THERMAX LIMITED

BOILER & HEATER GROUP

Document No.: DORL-FGSG-7940-059 (TL DOC. NO. :- D65-WH-CS-00661)


DORC Doc No.: A545-7950-5043-VD-LW1001-3007-00 & A545-7950-5043-VD-LW1002-3007-00
Rev: 04
Date: 17/09/2019
Pages: 35

DOCUMENT TITLE : SB-PLC IO LIST (POINT DATABASE FOR SB-PLC)

EIL JOB NO. : A545


PACKAGE/UNIT NO.: 115-LW-1001 & 1002
PR CODE : A545-111-LW-PR-7940

THERMAX OC NO. : QL1221/1222

SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE

OWNER :- DANGOTE OIL REFINING COMPANY

Project Name:

04  17.09.19  ISSUED FOR REVIEW  TJB  NVK  NVK 


03  24.05.19  ISSUED FOR REVIEW  TJB  NVK  NVK 
02  12.02.19  ISSUED FOR REVIEW  TJB  NVK  NVK 
01  23.05.16  ISSUED FOR REVIEW  TJB  NVK  NVK 
0  18.03.16  ISSUED FOR INFORMATION  TJB  NVK  NVK 
Rev.  Date  Purpose  Prepared By  Checked By  Approved By 

14-OCT-2019
TANEJA JUHI (MS) (C283)
1 of 35

Page 1 of 35
Revision History: 
 
1. 115‐XS‐1801 is included. 
 
2. IO count corrected. 
 
3. Typo Error corrected. 
 
4. All changes has been highlighted with Magenta Rose colour. 
 
 

14-OCT-2019
TANEJA JUHI (MS) (C283)
2 of 35

Page 2 of 35
POINT DATA BASE FOR SB‐PLC
NOTES:‐
1) Unless otherwise specified, Scope shall be as per Tender document.
2) For legends / abbreviation detail refer the legends detsial as mentioned below.
3) Range / Trip / Alarm Set Point Values will be mentioned later in this document.  Trip / Alarm Set Point Values may get changed at site during commissioning.
4) Proximity Barriers / Amplifiers shall be in vendors scope & will be installed in respective PLC Panels.
5) IO's mentioned here are as per P&ID's. Spare I/O count is being mentioned as below. Spare IO qty shall be considered as per the tender requirement.
6) The communication from Soot blower PLC panel to DCS is modbus and customer to consider 2000 soft tags for indication. Modbus list will be separately given alongwith sootblower PLC vendor doc.
7) Square rooting for DP type flow trasnmitters shall be done at DCS end.
8) Refer latest Rev. of doc nos are as follows:‐‐1) P&ID for Flue gas cooler‐ HP steam circuit‐ A545‐42‐115‐1118, 2) P&ID for Flue gas cooler‐ MP steam circuit‐ A545‐42‐115‐1127, 3) P&ID for Soot blower system‐ A545‐42‐115‐1011, 3) P&ID for HP dosing system‐ A545‐42‐115‐1112, 4) P&ID for Turbine‐ A545‐42‐115‐1113.

LEGEND DETAILS:‐
LEGEND DESCRIPTION LEGEND DESCRIPTION LEGEND DESCRIPTION
FGSG FLUE GAS STEAM GENERATOR SH SUPERHEATER CTRL CONTROL
FG FLUE GAS EVAP EVAPROATOR LVL LEVEL
FW FEED WATER SAB SEAL AIR BLOWER LO LOW
ATTEMP. ATTEMPERATOR F/B FEEDBACK LO LO LOW LOW
DIS. DISCHARGE SEL SELECTED HI HIGH
STM STEAM LS LIMIT SWICTH HI HI HIGH HIGH
FLW FLOW RUN RUNNING SQ. SQUARE
I/L INLET CMD COMMAND FF FOUNDATION FIELDBUS
O/L OUTLET OP OPEN AI ANALOG INPUT
IND. INDICATION CL CLOSE AO ANALOG OUTPUT
RCP RECIRCULATION PUMP NC NORMALLY CLOSED DI DIGITAL INPUT
HP HIGH PRESSURE NO NORMALLY OPEN DO DIGITAL OUTPUT
MP MEDIUM PRESSURE TRQ TORQUE CV CONTROL VALVE
LP LOW PRESSURE STR START SRR SATELLITE RACK ROOM
SB SOOT BLOWER STP STOP DIFF DIFFERENTIAL
ECO ECONOMISER POS POSITION INTER INTERROGATION
PRESS PRESSURE TEMP TEMPERATURE VLTG VOLTAGE
IS INTRINSICALLY SAFE MOV MOTORISED OPERATED VALVE LHS LEFT HAND SIDE
F/W FORWARD SW SWITCH RHS RIGHT HAND SIDE
F/W'DING FORWARDING OPRTD OPERATED PB PUSH BUTTON
R/T'ING RETRACTING SEQ SEQUENCE SB'ING SOOT BLOWING
SA SEAL AIR

IO SUMMARY
 QTY 
SYSTEM I/O  DESCRIPTION SPARE   REMARKS
ACTUAL TOTAL
(Note‐1)
AI‐IS  4‐20mA (2 WIRE) 4 1 5
ANALOG  I/P
AI‐NON IS 4‐20mA (4 WIRE)
2 WIRE
AI‐IS FF [FOUNDATION FIELDBUS I/O (HPT‐IS SPURS)]

AO‐IS 4‐20mA (2 WIRE)
SB‐PLC

ANALOG  O/P  AO‐NON IS 4‐20mA (4 WIRE)


PLC vendor needs to consider tested dual 
FF Redundant all I/Os.
AO‐IS

DI‐IS PROXIMITY TYPE‐‐24VDC
DIGITAL INPUT
DI‐NON IS  FIELD/MCC/MOV'S/ OTHERS‐‐INTER VLTG‐240VAC/24 VDC 742 149 891

DO‐NON IS (WET) LAMPS ‐ 24VDC WET DO 10 2 12
DIGITAL OUTPUT
DO‐NON IS (PFC)  FIELD/PDB/MOV'S/ OTHERS ‐ POT. FREE DRY CONTACT THROUGH RELAY 71 15 86

REV.03 CHANGES ARE MARKED IN GREEN COLOUR.
REV.02 CHANGES ARE MARKED IN ORANGE COLOUR.
REV.01 CHANGES ARE MARKED IN BLUE COLOUR.

4 17/09/2019 TJB NVK NVK


PLANT : LEKKI FREE TRADE ZONE, NIGERIA DIVISION: ENGINEERING
3 24/05/2019 TJB NVK NVK
ENGINEERS INDIA LIMITED 2 12/2/2019 TJB NVK NVK DRAWING NO REV.

NEW DELHI CLIENT : M/S DANGOTE OIL REFINING COMPANY


LTD.
DEPT: INSTRUMENTATION 0 18/3/2016 TJB NVK NVK D65‐WH‐CS‐00661 3
PREPARED
REVISION DATE CHECKED BY APP. BY Sheet : 1 Of 31
BY
14-OCT-2019
TANEJA JUHI (MS) (C283)
3 of 35

Page 3 of 35
Annexure‐I
Special care to be taken  in consideration for the 
Dangote FGSG Package (QL1221‐2): SB PLC Panels arrangement (front  FGSG‐1 (Looking from Flue Gas Exit Path) FGSG‐2 (Looking from Flue Gas Exit Path)
arrangemnet of the CB1  & CB3 Boxes  in  +7000 & 
view) details  in +4200, +7000, +10650 Elevation.
+10650 Elevation to avoid  fouling w.r.t. the bracing 

+10650 Elevation +10650 Elevation

115‐SBPLC‐1808 115‐SBPLC‐1809 115‐SBPLC‐1810 115‐SBPLC‐1811 115‐SBPLC‐2510 115‐SBPLC‐2511 115‐SBPLC‐2508 115‐SBPLC‐2509

Boiler Structural Bracing

Boiler Structural Bracing
1200mm Width Panels Bayed together 1200mm Width Panels Bayed together 1200mm Width Panels Bayed together 1200mm Width Panels Bayed together
CB3 CB1 CB3 CB1 CB3 CB1
I/O + Marshalling Panels I/O + Marshalling Panels I/O + Marshalling Panels I/O + Marshalling Panels

CB1 CB3

FOR 15 SB ( ALL "A" SERIES) FOR 15 SB ( ALL "B" SERIES) FOR 15 SB ( ALL "B" SERIES) FOR 15 SB ( ALL "A" SERIES)

+7000 Elevation +7000 Elevation

115‐SBPLC‐1804 115‐SBPLC‐1805 115‐SBPLC‐1806 115‐SBPLC‐1807 115‐SBPLC‐2506 115‐SBPLC‐2507 115‐SBPLC‐2504 115‐SBPLC‐2505

Boiler Structural Bracing

Boiler Structural Bracing
1200mm Width Panels Bayed together 1200mm Width Panels Bayed together
1200mm Width Panels Bayed together 1200mm Width Panels Bayed together
CB3 I/O + Marshalling Panels CB1 CB3 I/O + Marshalling Panels CB1 CB3 CB1
I/O + Marshalling Panels I/O + Marshalling Panels

CB1 CB3

FOR 15 SB ( ALL "C" SERIES) FOR 15 SB ( ALL "D" SERIES) FOR 15 SB ( ALL "D" SERIES) FOR 15 SB ( ALL "C" SERIES)

+4200 Elevation

115‐SBPLC‐1802 115‐SBPLC‐1803 115‐SBPLC‐1801 115‐SBPLC‐2501 115‐SBPLC‐2502 115‐SBPLC‐2503

800mm width panel + 1200mm width panel 600mm width panel 600mm width panel 800mm width panel + 1200mm width panel


Additional Structure included (by Thermax)  Additional Structure included (by 
CB3 I/O + Marshalling Panels CB1 CB3 CPU Panels CB1 CB3 CPU Panels CB1 CB3 I/O + Marshalling Panels CB1
for accessibility Thermax) for accessibility

FOR 15 SB (ALL "E" SERIES) + COMMON PART (AI + SB DRAIN MOV + SB ISO MOV) FOR 15 SB (ALL "E" SERIES) + COMMON PART (AI + SB DRAIN MOV + SB ISO MOV)

1. This drawings is pictorial representation of SB PLC Panels (Front View) Physical arrangement.
2. Panel canopies have not been shown in this drawing. Please refer respective vendor document (DORL‐FGSG‐7940‐060 ‐ PR for Soot Blower PLC) for details.

