C - DIFFERENTIAL
For feeders, Bus-bars, Transformers, Generators etc
1. High Impedance
2. Low Impedance
3. Restricted E/F
4. Biased
5. Pilot Wire
D - Distance
For transmission and sub-transmission lines and distribution feeders, also used
as back-up protection for transformers and generators without signaling with
signaling to provide unit protection e.g.:
1. Time-stepped distance protection
2. Permissive underreach protection (PUP)
3. Permissive overreach protection (POP)
4. Unblocking overreach protection (UOP)
5. Blocking overreach protection (BOP)
6. Power swing blocking
7. Phase comparison for transmission lines
8. Directional comparison for transmission lines
E - Miscellaneous:
1. Under and over voltage
2. Under and over frequency
3. A special relay for generators, transformers, motors etc.
4. Control relays: auto-reclose, tap change control, etc.
5. tripping and auxiliary relays
Speed
Fast operation: minimizes damage and danger
Very fast operation: minimizes system instability discrimination and security
can be costly to achieve.
Examples:
1. differential protection
2. differential protection with digital signaling
3. distance protection with signaling
4. directional comparison with signaling
Dependability / reliability
Protection must operate when required to Failure to operate can be extremely
damaging and disruptive Faults are rare. Protection must operate even after
years of inactivity Improved by use of:
1. Back-up Protection and
2. duplicate Protection
Security / Stability
Protection must not operate when not required to e.g. due to:
1. Load Switching
2. Faults on other parts of the system
3. Recoverable Power Swings
Overlap of protections
1. No blind spots
2. Where possible use overlapping CTs
Phase discrimination / selectivity
Correct indication of phases involved in the fault Important for Single Phase
Tripping and auto-Reclosing applications
Auxiliary supplies
Required for:
1. Tripping circuit breakers
2. Closing circuit breakers
3. Protection and trip relays
• AC. auxiliary supplies are only used on LV and MV systems.
• DC. auxiliary supplies are more secure than ac supplies.
• Separately fused supplies used for each protection.
• Duplicate batteries are occasionally provided for extra security.
• Modern protection relays need a continuous auxiliary supply.
• During operation, they draw a large current which increases due
to operation of output elements.
Relays are given a rated auxiliary voltage and an operative auxiliary voltage
range.
the rated value is marked on the relay. Refer to relay documentation for details
of operative range. it is important to make sure that the range of voltages which
can appear at the relay auxiliary supply terminals is within the operative range.
IEC recommended values (IEC 255-6):
Rated battery voltages:
12, 24, 48, 60, 11 0, 125, 220, 250, 440
Preferred operative range of relays:
80 to 10% of voltage rated
AC. component ripple in the dc supply:
<10% of voltage rated
COST
The cost of protection is equivalent to insurance policy against damage to plant,
and loss of supply and customer goodwill.
Acceptable cost is based on a balance of economics and technical factors. Cost
of protection should be balanced against the cost of potential hazards there is an
economic limit on what can be spent.
Minimum cost:
Must ensure that all faulty equipment is isolated by protection
Other factors:
1. Speed
2. Security/Stability
3. Sensitivity:
Degree of risk in allowing a low level fault to develop into a more
severe fault
4. Reliability
Distribution systems
1. Large number of switching and distribution points, transformers and
feeders.
2. Economics often overrides technical issues
3. Protection may be the minimum consistent with - statutory safety
regulations
4. Speed less important than on transmission systems
5. Back-up protection can be simple and is often inherent in the main
protection.
6. Although important, the consequences of maloperation or failure to
operate are less
serious than for transmission systems.
Transmission systems
1. Emphasis is on technical considerations rather than economics
2. Economics cannot be ignored but is of secondary importance compared
with the need for highly reliable, fully discriminative high speed
protection
3. Higher protection costs justifiable by high capital cost of power system
elements protected.
4. Risk of security of supply should be reduced to the lowest practical
levels
5. High speed protection requires unit protection
6. Duplicate protections used to improve reliability
7. Single phase tripping and auto-reclose may be required to maintain
system stability