Grid Performance
ENERCON E-160 EP5 E2 / 5500 kW / FTQS Wind Energy
Converter

Subject to technical change without prior notice.


Data Sheet
Grid Performance E-160 EP5 E2 / 5500 kW / FTQS

Publisher ENERCON GmbH ▪ Dreekamp 5 ▪ 26605 Aurich ▪ Germany


Phone: +49 4941 927-0 ▪ Fax: +49 4941 927-109
E-mail: info@enercon.de ▪ Internet: http://www.enercon.de
Managing Directors: Hans-Dieter Kettwig
Local court: Aurich ▪ Company registration number: HRB 411
VAT ID no.: DE 181 977 360

Copyright notice The entire content of this document is protected by copyright and – with regard to
other intellectual property rights – international laws and treaties. ENERCON GmbH
holds the rights in the content of this document unless another rights holder is ex-
pressly identified or obviously recognisable.
ENERCON GmbH grants the user the right to make copies and duplicates of this
document for informational purposes for its own intra-corporate use; making this
document available does not grant the user any further right of use. Any other du-
plication, modification, dissemination, publication, circulation, surrender to third
parties and/or utilisation of the contents of this document – also in part – shall re-
quire the express prior written consent of ENERCON GmbH unless any of the above
is permitted by mandatory legislation.
The user is prohibited from registering any industrial property rights in the know-how
Subject to technical change without prior notice.

reproduced in this document, or for parts thereof.


If and to the extent that ENERCON GmbH does not hold the rights in the content of
this document, the user shall adhere to the relevant rights holder’s terms of use.

Registered trademarks Any trademarks mentioned in this document are intellectual property of the respect-
ive registered trademark holders; the stipulations of the applicable trademark law
are valid without restriction.

Reservation of right ENERCON GmbH reserves the right to change, improve and expand this document
of modification and the subject matter described herein at any time without prior notice, unless con-
tractual agreements or legal requirements provide otherwise.

Document details

Document ID D0917410-0
Note Original document. Source document of this translation: D0914622-0/2020-01-20

Date Language DCC Plant/department


2020-01-22 en DA WRD GmbH / Validation

2 of 14 D0917410-0 / DA
Data Sheet
Grid Performance E-160 EP5 E2 / 5500 kW / FTQS

Applicable documents

The titles of the documents listed are the titles of the original language versions, with translations of these titles in brack-
ets where applicable. The titles of superordinate standards and guidelines are indicated in the original language or as an
English translation. Document IDs always refer to the original language versions. If the document ID does not contain a
revision, the most recent revision of the document applies. This list contains documents concerning optional components
if necessary.

Document ID Document

IEC 60034-3:2007 Rotating electrical machines - Part 3: Specific requirements for synchronous gener-
ators driven by steam turbines or combustion gas turbines

IEC 61400-21:2008 Ed. 2.0 Wind turbines - Part 21: Measurement and assessment of power quality character-
istics of grid connected wind turbines

Subject to technical change without prior notice.

D0917410-0 / DA 3 of 14
Data Sheet
Grid Performance E-160 EP5 E2 / 5500 kW / FTQS

Table of contents
1 General information ................................................................................................ 6

2 Characteristics ........................................................................................................ 7

3 Reactive power range  ............................................................................................ 8

4 Reference point ..................................................................................................... 12

List of symbols  ..................................................................................................... 13

Glossary of terms  ................................................................................................. 14


Subject to technical change without prior notice.

4 of 14 D0917410-0 / DA
Data Sheet
Grid Performance E-160 EP5 E2 / 5500 kW / FTQS

List of abbreviations

FACTS Flexible Alternating Current Transmission System


FTQS FACTS Transmission with Q+ option and STATCOM option (electrical configura-
tion with expanded reactive power range and STATCOM option)
IEC International Electrotechnical Commission
STATCOM Static compensator

Subject to technical change without prior notice.

D0917410-0 / DA 5 of 14
Data Sheet
Grid Performance E-160 EP5 E2 / 5500 kW / FTQS

1 General information
The grid performance and characteristics of the ENERCON wind energy converter are
distributed on two document types.
The present wind energy converter-specific document includes the grid performance de-
pendent on wind energy converter type and electrical configuration.
In the corresponding applicable document independent of wind energy converter, the
functions and grid performance applicable for all wind energy converters and electrical
configurations are documented.
Subject to technical change without prior notice.