14-OCT-2019
TANEJA JUHI (MS) (C283)
4 of 35

Page 4 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

ANALOG INPUT

SB PLC
1 115‐PT‐1834 PI1834 D43‐0WH‐007815P MP STM FOR SB'ING  PRESS 4‐20mA AI Open ‐ 0 30 Kg/cm2(g) NA NA ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ D84‐4WH‐000237 IS 2‐Wired. PROXIMITY BARRIER
+4200 Elevation

2 ‐ PAL1834 D43‐0WH‐007815P MP STM FOR SB'ING  PRESS LO ‐ SOFT ‐ ‐ ‐ ‐ Kg/cm2(g) ‐ ‐ ‐ ‐ 13.0 ‐ ‐ ‐ ‐ ‐ D84‐4WH‐000237 ‐

3 ‐ PALL1834 D43‐0WH‐007815P MP STM FOR SB'ING  PRESS LO LO ‐ SOFT ‐ ‐ ‐ ‐ Kg/cm2(g) ‐ ‐ ‐ ‐ ‐ ‐ 10.0 ‐ ‐ ‐ D84‐4WH‐000237 ‐

SB PLC
4 115‐PT‐1835 PI1835 D43‐0WH‐007815P SAB DIS. PRESS 4‐20mA AI Open ‐ 0 3500 mmWC NA NA ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ D84‐4WH‐000237 IS 2‐Wired. PROXIMITY BARRIER
+4200 Elevation

5 ‐ PAL1835 D43‐0WH‐007815P SAB DIS. PRESS LO ‐ SOFT ‐ ‐ ‐ ‐ mmWC ‐ ‐ ‐ ‐ 1500.0 ‐ ‐ ‐ ‐ ‐ D84‐4WH‐000237 ‐

6 ‐ PALL1835 D43‐0WH‐007815P SAB DIS. PRESS LO LO ‐ SOFT ‐ ‐ ‐ ‐ mmWC ‐ ‐ ‐ ‐ ‐ ‐ 1350.0 ‐ ‐ ‐ D84‐4WH‐000237 ‐

SB PLC
7 115‐TT‐1825 TI1825 D43‐0WH‐007815P LHS SB DRAIN LINE TEMP 4‐20mA AI Open ‐ 0 400 DegC NA NA ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ D84‐4WH‐000237 IS 2‐Wired. PROXIMITY BARRIER
+4200 Elevation

8 ‐ TALL1825 D43‐0WH‐007815P LHS SB DRAIN LINE TEMP LO LO ‐ SOFT ‐ ‐ ‐ ‐ DegC ‐ ‐ ‐ ‐ ‐ ‐ 210.0 ‐ ‐ ‐ D84‐4WH‐000237 ‐

SB PLC
9 115‐TT‐1826 TI1826 D43‐0WH‐007815P RHS SB DRAIN LINE TEMP 4‐20mA AI Open ‐ 0 400 DegC NA NA ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ D84‐4WH‐000237 IS 2‐Wired. PROXIMITY BARRIER
+4200 Elevation

10 ‐ TALL1826 D43‐0WH‐007815P RHS SB DRAIN LINE TEMP LO LO ‐ SOFT ‐ ‐ ‐ ‐ DegC ‐ ‐ ‐ ‐ ‐ ‐ 210.0 ‐ ‐ ‐ D84‐4WH‐000237 ‐

DIGITAL INPUT

SB PLC Pot. Free at MOV, interposing relay at SB‐PLC 
1 115‐ZSH‐1819 ZSH1819 D43‐0WH‐007815P OP LS MOV‐1819 DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation end.

SB PLC Pot. Free at MOV, interposing relay at SB‐PLC 
2 115‐ZSL‐1819 ZSL1819 D43‐0WH‐007815P CL LS MOV‐1819 DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation end.

SB PLC Pot. Free at MOV, interposing relay at SB‐PLC 
3 115‐TSH‐1819 TSH1819 D43‐0WH‐007815P OP TRQ LS MOV‐1819 DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation end.

SB PLC Pot. Free at MOV, interposing relay at SB‐PLC 
4 115‐TSL‐1819 TSL1819 D43‐0WH‐007815P CL TRQ LS MOV‐1819 DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation end.

SB PLC Pot. Free at MOV, interposing relay at SB‐PLC 
5 115‐XTM‐1819 XTM1819 D43‐0WH‐007815P TRIP F/B MOV‐1819 DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation end.

SB PLC Pot. Free at MOV, interposing relay at SB‐PLC 
6 115‐XR‐1819 XR1819 D43‐0WH‐007815P REMOTE SEL MOV‐1819 DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation end.

SB PLC Pot. Free at MOV, interposing relay at SB‐PLC 
7 115‐ZSH‐1820 ZSH1820 D43‐0WH‐007815P OP LS MOV‐1820 DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation end.

SB PLC Pot. Free at MOV, interposing relay at SB‐PLC 
8 115‐ZSL‐1820 ZSL1820 D43‐0WH‐007815P CL LS MOV‐1820 DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation end.

SB PLC Pot. Free at MOV, interposing relay at SB‐PLC 
9 115‐TSH‐1820 TSH1820 D43‐0WH‐007815P OP TRQ LS MOV‐1820 DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation end.

SB PLC Pot. Free at MOV, interposing relay at SB‐PLC 
10 115‐TSL‐1820 TSL1820 D43‐0WH‐007815P CL TRQ LS MOV‐1820 DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation end.

SB PLC Pot. Free at MOV, interposing relay at SB‐PLC 
11 115‐XTM‐1820 XTM1820 D43‐0WH‐007815P TRIP F/B MOV‐1820 DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation end.

SB PLC Pot. Free at MOV, interposing relay at SB‐PLC 
12 115‐XR‐1820 XR1820 D43‐0WH‐007815P REMOTE SEL MOV‐1820 DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation end.

SB PLC Pot. Free at MOV, interposing relay at SB‐PLC 
13 115‐ZSH‐1821 ZSH1821 D43‐0WH‐007815P OP LS MOV‐1821 DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation end.

SB PLC Pot. Free at MOV, interposing relay at SB‐PLC 
14 115‐ZSL‐1821 ZSL1821 D43‐0WH‐007815P CL LS MOV‐1821 DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation end.

SB PLC Pot. Free at MOV, interposing relay at SB‐PLC 
15 115‐TSH‐1821 TSH1821 D43‐0WH‐007815P OP TRQ LS MOV‐1821 DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation end.

14-OCT-2019
TANEJA JUHI (MS) (C283)
1
5 of 35

Page 5 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC Pot. Free at MOV, interposing relay at SB‐PLC 
16 115‐TSL‐1821 TSL1821 D43‐0WH‐007815P CL TRQ LS MOV‐1821 DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation end.

SB PLC Pot. Free at MOV, interposing relay at SB‐PLC 
17 115‐XTM‐1821 XTM1821 D43‐0WH‐007815P TRIP F/B MOV‐1821 DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation end.

SB PLC Pot. Free at MOV, interposing relay at SB‐PLC 
18 115‐XR‐1821 XR1821 D43‐0WH‐007815P REMOTE SEL MOV‐1821 DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation end.

SB PLC
19 115‐ZSR‐1806AA ZSR1806AA D43‐0WH‐007815P REST POS. LS LRSB‐1806AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
20 115‐ZSF‐1806AA ZSF1806AA D43‐0WH‐007815P F/W POS. LS LRSB‐1806AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
21 115‐WSF‐1806AA WSF1806AA D43‐0WH‐007815P F/W'DING F/B LRSB‐1806AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
22 115‐WSR‐1806AA WSR1806AA D43‐0WH‐007815P R/T'ING F/B LRSB‐1806AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
23 115‐XT‐1806AA XT1806AA D43‐0WH‐007815P TRIP F/B LRSB‐1806AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
24 115‐XA‐1806AA XA1806AA D43‐0WH‐007815P AUTO SEL.   LRSB‐1806AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
25 115‐ZLH‐1806A ZLH1806A D43‐0WH‐007815P OP LS MOV‐1806A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
26 115‐ZLL‐1806A ZLL1806A D43‐0WH‐007815P CL LS MOV‐1806A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
27 115‐TLX‐1806A TLX1806A D43‐0WH‐007815P TRQ SW OPRTD MOV‐1806A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
28 115‐XTM‐1806A XTM1806A D43‐0WH‐007815P TRIP F/B MOV‐1806A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
29 115‐XR‐1806A XR1806A D43‐0WH‐007815P REMOTE SEL MOV‐1806A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
30 115‐ZSR‐1806BB ZSR1806BB D43‐0WH‐007815P REST POS. LS LRSB‐1806BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
31 115‐ZSF‐1806BB ZSF1806BB D43‐0WH‐007815P F/W POS. LS LRSB‐1806BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
32 115‐WSF‐1806BB WSF1806BB D43‐0WH‐007815P F/W'DING F/B LRSB‐1806BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
33 115‐WSR‐1806BB WSR1806BB D43‐0WH‐007815P R/T'ING F/B LRSB‐1806BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
34 115‐XT‐1806BB XT1806BB D43‐0WH‐007815P TRIP F/B LRSB‐1806BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
35 115‐XA‐1806BB XA1806BB D43‐0WH‐007815P AUTO SEL.   LRSB‐1806BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
36 115‐ZLH‐1806B ZLH1806B D43‐0WH‐007815P OP LS MOV‐1806B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
37 115‐ZLL‐1806B ZLL1806B D43‐0WH‐007815P CL LS MOV‐1806B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
38 115‐TLX‐1806B TLX1806B D43‐0WH‐007815P TRQ SW OPRTD MOV‐1806B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
39 115‐XTM‐1806B XTM1806B D43‐0WH‐007815P TRIP F/B MOV‐1806B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
40 115‐XR‐1806B XR1806B D43‐0WH‐007815P REMOTE SEL MOV‐1806B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
41 115‐ZSR‐1806CC ZSR1806CC D43‐0WH‐007815P REST POS. LS LRSB‐1806CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
42 115‐ZSF‐1806CC ZSF1806CC D43‐0WH‐007815P F/W POS. LS LRSB‐1806CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
2
6 of 35

Page 6 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
43 115‐WSF‐1806CC WSF1806CC D43‐0WH‐007815P F/W'DING F/B LRSB‐1806CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
44 115‐WSR‐1806CC WSR1806CC D43‐0WH‐007815P RETRCCTING F/B LRSB‐1806CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
45 115‐XT‐1806CC XT1806CC D43‐0WH‐007815P TRIP F/B LRSB‐1806CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
46 115‐XA‐1806CC XA1806CC D43‐0WH‐007815P AUTO SEL.   LRSB‐1806CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
47 115‐ZLH‐1806C ZLH1806C D43‐0WH‐007815P OP LS MOV‐1806C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
48 115‐ZLL‐1806C ZLL1806C D43‐0WH‐007815P CL LS MOV‐1806C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
49 115‐TLX‐1806C TLX1806C D43‐0WH‐007815P TRQ SW OPRTD MOV‐1806C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
50 115‐XTM‐1806C XTM1806C D43‐0WH‐007815P TRIP F/B MOV‐1806C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
51 115‐XR‐1806C XR1806C D43‐0WH‐007815P REMOTE SEL MOV‐1806C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
52 115‐ZSR‐1806DD ZSR1806DD D43‐0WH‐007815P REST POS. LS LRSB‐1806DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
53 115‐ZSF‐1806DD ZSF1806DD D43‐0WH‐007815P F/W POS. LS LRSB‐1806DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
54 115‐WSF‐1806DD WSF1806DD D43‐0WH‐007815P F/W'DING F/B LRSB‐1806DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
55 115‐WSR‐1806DD WSR1806DD D43‐0WH‐007815P R/T'ING F/B LRSB‐1806DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
56 115‐XT‐1806DD XT1806DD D43‐0WH‐007815P TRIP F/B LRSB‐1806DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
57 115‐XA‐1806DD XA1806DD D43‐0WH‐007815P AUTO SEL.   LRSB‐1806DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
58 115‐ZLH‐1806D ZLH1806D D43‐0WH‐007815P OP LS MOV‐1806D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
59 115‐ZLL‐1806D ZLL1806D D43‐0WH‐007815P CL LS MOV‐1806D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
60 115‐TLX‐1806D TLX1806D D43‐0WH‐007815P TRQ SW OPRTD MOV‐1806D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
61 115‐XTM‐1806D XTM1806D D43‐0WH‐007815P TRIP F/B MOV‐1806D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
62 115‐XR‐1806D XR1806D D43‐0WH‐007815P REMOTE SEL MOV‐1806D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
63 115‐ZSR‐1806EE ZSR1806EE D43‐0WH‐007815P REST POS. LS LRSB‐1806EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
64 115‐ZSF‐1806EE ZSF1806EE D43‐0WH‐007815P F/W POS. LS LRSB‐1806EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
65 115‐WSF‐1806EE WSF1806EE D43‐0WH‐007815P F/W'DING F/B LRSB‐1806EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
66 115‐WSR‐1806EE WSR1806EE D43‐0WH‐007815P R/T'ING F/B LRSB‐1806EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation and will return to PLC as a DI.

