SINAMICS V20
Technical Slides
Simple. Rugged. Efficient.
Unrestricted © Siemens 2020 siemens.com/sinamics-v20
1 Introduction
2 Product
3 Communication
4 Tools
5 Customer benefits
6 Useful tools
V20
Comprehensive options…
Circuit breaker
V20 BOP
Line
(Basic Operator Panel)
filter
Shield
connection kit
SD/MMC
Memory card
Output
reactor
Braking
Parameter loader
Robustness
Easy to use
Unrestricted © Siemens 2020
Page 7
Easy automation system
SINAMICS V20
SIMATIC Panel SIMATIC PLC
Ethernet/PROFINET .…
USS
MODBUS RTU
1 Introduction
2 Product
3 Communication
4 Tools
5 Customer benefits
6 Useful tools
Easy to install
• Compact size , push-through and side by side possible
• USS and MODBUS on terminals
• EMC filtered variant (1AC FSAA/AB/AC with EMC C1) and IT network support
• I/O extension module provide more I/O numbers (2DI, 2RO).
Easy to use
• Parameter loading without power supply
• Smart access Wifi module support wireless configuring V20
• Lua script bring more flexibility of customized application
• Application and connection macros
• “Keep on running mode” for uninterrupted operation
• Wider voltage range, temperature range, advanced cooling design and coated
PCB increase robustness
Made by Siemens - Designed and assembled under German quality guidelines and long-term drive
experience
Power on
DigitalAC
3
Supply
Output
Drive Running *
1 2 3 4 General
Confirm / change Select Select
parameter
motor data connection macro application macro
settings
3 AC Supply
DI 1 Digital Output
DI 2
AC Supply
3
Driv e Running *
DI 3
3
AI DI 1 – ON
DI 1
/ OFF Analogue Output
Speed *
Digital Output
DI 2 Drive Running *
DI 2 – Local / Remote
M
0V
Start motor
DI 3
“PNP”
DI 3 – DC Braking (optio n)
PLC outputs
3
DIrequi
* Optional. Not 1 –rForward
ed Analogue Output
I V DI 2 – Reverse Speed *
M DI 3 - DC Braking (option)
Note: Analog input DIP switch, AI – Speed
3
Set-point
DI 1 – ON / OFF
Set to V unless a “constant current” source DI 2required
* Optional. Not – Fixed speed 1
M DI 3 – Fixed speed 3
* Optional. Not requir ed
Macro-based commissioning of the V20 – with a few steps from the first startup through to the running
motor
I/O extension module Lua script High and Low overload for FSE
Robustness
1 2 3
V20_xxxx
Online/offline Fault /
identification alarm quick menu
Feature Specification
Digital inputs 24V
PNP and NPN configurable by wiring
Programmable
24V output Shared power supply with the V20.
Total output current is 50mA
Relay outputs 30V DC or 230V AC
Parameterizable
6SL3256-0VE00-6AA0
Extension port Connect to second extension module like BOP
• 2 digital inputs interface module or Smart Access.
• 2 relay outputs
• SINAMICS V20 400V
• Firmware 3.94 or above
Status LED
Easy menu structure for quick
commissioning
Up
The LED shows directly the actual inverter
Units
Reverse status
Graphical display
Down
Values and Units
Status icons
OK
Stop
Auto/Manual/Jog mode
Start Function
BOP interface:
• Connection between inverter and ext. BOP
• Integrated SD/MMC card slot for parameter
loading / storing / cloning
Parameter loader
• Loading and storing resp. cloning of
parameter sets
• The converter need not be connected
to the power supply
• Max. 100 parameters sets can be
managed on one memory card
1AC 230V
Rated Data Order Number
EMC Standards
3AC 400V
Rated Data Order Number
Prated (LO) Prated (LO) IL1) 400V IL 480V Prated (HO) Prated (HO) IH2) 400V IH 480V
Fan FS
kW hp A A kW hp A A
0.37 ½ 1.3 1.3 0.37 ½ 1.3 1.3 6SL3210-5BE13-7 V0 No
0.55 ¾ 1.7 1.7 0.55 ¾ 1.7 1.7 6SL3210-5BE15-5 V0 No
0.75 1 2.2 2.2 0.75 1 2.2 2.2 6SL3210-5BE17-5 V0 No
A
1.1 1-½ 3.1 3.1 1.1 1-½ 3.1 3.1 6SL3210-5BE21-1 V0 1
1.5 2 4.1 4.1 1.5 2 4.1 4.1 6SL3210-5BE21-5 V0 1
2.2 3 5.6 4.8 2.2 3 5.6 4.8 6SL3210-5BE22-2 V0 1
3 4 7.3 7.3 3 4 7.3 7.3 6SL3210-5BE23-0 V0 1
B
4 5 8.8 8.24 4 5 8.8 8.24 6SL3210-5BE24-0 V0 1
5.5 1-½ 12.5 11 5.5 1-½ 12.5 11 6SL3210-5BE25-5 V0 1 C
7.5 10 16.5 16.5 7.5 10 16.5 16.5 6SL3210-5BE27-5 V0 2
11 15 25 21 11 15 25 21 6SL3210-5BE31-1 V0 2 D
15 20 31 31 15 20 31 31 6SL3210-5BE31-5 V0 2
22 30 45 40 18,5 25 38 34 6SL3210-5BE31-8 V0 2
E
30 40 60 52 22 30 45 49 6SL3210-5BE32-2 V0 2
EMC Standards
With integrated line filter category C3 C
Without integrated filter U
1) The output current I L is based on the duty cycle for low overload (LO).
