOTES ON IS 456:2000
For curtailment
Reinforcement extended beyond pt not required to resist flexure
Curtailment = effective depth of member or 12 times the dia of bar whichever is greater
Spacing>d/8*βb βb ratio of area of cutoff bar to total area of bar and d effective depth
At least
1/3 positive moment reinforcement in simple member
1/4 positive moment reinforcement in continuous member
To
Ld/3 Ld -development length
At least
1/3 of total reinforcement provided for negative reinforcement shall be extended not <effective
depth of member 12ϕ or 1/16 of clear span whichever is greater
Bars in bundled shall terminate at different points at spaced no less than 40 times the dia of bar
except bundled stopping at support.
Reinforcing Splices
Splices are provided in reinforcing bar and shall be as far as possible from section of maximum
stress.
Splices should not be in flexural member where bending moment is more than moment of
resistance.
Where more than ½ of bars are spliced or where at maximum stress point than special precaution
must be taken such as increasing length of lap, closely spaced stirrups or using spirals.
Lap splices
Lap splices shall not be used for bar larger than 36 mm
NOTES ON IS 456:2000
Bar larger than 36 mm may be welded, in cases where welding is not permissible than lapping is
permitted.
1) If minimum cover of top section < 2 times the dia of bar lapped bar than lap length is
increased by 1.4 times
2) Minimum cover to either face < twice the diameter of lap bar or clear distance between
adjacent bar is less than 75mm or 6 times the dia of bar whichever is greatest.
Spacing of reinforcement
Slabs
Nominal cover for column is 40 mm or less than the diameter of bar used.
In case the minimum dimension of column is less or equal to 200 mm than cover should be 25
mm and size of bar does not exceed 12 mm.
For footing cover shall be 50 mm.
Beams
Tension reinforcement
Minimum reinforcement
As 0.85
=
bd Fy
As Minimum area of tension reinforcement,
Maximum reinforcement
Compression reinforcement
Where the depth of the web in a beam exceeds 750 mm, side face reinforcement shall be
provided along the two faces.
Total area of such reinforcement shall be not less than 0.1 percent of the web area and shall be
distributed equally on two faces at a spacing not exceeding 300 mm or web thickness whichever
is less.
Minimum spacing of shear reinforcement
Asv 0.4
≥
b∗sv .087∗Fy
Slabs
Minimum reinforcement
High strength deformed bar or welded wire fabric not ¿ 0.12 of total cross section area
Maximum diameter
Columns
Longitudinal reinforcement
Minimum cross section of longitudinal reinforcement not less than 0.8 percent of c/s area of
column.
Maximum cross section of longitudinal reinforcement not less than 6 percent of c/s area of
column.
If bars are lapped than 4 percent of c/s area of column.
Pedestal is a compression member, the effective length of which does not exceed three times the least
lateral dimension.
If the longitudinal bars are not spaced more than 75 mm on either side, transverse reinforcement need
only to go round comer and alternate bars for the purpose of providing effective lateral supports.
NOTES ON IS 456:2000
If the longitudinal bars spaced at a distance of not exceeding 48 times the diameter of the tie are
effectively tied in two directions, additional longitudinal bars in between these bars need to be tied in one
direction by open ties
No bar of the inner row is closer to the nearest compression face than three times the diameter of the
largest bar in the inner row.
Where the longitudinal bars in a compression member are grouped than the diameter of such transverse
reinforcement need not, however, exceed 20 mm.
Pitch-The pitch of transverse reinforcement shall be not more than the least of the following distances:
Reinforcement
Positive Reinforcement
The tensile reinforcement required to resist positive bending moment in any span of a deep beam
shall:
NOTES ON IS 456:2000
Negative Reinforcement
Termination of reinforcement - For tensile reinforcement required to resist negative bending
moment over a support of a deep beam:
1 It shall be permissible to terminate not more than half of the reinforcement at a distance of 0.5
D from the face of the support and
2 The remainder shall extend over the full span.
Distribution-When ratio of clear span to overall depth is in the range 1.0 to 2.5, tensile
reinforcement over a support of a deep beam shall be placed in two zones comprising:
1) a zone of depth 0.2 D, adjacent to the tension face, which shall contain a proportion of the
tension steel given by
l
0.5( −0.5)
D
where ,1 = clear span, and D = overall depth.
2) A zone measuring 0.3 D on either side of the mid-depth of the beam, which shall contain the
remainder of the tension steel, evenly distributed. For span to depth ratios less than unity, the
steel shall be evenly distributed over a depth of 0.8 D measured from the tension face.
FLAT SLABS
The term flat slab means a reinforced concrete slab with or without drops, supported generally
without beams, by columns with or without flared column heads .
Drop
The drops when provided shall be rectangular in plan
Drop length in each direction not less than one- third of the panel length in that direction.
For exterior panels, the width of drops at right angles to the non- continuous edge and measured
from the center-line of the columns shall be equal to one-half the width of drop for interior
panels.
Column Heads
Where column heads are provided, that portion of a column head which lies within the largest
right circular cone or pyramid that has a vertex angle of 900 and can be included entirely within
the outlines of the column and the column head, shall be considered for design purposes.