SB PLC
67 115‐XT‐1806EE XT1806EE D43‐0WH‐007815P TRIP F/B LRSB‐1806EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
68 115‐XA‐1806EE XA1806EE D43‐0WH‐007815P AUTO SEL.   LRSB‐1806EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
69 115‐ZLH‐1806E ZLH1806E D43‐0WH‐007815P OP LS MOV‐1806E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
3
7 of 35

Page 7 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
70 115‐ZLL‐1806E ZLL1806E D43‐0WH‐007815P CL LS MOV‐1806E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
71 115‐TLX‐1806E TLX1806E D43‐0WH‐007815P TRQ SW OPRTD MOV‐1806E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation and will return to PLC as a DI.

SB PLC
72 115‐XTM‐1806E XTM1806E D43‐0WH‐007815P TRIP F/B MOV‐1806E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
73 115‐XR‐1806E XR1806E D43‐0WH‐007815P REMOTE SEL MOV‐1806E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation and will return to PLC as a DI.

SB PLC
74 115‐ZSR‐1807AA ZSR1807AA D43‐0WH‐007815P REST POS. LS LRSB‐1807AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
75 115‐ZSF‐1807AA ZSF1807AA D43‐0WH‐007815P F/W POS. LS LRSB‐1807AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
76 115‐WSF‐1807AA WSF1807AA D43‐0WH‐007815P F/W'DING F/B LRSB‐1807AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
77 115‐WSR‐1807AA WSR1807AA D43‐0WH‐007815P R/T'ING F/B LRSB‐1807AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
78 115‐XT‐1807AA XT1807AA D43‐0WH‐007815P TRIP F/B LRSB‐1807AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
79 115‐XA‐1807AA XA1807AA D43‐0WH‐007815P AUTO SEL.   LRSB‐1807AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
80 115‐ZLH‐1807A ZLH1807A D43‐0WH‐007815P OP LS MOV‐1807A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
81 115‐ZLL‐1807A ZLL1807A D43‐0WH‐007815P CL LS MOV‐1807A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
82 115‐TLX‐1807A TLX1807A D43‐0WH‐007815P TRQ SW OPRTD MOV‐1807A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
83 115‐XTM‐1807A XTM1807A D43‐0WH‐007815P TRIP F/B MOV‐1807A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
84 115‐XR‐1807A XR1807A D43‐0WH‐007815P REMOTE SEL MOV‐1807A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
85 115‐ZSR‐1807BB ZSR1807BB D43‐0WH‐007815P REST POS. LS LRSB‐1807BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
86 115‐ZSF‐1807BB ZSF1807BB D43‐0WH‐007815P F/W POS. LS LRSB‐1807BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
87 115‐WSF‐1807BB WSF1807BB D43‐0WH‐007815P F/W'DING F/B LRSB‐1807BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
88 115‐WSR‐1807BB WSR1807BB D43‐0WH‐007815P R/T'ING F/B LRSB‐1807BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
89 115‐XT‐1807BB XT1807BB D43‐0WH‐007815P TRIP F/B LRSB‐1807BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
90 115‐XA‐1807BB XA1807BB D43‐0WH‐007815P AUTO SEL.   LRSB‐1807BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
91 115‐ZLH‐1807B ZLH1807B D43‐0WH‐007815P OP LS MOV‐1807B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
92 115‐ZLL‐1807B ZLL1807B D43‐0WH‐007815P CL LS MOV‐1807B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
93 115‐TLX‐1807B TLX1807B D43‐0WH‐007815P TRQ SW OPRTD MOV‐1807B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
94 115‐XTM‐1807B XTM1807B D43‐0WH‐007815P TRIP F/B MOV‐1807B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
95 115‐XR‐1807B XR1807B D43‐0WH‐007815P REMOTE SEL MOV‐1807B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
96 115‐ZSR‐1807CC ZSR1807CC D43‐0WH‐007815P REST POS. LS LRSB‐1807CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

14-OCT-2019
TANEJA JUHI (MS) (C283)
4
8 of 35

Page 8 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
97 115‐ZSF‐1807CC ZSF1807CC D43‐0WH‐007815P F/W POS. LS LRSB‐1807CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
98 115‐WSF‐1807CC WSF1807CC D43‐0WH‐007815P F/W'DING F/B LRSB‐1807CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
99 115‐WSR‐1807CC WSR1807CC D43‐0WH‐007815P RETRCCTING F/B LRSB‐1807CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
100 115‐XT‐1807CC XT1807CC D43‐0WH‐007815P TRIP F/B LRSB‐1807CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
101 115‐XA‐1807CC XA1807CC D43‐0WH‐007815P AUTO SEL.   LRSB‐1807CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
102 115‐ZLH‐1807C ZLH1807C D43‐0WH‐007815P OP LS MOV‐1807C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
103 115‐ZLL‐1807C ZLL1807C D43‐0WH‐007815P CL LS MOV‐1807C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
104 115‐TLX‐1807C TLX1807C D43‐0WH‐007815P TRQ SW OPRTD MOV‐1807C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
105 115‐XTM‐1807C XTM1807C D43‐0WH‐007815P TRIP F/B MOV‐1807C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
106 115‐XR‐1807C XR1807C D43‐0WH‐007815P REMOTE SEL MOV‐1807C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
107 115‐ZSR‐1807DD ZSR1807DD D43‐0WH‐007815P REST POS. LS LRSB‐1807DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
108 115‐ZSF‐1807DD ZSF1807DD D43‐0WH‐007815P F/W POS. LS LRSB‐1807DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
109 115‐WSF‐1807DD WSF1807DD D43‐0WH‐007815P F/W'DING F/B LRSB‐1807DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
110 115‐WSR‐1807DD WSR1807DD D43‐0WH‐007815P R/T'ING F/B LRSB‐1807DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
111 115‐XT‐1807DD XT1807DD D43‐0WH‐007815P TRIP F/B LRSB‐1807DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
112 115‐XA‐1807DD XA1807DD D43‐0WH‐007815P AUTO SEL.   LRSB‐1807DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
113 115‐ZLH‐1807D ZLH1807D D43‐0WH‐007815P OP LS MOV‐1807D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
114 115‐ZLL‐1807D ZLL1807D D43‐0WH‐007815P CL LS MOV‐1807D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
115 115‐TLX‐1807D TLX1807D D43‐0WH‐007815P TRQ SW OPRTD MOV‐1807D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
116 115‐XTM‐1807D XTM1807D D43‐0WH‐007815P TRIP F/B MOV‐1807D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
117 115‐XR‐1807D XR1807D D43‐0WH‐007815P REMOTE SEL MOV‐1807D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
118 115‐ZSR‐1807EE ZSR1807EE D43‐0WH‐007815P REST POS. LS LRSB‐1807EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
119 115‐ZSF‐1807EE ZSF1807EE D43‐0WH‐007815P F/W POS. LS LRSB‐1807EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
120 115‐WSF‐1807EE WSF1807EE D43‐0WH‐007815P F/W'DING F/B LRSB‐1807EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
121 115‐WSR‐1807EE WSR1807EE D43‐0WH‐007815P R/T'ING F/B LRSB‐1807EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
122 115‐XT‐1807EE XT1807EE D43‐0WH‐007815P TRIP F/B LRSB‐1807EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
123 115‐XA‐1807EE XA1807EE D43‐0WH‐007815P AUTO SEL.   LRSB‐1807EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
5
9 of 35

Page 9 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
124 115‐ZLH‐1807E ZLH1807E D43‐0WH‐007815P OP LS MOV‐1807E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
125 115‐ZLL‐1807E ZLL1807E D43‐0WH‐007815P CL LS MOV‐1807E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
126 115‐TLX‐1807E TLX1807E D43‐0WH‐007815P TRQ SW OPRTD MOV‐1807E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation and will return to PLC as a DI.

SB PLC
127 115‐XTM‐1807E XTM1807E D43‐0WH‐007815P TRIP F/B MOV‐1807E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
128 115‐XR‐1807E XR1807E D43‐0WH‐007815P REMOTE SEL MOV‐1807E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
129 115‐ZSR‐1808AA ZSR1808AA D43‐0WH‐007815P REST POS. LS LRSB‐1808AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
130 115‐ZSF‐1808AA ZSF1808AA D43‐0WH‐007815P F/W POS. LS LRSB‐1808AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
131 115‐WSF‐1808AA WSF1808AA D43‐0WH‐007815P F/W'DING F/B LRSB‐1808AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
132 115‐WSR‐1808AA WSR1808AA D43‐0WH‐007815P R/T'ING F/B LRSB‐1808AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
133 115‐XT‐1808AA XT1808AA D43‐0WH‐007815P TRIP F/B LRSB‐1808AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
134 115‐XA‐1808AA XA1808AA D43‐0WH‐007815P AUTO SEL.   LRSB‐1808AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
135 115‐ZLH‐1808A ZLH1808A D43‐0WH‐007815P OP LS MOV‐1808A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
136 115‐ZLL‐1808A ZLL1808A D43‐0WH‐007815P CL LS MOV‐1808A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
137 115‐TLX‐1808A TLX1808A D43‐0WH‐007815P TRQ SW OPRTD MOV‐1808A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
138 115‐XTM‐1808A XTM1808A D43‐0WH‐007815P TRIP F/B MOV‐1808A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
139 115‐XR‐1808A XR1808A D43‐0WH‐007815P REMOTE SEL MOV‐1808A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
140 115‐ZSR‐1808BB ZSR1808BB D43‐0WH‐007815P REST POS. LS LRSB‐1808BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
141 115‐ZSF‐1808BB ZSF1808BB D43‐0WH‐007815P F/W POS. LS LRSB‐1808BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
142 115‐WSF‐1808BB WSF1808BB D43‐0WH‐007815P F/W'DING F/B LRSB‐1808BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
143 115‐WSR‐1808BB WSR1808BB D43‐0WH‐007815P R/T'ING F/B LRSB‐1808BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
144 115‐XT‐1808BB XT1808BB D43‐0WH‐007815P TRIP F/B LRSB‐1808BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
145 115‐XA‐1808BB XA1808BB D43‐0WH‐007815P AUTO SEL.   LRSB‐1808BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
146 115‐ZLH‐1808B ZLH1808B D43‐0WH‐007815P OP LS MOV‐1808B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
147 115‐ZLL‐1808B ZLL1808B D43‐0WH‐007815P CL LS MOV‐1808B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
148 115‐TLX‐1808B TLX1808B D43‐0WH‐007815P TRQ SW OPRTD MOV‐1808B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
149 115‐XTM‐1808B XTM1808B D43‐0WH‐007815P TRIP F/B MOV‐1808B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
150 115‐XR‐1808B XR1808B D43‐0WH‐007815P REMOTE SEL MOV‐1808B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
6
10 of 35