6 of 14 D0917410-0 / DA
Data Sheet
Grid Performance E-160 EP5 E2 / 5500 kW / FTQS

2 Characteristics
All characteristics of the wind energy converter refer to the reference point specified in
ch. 4, p. 12. The electrical properties can only be achieved with the corresponding con-
trol system.
An excerpt from the power quality measurements according to IEC 61400-21:2008 Ed. 2.0
is available upon request.
Tab. 1: Wind energy converter characteristics
Characteristics Value
Nominal frequency fn
  50 Hz
60 Hz
Nominal active power Pn   5500 kW
Nominal reactive power Qn   3400 kvar
Rated apparent power Smax   6500 kVA
Nominal voltage Un   690 V

Subject to technical change without prior notice.


Nominal current In
  4602 A
Rated current Imax
  5439 A
Maximum initial symmetrical short-circuit current Ik",max
    5730 A
Maximum initial periodic short-circuit current Ip,max, √2 x Ik",max 8103 A
     

Maximum symmetrical breaking current Ib,max


  5730 A
Maximum continuous short-circuit current Ik,max
  5730 A
Number of power cabinets - 2

D0917410-0 / DA 7 of 14
Data Sheet
Grid Performance E-160 EP5 E2 / 5500 kW / FTQS

3 Reactive power range


The wind energy converter features a reactive power range that provides for the discharge
of reactive power (Qexport) into the grid and the intake of reactive power (Qimport) from the
   

grid.
Tab. 2: Reactive power values (export/import))
Parameter Value
Maximum reactive power (export) Qmax
  3400 kvar
Minimum reactive power (import) Qmin
  -3400 kvar

Reactive power export corresponds to the behaviour of an overexcited synchronous ma-


chine. Reactive power import corresponds to the behaviour of an underexcited synchro-
nous machine (acc. to IEC 60034-3:2007).
The chart below illustrates the reactive power range as determined by active power and
grid voltage.
Subject to technical change without prior notice.

Fig. 1: Reactive power range as determined by the active power and grid voltage

90 % Un  

95 % Un  

≥100 % Un  

8 of 14 D0917410-0 / DA
Data Sheet
Grid Performance E-160 EP5 E2 / 5500 kW / FTQS

The chart is given in table format below.


Tab. 3: Reactive power range as determined by active power and grid voltage (≥100 % Un)  

P/Pn  ≥100 % Un  

Q/Pn (Qexport)
    Q/Pn (Qimport)
   

1 0,618 -0,618
0 0,618 -0,618

Tab. 4: Reactive power range as determined by active power and grid voltage (<100 % Un)  

95 % Un   90 % Un  

P/Pn  Q/Pn   Q/Pn   Q/Pn   Q/Pn  

(Qexport)
  (Qimport)
  (Qexport)
  (Qimport)
 

0.50 0.618 -0.618 0.618 -0.618


0.52 0.618 -0.618 0.618 -0.618
0.54 0.618 -0.618 0.618 -0.618

Subject to technical change without prior notice.


0.56 0.618 -0.618 0.618 -0.618
0.58 0.618 -0.618 0.618 -0.618
0.60 0.618 -0.618 0.618 -0.618
0.62 0.618 -0.618 0.618 -0.618
0.64 0.618 -0.618 0.618 -0.618
0.66 0.618 -0.618 0.618 -0.618
0.68 0.618 -0.618 0.618 -0.618
0.70 0.618 -0.618 0.618 -0.618
0.72 0.618 -0.618 0.618 -0.618
0.74 0.618 -0.618 0.618 -0.618
0.76 0.618 -0.618 0.618 -0.618
0.78 0.618 -0.618 0.618 -0.618
0.80 0.618 -0.618 0.618 -0.618
0.81 0.618 -0.618 0.618 -0.618
0.82 0.618 -0.618 0.618 -0.618
0.83 0.618 -0.618 0.618 -0.618
0.84 0.618 -0.618 0.618 -0.618
0.85 0.618 -0.618 0.618 -0.618
0.86 0.618 -0.618 0.618 -0.618
0.87 0.618 -0.618 0.612 -0.612
0.88 0.618 -0.618 0.597 -0.597
0.89 0.618 -0.618 0.582 -0.582
0.90 0.618 -0.618 0.567 -0.567
0.91 0.618 -0.618 0.551 -0.551

