3D Disconnectors and Earthing Switches Equipment Selection

Selection of earthing switches for general switchgear construction

12 kV Position: 1 2 3 4 5 6 7 – 8 9 Order codes

50/60 Hz Order No.: 3 D n n n n n – n n – « n n n


Rated lightning impulse

Rated short-duration

Pole-centre distance
withstand voltage
withstand voltage

withstand current

withstand current
power-frequency

Number of poles
Rated short-time
Rated voltage

See page 23
Rated peak
Ur Up Ud Ith Idyn

kV kV kV kA kA mm
12 75 28 20 50 3 210 3 D E 1 0 1 2 – 0 J
31.5 80 3 210 3 D E 1 0 1 2 – 0 N
50 125 3 210 3 D E 1 0 1 2 – 0 S
63 160 3 210 3 D E 1 0 1 2 – 0 U

24 kV
50/60 Hz
2
Ur Up Ud Ith Idyn

kV kV kV kA kA mm
24 125 50 20 50 1 – 3 D D 1 0 1 4 – 0 J
3 275 3 D E 1 0 1 4 – 0 J
31.5 80 1 – 3 D D 1 0 1 4 – 0 N
3 275 3 D E 1 0 1 4 – 0 N

36 kV
50/60 Hz
Ur Up Ud Ith Idyn

kV kV kV kA kA mm
36 170 70 20 50 3 400 3 D E 1 0 1 6 – 0 J
31.5 80 3 400 3 D E 1 0 1 6 – 0 N

Configuration example
Earthing switch, 1-pole 3 D D
Rated voltage Ur = 24 kV
Rated short-time withstand current Ith = 31.5 kA 1 0 1 4 – 0 N

Example for Order No.: 3 D D 1 0 1 4 – 0 N


Order codes:

Siemens HG 11.31 · 2008 21