Page 10 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
151 115‐ZSR‐1808CC ZSR1808CC D43‐0WH‐007815P REST POS. LS LRSB‐1808CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
152 115‐ZSF‐1808CC ZSF1808CC D43‐0WH‐007815P F/W POS. LS LRSB‐1808CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
153 115‐WSF‐1808CC WSF1808CC D43‐0WH‐007815P F/W'DING F/B LRSB‐1808CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
154 115‐WSR‐1808CC WSR1808CC D43‐0WH‐007815P RETRCCTING F/B LRSB‐1808CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
155 115‐XT‐1808CC XT1808CC D43‐0WH‐007815P TRIP F/B LRSB‐1808CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
156 115‐XA‐1808CC XA1808CC D43‐0WH‐007815P AUTO SEL.   LRSB‐1808CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
157 115‐ZLH‐1808C ZLH1808C D43‐0WH‐007815P OP LS MOV‐1808C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
158 115‐ZLL‐1808C ZLL1808C D43‐0WH‐007815P CL LS MOV‐1808C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
159 115‐TLX‐1808C TLX1808C D43‐0WH‐007815P TRQ SW OPRTD MOV‐1808C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
160 115‐XTM‐1808C XTM1808C D43‐0WH‐007815P TRIP F/B MOV‐1808C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
161 115‐XR‐1808C XR1808C D43‐0WH‐007815P REMOTE SEL MOV‐1808C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
162 115‐ZSR‐1808DD ZSR1808DD D43‐0WH‐007815P REST POS. LS LRSB‐1808DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
163 115‐ZSF‐1808DD ZSF1808DD D43‐0WH‐007815P F/W POS. LS LRSB‐1808DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
164 115‐WSF‐1808DD WSF1808DD D43‐0WH‐007815P F/W'DING F/B LRSB‐1808DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
165 115‐WSR‐1808DD WSR1808DD D43‐0WH‐007815P R/T'ING F/B LRSB‐1808DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
166 115‐XT‐1808DD XT1808DD D43‐0WH‐007815P TRIP F/B LRSB‐1808DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
167 115‐XA‐1808DD XA1808DD D43‐0WH‐007815P AUTO SEL.   LRSB‐1808DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
168 115‐ZLH‐1808D ZLH1808D D43‐0WH‐007815P OP LS MOV‐1808D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
169 115‐ZLL‐1808D ZLL1808D D43‐0WH‐007815P CL LS MOV‐1808D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
170 115‐TLX‐1808D TLX1808D D43‐0WH‐007815P TRQ SW OPRTD MOV‐1808D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
171 115‐XTM‐1808D XTM1808D D43‐0WH‐007815P TRIP F/B MOV‐1808D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
172 115‐XR‐1808D XR1808D D43‐0WH‐007815P REMOTE SEL MOV‐1808D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
173 115‐ZSR‐1808EE ZSR1808EE D43‐0WH‐007815P REST POS. LS LRSB‐1808EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
174 115‐ZSF‐1808EE ZSF1808EE D43‐0WH‐007815P F/W POS. LS LRSB‐1808EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
175 115‐WSF‐1808EE WSF1808EE D43‐0WH‐007815P F/W'DING F/B LRSB‐1808EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation and will return to PLC as a DI.

SB PLC
176 115‐WSR‐1808EE WSR1808EE D43‐0WH‐007815P R/T'ING F/B LRSB‐1808EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
177 115‐XT‐1808EE XT1808EE D43‐0WH‐007815P TRIP F/B LRSB‐1808EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
7
11 of 35

Page 11 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
178 115‐XA‐1808EE XA1808EE D43‐0WH‐007815P AUTO SEL.   LRSB‐1808EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
179 115‐ZLH‐1808E ZLH1808E D43‐0WH‐007815P OP LS MOV‐1808E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
180 115‐ZLL‐1808E ZLL1808E D43‐0WH‐007815P CL LS MOV‐1808E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
181 115‐TLX‐1808E TLX1808E D43‐0WH‐007815P TRQ SW OPRTD MOV‐1808E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
182 115‐XTM‐1808E XTM1808E D43‐0WH‐007815P TRIP F/B MOV‐1808E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
183 115‐XR‐1808E XR1808E D43‐0WH‐007815P REMOTE SEL MOV‐1808E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
184 115‐ZSR‐1809AA ZSR1809AA D43‐0WH‐007815P REST POS. LS LRSB‐1809AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
185 115‐ZSF‐1809AA ZSF1809AA D43‐0WH‐007815P F/W POS. LS LRSB‐1809AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
186 115‐WSF‐1809AA WSF1809AA D43‐0WH‐007815P F/W'DING F/B LRSB‐1809AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
187 115‐WSR‐1809AA WSR1809AA D43‐0WH‐007815P R/T'ING F/B LRSB‐1809AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
188 115‐XT‐1809AA XT1809AA D43‐0WH‐007815P TRIP F/B LRSB‐1809AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
189 115‐XA‐1809AA XA1809AA D43‐0WH‐007815P AUTO SEL.   LRSB‐1809AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
190 115‐ZLH‐1809A ZLH1809A D43‐0WH‐007815P OP LS MOV‐1809A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
191 115‐ZLL‐1809A ZLL1809A D43‐0WH‐007815P CL LS MOV‐1809A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
192 115‐TLX‐1809A TLX1809A D43‐0WH‐007815P TRQ SW OPRTD MOV‐1809A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
193 115‐XTM‐1809A XTM1809A D43‐0WH‐007815P TRIP F/B MOV‐1809A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
194 115‐XR‐1809A XR1809A D43‐0WH‐007815P REMOTE SEL MOV‐1809A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
195 115‐ZSR‐1809BB ZSR1809BB D43‐0WH‐007815P REST POS. LS LRSB‐1809BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
196 115‐ZSF‐1809BB ZSF1809BB D43‐0WH‐007815P F/W POS. LS LRSB‐1809BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
197 115‐WSF‐1809BB WSF1809BB D43‐0WH‐007815P F/W'DING F/B LRSB‐1809BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
198 115‐WSR‐1809BB WSR1809BB D43‐0WH‐007815P R/T'ING F/B LRSB‐1809BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
199 115‐XT‐1809BB XT1809BB D43‐0WH‐007815P TRIP F/B LRSB‐1809BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
200 115‐XA‐1809BB XA1809BB D43‐0WH‐007815P AUTO SEL.   LRSB‐1809BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
201 115‐ZLH‐1809B ZLH1809B D43‐0WH‐007815P OP LS MOV‐1809B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
202 115‐ZLL‐1809B ZLL1809B D43‐0WH‐007815P CL LS MOV‐1809B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
203 115‐TLX‐1809B TLX1809B D43‐0WH‐007815P TRQ SW OPRTD MOV‐1809B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
204 115‐XTM‐1809B XTM1809B D43‐0WH‐007815P TRIP F/B MOV‐1809B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
8
12 of 35

Page 12 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
205 115‐XR‐1809B XR1809B D43‐0WH‐007815P REMOTE SEL MOV‐1809B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
206 115‐ZSR‐1809CC ZSR1809CC D43‐0WH‐007815P REST POS. LS LRSB‐1809CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
207 115‐ZSF‐1809CC ZSF1809CC D43‐0WH‐007815P F/W POS. LS LRSB‐1809CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
208 115‐WSF‐1809CC WSF1809CC D43‐0WH‐007815P F/W'DING F/B LRSB‐1809CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
209 115‐WSR‐1809CC WSR1809CC D43‐0WH‐007815P RETRCCTING F/B LRSB‐1809CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
210 115‐XT‐1809CC XT1809CC D43‐0WH‐007815P TRIP F/B LRSB‐1809CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
211 115‐XA‐1809CC XA1809CC D43‐0WH‐007815P AUTO SEL.   LRSB‐1809CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
212 115‐ZLH‐1809C ZLH1809C D43‐0WH‐007815P OP LS MOV‐1809C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
213 115‐ZLL‐1809C ZLL1809C D43‐0WH‐007815P CL LS MOV‐1809C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
214 115‐TLX‐1809C TLX1809C D43‐0WH‐007815P TRQ SW OPRTD MOV‐1809C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
215 115‐XTM‐1809C XTM1809C D43‐0WH‐007815P TRIP F/B MOV‐1809C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
216 115‐XR‐1809C XR1809C D43‐0WH‐007815P REMOTE SEL MOV‐1809C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
217 115‐ZSR‐1809DD ZSR1809DD D43‐0WH‐007815P REST POS. LS LRSB‐1809DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
218 115‐ZSF‐1809DD ZSF1809DD D43‐0WH‐007815P F/W POS. LS LRSB‐1809DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
219 115‐WSF‐1809DD WSF1809DD D43‐0WH‐007815P F/W'DING F/B LRSB‐1809DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
220 115‐WSR‐1809DD WSR1809DD D43‐0WH‐007815P R/T'ING F/B LRSB‐1809DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
221 115‐XT‐1809DD XT1809DD D43‐0WH‐007815P TRIP F/B LRSB‐1809DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
222 115‐XA‐1809DD XA1809DD D43‐0WH‐007815P AUTO SEL.   LRSB‐1809DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
223 115‐ZLH‐1809D ZLH1809D D43‐0WH‐007815P OP LS MOV‐1809D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
224 115‐ZLL‐1809D ZLL1809D D43‐0WH‐007815P CL LS MOV‐1809D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
225 115‐TLX‐1809D TLX1809D D43‐0WH‐007815P TRQ SW OPRTD MOV‐1809D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
226 115‐XTM‐1809D XTM1809D D43‐0WH‐007815P TRIP F/B MOV‐1809D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
227 115‐XR‐1809D XR1809D D43‐0WH‐007815P REMOTE SEL MOV‐1809D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
228 115‐ZSR‐1809EE ZSR1809EE D43‐0WH‐007815P REST POS. LS LRSB‐1809EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
229 115‐ZSF‐1809EE ZSF1809EE D43‐0WH‐007815P F/W POS. LS LRSB‐1809EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
230 115‐WSF‐1809EE WSF1809EE D43‐0WH‐007815P F/W'DING F/B LRSB‐1809EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
231 115‐WSR‐1809EE WSR1809EE D43‐0WH‐007815P R/T'ING F/B LRSB‐1809EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
9
13 of 35

Page 13 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
232 115‐XT‐1809EE XT1809EE D43‐0WH‐007815P TRIP F/B LRSB‐1809EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
233 115‐XA‐1809EE XA1809EE D43‐0WH‐007815P AUTO SEL.   LRSB‐1809EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
234 115‐ZLH‐1809E ZLH1809E D43‐0WH‐007815P OP LS MOV‐1809E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
235 115‐ZLL‐1809E ZLL1809E D43‐0WH‐007815P CL LS MOV‐1809E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation and will return to PLC as a DI.

SB PLC
236 115‐TLX‐1809E TLX1809E D43‐0WH‐007815P TRQ SW OPRTD MOV‐1809E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
237 115‐XTM‐1809E XTM1809E D43‐0WH‐007815P TRIP F/B MOV‐1809E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
238 115‐XR‐1809E XR1809E D43‐0WH‐007815P REMOTE SEL MOV‐1809E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
239 115‐ZSR‐1810AA ZSR1810AA D43‐0WH‐007815P REST POS. LS LRSB‐1810AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
240 115‐ZSF‐1810AA ZSF1810AA D43‐0WH‐007815P F/W POS. LS LRSB‐1810AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
241 115‐WSF‐1810AA WSF1810AA D43‐0WH‐007815P F/W'DING F/B LRSB‐1810AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
242 115‐WSR‐1810AA WSR1810AA D43‐0WH‐007815P R/T'ING F/B LRSB‐1810AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
243 115‐XT‐1810AA XT1810AA D43‐0WH‐007815P TRIP F/B LRSB‐1810AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
244 115‐XA‐1810AA XA1810AA D43‐0WH‐007815P AUTO SEL.   LRSB‐1810AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
245 115‐ZLH‐1810A ZLH1810A D43‐0WH‐007815P OP LS MOV‐1810A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
246 115‐ZLL‐1810A ZLL1810A D43‐0WH‐007815P CL LS MOV‐1810A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
247 115‐TLX‐1810A TLX1810A D43‐0WH‐007815P TRQ SW OPRTD MOV‐1810A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
248 115‐XTM‐1810A XTM1810A D43‐0WH‐007815P TRIP F/B MOV‐1810A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
249 115‐XR‐1810A XR1810A D43‐0WH‐007815P REMOTE SEL MOV‐1810A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
250 115‐ZSR‐1810BB ZSR1810BB D43‐0WH‐007815P REST POS. LS LRSB‐1810BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
251 115‐ZSF‐1810BB ZSF1810BB D43‐0WH‐007815P F/W POS. LS LRSB‐1810BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
252 115‐WSF‐1810BB WSF1810BB D43‐0WH‐007815P F/W'DING F/B LRSB‐1810BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
253 115‐WSR‐1810BB WSR1810BB D43‐0WH‐007815P R/T'ING F/B LRSB‐1810BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
254 115‐XT‐1810BB XT1810BB D43‐0WH‐007815P TRIP F/B LRSB‐1810BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
255 115‐XA‐1810BB XA1810BB D43‐0WH‐007815P AUTO SEL.   LRSB‐1810BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
256 115‐ZLH‐1810B ZLH1810B D43‐0WH‐007815P OP LS MOV‐1810B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
257 115‐ZLL‐1810B ZLL1810B D43‐0WH‐007815P CL LS MOV‐1810B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
258 115‐TLX‐1810B TLX1810B D43‐0WH‐007815P TRQ SW OPRTD MOV‐1810B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
10
14 of 35

