MINERVA® Marine

MX / T2000 Panel Range

Features:

Enhances fire detection and eliminates


unwanted alarms using “fuzzy logic”
Assists fire fighting and training by providing
on-screen risk management information
Helps fire crews by giving smoke density and
temperature readings in the affected areas
Simplifies maintainance by pin-pointing faults
Enables remote fault finding to be carried out
Flexible interfacing with graphic management
systems

MINERVA® Marine Panel Range and compensations to be made for changes in


environmental conditions. In short, maximum
MINERVA® MX is a comprehensive range of fire security whilst minimising the risk of false alarms.
controllers designed and built to BSEN ISO9001/2
and EN54. An advanced proven microprocessor Modular in design MINERVA® MX provides
based system, MINERVA® MX provides conventional economical fire detection for small vessels but is also
and digital addressable detection for new, refurbished flexible enough to implement the complex event
and refitted detection systems. procedures required in larger ones. Detectors are
controlled in groups of up to 240 zones all software
A wide range of detectors and ancillaries makes configurable, so avoiding the expensive need to
MINERVA® MX suitable for applications from general hardwire each zone back to the control panel. Further
cargo vessels to large passenger vessels and offshore savings are made possible by harnessing the power of
installation. the latest micro-processing technology to enable a
single loop of two-core cabling to carry both detection
What should you expect of your fire and command signals.
detection system?
In broad terms: cost effective reliability and flexibility. Backwards compatibility is also achieved by using an
In today's vessels under today's conditions you should ancillary module which allows existing fire systems to
also be looking for ease of operation, flexible be updated and extended cost effectively, utilising
programming, precise fire source pin-pointing and the existing wiring where possible and with minimal
kind of circuitry and sensitivity which ensures rapid disruption. Other ancillary modules offer even greater
activation in the event of a fire. system flexibility: short circuit sensing isolation
ensures the MX/T2000 continues in operation, even
MINERVA® MX meets all these if a wiring fault occurs. Local sounder activation
expectations as a matter of course further reduces wiring costs and switch monitoring
MX/T2000 is a comprehensive range of fire allows easy interface to a vessels machinery control
controllers designed and built to BSEN ISO9001/2 by system.
the world’s leading fire and security company. The
MX/T2000 has been approved by all the major Further flexibility and installation savings can be made
marine authorities. using the loop power MX/T2000 options. Loop
powered MX/T2000 panels allow sounders to be
An advanced proven micro-processor based system powered from the same loop wires that carry
MINERVA® MX provides conventional as well as communications and power to the detectors and
addressable detection at the price of today's other ancillaries.
conventional systems. The decision to sound the
alarm is made at the controller allowing adjustments

Fire Detection
PSF126UM.qxd 08/04/2004 09:30 Page 2

MINERVA® MX Key Functions


Thanks to powerful software each zone can be given a tailor-made The displayed temperature and smoke density reading allows the
response text message to help locate the source of a fire. Software operator to quickly visualise the situation and select the appropriate
configuration and reconfiguration can be carried out on site, with procedures to be implemented.
minimum disruption and the avoidance of system down time. Correct
execution of the software is ensured by twin micro-processors that For management information, a printer can also be connected to the
perform watchdog functions on each other. MX/T2000 providing a hard copy of events. MINERVA® MX has the
capacity to store up to 1000 events in its memory. Finally a weekly test
MINERVA® MX sounders can be set for either continuous, pulse, or a reminder facility can be built in, while a walk-test facility allows truly
combination of two tones via the system software. cost-effective systems checking by a single operative.
To aid the rapid location of fire, remote repeater panels or geographical
mimics can be connected to the controllers for greater monitoring
convenience, as can visual display units.

MX / T2000

The MX/T2000 panels are intelligent EN54 . Optional IOB800 input/output expansion
approved and marine approved sub-panels, card mounted on the PSB800
which can be networked to provide up to 396
detection loops and installed to BS5839:Pt.1. The panel has a strong cast aluminium front
door, which incorporates a modular user
. The T2000 sub-panel supports up to four interface that fully complies with EN54:pt.2.
loops supporting up to 1000 addressable The user interface incorporates the ODM800
devices and can be expanded using operator display module with a 16 x 40-
additional loop sub-panels character backlit LCD display, simple
alphanumeric keypad and 5 softkeys. The
The panel consists of a strong stainless steel OCM800 operator control module provides
enclosure incorporating a removable chassis all mandatory operator control keys and LED
plate. The chassis plate holds: functions including Manned/Unmanned
switching. Two control keys and 2 indication
. PSB800 5A 24Vd.c. battery backed power LEDs are provided for vessel-specific
supply and loop booster to EN54:pt.4 functions.
. FIM800 field interface PCB incorporating
two MX DIGITAL loops Control keys and LEDs are labelled in English
. CPU800 32 bit processor and memory according to the default approved
card functionality. The slide in decals can be
. Optional network card, additional loop reversed and alternative text added.
card(s) and remote diagnostic modem