2) The output current I H is based on the duty cycle for high overload (HO).
FS Prated Braking resistor Line reactor Output reactor Shield External Line filter Corresponding to the IEC standard 1)
FSAA 0.25
0.37 3CC01-0AB3
0.55
FSAB
0.75 16 3NA3805
Protection
Energy saving • Frost protection
• Condensation protection
• ECO mode
• Cavitation protection
• Hibernation mode
• Kinetic buffering
• Energy consumption monitoring
• Load failure detection
1 Introduction
2 Product
3 Communication
4 Tools
5 Customer benefits
6 Useful tools
Communication
• Integrated communication interface for USS and MODBUS RTU, additional
modules are not required.
• Set points can also be specified via the analog input
• Integrated communication macros
• The automation system can be conveniently set up via the standardized libraries in
the PLC
USS® - Protocol
The USS® protocol is a simple serial data transfer protocol for the drives technology defined by Siemens AG.
Major features oft the USS® protocol are:
• Support of a multi-point-capable coupling, e.g. EIA RS 485-Hardware, or point to point coupling e.g. EIA RS 232
• Master slave access technique, single master system, maximum 32 nodes (31 slaves)
• Baud rate 2,4 – 187,5kbit/s
• Cable length maximum 1200m (3300ft)
• Operation with either variable or fixed telegram lengths
• Same bus physic as PROFIBUS (DIN 19245 Part 1)
• Data interface to the basic unit according profile “Variable Speed Drives”. Information to the drive with USS® protocol are transmitted the same way as
PROFIBUS-DP
The USS® protocol can be implemented on industrial controller and on PC’s. SIMATIC S7 200 and S7 1200 support the protocol as standard. Building automation
systems Desigo PX with additional I/O module have implemented the protocol as well.
Further information:
http://support.automation.siemens.com/WW/view/en/24178253
1 Introduction
2 Product
3 Communication
4 Tools
5 Customer benefits
6 Useful tools
Configurator
• Quickly and simply configuring drive components
• Configure drive systems for pumps, fans and
compressors applications starting from 1 kW up to 2.6
MW
• Selection from a wide range of products
• Comprehensive documentation
• Support for retrofit projects
• Can be directly ordered through the Industry Mall
DT Configurator
1 Introduction
2 Product
3 Communication
4 Tools
5 Customer benefits
6 Useful tools
Easy to USE
Macro-based commissioning and development for
operation in harsh environments.
Energy efficiency
Easy to SAVE MONEY Productivity
Compact
The cost-effective, reliable and easy to use inverter for basic applications
Communication
USS and MODBUS RTU selectable with full flexibility to control telegram
frame. Easy integration in existing systems. Connection macros
and standard libraries support commissioning.
Installation Compact design, side-by-side mounting and flexible device • Compact installation allows smaller cabinets to be used
installation for both wall mounting and push-through mounting. • Push-through mounting allows the cabinet to be cooled more easily
Operation without additional option modules possible. • Can be run “out-of-the-box” without other options
• Basic operator actions at a built-in BOP (Basic Operator Panel)
Communication The communication port is available at the terminals. • Easy integration into existing systems
The preset parameters of the USS and MODBUS RTU are • Easy integration into micro automation systems
defined in the connection macro. • Easier commissioning through standard libraries and connection
macros
Braking module The dynamic energy is dissipated as heat in a braking resistor • Possible to use dynamic braking to increase braking performance
with an adjustable duty cycle of between 5 % and 100 %. • Inverters ≥ 7.5 kW have an integrated braking module. In this case,
the braking resistor can be directly connected.