Page 14 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
259 115‐XTM‐1810B XTM1810B D43‐0WH‐007815P TRIP F/B MOV‐1810B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
260 115‐XR‐1810B XR1810B D43‐0WH‐007815P REMOTE SEL MOV‐1810B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
261 115‐ZSR‐1810CC ZSR1810CC D43‐0WH‐007815P REST POS. LS LRSB‐1810CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
262 115‐ZSF‐1810CC ZSF1810CC D43‐0WH‐007815P F/W POS. LS LRSB‐1810CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
263 115‐WSF‐1810CC WSF1810CC D43‐0WH‐007815P F/W'DING F/B LRSB‐1810CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
264 115‐WSR‐1810CC WSR1810CC D43‐0WH‐007815P RETRCCTING F/B LRSB‐1810CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
265 115‐XT‐1810CC XT1810CC D43‐0WH‐007815P TRIP F/B LRSB‐1810CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
266 115‐XA‐1810CC XA1810CC D43‐0WH‐007815P AUTO SEL.   LRSB‐1810CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
267 115‐ZLH‐1810C ZLH1810C D43‐0WH‐007815P OP LS MOV‐1810C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
268 115‐ZLL‐1810C ZLL1810C D43‐0WH‐007815P CL LS MOV‐1810C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
269 115‐TLX‐1810C TLX1810C D43‐0WH‐007815P TRQ SW OPRTD MOV‐1810C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
270 115‐XTM‐1810C XTM1810C D43‐0WH‐007815P TRIP F/B MOV‐1810C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
271 115‐XR‐1810C XR1810C D43‐0WH‐007815P REMOTE SEL MOV‐1810C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
272 115‐ZSR‐1810DD ZSR1810DD D43‐0WH‐007815P REST POS. LS LRSB‐1810DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
273 115‐ZSF‐1810DD ZSF1810DD D43‐0WH‐007815P F/W POS. LS LRSB‐1810DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
274 115‐WSF‐1810DD WSF1810DD D43‐0WH‐007815P F/W'DING F/B LRSB‐1810DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
275 115‐WSR‐1810DD WSR1810DD D43‐0WH‐007815P R/T'ING F/B LRSB‐1810DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
276 115‐XT‐1810DD XT1810DD D43‐0WH‐007815P TRIP F/B LRSB‐1810DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
277 115‐XA‐1810DD XA1810DD D43‐0WH‐007815P AUTO SEL.   LRSB‐1810DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
278 115‐ZLH‐1810D ZLH1810D D43‐0WH‐007815P OP LS MOV‐1810D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
279 115‐ZLL‐1810D ZLL1810D D43‐0WH‐007815P CL LS MOV‐1810D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
280 115‐TLX‐1810D TLX1810D D43‐0WH‐007815P TRQ SW OPRTD MOV‐1810D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
281 115‐XTM‐1810D XTM1810D D43‐0WH‐007815P TRIP F/B MOV‐1810D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
282 115‐XR‐1810D XR1810D D43‐0WH‐007815P REMOTE SEL MOV‐1810D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
283 115‐ZSR‐1810EE ZSR1810EE D43‐0WH‐007815P REST POS. LS LRSB‐1810EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
284 115‐ZSF‐1810EE ZSF1810EE D43‐0WH‐007815P F/W POS. LS LRSB‐1810EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation and will return to PLC as a DI.

SB PLC
285 115‐WSF‐1810EE WSF1810EE D43‐0WH‐007815P F/W'DING F/B LRSB‐1810EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
11
15 of 35

Page 15 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
286 115‐WSR‐1810EE WSR1810EE D43‐0WH‐007815P R/T'ING F/B LRSB‐1810EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
287 115‐XT‐1810EE XT1810EE D43‐0WH‐007815P TRIP F/B LRSB‐1810EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
288 115‐XA‐1810EE XA1810EE D43‐0WH‐007815P AUTO SEL.   LRSB‐1810EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
289 115‐ZLH‐1810E ZLH1810E D43‐0WH‐007815P OP LS MOV‐1810E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
290 115‐ZLL‐1810E ZLL1810E D43‐0WH‐007815P CL LS MOV‐1810E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
291 115‐TLX‐1810E TLX1810E D43‐0WH‐007815P TRQ SW OPRTD MOV‐1810E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
292 115‐XTM‐1810E XTM1810E D43‐0WH‐007815P TRIP F/B MOV‐1810E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
293 115‐XR‐1810E XR1810E D43‐0WH‐007815P REMOTE SEL MOV‐1810E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
294 115‐ZSR‐1811AA ZSR1811AA D43‐0WH‐007815P REST POS. LS LRSB‐1811AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
295 115‐ZSF‐1811AA ZSF1811AA D43‐0WH‐007815P F/W POS. LS LRSB‐1811AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
296 115‐WSF‐1811AA WSF1811AA D43‐0WH‐007815P F/W'DING F/B LRSB‐1811AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
297 115‐WSR‐1811AA WSR1811AA D43‐0WH‐007815P R/T'ING F/B LRSB‐1811AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
298 115‐XT‐1811AA XT1811AA D43‐0WH‐007815P TRIP F/B LRSB‐1811AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
299 115‐XA‐1811AA XA1811AA D43‐0WH‐007815P AUTO SEL.   LRSB‐1811AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
300 115‐ZLH‐1811A ZLH1811A D43‐0WH‐007815P OP LS MOV‐1811A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
301 115‐ZLL‐1811A ZLL1811A D43‐0WH‐007815P CL LS MOV‐1811A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
302 115‐TLX‐1811A TLX1811A D43‐0WH‐007815P TRQ SW OPRTD MOV‐1811A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
303 115‐XTM‐1811A XTM1811A D43‐0WH‐007815P TRIP F/B MOV‐1811A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
304 115‐XR‐1811A XR1811A D43‐0WH‐007815P REMOTE SEL MOV‐1811A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
305 115‐ZSR‐1811BB ZSR1811BB D43‐0WH‐007815P REST POS. LS LRSB‐1811BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
306 115‐ZSF‐1811BB ZSF1811BB D43‐0WH‐007815P F/W POS. LS LRSB‐1811BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
307 115‐WSF‐1811BB WSF1811BB D43‐0WH‐007815P F/W'DING F/B LRSB‐1811BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
308 115‐WSR‐1811BB WSR1811BB D43‐0WH‐007815P R/T'ING F/B LRSB‐1811BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
309 115‐XT‐1811BB XT1811BB D43‐0WH‐007815P TRIP F/B LRSB‐1811BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
310 115‐XA‐1811BB XA1811BB D43‐0WH‐007815P AUTO SEL.   LRSB‐1811BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
311 115‐ZLH‐1811B ZLH1811B D43‐0WH‐007815P OP LS MOV‐1811B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
312 115‐ZLL‐1811B ZLL1811B D43‐0WH‐007815P CL LS MOV‐1811B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
12
16 of 35

Page 16 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
313 115‐TLX‐1811B TLX1811B D43‐0WH‐007815P TRQ SW OPRTD MOV‐1811B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
314 115‐XTM‐1811B XTM1811B D43‐0WH‐007815P TRIP F/B MOV‐1811B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
315 115‐XR‐1811B XR1811B D43‐0WH‐007815P REMOTE SEL MOV‐1811B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
316 115‐ZSR‐1811CC ZSR1811CC D43‐0WH‐007815P REST POS. LS LRSB‐1811CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
317 115‐ZSF‐1811CC ZSF1811CC D43‐0WH‐007815P F/W POS. LS LRSB‐1811CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
318 115‐WSF‐1811CC WSF1811CC D43‐0WH‐007815P F/W'DING F/B LRSB‐1811CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
319 115‐WSR‐1811CC WSR1811CC D43‐0WH‐007815P RETRCCTING F/B LRSB‐1811CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
320 115‐XT‐1811CC XT1811CC D43‐0WH‐007815P TRIP F/B LRSB‐1811CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
321 115‐XA‐1811CC XA1811CC D43‐0WH‐007815P AUTO SEL.   LRSB‐1811CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
322 115‐ZLH‐1811C ZLH1811C D43‐0WH‐007815P OP LS MOV‐1811C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
323 115‐ZLL‐1811C ZLL1811C D43‐0WH‐007815P CL LS MOV‐1811C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
324 115‐TLX‐1811C TLX1811C D43‐0WH‐007815P TRQ SW OPRTD MOV‐1811C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
325 115‐XTM‐1811C XTM1811C D43‐0WH‐007815P TRIP F/B MOV‐1811C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
326 115‐XR‐1811C XR1811C D43‐0WH‐007815P REMOTE SEL MOV‐1811C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
327 115‐ZSR‐1811DD ZSR1811DD D43‐0WH‐007815P REST POS. LS LRSB‐1811DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
328 115‐ZSF‐1811DD ZSF1811DD D43‐0WH‐007815P F/W POS. LS LRSB‐1811DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
329 115‐WSF‐1811DD WSF1811DD D43‐0WH‐007815P F/W'DING F/B LRSB‐1811DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
330 115‐WSR‐1811DD WSR1811DD D43‐0WH‐007815P R/T'ING F/B LRSB‐1811DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
331 115‐XT‐1811DD XT1811DD D43‐0WH‐007815P TRIP F/B LRSB‐1811DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
332 115‐XA‐1811DD XA1811DD D43‐0WH‐007815P AUTO SEL.   LRSB‐1811DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
333 115‐ZLH‐1811D ZLH1811D D43‐0WH‐007815P OP LS MOV‐1811D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
334 115‐ZLL‐1811D ZLL1811D D43‐0WH‐007815P CL LS MOV‐1811D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
335 115‐TLX‐1811D TLX1811D D43‐0WH‐007815P TRQ SW OPRTD MOV‐1811D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
336 115‐XTM‐1811D XTM1811D D43‐0WH‐007815P TRIP F/B MOV‐1811D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
337 115‐XR‐1811D XR1811D D43‐0WH‐007815P REMOTE SEL MOV‐1811D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
338 115‐ZSR‐1811EE ZSR1811EE D43‐0WH‐007815P REST POS. LS LRSB‐1811EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
339 115‐ZSF‐1811EE ZSF1811EE D43‐0WH‐007815P F/W POS. LS LRSB‐1811EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
13
17 of 35

Page 17 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
340 115‐WSF‐1811EE WSF1811EE D43‐0WH‐007815P F/W'DING F/B LRSB‐1811EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
341 115‐WSR‐1811EE WSR1811EE D43‐0WH‐007815P R/T'ING F/B LRSB‐1811EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
342 115‐XT‐1811EE XT1811EE D43‐0WH‐007815P TRIP F/B LRSB‐1811EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
343 115‐XA‐1811EE XA1811EE D43‐0WH‐007815P AUTO SEL.   LRSB‐1811EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
344 115‐ZLH‐1811E ZLH1811E D43‐0WH‐007815P OP LS MOV‐1811E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation and will return to PLC as a DI.