MINERVA® MX T2000 Repeaters

The MINERVA® MX full function repeater is an The back box has a removable chassis plate
EN54 Marine approved repeater with optional with the PSM800 power supply, APM800
addressable EN54:Pt.4 power supply. The addressable PSU monitor module and space
repeater consists of a stainless steel backbox for 2 x 7 Ah batteries to provide 72 h backup.
and cast aluminium front door which The MINERVA® MX repeater with Power
incorporates the ODM800 operator display Supply is connected to the Panel via the
module with a 16 x 40-character backlit LCD remote bus (RS485, 1200 m distance). A
display, simple alphanumeric keypad and 5 maximum of 7 repeaters (including one MX
softkeys. The OCM800 operator control REMOTE repeater) can be linked to each
module provides all mandatory operator MINERVA® MX panel and can provide full
control keys and LED functions including repeater functions for all panels on the system.
Manned/Unmanned switching. Two control The operator control module (OCM800) can
keys and 2 indication LEDs are provided for support up to 80 inputs and outputs in the
vessel-specific functions. form of LED annunciators, IOB800
input/output modules, XIOM universal I/O
Control keys and LEDs are labelled in English modules or the XIOM 800 LED mimic
according to the default approved module.
functionality. The slide in decals can be
reversed and alternative text added.
PSF126UM.qxd 08/04/2004 09:30 Page 3

Interfacing Options

MX Remote
PC
OEM
Interface

Modem

Modem

Max distance between Max distance between


nodes is 1000m using nodes is 3000m using
MICC cable twisted/sheilded pair cable
MX CCU
TLI800

Network
Interface
MX Graph
To PLC
TLO530 TLO530
Fibre Fibre
Interface Interface
Max distance between
nodes is 4000m using
fibre optic cable

Up to 99 MX/T2000 sub-panels can be linked together provid- Graphical Management Systems


ing unrivalled design flexibility. Provides intuitive user friendly graphics for easier incident man-
agement on large passenger vessels.
Interfacing to PLCs
An industrial standard protocol is available to allow the Peer-to-Peer Interface to 3rd Party Systems
MX/T2000 to communicate with PLCs. This is especially useful Unique protocol to allow development of peer-to-peer interface.
in offshore type installations.

Remote Diagnostics
Reduces the cost of service and fault finding by using a trained
engineer in an office to remotely identify faults and solutions via
our unique MX Remote.
PSF126UM.qxd 08/04/2004 09:30 Page 4

Technical Specifications Detector Base Command Modules


Mechanical 801IB Isolator Base
Dimensions (WxHxD): Controller 440 x 320 x 135mm 801RB Relay Base
Colour: Dawn Grey (Housing) Pantone - 431C 802SB Loop Powered Sounder Base
Modules) 5B 5” Universal Base
Installation: Surface or Semi-flush Mounted
Command Modules
Environmental SNM800 Sounder Module
Operating Temp. Range:_ 8°C to + 55°C RIM800 Relay Module
Storage Temp. Range: _ 20°C to + 70°C CIM800 Contact Monitor Module
Humidity: Up to 95% RH (Non-condensing) SB520 Sounder Booster Module
Housing Protection To: IP42 TM520 Timer Module
DIM800 Conventional Detector Module
Electrical APM800 Power Supply Monitor Module
Mains Supply: 120V-240Vac + 10% / -15% at MIM800 Mini Input Module
50/60Hz
CP820M Indoor Callpoint
Secondary Supply: 24V d.c. Nominal
CP830M Outdoor Callpoint

Input
T2000 Sub-Panel
No. of Loops: 4
Addresses per Loop: 250 Max

Output
T2000 Sub-Panel
Display: 240 Zone
16 x 40 Character
Sounder: There are two separate monitored
sounder outputs each rated at 2A.
Alarm: Fire _ Relay output rated at 30V d.c.
at 1.0A volt free c/o.
Fault _ Relay output rated at 30V d.c.
at 1.0A volt free c/o.

