Documente Academic
Documente Profesional
Documente Cultură
PRODUCTS INTRODUCE
Type fuse link belong to “K”and“T”type fuse, it has general type, universal type and screw type available according to IEC-282
standard. Key is suitable for drop-off fuse cut out with rated voltage 11-36kv.
+ fuse links are designed to carry 150% of their rated current without damage to the fuse link itself or the cutout in which it is
installed.
+ This capacity is for special loading situations, such as short-time overloads and cold load pick-up. It have two type, type K
fuse links and type T fuse links, The fast characteristics of Type K fuse links were to provide fuse links that would meet existing
coordination schemes. Type T fuse links provide slower time-current characteristics than the Type K links. Type T links
coordinate particularly well with automatic oil circuit recloses.
+ Materials used of Type K links
- The fusible section of the 1 through 3 ampere Type K links consist of a stainless steel fuse strain wire; the 6 through 10
ampere, stainless-steel strain wire and a copper-alloy fuse wire; 12 through 100 amperes, a stainless steel strain wire and a
silver-copper fuse wire; 140 and 200 ampere, a silver-copper fuse wire large enough to serve as both strain and fuse wire.
+ Fuse elements of Type T fuse links
1 through 3 ampere Type T fuse links employ a fusing section consisting of a stainless-steel wire serving as both strain and
fuse wire; 6 through 100 ampere, a stainless-steel strain wire and a pure-tin fuse wire in parallel. 140 and 200 ampere T links
have a copper element mechanically crimped at one end, soldered at the other end. On overloads or low faults, the solder
becomes a fluid and the link separates; on higher fault currents, the link separates when the copper wire melts.
934D4 Đường D KCN Cát Lái P. Thạnh Mỹ Lợi, Q. 2, tp HCM Tel: 028 37421888 Fax: 028 37423783 Website: www.morstar.vn
Morstar has a policy of continuous product improvement, we reserve the right to change design and specifications without notice. Page 1 of 3
FEATURESU
- A Removable Buttons - Allow fuse links to be used in all open and enclosed cutouts, including cutouts with arc-shortening
rods. Fuse link type, ampere size and date of manufacture marked on periphery of screw terminal.
- B Fuse element: eutectic alloy which can be melted at low temperature to avoid the burning of arc-extinguishing tube.
- C High strength strain wire, which can withstand the tensile strength from fuse cutout flipper and outside pulling strength.
- D Swaged connected end guarantees the reliable connection of elements and are not easily damaged.
- E Swaged cable section prevents splaying of strands of cable, to ensure the cable’s smooth withdrawal from tube during the
melting of fuse link.
- F Tinned copper stranded cable, resists corrosion, its cable diameter can resist corona.
- G Auxiliary arc-extinguishing tube, improves the capability of interrupting low fault current, and has the special ability to
interrupt full range fault. Marked on length of tube to aid in identification of fuse type K or T
- H Captive Washer - Will not fall off prior to or during installation. (Can be removed for use where 1/2" button or no button is
required.)
Table 1. Speed Ratio Tin Element(s) Slow T Dual Element Designation Fast Medium Slow Very Slow Extra Slow Type
K, T Speed Ratio 6-8 10-13
934D4 Đường D KCN Cát Lái P. Thạnh Mỹ Lợi, Q. 2, tp HCM Tel: 028 37421888 Fax: 028 37423783 Website: www.morstar.vn
Morstar has a policy of continuous product improvement, we reserve the right to change design and specifications without notice. Page 2 of 3
Designation Fast Slow Description RATINGS & TIME-CURRENT
CHARACTERISTIC (TCC) CURVES
934D4 Đường D KCN Cát Lái P. Thạnh Mỹ Lợi, Q. 2, tp HCM Tel: 028 37421888 Fax: 028 37423783 Website: www.morstar.vn
Morstar has a policy of continuous product improvement, we reserve the right to change design and specifications without notice. Page 3 of 3