SB PLC
345 115‐ZLL‐1811E ZLL1811E D43‐0WH‐007815P CL LS MOV‐1811E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
346 115‐TLX‐1811E TLX1811E D43‐0WH‐007815P TRQ SW OPRTD MOV‐1811E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
347 115‐XTM‐1811E XTM1811E D43‐0WH‐007815P TRIP F/B MOV‐1811E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
348 115‐XR‐1811E XR1811E D43‐0WH‐007815P REMOTE SEL MOV‐1811E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
349 115‐ZSR‐1812AA ZSR1812AA D43‐0WH‐007815P REST POS. LS LRSB‐1812AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
350 115‐ZSF‐1812AA ZSF1812AA D43‐0WH‐007815P F/W POS. LS LRSB‐1812AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
351 115‐WSF‐1812AA WSF1812AA D43‐0WH‐007815P F/W'DING F/B LRSB‐1812AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
352 115‐WSR‐1812AA WSR1812AA D43‐0WH‐007815P R/T'ING F/B LRSB‐1812AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
353 115‐XT‐1812AA XT1812AA D43‐0WH‐007815P TRIP F/B LRSB‐1812AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
354 115‐XA‐1812AA XA1812AA D43‐0WH‐007815P AUTO SEL.   LRSB‐1812AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
355 115‐ZLH‐1812A ZLH1812A D43‐0WH‐007815P OP LS MOV‐1812A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
356 115‐ZLL‐1812A ZLL1812A D43‐0WH‐007815P CL LS MOV‐1812A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
357 115‐TLX‐1812A TLX1812A D43‐0WH‐007815P TRQ SW OPRTD MOV‐1812A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
358 115‐XTM‐1812A XTM1812A D43‐0WH‐007815P TRIP F/B MOV‐1812A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
359 115‐XR‐1812A XR1812A D43‐0WH‐007815P REMOTE SEL MOV‐1812A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
360 115‐ZSR‐1812BB ZSR1812BB D43‐0WH‐007815P REST POS. LS LRSB‐1812BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
361 115‐ZSF‐1812BB ZSF1812BB D43‐0WH‐007815P F/W POS. LS LRSB‐1812BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
362 115‐WSF‐1812BB WSF1812BB D43‐0WH‐007815P F/W'DING F/B LRSB‐1812BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
363 115‐WSR‐1812BB WSR1812BB D43‐0WH‐007815P R/T'ING F/B LRSB‐1812BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
364 115‐XT‐1812BB XT1812BB D43‐0WH‐007815P TRIP F/B LRSB‐1812BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
365 115‐XA‐1812BB XA1812BB D43‐0WH‐007815P AUTO SEL.   LRSB‐1812BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
366 115‐ZLH‐1812B ZLH1812B D43‐0WH‐007815P OP LS MOV‐1812B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
14
18 of 35

Page 18 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
367 115‐ZLL‐1812B ZLL1812B D43‐0WH‐007815P CL LS MOV‐1812B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
368 115‐TLX‐1812B TLX1812B D43‐0WH‐007815P TRQ SW OPRTD MOV‐1812B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
369 115‐XTM‐1812B XTM1812B D43‐0WH‐007815P TRIP F/B MOV‐1812B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
370 115‐XR‐1812B XR1812B D43‐0WH‐007815P REMOTE SEL MOV‐1812B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
371 115‐ZSR‐1812CC ZSR1812CC D43‐0WH‐007815P REST POS. LS LRSB‐1812CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
372 115‐ZSF‐1812CC ZSF1812CC D43‐0WH‐007815P F/W POS. LS LRSB‐1812CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
373 115‐WSF‐1812CC WSF1812CC D43‐0WH‐007815P F/W'DING F/B LRSB‐1812CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
374 115‐WSR‐1812CC WSR1812CC D43‐0WH‐007815P RETRCCTING F/B LRSB‐1812CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
375 115‐XT‐1812CC XT1812CC D43‐0WH‐007815P TRIP F/B LRSB‐1812CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
376 115‐XA‐1812CC XA1812CC D43‐0WH‐007815P AUTO SEL.   LRSB‐1812CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
377 115‐ZLH‐1812C ZLH1812C D43‐0WH‐007815P OP LS MOV‐1812C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
378 115‐ZLL‐1812C ZLL1812C D43‐0WH‐007815P CL LS MOV‐1812C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
379 115‐TLX‐1812C TLX1812C D43‐0WH‐007815P TRQ SW OPRTD MOV‐1812C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
380 115‐XTM‐1812C XTM1812C D43‐0WH‐007815P TRIP F/B MOV‐1812C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
381 115‐XR‐1812C XR1812C D43‐0WH‐007815P REMOTE SEL MOV‐1812C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
382 115‐ZSR‐1812DD ZSR1812DD D43‐0WH‐007815P REST POS. LS LRSB‐1812DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
383 115‐ZSF‐1812DD ZSF1812DD D43‐0WH‐007815P F/W POS. LS LRSB‐1812DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
384 115‐WSF‐1812DD WSF1812DD D43‐0WH‐007815P F/W'DING F/B LRSB‐1812DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
385 115‐WSR‐1812DD WSR1812DD D43‐0WH‐007815P R/T'ING F/B LRSB‐1812DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
386 115‐XT‐1812DD XT1812DD D43‐0WH‐007815P TRIP F/B LRSB‐1812DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
387 115‐XA‐1812DD XA1812DD D43‐0WH‐007815P AUTO SEL.   LRSB‐1812DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
388 115‐ZLH‐1812D ZLH1812D D43‐0WH‐007815P OP LS MOV‐1812D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
389 115‐ZLL‐1812D ZLL1812D D43‐0WH‐007815P CL LS MOV‐1812D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
390 115‐TLX‐1812D TLX1812D D43‐0WH‐007815P TRQ SW OPRTD MOV‐1812D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
391 115‐XTM‐1812D XTM1812D D43‐0WH‐007815P TRIP F/B MOV‐1812D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
392 115‐XR‐1812D XR1812D D43‐0WH‐007815P REMOTE SEL MOV‐1812D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
393 115‐ZSR‐1812EE ZSR1812EE D43‐0WH‐007815P REST POS. LS LRSB‐1812EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation and will return to PLC as a DI.

14-OCT-2019
TANEJA JUHI (MS) (C283)
15
19 of 35

Page 19 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
394 115‐ZSF‐1812EE ZSF1812EE D43‐0WH‐007815P F/W POS. LS LRSB‐1812EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
395 115‐WSF‐1812EE WSF1812EE D43‐0WH‐007815P F/W'DING F/B LRSB‐1812EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
396 115‐WSR‐1812EE WSR1812EE D43‐0WH‐007815P R/T'ING F/B LRSB‐1812EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
397 115‐XT‐1812EE XT1812EE D43‐0WH‐007815P TRIP F/B LRSB‐1812EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
398 115‐XA‐1812EE XA1812EE D43‐0WH‐007815P AUTO SEL.   LRSB‐1812EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
399 115‐ZLH‐1812E ZLH1812E D43‐0WH‐007815P OP LS MOV‐1812E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
400 115‐ZLL‐1812E ZLL1812E D43‐0WH‐007815P CL LS MOV‐1812E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
401 115‐TLX‐1812E TLX1812E D43‐0WH‐007815P TRQ SW OPRTD MOV‐1812E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
402 115‐XTM‐1812E XTM1812E D43‐0WH‐007815P TRIP F/B MOV‐1812E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
403 115‐XR‐1812E XR1812E D43‐0WH‐007815P REMOTE SEL MOV‐1812E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
404 115‐ZSR‐1813AA ZSR1813AA D43‐0WH‐007815P REST POS. LS LRSB‐1813AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
405 115‐ZSF‐1813AA ZSF1813AA D43‐0WH‐007815P F/W POS. LS LRSB‐1813AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
406 115‐WSF‐1813AA WSF1813AA D43‐0WH‐007815P F/W'DING F/B LRSB‐1813AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
407 115‐WSR‐1813AA WSR1813AA D43‐0WH‐007815P R/T'ING F/B LRSB‐1813AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
408 115‐XT‐1813AA XT1813AA D43‐0WH‐007815P TRIP F/B LRSB‐1813AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
409 115‐XA‐1813AA XA1813AA D43‐0WH‐007815P AUTO SEL.   LRSB‐1813AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
410 115‐ZLH‐1813A ZLH1813A D43‐0WH‐007815P OP LS MOV‐1813A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
411 115‐ZLL‐1813A ZLL1813A D43‐0WH‐007815P CL LS MOV‐1813A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
412 115‐TLX‐1813A TLX1813A D43‐0WH‐007815P TRQ SW OPRTD MOV‐1813A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
413 115‐XTM‐1813A XTM1813A D43‐0WH‐007815P TRIP F/B MOV‐1813A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
414 115‐XR‐1813A XR1813A D43‐0WH‐007815P REMOTE SEL MOV‐1813A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
415 115‐ZSR‐1813BB ZSR1813BB D43‐0WH‐007815P REST POS. LS LRSB‐1813BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
416 115‐ZSF‐1813BB ZSF1813BB D43‐0WH‐007815P F/W POS. LS LRSB‐1813BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
417 115‐WSF‐1813BB WSF1813BB D43‐0WH‐007815P F/W'DING F/B LRSB‐1813BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
418 115‐WSR‐1813BB WSR1813BB D43‐0WH‐007815P R/T'ING F/B LRSB‐1813BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
419 115‐XT‐1813BB XT1813BB D43‐0WH‐007815P TRIP F/B LRSB‐1813BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
420 115‐XA‐1813BB XA1813BB D43‐0WH‐007815P AUTO SEL.   LRSB‐1813BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
16
20 of 35

Page 20 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
421 115‐ZLH‐1813B ZLH1813B D43‐0WH‐007815P OP LS MOV‐1813B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
422 115‐ZLL‐1813B ZLL1813B D43‐0WH‐007815P CL LS MOV‐1813B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
423 115‐TLX‐1813B TLX1813B D43‐0WH‐007815P TRQ SW OPRTD MOV‐1813B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
424 115‐XTM‐1813B XTM1813B D43‐0WH‐007815P TRIP F/B MOV‐1813B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
425 115‐XR‐1813B XR1813B D43‐0WH‐007815P REMOTE SEL MOV‐1813B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
426 115‐ZSR‐1813CC ZSR1813CC D43‐0WH‐007815P REST POS. LS LRSB‐1813CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
427 115‐ZSF‐1813CC ZSF1813CC D43‐0WH‐007815P F/W POS. LS LRSB‐1813CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
428 115‐WSF‐1813CC WSF1813CC D43‐0WH‐007815P F/W'DING F/B LRSB‐1813CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
429 115‐WSR‐1813CC WSR1813CC D43‐0WH‐007815P RETRCCTING F/B LRSB‐1813CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
430 115‐XT‐1813CC XT1813CC D43‐0WH‐007815P TRIP F/B LRSB‐1813CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
431 115‐XA‐1813CC XA1813CC D43‐0WH‐007815P AUTO SEL.   LRSB‐1813CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
432 115‐ZLH‐1813C ZLH1813C D43‐0WH‐007815P OP LS MOV‐1813C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
433 115‐ZLL‐1813C ZLL1813C D43‐0WH‐007815P CL LS MOV‐1813C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
434 115‐TLX‐1813C TLX1813C D43‐0WH‐007815P TRQ SW OPRTD MOV‐1813C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
435 115‐XTM‐1813C XTM1813C D43‐0WH‐007815P TRIP F/B MOV‐1813C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
436 115‐XR‐1813C XR1813C D43‐0WH‐007815P REMOTE SEL MOV‐1813C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
437 115‐ZSR‐1813DD ZSR1813DD D43‐0WH‐007815P REST POS. LS LRSB‐1813DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
438 115‐ZSF‐1813DD ZSF1813DD D43‐0WH‐007815P F/W POS. LS LRSB‐1813DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
439 115‐WSF‐1813DD WSF1813DD D43‐0WH‐007815P F/W'DING F/B LRSB‐1813DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
440 115‐WSR‐1813DD WSR1813DD D43‐0WH‐007815P R/T'ING F/B LRSB‐1813DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
441 115‐XT‐1813DD XT1813DD D43‐0WH‐007815P TRIP F/B LRSB‐1813DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
442 115‐XA‐1813DD XA1813DD D43‐0WH‐007815P AUTO SEL.   LRSB‐1813DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
443 115‐ZLH‐1813D ZLH1813D D43‐0WH‐007815P OP LS MOV‐1813D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
444 115‐ZLL‐1813D ZLL1813D D43‐0WH‐007815P CL LS MOV‐1813D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
445 115‐TLX‐1813D TLX1813D D43‐0WH‐007815P TRQ SW OPRTD MOV‐1813D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
446 115‐XTM‐1813D XTM1813D D43‐0WH‐007815P TRIP F/B MOV‐1813D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
447 115‐XR‐1813D XR1813D D43‐0WH‐007815P REMOTE SEL MOV‐1813D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
17
21 of 35

Page 21 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
448 115‐ZSR‐1813EE ZSR1813EE D43‐0WH‐007815P REST POS. LS LRSB‐1813EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
449 115‐ZSF‐1813EE ZSF1813EE D43‐0WH‐007815P F/W POS. LS LRSB‐1813EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
450 115‐WSF‐1813EE WSF1813EE D43‐0WH‐007815P F/W'DING F/B LRSB‐1813EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
451 115‐WSR‐1813EE WSR1813EE D43‐0WH‐007815P R/T'ING F/B LRSB‐1813EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
452 115‐XT‐1813EE XT1813EE D43‐0WH‐007815P TRIP F/B LRSB‐1813EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
453 115‐XA‐1813EE XA1813EE D43‐0WH‐007815P AUTO SEL.   LRSB‐1813EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation and will return to PLC as a DI.