The right is reserved to modify or withdraw any product


or service without notice

Technical Information Sheet PSF126UM Issue 1

www.tycosafetyproducts-europe.com
©Tyco Safety Products 2003
PSF128UM.qxd 08/04/2004 09:25 Page 1

MINERVA® Marine

MX Virtual Multi-Sensor Detectors

Features:

Over 20 fire detection modes


Tyco MX FASTLOGIC Expert algorithms
MX HPO detection Algorithms
Up to 250 detectors per loop
Remote detector verification & temperature
read out
Programmable alarm LED with 360o viewing
angle
Optional detector locking pin
Variety of sounder and relay detector bases
Address flag stays with the base
Approved by all major classification societies
for use on vessels
Lower cost system design and installation as
one detection type can be used throughout
the vessel
Lower cost of ownership as no radioactive
source disposal costs together with less
spares holding
MX Virtual Multi-Sensor Detectors
Enhanced safety in accomodation areas by
using the unique Carbon Monoxide (CO)
detectors The 800 Series are addressable multi-sensor fire,
Major cable saving options using loop pow- smoke and heat detectors, which can be
ered ancillaries implemented as several MX VIRTUAL detectors by the
Allows easier decision making by operator MX detection panel. The 800 Series are designed
because of remote temperature and smoke and approved to EN54. The 800 Series of MX
density read-out VIRTUAL detectors provide the latest fire detection
technology in an attractive cost effective package.

Fire Detection
PSF128UM.qxd 08/04/2004 09:25 Page 2

General Detection Modes


The 800 Series detectors are supplied in an extremely robust and All 800 Series detectors communicate to the MX detection panel
reliable fully sealed construction, which has undergone stringent using the fast reliable MX DIGITAL loop protocol. This allows each
environmental type testing. All electrical contacts are moulded into the detector to operate in one or two of several detection modes, thus
plastic to eliminate any movement. allowing it to be easily optimised to the risk.
To meet detection applications with multiple risks the 811PH and
The detectors are constructed from hardwearing Fire Resistant FR110 811CH detectors allow two detection modes to operate
Bayblend. The multi-sensor detectors are environmentally friendly. simultaneously.
They use no radioactive parts and can be returned to the factory for
recycling at the end of their life. Virtual Detectors
All 800 Series detectors are supplied with integral dust covers as part
of the packaging. Dust covers are retained throughout installation and The use of virtual detection means that installations can change the
removed at commissioning time. detection mode without any physical change, taking place. Not only
can the detection be changed at the time of installation and
commissioning but also during the life of the vessel as vessel usage
Installation & Service Features changes.
Some MX detection panels even allow the detection mode to be
The 800 Series MX VIRTUAL detectors include a host of installation changed at different times of the day or automatically as occupancy
and service features which are provided to reduce installation and and activity in the space changes.
service costs and reduce repair times. As well as providing great flexibility, using only two detector models
means whole life costs are reduced by reducing manufacturing,
. Standard bases with multiple mounting options speed and simplify stocking and service stocks. This also reduces the number of times
installation detectors have to be changed during the life of the installation.
. Unique ‘park’ position for commissioning and service procedures
. Detector Addressing programmed from the MX SERVICE Tool or
MX Panel
. Address flag – fixed to the base to prevent mix ups during service
. Compatible with Tyco 600 and 900 Series bases – for easy
upgrade
. Panel Auto-Config and Self learn functions – supported by the
detectors
. Full range of remote installation and service tools
. Dirty Detector Read-out can be viewed on the MX SERVICE tool or
panel

811PH Multi-Sensor Smoke and Heat Detectors


The 811PH is a state-of-the-art smoke and Technical Specification
heat detector which allows a full set of Dimensions: 109dia x 43H mm
detection modes to be implemented in the Operating Temp: -20o to +70oC
MX detection panel to suit most smoke and
heat detection applications. Storage Temp: -40o to +80oC
The 811PH incorporates a unique Relative Humidity: 95% (non
“mousehole” design optical chamber with an condensing)
unrivalled signal to noise ratio providing high Standards: EN54 pt 5
resilience to dust and dirt which means
reduced service costs. In addition a unique EN54 pt 7
chamber cover actually draws slow moving
smoke into the chamber to provide a more
responsive detector.
The 811PH provides all the features of MX
VIRTUAL detectors including self verification,
temperature and smoke level indication and
unrivalled service functions.
811CH Multi-Sensor Carbon Monoxide and Heat Detectors
The 811CH is a state-of-the-art carbon The 811CH incorporates a reliable electro-
monoxide and heat detector which allows a chemical CO detection cell and high
full set of detection modes to be implemented specification low thermal mass thermistor for
in the MX detection panel to suit most fire and accurate temperature detection. The 811CH
heat detection applications. The 811CH is provides all the features of MX VIRTUAL
particularly well suited to accomodation areas, detectors including self verification,
storage areas and applications where smoke temperature and CO level indication and
detector positioning is difficult or where unrivalled service functions.
smoke detectors are prone to false alarm. The
integration of heat detection into the 811CH Technical Specification
allows the detector to operate in a wide
variety of applications where combined risks Dimensions: 109dia x 43H mm
mean that CO detection alone would be Operating Temp: 0o to +55oC
insufficient. Storage Temp: -20o to +55oC
Relative Humidity: 95% (non
condensing)
Standards: EN54 pt 5
EN54 pt 7
PSF128UM.qxd 08/04/2004 09:25 Page 3

811H Heat Detectors


The 811H is a flexible cost-effective Technical Specification
addressable heat detector with all the features Dimensions: 109dia x 43H mm
of MX VIRTUAL detectors. The 811H returns Operating temp: -25 to +70oC
the temperature to the MX detection panel Storage temp: -40 to +80oC
which allows various detection modes to be Standards: EN54:pt.5
implemented. The 811H uses a high quality
thermistor with very low thermal mass. This
allows the detectors to provide fast accurate
temperature detection as well as heat
detection.