D0917410-0 / DA 9 of 14
Data Sheet
Grid Performance E-160 EP5 E2 / 5500 kW / FTQS

95 % Un   90 % Un  

P/Pn  Q/Pn   Q/Pn   Q/Pn   Q/Pn  

(Qexport)
  (Qimport)
  (Qexport)
  (Qimport)
 

0.92 0.618 -0.618 0.534 -0.534


0.93 0.618 -0.618 0.516 -0.516
0.94 0.614 -0.614 0.498 -0.498
0.95 0.598 -0.598 0.478 -0.478
0.96 0.582 -0.582 0.458 -0.458
0.97 0.565 -0.565 0.436 -0.436
0.98 0.548 -0.548 0.413 -0.413
0.99 0.530 -0.530 0.389 -0.389
1.00 0.510 -0.510 0.362 -0.362

Reactive power points between two adjacent table values of voltage or active power must
be determined through linear interpolation.
Subject to technical change without prior notice.

Reactive power controller


The reactive power of the wind energy converter is configurable. The setpoints below can
be configured directly in the wind energy converter control system.
Tab. 5: Reactive power regulator adjustment range
Parameter Range Increment
Q Qmin … Qmax
    1 kvar
cos (phi) -0,851 … 0,851 0,001

Alternatively, a project-specific setpoint can be set in the wind energy converter using a
superordinate control system in the wind farm so as to apply the illustrated reactive power
range.
The tolerance of the reactive power feed in is < ±2.5 % of nominal active power over a
10-minute average.

10 of 14 D0917410-0 / DA
Data Sheet
Grid Performance E-160 EP5 E2 / 5500 kW / FTQS

Power consumption
The STATCOM option enables the wind energy converter to feed in its maximum reactive
power according to the PQ chart (fig. 1, p. 8) at any time, irrespective of the current wind
speed.
If the wind speed is sufficient to cover the wind energy converter’s own consumption and
its internal losses, the wind energy converter feeds active power into the grid in addition to
maximum reactive power.
In calm conditions or at very low wind speeds the wind energy converter draws active
power from the grid to cover its power consumption and internal losses. This active power
consumption is shown as a red hatched area in the chart below. Active power is shown as
a 10-minute average.

P/Q n

Q/Pn Qexport Qimport

Q max -0.01 Q min

-0.05

Subject to technical change without prior notice.


Fig. 2: Power consumption of wind energy converter (with STATCOM option)

The energy consumption of a wind energy converter with reactive power export or reactive
power import at very low wind speeds depends on the project-specific weather conditions
(wind, temperature etc.).

D0917410-0 / DA 11 of 14
Data Sheet
Grid Performance E-160 EP5 E2 / 5500 kW / FTQS

4 Reference point
Subject to technical change without prior notice.

Reference point

Fig. 3: Reference point

12 of 14 D0917410-0 / DA
Data Sheet
Grid Performance E-160 EP5 E2 / 5500 kW / FTQS

List of symbols
Tab. 6: Symbols
Symbol Designation
fn
  Nominal frequency
Ib,max
  Maximum symmetrical breaking current
Ik,max
  Maximum continuous short-circuit current
Ik",max
    Maximum initial symmetrical short-circuit current
Imax
  Rated current
In
  Nominal current
Ip,max
  Maximum peak symmetrical short-circuit current
Pn   Nominal active power
Qexport   Reactive power (export)
Qimport   Reactive power (import)

Subject to technical change without prior notice.


Qmax   Maximum reactive power (export)
Qmin   Minimum reactive power (import)
Qn   Nominal reactive power
Smax   Rated apparent power
Un   Nominal voltage

D0917410-0 / DA 13 of 14
Data Sheet
Grid Performance E-160 EP5 E2 / 5500 kW / FTQS

Glossary of terms
Rated current Maximum continuous output current under normal operating con-
ditions for which an electrical system is designed.
Reactive power Electrical power that “commutes” between generators and con-
sumers in a grid. It puts load on the grid without actually being
used up. Reactive power is the result of phase shift between cur-
rent and voltage due to inductive and capacitive consumers (e.g.
electric motors) in a grid running with alternating or three-phase
current. For this reason, power stations must be able to provide
Text
and absorb reactive power in addition to active power.
Subject to technical change without prior notice.

14 of 14 D0917410-0 / DA