SB PLC
454 115‐ZLH‐1813E ZLH1813E D43‐0WH‐007815P OP LS MOV‐1813E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
455 115‐ZLL‐1813E ZLL1813E D43‐0WH‐007815P CL LS MOV‐1813E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
456 115‐TLX‐1813E TLX1813E D43‐0WH‐007815P TRQ SW OPRTD MOV‐1813E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
457 115‐XTM‐1813E XTM1813E D43‐0WH‐007815P TRIP F/B MOV‐1813E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
458 115‐XR‐1813E XR1813E D43‐0WH‐007815P REMOTE SEL MOV‐1813E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
459 115‐ZSR‐1814AA ZSR1814AA D43‐0WH‐007815P REST POS. LS LRSB‐1814AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
460 115‐ZSF‐1814AA ZSF1814AA D43‐0WH‐007815P F/W POS. LS LRSB‐1814AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
461 115‐WSF‐1814AA WSF1814AA D43‐0WH‐007815P F/W'DING F/B LRSB‐1814AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
462 115‐WSR‐1814AA WSR1814AA D43‐0WH‐007815P R/T'ING F/B LRSB‐1814AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
463 115‐XT‐1814AA XT1814AA D43‐0WH‐007815P TRIP F/B LRSB‐1814AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
464 115‐XA‐1814AA XA1814AA D43‐0WH‐007815P AUTO SEL.   LRSB‐1814AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
465 115‐ZLH‐1814A ZLH1814A D43‐0WH‐007815P OP LS MOV‐1814A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
466 115‐ZLL‐1814A ZLL1814A D43‐0WH‐007815P CL LS MOV‐1814A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
467 115‐TLX‐1814A TLX1814A D43‐0WH‐007815P TRQ SW OPRTD MOV‐1814A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
468 115‐XTM‐1814A XTM1814A D43‐0WH‐007815P TRIP F/B MOV‐1814A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
469 115‐XR‐1814A XR1814A D43‐0WH‐007815P REMOTE SEL MOV‐1814A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
470 115‐ZSR‐1814BB ZSR1814BB D43‐0WH‐007815P REST POS. LS LRSB‐1814BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
471 115‐ZSF‐1814BB ZSF1814BB D43‐0WH‐007815P F/W POS. LS LRSB‐1814BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
472 115‐WSF‐1814BB WSF1814BB D43‐0WH‐007815P F/W'DING F/B LRSB‐1814BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
473 115‐WSR‐1814BB WSR1814BB D43‐0WH‐007815P R/T'ING F/B LRSB‐1814BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
474 115‐XT‐1814BB XT1814BB D43‐0WH‐007815P TRIP F/B LRSB‐1814BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
18
22 of 35

Page 22 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
475 115‐XA‐1814BB XA1814BB D43‐0WH‐007815P AUTO SEL.   LRSB‐1814BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
476 115‐ZLH‐1814B ZLH1814B D43‐0WH‐007815P OP LS MOV‐1814B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
477 115‐ZLL‐1814B ZLL1814B D43‐0WH‐007815P CL LS MOV‐1814B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
478 115‐TLX‐1814B TLX1814B D43‐0WH‐007815P TRQ SW OPRTD MOV‐1814B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
479 115‐XTM‐1814B XTM1814B D43‐0WH‐007815P TRIP F/B MOV‐1814B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
480 115‐XR‐1814B XR1814B D43‐0WH‐007815P REMOTE SEL MOV‐1814B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
481 115‐ZSR‐1814CC ZSR1814CC D43‐0WH‐007815P REST POS. LS LRSB‐1814CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
482 115‐ZSF‐1814CC ZSF1814CC D43‐0WH‐007815P F/W POS. LS LRSB‐1814CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
483 115‐WSF‐1814CC WSF1814CC D43‐0WH‐007815P F/W'DING F/B LRSB‐1814CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
484 115‐WSR‐1814CC WSR1814CC D43‐0WH‐007815P RETRCCTING F/B LRSB‐1814CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
485 115‐XT‐1814CC XT1814CC D43‐0WH‐007815P TRIP F/B LRSB‐1814CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
486 115‐XA‐1814CC XA1814CC D43‐0WH‐007815P AUTO SEL.   LRSB‐1814CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
487 115‐ZLH‐1814C ZLH1814C D43‐0WH‐007815P OP LS MOV‐1814C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
488 115‐ZLL‐1814C ZLL1814C D43‐0WH‐007815P CL LS MOV‐1814C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
489 115‐TLX‐1814C TLX1814C D43‐0WH‐007815P TRQ SW OPRTD MOV‐1814C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
490 115‐XTM‐1814C XTM1814C D43‐0WH‐007815P TRIP F/B MOV‐1814C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
491 115‐XR‐1814C XR1814C D43‐0WH‐007815P REMOTE SEL MOV‐1814C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
492 115‐ZSR‐1814DD ZSR1814DD D43‐0WH‐007815P REST POS. LS LRSB‐1814DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
493 115‐ZSF‐1814DD ZSF1814DD D43‐0WH‐007815P F/W POS. LS LRSB‐1814DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
494 115‐WSF‐1814DD WSF1814DD D43‐0WH‐007815P F/W'DING F/B LRSB‐1814DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
495 115‐WSR‐1814DD WSR1814DD D43‐0WH‐007815P R/T'ING F/B LRSB‐1814DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
496 115‐XT‐1814DD XT1814DD D43‐0WH‐007815P TRIP F/B LRSB‐1814DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
497 115‐XA‐1814DD XA1814DD D43‐0WH‐007815P AUTO SEL.   LRSB‐1814DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
498 115‐ZLH‐1814D ZLH1814D D43‐0WH‐007815P OP LS MOV‐1814D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
499 115‐ZLL‐1814D ZLL1814D D43‐0WH‐007815P CL LS MOV‐1814D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
500 115‐TLX‐1814D TLX1814D D43‐0WH‐007815P TRQ SW OPRTD MOV‐1814D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
501 115‐XTM‐1814D XTM1814D D43‐0WH‐007815P TRIP F/B MOV‐1814D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
19
23 of 35

Page 23 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
502 115‐XR‐1814D XR1814D D43‐0WH‐007815P REMOTE SEL MOV‐1814D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
503 115‐ZSR‐1814EE ZSR1814EE D43‐0WH‐007815P REST POS. LS LRSB‐1814EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
504 115‐ZSF‐1814EE ZSF1814EE D43‐0WH‐007815P F/W POS. LS LRSB‐1814EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
505 115‐WSF‐1814EE WSF1814EE D43‐0WH‐007815P F/W'DING F/B LRSB‐1814EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
506 115‐WSR‐1814EE WSR1814EE D43‐0WH‐007815P R/T'ING F/B LRSB‐1814EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
507 115‐XT‐1814EE XT1814EE D43‐0WH‐007815P TRIP F/B LRSB‐1814EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
508 115‐XA‐1814EE XA1814EE D43‐0WH‐007815P AUTO SEL.   LRSB‐1814EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation and will return to PLC as a DI.

SB PLC
509 115‐ZLH‐1814E ZLH1814E D43‐0WH‐007815P OP LS MOV‐1814E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
510 115‐ZLL‐1814E ZLL1814E D43‐0WH‐007815P CL LS MOV‐1814E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
511 115‐TLX‐1814E TLX1814E D43‐0WH‐007815P TRQ SW OPRTD MOV‐1814E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
512 115‐XTM‐1814E XTM1814E D43‐0WH‐007815P TRIP F/B MOV‐1814E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
513 115‐XR‐1814E XR1814E D43‐0WH‐007815P REMOTE SEL MOV‐1814E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
514 115‐ZSR‐1815AA ZSR1815AA D43‐0WH‐007815P REST POS. LS LRSB‐1815AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
515 115‐ZSF‐1815AA ZSF1815AA D43‐0WH‐007815P F/W POS. LS LRSB‐1815AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
516 115‐WSF‐1815AA WSF1815AA D43‐0WH‐007815P F/W'DING F/B LRSB‐1815AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
517 115‐WSR‐1815AA WSR1815AA D43‐0WH‐007815P R/T'ING F/B LRSB‐1815AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
518 115‐XT‐1815AA XT1815AA D43‐0WH‐007815P TRIP F/B LRSB‐1815AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
519 115‐XA‐1815AA XA1815AA D43‐0WH‐007815P AUTO SEL.   LRSB‐1815AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
520 115‐ZLH‐1815A ZLH1815A D43‐0WH‐007815P OP LS MOV‐1815A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
521 115‐ZLL‐1815A ZLL1815A D43‐0WH‐007815P CL LS MOV‐1815A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
522 115‐TLX‐1815A TLX1815A D43‐0WH‐007815P TRQ SW OPRTD MOV‐1815A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
523 115‐XTM‐1815A XTM1815A D43‐0WH‐007815P TRIP F/B MOV‐1815A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
524 115‐XR‐1815A XR1815A D43‐0WH‐007815P REMOTE SEL MOV‐1815A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
525 115‐ZSR‐1815BB ZSR1815BB D43‐0WH‐007815P REST POS. LS LRSB‐1815BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
526 115‐ZSF‐1815BB ZSF1815BB D43‐0WH‐007815P F/W POS. LS LRSB‐1815BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
527 115‐WSF‐1815BB WSF1815BB D43‐0WH‐007815P F/W'DING F/B LRSB‐1815BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
528 115‐WSR‐1815BB WSR1815BB D43‐0WH‐007815P R/T'ING F/B LRSB‐1815BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
20
24 of 35