5B 5” Universal Base
This is the most common base designed to fix Features
directly to the accomodation ceiling panel or . Variety of Fixing Options
deckhead mountings. This base allows a . Remote LED Connections
detector to be plugged in directly or a . Anti-Tamper Facility
functional base to be plugged in between the . Park position and address flag holder
base and detector. . Integral breakout locking key

801RB Functional Relay Base


The 801RB provides dual relay contacts for Features
signalling external devices on MX addressable . Dual pole 24V DC relay contacts (60VA)
systems. A very low operating current even . Status indication LED
when the relay is energised enables the relay . Very low power consumption (<20µA
base to be used without any additional power. except startup)
The dual contacts are under the control of a
programmable output, through the powerful
cause and effect software.
PSF128UM.qxd 08/04/2004 09:25 Page 4

MKII Sounder Base


A new low current range of sounder bases for • Do not require use of a standard base
use with the MX Fire Alarm Control Panel. (maybe installed directly onto a standard
Features deckhead mouting)
• Fully programmable
• Manufactured to EN54 part 3
• Integral sounder and detector base
• Volume and tone adjustable after installa-
tion
• Low Power Synchronisation
801RIL Remote Indication LED
All detector bases have the ability to drive a Features
remote LED in the event that the installed . UK Single gang mounting
position of the detector is not easily visible. . High intensity red LED
The 801RIL is compatible with all 800 Series
detectors.

800HL Indication Lamp


The 800HL remote indicator lamp provides a
larger indicator for use in place of the RIL
when longer distances are involved. Typically
used to indicate the source of an alarm in
vessels with long alleyways eg. passenger
vessels.

The right is reserved to modify or withdraw any product


or service without notice

Technical Information Sheet PSF128UM Issue 1

www.tycosafetyproducts-europe.com
©Tyco Safety Products 2003
PSF129UM.qxd 08/04/2004 09:33 Page 1

MINERVA® Marine

System 800 Fire Detection - Hazardous Areas

Features:

ATEX certified intrinsically safe Ex II1G


Higher reliability through the use of galvanic
barriers
Lower cost system design and installation as
one type of detector can be used throughout,
coupled with a full range of devices
Enhanced safety in Accommodation areas
Provides the designer with greater flexibility in
protecting hazardous areas

System 800 Fire Detection Hazardous


Areas

There is a risk of fire or explosion in all areas


containing flammable substances in the form of
liquids, gases, dust or materials. Where these
combustible materials are mixed with air in sufficient
concentration they form flammable atmospheres and
the areas containing them are designated Hazardous
Areas. When a source of ignition, such as a spark is
applied in a hazardous area, an explosion could take
place.

Electrical equipment supplied for use in Hazardous


Areas must comply with requirements to ensure that
its introduction into the area does not increase the
existing risk. We have designed Intrinsically Safe (I.S.)
systems and equipment for use in Hazardous Areas
which can be connected to Fire Detection Systems
installed in Safe Areas.

Fire Detection
PSF129UM.qxd 08/04/2004 09:33 Page 2

801PHEx Smoke & Heat Detector


The 801PHEx Intrinsically Safe Optical Smoke & Heat Detector forms part of the 800Ex
Intrinsically Safe Series of MX Addressable Fire Detectors. The detector plugs into an MUBEx
base.
The detector is designed to transmit to a remote MINERVA® MX / T2000 fire controller, digital
signals which represent the status of the optical smoke and heat elements of the detector.
Software within the controller is used to interpret the returned optical and heat values to raise an
alarm or other appropriate responses according to the type of detector configured in ‘MX
CONSYS’.
The mode of detector may be:
Optical smoke only detector (sensitivity High, Normal or Low)
HPO smoke detector (sensitivity High, Normal or Low)
Heat only rate-of-rise (A1R) detector (no sensitivity selection)
Heat fixed temperature 60oC (A2S) (no sensitivity selection)
Optical (sensitivity High, Normal or Low) combined with heat fixed temperature 60oC (A2S)
HPO (sensitivity High, Normal or Low) combined with heat fixed temperature 60oC (A2S)
These detectors are designed to comply with EN 50 014 and EN 50 020 for intrinsically safe
apparatus. They are certified:

ATEX Code: Ex II 1G
Cenelec Code: EEx ia IIC T5

801CHEx CO & Heat Detector


The 801CHEx Intrinsically Safe Carbon Monoxide plus Heat Detector forms part of the 800Ex
Intrinsically Safe Series of MX Addressable Fire Detectors. The detector plugs into an MUBEx
base.
The detector is designed to transmit to a remote MINERVA® MX / T2000 fire controller, digital
signals which represent the status of the carbon monoxide and heat elements of the detector.
Software within the controller is used to interpret the returned Carbon Monoxide and heat values
to raise an alarm or other appropriate responses according to the type of detector configured in
‘MX CONSYS’.
The mode of detector may be:
Heat only detector (A1R or A2S) (sensitivity: High, Normal or Low)
Compensated Carbon Monoxide detector (sensitivity: High, Normal or Low)
Compensated Carbon Monoxide detector (sensitivity: High or Normal ) combined with heat
(A1R)
These detectors are designed to comply with EN 50 014 and EN 50 020 for intrinsically safe
apparatus. They are certified:

ATEX Code: Ex II 1G
Cenelec Code: EEx ia IIC T5

801HEx Heat Detector


The 801HEx Intrinsically Safe Heat Detector forms part of the 800Ex Intrinsically Safe Series of
MX Addressable Fire Detectors. The detector plugs into an MUBEx base.
The detector is designed to transmit to a remote MINERVA® MX / T2000 fire controller, digital
signals which represent the status of the heat element of the detector.
Software within the controller is used to interpret the returned heat values to raise an alarm or
other appropriate response according to the type of detector configured in ‘MX CONSYS’.
The mode of detector may be:
EN54-5 A1R, rate-of-rise normal ambient
EN54-5 A2S, fixed 60oC
EN54-5 CR, rate-of-rise high ambient
These detectors are designed to comply with EN 50 014 and EN 50 020 for intrinsically safe
apparatus. They are certified:

ATEX Code: Ex II 1G
Cenelec Code: EEx ia IIC T5
PSF129UM.qxd 08/04/2004 09:33 Page 3

IS28 Banshee Sounder

The IS28 intrinsically safe banshee sounder has been developed for use in hazardous areas.
Up to a maximum of four sounders may be used. Each IS28 banshee has an output of 94dBA at one metre,
this sound output will reduce to approximately 90dBA when four sounders are fitted to a circuit.

Certification No. Classification


ITS03ATEX21311X EEx ia 11C T5

CP 840Ex Break Glass Callpoint

The CP840Ex Intrinsically Safe Weatherproof Break Glass Callpoint is designed to monitor and signal the
condition of the switch contact associated with the break glass.
The callpoint is designed to comply with EN 50 014 and EN 50 020 for intrinsically safe apparatus. It is
certified:

ATEX Code: Ex II 1 G
Cenelec Code: EEx ia IIC T5

IF800Ex Interface Module

The Intrinsically Safe IF800Ex Interface Module is designed to monitor fire contacts such as extinguishing
system controls, ventilation controls, fire door controls etc.
The IF800Ex is contained within a grey compression moulded glass filled polyester box with 3 x 20 mm cable
gland holes. The electronic components are mounted on a double sided printed circuit board built into a
potted module formed from a plastic moulding. Connectivity is via two terminal blocks fitted to the PCB.
The interface module is designed to comply with EN 50 014 and EN 50 020 for intrinsically safe apparatus. It
is certified:

ATEX Code: Ex II 1 G
Cenelec Code: EEx ia IIC T5

EXI800 Interface Module & Galvanic Isolator

The EXI800 Interface Module, used with a galvanic isolator, provides a path for an MX Panel to transparently
communicate to slave devices (800Ex Detectors, IF800Ex Interface Module or CP840Ex Addressable Break
Glass Callpoint) connected to the Intrinsically Safe loop. The interface reduces the standard MX loop supply
voltage and signalling currents to levels that are acceptable for hazardous areas.
The EXI800 can detect a short circuit on the left-loop, the right-loop, or the IS loop and will isolate the
offending loop connections from the other loop connections.
The IS loop output of the EXI800 interfaces with the Pepperl+Fuchs KFD0-CS-Ex1.54 Galvanic Isolator,
supplying loop voltage and signalling currents to the Intrinsically Safe loop.

I.S. Barrier Enclosures

A range of polycarbonate enclosures to suit the sounder driver, EXI800 and the Galvanic Isolator. The
enclosures provide see-through lids and can accommodate barriers in the safe area.