I/O extension Provide more digital signals ( 2 digital inputs and 2 relay • Improve the flexibility and extended capability.
module outputs) integrated into the application system. • A typical application is to support 4 multi-pump application in
booster station with V20 multi-pump Lua script.
Macro approach
Optimized application settings for quick commissioning and maximum
performance.
Parameter cloning
Easy transfer of parameter settings from one inverter to another in all
frame size. Up to 32G SD card is supported.
Robustness
Wider voltage range, -10C to 60C ambient temperature range for all power ,
better cooling design and coated PCB increase robustness of the drive
in quality.
Parameter cloning Parameter settings can be easily transferred from one unit to another • Less technical support required
using the BOP (Basic Operator Panel) interface – or even without power • Short commissioning time
supply by using the parameter loader.
• The product is delivered to the customer already preset
Macro approach Connection and application macros to simplify I/O configuration and • Shorter training and commissioning time
make the appropriate settings. • Integrated and optimized application setting
• Simple connection and application macros can be selected
• instead of configuring long complicated parameter lists
• Errors caused by wrong parameter settings can be avoided
Keep running mode The function provides higher productivity in production by automatic • Stable operation under difficult line supply conditions
adaptation in the case of unstable line supplies. • Higher productivity through prevention of interruptions of the production line
• Adaptation to application-relevant reactions through flexible definition in case of
fault/alarm
Robustness Wider voltage range, better cooling design and coated PCB increase • Operation possible when the line supply voltage fluctuates
robustness of the drive in difficult environments. • Reliable operation for line voltages:
• 1AC 200 V … 240 V (-10 % / +10 %)
• 3AC 380 V … 480 V (-15 % / +10 %)
• Operation up to an ambient temperature of 60 °C
ECO Mode
Machine setting according to the relevant application and adjustment of the
current flow to save energy.
DC coupling
Re-use regenerative energy across multiple inverters.
Hibernation Mode
Integrated energy saving functions for standby mode.
20.00
20.00 kWh Measure energy
Estimate energy consumption and saving.
Low-overload
With low overload cycle, the frame size E V20 can reach a higher output
current and power. A smaller inverter can be used.
Design and integrated energy-saving functions allow drastically slashed energy consumption.
Energy reduction Integrated ECO mode for V/f and V2/f automatically adapts the • Energy saving during low dynamic load cycles
during operation flux to save energy. The energy consumption can be shown in • If the setpoint changes, the ECO mode is automatically deactivated
kWh, CO2 or even in the local currency.
• Tells end users the actual energy that has been saved
DC coupling Applications that use SINAMICS V20 drives with the same • Generate and save energy in applications that use coupled motors
power rating can share a common DC bus to reuse the • Multiple inverters can optimally share resources
regenerative energy. • Reduce the need for dynamic braking and external components
Hibernation mode Inverter and motor only operate when the plant or machine • Smart hibernation saves energy
requires them to. Hibernation mode will be activated • Extended lifetime of motor
automatically when the frequency demand or the feedback
• Reduced pump wear at low speed
from a sensor drops below a specific threshold.
• Less time to program PLC code for pump/fan applications (PLC)
High overload and SINAMICS V20 FSE (22 kW and 30 kW) integrated two • With low overload cycle, the inverter can reach a higher output current and
low overload mode different load cycles. power. A smaller inverter can be used.
for FSE • Low Overload (LO): 110% IL for 60 s (cycle time: 300 s) • Optimally designed for variable applications:
• High Overload (HO): 150% IH for 60 s (cycle time: 300 s) • Low Overload for applications with a low dynamic response (continuous
duty)
• High Overload for applications with a high dynamic response (cyclic duty)
1 Introduction
2 Product
3 Communication
4 Tools
5 Customer benefits
6 Useful tools
SIOS:
Sizer
siemens.com/automation/service&support
https://www.automation.
siemens.com/sizerlight
Service Reference
Service Catalog www.siemens.com/sinamics-applications
www.siemens.com/industryservices
• Preguntas
Correos de soporte:
• industrycommunications.col@siemens
• support.industry.siemens.com/
• support.aan.automation@siemens.com
www.siemens.com/sinamics-v20
Subject to changes and errors. The information given in this document only contains general descriptions and/or performance features which may
not always specifically reflect those described, or which may undergo modification in the course of further development of the products. The requested
performance features are binding only when they are expressly agreed upon in the concluded contract.
All product designations, product names, etc. may contain trademarks or other rights of Siemens AG, its affiliated companies or third parties.
Their unauthorized use may infringe the rights of the respective owner.