τ
The shear stress v , shall be the value calculated as
NOTES ON IS 456:2000
The nominal shear stress in flat slabs shall be taken as V / b0 d where V is the shear force due to
design load, b0 is the periphery of the critical section and d is the effective depth.
Permissible Shear Stress
When shear reinforcement is not provided the calculated shear stress at the critical section shall
not exceed ks c.τ
where,
ks= (0.5 + βc) but not greater than 1, βc being the ratio of short side to long side of the column/
capital; and
τc= 0.25√ fck in limit state method of design, and 0.16 & in working stress method of design.
When the shear stress at the critical section exceeds the permissible shear stress value, but less
than 1.5 τc , shear reinforcement shall be provided. If the shear stress exceeds 1.5 τc the flat slab
shall be redesigned.
Slab Reinforcement
The spacing of bars in a flat slab, shall not exceed 2 times the slab thickness, except where a slab
is of cellular or ribbed construction.
Area of reinforcement
When drop panels are used, the thickness of drop panel for determination of area of
reinforcement shall be the lesser of the following:
a) Thickness of drop, and
b) Thickness of slab plus one quarter the distance between edge of drop and edge of capital.
WALLS
Effective Height
NOTES ON IS 456:2000
Where Hw = the unsupported height of the wall. L1 = the horizontal distance between centers of
lateral restraint.
The minimum ratio of vertical reinforcement to gross concrete area shall be:
1) 0.001 2 for deformed bars not larger than 16 mm in diameter and with a characteristic strength of 4 15
N/mm* or greater.
Vertical reinforcement shall be spaced not farther apart than three times the wall thickness nor 450 mm.
For walls having thickness more than 200 mm, the vertical and horizontal reinforcement shall be provided in
Cracking
The surface width of the cracks should not, in general, exceed 0.3 mm in members where
cracking is not harmful and does not have any serious adverse effects upon the preservation of
reinforcing steel nor upon the durability of the structures.
In members where cracking in the tensile zone is harmful either because they are exposed to the
effects of the weather or continuously exposed to moisture or in contact soil or ground water, an
upper limit of 0.2 mm is suggested for the maximum width of cracks.
For particularly aggressive environment, such as the ‘severe’ category assessed surface width of
cracks should not in general, exceed 0.1 mm.
Design Values
Materials
The design strength of-the materials, fd is given by
fck
fd = γm
fck - characteristic strength of the material , and
γm -partial safety factor appropriate to the material and the limit state being considered.
Load
The design load, Fd , is given by
Fd =F γf
where F= characteristic load as per IS 875
γf = partial safety factor appropriate to the nature of loading and the limit state being considered.
Partial Safety Factors
NOTES ON IS 456:2000
does not exceed 0.05 times the lateral dimension, the members may be designed by the following
equation:
Minimum ecc = l/500 + lld/30 or 20 mm
Pu = 0.4 fck Ac + 0.67 fy Asc
Pu Axial load on the member,
Fck Characteristic compressive strength of the concrete,
Ac Area of concrete,
Fy Characteristic strength of the compression reinforcement, and
Asc Area of longitudinal reinforcement for columns.
Compression Members with Helical Reinforcement
The ratio of the volume of helical reinforcement to the volume of the core shall not be less than
0.36(Ag/Ac -1)fck/fy
Where
Ag Gross area of the section,
Ac Area of the core of the helically reinforced column measured to the outside diameter
of the helix,
Fck characteristic compressive strength of the concrete, and
Fy Characteristic strength of the helical reinforcement but not exceeding 415 N/mm2.
Vu
τv = bd
Vu - shear force due to design loads
.b - breadth of the member, which for flanged section shall be taken as the breadth of the web
.d - effective depth
Beams of Varying Depth
In the case of beams of varying depth the equation shall be modified as:
NOTES ON IS 456:2000
Mu
Vu+ tan β
τv = d
bd
Mu- bending moment at the section
.β - angle between top and bottom edge of beam.
For solid slabs, the design shear strength for concrete shall be τc*k has the values given below:
0.87 fy Asv d
Vus =
Sv
Where
Asv Total cross-sectional area of stirrup legs or bent-up bars within a distance Sv
Sv .Spacing of the stirrups or bent-up bars along the length of the member,
.τv Nominal shear stress,
NOTES ON IS 456:2000
RESTRAINED SLABS
Maximum bending moment
Mx= α x* w* l2 x
My= α y *w* l2 x
α x and α y are taken from table 26
SIMPLY SUPPORTED SLABS
Mx= α x* w* l2 x
My= α y *w* l2 x
α x and α y are taken from table 27
Xu 0.87∗Fy∗Ast
=
d 0.36 F . ck∗b∗d
Xu Xu .max
If < (Under reinforced)
d d
Ast∗Fy
Mu=0.87*Fy*Ast*d*(1- )
b∗d∗Fck
Xu Xu .max
If =
d d
NOTES ON IS 456:2000
Balance section
Xu .max Xu .max
Mu.lim=0.36* *(1-0.42 )b*d2 *Fck
d d
Xu Xu .max
If > (over reinforced)
d d
Than section should be redesign.
Xu-depth of neutral axis
d- effective depth
Fy- strength of reinforcement
Ast- area of tension reinforcement
Fck compressive strength of concrete
b- width of compression face
Mu.lim- moment of resistance of section without compression reinforcement
Xu.max-limiting value of Xu