The enclosures are impact resistant, flame retardant and dustproof to IP65.
PSF129UM.qxd 08/04/2004 09:33 Page 4

Technical Information

To preclude the risk of an explosion, equipment in the Hazardous Area Area equipment and the source of power in the Safe Area. The
must not be capable of causing ignition under normal operating, or electrical power which may be supplied or drawn from a Safe Area (i.e.
specific fault conditions. Limiting the energy which can be stored in, an area with no definable hazard) is limited by using Galvanic Isolators
and released by the electronic circuitry and cables in the Hazardous or Isolating I.S. Interface Units.
Area is achieved by using Intrinsically Safe equipment and by placing
restrictions on the cable parameters. The main advantage of intrinsic safety over other methods of
protection is the fact that the majority of maintenance operations can
Intrinsic safety is a technique for ensuring that the electrical energy and be carried out whilst the system is live.
temperature rise occurring during normal operation and during all
probable fault conditions are not able to cause ignition. Intrinsically Safe Systems
System 800 ATEX Certificate: BAS01ATEX1394X
Intrinsic safety relies on limiting the voltage and current in the circuit so
that if a fault occurs the power available in the circuit is insufficient to
The System 800 ATEX system certificate allows the M800 Ex MX
cause ignition.
Digital addressable fire sensors to be fitted into category 'ia' for gas
To complete the explosion protection concept of a circuit a Safety
group IIC in Zone 0, Zone 1 and Zone 2 hazardous areas.
Barrier must be connected between the Hazardous
Hazardous Area

Safe Area
Wiring
Wiring

Detectors

Sounder

T2000

Callpoint
Barrier Enclosure

The right is reserved to modify or withdraw any product


or service without notice

Technical Information Sheet PSF129UM Issue 1

www.tycosafetyproducts-europe.com
©Tyco Safety Products 2003
PSF133UM.qxd 13/04/2004 14:13 Page 1

MINERVA® MX Marine
811F & 811FEx MXTechnology® Addressable Solar Blind
InfraRed Flame Detectors

Features:

Unlike UV and UV/IR detection, not blinded


by oil mist in machinery spaces
Reduces cabling, no interface required
No additional power source required
Easy installation, uses a common plug in
base for smoke and heat detectors
Can be used on all vessels as fully marine
approved

Standard or Intrinsically Safe


ATEX approved Ordering Information:

The 811F and 811FEx point type flame detectors are Stockcode Description
part of the MXTechnology® range of digital 516.800.007 811F MX IR Flame Detector
addressable fire detectors. MXTechnology® 516.800.067 811FEx MX IR Flame
incorporates heat, optical and carbon monoxide Detector Intrinsically Safe
detection. The 811F and 811FEx flame detectors 517.050.017 5B 5" Universal Base
present a cost effective solution to providing false 516.800.903 801IB Isolator Base
alarm free flame detection for enclosed applications. 517.050.610 MUBEx Base for
600/800Ex
Both the 811F and the 811FEx are full featured solar 514.001.063 EXI800 MX I.S. Loop
blind flame detectors for enclosed use and boast a Interface
high degree of false alarm immunity. The standard 517.001.259 Pepperl & Fuchs KFD0-CS-
unit is the 811F and it is designed for direct Ex1.54 Galvanic Isolator
connection to the MX digital loop, employing the 517.001.247 DX170 MTL5/7000
same detector base or functional base as other 800 Enclosure
series fire detectors. 592.001.012 T110 IR Test Source
592.001.018 T110 Test Source Adapter
The 811FEx is an intrinsically safe version intended
for use in hazardous atmospheres and must be
connected via an EXI800 interface and galvanic
isolator. The detectors are designed to comply with
EN 50 014 and EN50 020 for intrinsically safe
apparatus. They are certified: ATEX code: II 1 G
Cenelec code: EEx ia IIC T4.

Fire Detection
PSF133UM.qxd 13/04/2004 14:13 Page 2

Mechanical Environmental
Detector Material: FR110 ‘BAYBLEND’ Operating temperature: -20oC to +70oC
Dimensions (mm): 108 x 21.2
Weight: - 811F 74g Operation below 0oC is not recommended unless steps are taken to
- 811FEx 108g eliminate condensation and hence ice formation on the detector.

Electrical Storage Temperature: -40oC to +80oC


Loop Voltage: 20 – 40 V Relative Humidity: 90% RH continuous (non-
Quiescent current: 300 micro Amp condensing) and up to 99% RH
Alarm current: 3 mA typical intermittent (non-condensing)

Performance
Intrinsic Safety Rating Range: 0.1m2 n-heptane at 20m
Maximum Voltage for Safety (Ui) 28V 0.4m2 n-heptane at 50m
Maximum Current for Safety (Ii) 93mA Field of View: 100o
Maximum Power Input (Pi) 650mW
Mounting Bases
Equivalent Inductance (Li) 0
5B: 5” Universal Base
Equivalent Capacitance (Ci) 0
MUBEx: I.S. Universal base

Hazardous Area Functional bases that provide relays, sounders and isolation can be
ATEX code: ATEX 0422X II 1 G EEx ia IIC T4 used with the 811F but cannot form part of an intrinsically safe
circuit.

Connections: L -VE IN/OUT


L1 +VE IN/OUT
801F Only R Remore LED -VE

50o 50o
Note 1: When the risk is a hot
0.05m2
4m vibrating body the detector should
be mounted securely using a
9.5m
suitably fabricated bracket at an
8m angle or on a vertical surface to
0.1m2
view the risk.
19m
12m
0.2m2
Note 2: Diagram not to scale

28.5m
16m
0.4m2

38m
Approx Flame Area

MX Technology® is a registered trademark of a subsidiary of Tyco International Ltd.

The right is reserved to modify or withdraw any product


or service without notice

Technical Information Sheet PSF133UM Issue 1

www.tycosafetyproducts-europe.com
©Tyco Safety Products 2003
PSF127UM.qxd 08/04/2004 10:24 Page 1

MINERVA® Marine

800 Series Ancillary Equipment

Features:

Dramatically reduces cabling costs by using


these modules
For passenger ships incorporates loop
powered sounders
Reduced cabling costs for ventilation shut
down, fire door, fire damper monitoring and
control and sprinkler monitoring
Higher systems integrity through continuous
monitoring

800 Series Ancillary Equipment

An extensive range of ancillary modules has been


specifically designed for use with the MX/T2000
range of Fire Controllers.
The 800 range of ancillary modules provide the MX
Fire Controller with a wide degree of systems applica-
tion flexibility. This allows the field addressable loop
from the control panel to both receive inputs to the
system and control outputs from it.

This broad range of modules allows the scope of the


fire detection system to be significantly extended
beyond a simple fire detector alarm sounder based
alarm system.

Fire Detection
PSF127UM.qxd 08/04/2004 10:24 Page 2

The command modules enable fire doors to be closed, fire dampers to be controlled, plus provide an interface to shut down HVAC and other plant
control equipment. With the high systems integrity offered on the MX Controller the command modules can also be used to control a public
address based evacuation system.

CIM800 Contact Input Module


The CIM800 is a flexible addressable input-monitoring device that fits in the standard ancillary
housings.

The CIM800 provides a single input to current MX panels though this can be implemented as
two separately wired spurs (Style B) or as a loop (Style A). Both spur and loop input wiring can
be configured to monitor normally open or normally closed inputs. In addition both can be
configured to initiate an alarm or short circuit fault message in the event of a short circuit on
normally open monitoring circuits.

DIM800 Detector Input Module


The DIM800 is designed to power and monitor a circuit of low voltage conventional detectors
and callpoints. The detection circuit is powered from an external 24V d.c. supply and is reset by
the MX addressable panel. The DIM800 monitors the external 24V d.c. and provides a fault
signal if it is lost. The input detection circuit can be wired as one or two spur circuits (Class B),
one loop configured circuit (Class A) or one 4 wire detection circuit.

The DIM800 is designed to be compatible with most conventional detection products.


Compatibility has been tested to date on the following products:
Compatible Thorn detectors:
M300 Series , M600 Series , S100 Series, H Series, S231F, S231F+, CP200

RIM800 Relay Interface Module


The RIM800 provides a single programmable relay output from the MX DIGITAL addressable
loop which can be programmed for a variety of applications including signalling fire conditions
to plant, machinery, fire doors, dampers & security systems.

The RIM800 relay coil is monitored. The RIM800 relay contact is rated for 2A @ 24V d.c. but
can be used to switch mains voltage when used with the HVR800.

MIO800 Multi Input Output Module


The MIO800 is a general purpose interface module for use with MX TechnologyTM fire detection
systems. It allows multiple input and output connections to be made between external
equipment and the MX Digital loop. Three inputs and four outputs are provided. Each input and
output can be programmed independantly using the MX Consys configuration tool to provide
customised functionality.

An IP55 rated D800 style housing is used as the standard enclosure with the option of a DIN-
Rail mounting kit for in-cabinet installations.
PSF127UM.qxd 08/04/2004 10:25 Page 3

SNM800 Sounder Notification Module


The SNM800 is a remote addressable sounder circuit output device capable of switching
sounder and speaker circuits up to 2A @ 24V d.c. or provide a monitored output facility for other
applications. These can be used in addition to the two sounder circuits provided as standard on
most MX detection panels.
The SNM800 can support sounder circuits wired as a spur (Class B – Style Y) or in a loop
configuration (Class A – Style Z).
The SNM800 can be configured with a RIM800 to provide a secure monitored extinguishing
release solenoid control.

TM520 Timer Module


The TM520 provides an output that can be activated based on a delay time. If either the key-
switch on the module is activated, or a predefined event within the control panel occurs then a
timed delay (set between 10 minutes and 2 hours 10 minutes) is started. When the delay
reaches zero the TM520 output is activated. The unit sounds an internal buzzer and shows a
red LED when the output is active, and shows a yellow LED when the timer is counting down.
To provide a warning that the delay is nearly over, the red LED and the buzzer will pulse 5
minutes before the end of the delay .
The TM520 requires a separate 24V DC supply to operate. The module is not addressable and
will therefore not take an address on the loop.

APM800 Addressable Power Supply Monitor Module


The APM800 is an MX addressable power supply monitoring module which is usually used
with the PSM800 power supply module to make an addressable power supply. The APM800 is
designed to fix to studs on the top of the PSM800.
The APM800 monitors the PSM800 for mains failure, earth fault, battery charger fault and
battery fault. It can reset the PSM800 resettable 24Vd.c. output and initiate a battery test which
then reports battery voltage and current to the controller.

SB520 Sounder Boost Module


The SB520 enables the SNM800 to drive sounder circuits with higher currents whilst
maintaining the reverse polarity integrity line monitoring.

MIM800 Mini-Input Module


The MIM800 is a small MX addressable module designed for monitoring a single input circuit.
The MIM800 can monitor normally open or normally closed inputs and provides open and short
circuit monitoring of the line.

The MIM800 is designed for fitting in small devices such as flow switches, special detection
devices and explosion proof callpoints. A variant of the MIM800 is used in all callpoints and
pullstations.
PSF127UM.qxd 08/04/2004 10:25 Page 4

HVR800 High Voltage Relay

The HVR800 is a non-addressable device which allows a low current mains rated relay
to switch up to 10A. Alternatively a low voltage drive signal such as that provided by the
RIM800 or 80 way mimic can be used to switch the integral mains relay.

CP820M Indoor Callpoint

The CP820M is an indoor MX addressable manual callpoint with programmable status


LED. The CP820M is designed for LPCB approvals . The CP820M provides high speed
communication to the MX panel of a manual fire alarm.

CP830M Outdoor Callpoint

The CP830M is an outdoor MX addressable manual callpoint with programmable status


LED. The CP830M is designed for LPCB approvals . The CP830M provides high speed
communication to the MX panel of a manual fire alarm.
PSF127UM.qxd 08/04/2004 10:25 Page 5

MX Ancillary Module Housings

Double Gang Mounting Cover

The double gang mounting cover allows any of the 800 module
range to be mounted individually onto a standard electrical double
gang backbox.

The mounting cover allows either surface or flush mounting.

Ancillary Housing 8

The Ancillary Housing 8 can incorporate:

- 8 x standard 800 Ancillary modules

Additionally a stacking kit is available that doubles the number of


modules that can be accommodated within the Ancillary 8 housing.

Ancillary Housing 3

The Ancillary Housing 3 is a low cost polycarbonate housing that can


incorporate:

- 3 x standard 800 Ancillary modules

D800 Ancillary Housing

The D800 Ancillary Housing is a surface mount IP55 polycarbonate


housing which will accomodate any one of the 800 module range
except for the APM800/MIM800/TM520.
PSF127UM.qxd 08/04/2004 10:25 Page 6

MX Ancillary Module Technical Look-Up Table

Module No. Of No. Of Output No Of Powered Operating Operating Dimensions


Inputs Outputs Rating Addresses From Temperature Humidity (mm)
Used

CIM800 2 N/A - 1 Loop -25ºC to +70ºC <95% RH 60 x 84 x 14


DIM800 2 N/A - 1 24V dc -25ºC to +70ºC <95% RH 60 x 84 x 14
PSU
RIM800 N/A 1 24Vdc 2A 1 Loop -25ºC to +70ºC <95% RH 60 x 84 x 14
SB520 N/A 1 15A for - 24V dc -25ºC to +70ºC <95% RH 60 x 84 x 14
sounders PSU
SNM800 N/A 1 2A for 1 24V dc -25ºC to +70ºC <95% RH 60 x 84 x 14
sounders PSU
TM520 1 1 24Vdc 1A - 24V dc -20ºC to +70ºC <95% RH 87 x 148 x 14
PSU
APM800 N/A N/A N/A 1 PSM800 -25ºC to +70ºC <95% RH 57 x 127 x 25
MIM800 1 1 4.5mA 1 Loop -25ºC to +70ºC <95% RH 13 x 48 x 57
10A at 24Vdc/
HVR800 1 1 24Vdc/ - 24Vac/ -25ºC to +70ºC <95% RH 26.5 x 73.6 x 41.5
240Vac 120Vac/
240Vac
CP820M N/A N/A N/A 1 Loop -25ºC to +70ºC <95% RH 87 x 87 x 19
CP830M N/A N/A N/A 1 Loop -25ºC to +70ºC <95% RH 135 x 135 x 30
MIO800 3 4 24Vdc 1 Loop -25ºC to +70ºC <95% RH 72 x 110 x 18
2A