Page 24 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
529 115‐XT‐1815BB XT1815BB D43‐0WH‐007815P TRIP F/B LRSB‐1815BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
530 115‐XA‐1815BB XA1815BB D43‐0WH‐007815P AUTO SEL.   LRSB‐1815BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
531 115‐ZLH‐1815B ZLH1815B D43‐0WH‐007815P OP LS MOV‐1815B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
532 115‐ZLL‐1815B ZLL1815B D43‐0WH‐007815P CL LS MOV‐1815B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
533 115‐TLX‐1815B TLX1815B D43‐0WH‐007815P TRQ SW OPRTD MOV‐1815B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
534 115‐XTM‐1815B XTM1815B D43‐0WH‐007815P TRIP F/B MOV‐1815B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
535 115‐XR‐1815B XR1815B D43‐0WH‐007815P REMOTE SEL MOV‐1815B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
536 115‐ZSR‐1815CC ZSR1815CC D43‐0WH‐007815P REST POS. LS LRSB‐1815CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
537 115‐ZSF‐1815CC ZSF1815CC D43‐0WH‐007815P F/W POS. LS LRSB‐1815CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
538 115‐WSF‐1815CC WSF1815CC D43‐0WH‐007815P F/W'DING F/B LRSB‐1815CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
539 115‐WSR‐1815CC WSR1815CC D43‐0WH‐007815P RETRCCTING F/B LRSB‐1815CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
540 115‐XT‐1815CC XT1815CC D43‐0WH‐007815P TRIP F/B LRSB‐1815CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
541 115‐XA‐1815CC XA1815CC D43‐0WH‐007815P AUTO SEL.   LRSB‐1815CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
542 115‐ZLH‐1815C ZLH1815C D43‐0WH‐007815P OP LS MOV‐1815C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
543 115‐ZLL‐1815C ZLL1815C D43‐0WH‐007815P CL LS MOV‐1815C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
544 115‐TLX‐1815C TLX1815C D43‐0WH‐007815P TRQ SW OPRTD MOV‐1815C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
545 115‐XTM‐1815C XTM1815C D43‐0WH‐007815P TRIP F/B MOV‐1815C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
546 115‐XR‐1815C XR1815C D43‐0WH‐007815P REMOTE SEL MOV‐1815C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
547 115‐ZSR‐1815DD ZSR1815DD D43‐0WH‐007815P REST POS. LS LRSB‐1815DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
548 115‐ZSF‐1815DD ZSF1815DD D43‐0WH‐007815P F/W POS. LS LRSB‐1815DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
549 115‐WSF‐1815DD WSF1815DD D43‐0WH‐007815P F/W'DING F/B LRSB‐1815DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
550 115‐WSR‐1815DD WSR1815DD D43‐0WH‐007815P R/T'ING F/B LRSB‐1815DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
551 115‐XT‐1815DD XT1815DD D43‐0WH‐007815P TRIP F/B LRSB‐1815DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
552 115‐XA‐1815DD XA1815DD D43‐0WH‐007815P AUTO SEL.   LRSB‐1815DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
553 115‐ZLH‐1815D ZLH1815D D43‐0WH‐007815P OP LS MOV‐1815D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
554 115‐ZLL‐1815D ZLL1815D D43‐0WH‐007815P CL LS MOV‐1815D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
555 115‐TLX‐1815D TLX1815D D43‐0WH‐007815P TRQ SW OPRTD MOV‐1815D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
21
25 of 35

Page 25 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
556 115‐XTM‐1815D XTM1815D D43‐0WH‐007815P TRIP F/B MOV‐1815D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
557 115‐XR‐1815D XR1815D D43‐0WH‐007815P REMOTE SEL MOV‐1815D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
558 115‐ZSR‐1815EE ZSR1815EE D43‐0WH‐007815P REST POS. LS LRSB‐1815EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
559 115‐ZSF‐1815EE ZSF1815EE D43‐0WH‐007815P F/W POS. LS LRSB‐1815EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
560 115‐WSF‐1815EE WSF1815EE D43‐0WH‐007815P F/W'DING F/B LRSB‐1815EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
561 115‐WSR‐1815EE WSR1815EE D43‐0WH‐007815P R/T'ING F/B LRSB‐1815EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
562 115‐XT‐1815EE XT1815EE D43‐0WH‐007815P TRIP F/B LRSB‐1815EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
563 115‐XA‐1815EE XA1815EE D43‐0WH‐007815P AUTO SEL.   LRSB‐1815EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation and will return to PLC as a DI.

SB PLC
564 115‐ZLH‐1815E ZLH1815E D43‐0WH‐007815P OP LS MOV‐1815E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
565 115‐ZLL‐1815E ZLL1815E D43‐0WH‐007815P CL LS MOV‐1815E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
566 115‐TLX‐1815E TLX1815E D43‐0WH‐007815P TRQ SW OPRTD MOV‐1815E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
567 115‐XTM‐1815E XTM1815E D43‐0WH‐007815P TRIP F/B MOV‐1815E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
568 115‐XR‐1815E XR1815E D43‐0WH‐007815P REMOTE SEL MOV‐1815E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
569 115‐ZSR‐1816AA ZSR1816AA D43‐0WH‐007815P REST POS. LS LRSB‐1816AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
570 115‐ZSF‐1816AA ZSF1816AA D43‐0WH‐007815P F/W POS. LS LRSB‐1816AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
571 115‐WSF‐1816AA WSF1816AA D43‐0WH‐007815P F/W'DING F/B LRSB‐1816AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
572 115‐WSR‐1816AA WSR1816AA D43‐0WH‐007815P R/T'ING F/B LRSB‐1816AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
573 115‐XT‐1816AA XT1816AA D43‐0WH‐007815P TRIP F/B LRSB‐1816AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
574 115‐XA‐1816AA XA1816AA D43‐0WH‐007815P AUTO SEL.   LRSB‐1816AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
575 115‐ZLH‐1816A ZLH1816A D43‐0WH‐007815P OP LS MOV‐1816A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
576 115‐ZLL‐1816A ZLL1816A D43‐0WH‐007815P CL LS MOV‐1816A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
577 115‐TLX‐1816A TLX1816A D43‐0WH‐007815P TRQ SW OPRTD MOV‐1816A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
578 115‐XTM‐1816A XTM1816A D43‐0WH‐007815P TRIP F/B MOV‐1816A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
579 115‐XR‐1816A XR1816A D43‐0WH‐007815P REMOTE SEL MOV‐1816A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
580 115‐ZSR‐1816BB ZSR1816BB D43‐0WH‐007815P REST POS. LS LRSB‐1816BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
581 115‐ZSF‐1816BB ZSF1816BB D43‐0WH‐007815P F/W POS. LS LRSB‐1816BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
582 115‐WSF‐1816BB WSF1816BB D43‐0WH‐007815P F/W'DING F/B LRSB‐1816BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
22
26 of 35

Page 26 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
583 115‐WSR‐1816BB WSR1816BB D43‐0WH‐007815P R/T'ING F/B LRSB‐1816BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
584 115‐XT‐1816BB XT1816BB D43‐0WH‐007815P TRIP F/B LRSB‐1816BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
585 115‐XA‐1816BB XA1816BB D43‐0WH‐007815P AUTO SEL.   LRSB‐1816BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
586 115‐ZLH‐1816B ZLH1816B D43‐0WH‐007815P OP LS MOV‐1816B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
587 115‐ZLL‐1816B ZLL1816B D43‐0WH‐007815P CL LS MOV‐1816B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
588 115‐TLX‐1816B TLX1816B D43‐0WH‐007815P TRQ SW OPRTD MOV‐1816B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
589 115‐XTM‐1816B XTM1816B D43‐0WH‐007815P TRIP F/B MOV‐1816B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
590 115‐XR‐1816B XR1816B D43‐0WH‐007815P REMOTE SEL MOV‐1816B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
591 115‐ZSR‐1816CC ZSR1816CC D43‐0WH‐007815P REST POS. LS LRSB‐1816CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
592 115‐ZSF‐1816CC ZSF1816CC D43‐0WH‐007815P F/W POS. LS LRSB‐1816CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
593 115‐WSF‐1816CC WSF1816CC D43‐0WH‐007815P F/W'DING F/B LRSB‐1816CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
594 115‐WSR‐1816CC WSR1816CC D43‐0WH‐007815P RETRCCTING F/B LRSB‐1816CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
595 115‐XT‐1816CC XT1816CC D43‐0WH‐007815P TRIP F/B LRSB‐1816CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
596 115‐XA‐1816CC XA1816CC D43‐0WH‐007815P AUTO SEL.   LRSB‐1816CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
597 115‐ZLH‐1816C ZLH1816C D43‐0WH‐007815P OP LS MOV‐1816C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
598 115‐ZLL‐1816C ZLL1816C D43‐0WH‐007815P CL LS MOV‐1816C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
599 115‐TLX‐1816C TLX1816C D43‐0WH‐007815P TRQ SW OPRTD MOV‐1816C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
600 115‐XTM‐1816C XTM1816C D43‐0WH‐007815P TRIP F/B MOV‐1816C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
601 115‐XR‐1816C XR1816C D43‐0WH‐007815P REMOTE SEL MOV‐1816C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
602 115‐ZSR‐1816DD ZSR1816DD D43‐0WH‐007815P REST POS. LS LRSB‐1816DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
603 115‐ZSF‐1816DD ZSF1816DD D43‐0WH‐007815P F/W POS. LS LRSB‐1816DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
604 115‐WSF‐1816DD WSF1816DD D43‐0WH‐007815P F/W'DING F/B LRSB‐1816DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
605 115‐WSR‐1816DD WSR1816DD D43‐0WH‐007815P R/T'ING F/B LRSB‐1816DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
606 115‐XT‐1816DD XT1816DD D43‐0WH‐007815P TRIP F/B LRSB‐1816DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
607 115‐XA‐1816DD XA1816DD D43‐0WH‐007815P AUTO SEL.   LRSB‐1816DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
608 115‐ZLH‐1816D ZLH1816D D43‐0WH‐007815P OP LS MOV‐1816D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
609 115‐ZLL‐1816D ZLL1816D D43‐0WH‐007815P CL LS MOV‐1816D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
23
27 of 35

Page 27 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
610 115‐TLX‐1816D TLX1816D D43‐0WH‐007815P TRQ SW OPRTD MOV‐1816D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
611 115‐XTM‐1816D XTM1816D D43‐0WH‐007815P TRIP F/B MOV‐1816D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
612 115‐XR‐1816D XR1816D D43‐0WH‐007815P REMOTE SEL MOV‐1816D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
613 115‐ZSR‐1816EE ZSR1816EE D43‐0WH‐007815P REST POS. LS LRSB‐1816EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
614 115‐ZSF‐1816EE ZSF1816EE D43‐0WH‐007815P F/W POS. LS LRSB‐1816EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
615 115‐WSF‐1816EE WSF1816EE D43‐0WH‐007815P F/W'DING F/B LRSB‐1816EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
616 115‐WSR‐1816EE WSR1816EE D43‐0WH‐007815P R/T'ING F/B LRSB‐1816EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
617 115‐XT‐1816EE XT1816EE D43‐0WH‐007815P TRIP F/B LRSB‐1816EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
618 115‐XA‐1816EE XA1816EE D43‐0WH‐007815P AUTO SEL.   LRSB‐1816EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation and will return to PLC as a DI.

SB PLC
619 115‐ZLH‐1816E ZLH1816E D43‐0WH‐007815P OP LS MOV‐1816E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
620 115‐ZLL‐1816E ZLL1816E D43‐0WH‐007815P CL LS MOV‐1816E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
621 115‐TLX‐1816E TLX1816E D43‐0WH‐007815P TRQ SW OPRTD MOV‐1816E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
622 115‐XTM‐1816E XTM1816E D43‐0WH‐007815P TRIP F/B MOV‐1816E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
623 115‐XR‐1816E XR1816E D43‐0WH‐007815P REMOTE SEL MOV‐1816E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
624 115‐ZSR‐1817AA ZSR1817AA D43‐0WH‐007815P REST POS. LS LRSB‐1817AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
625 115‐ZSF‐1817AA ZSF1817AA D43‐0WH‐007815P F/W POS. LS LRSB‐1817AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
626 115‐WSF‐1817AA WSF1817AA D43‐0WH‐007815P F/W'DING F/B LRSB‐1817AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
627 115‐WSR‐1817AA WSR1817AA D43‐0WH‐007815P R/T'ING F/B LRSB‐1817AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
628 115‐XT‐1817AA XT1817AA D43‐0WH‐007815P TRIP F/B LRSB‐1817AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
629 115‐XA‐1817AA XA1817AA D43‐0WH‐007815P AUTO SEL.   LRSB‐1817AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
630 115‐ZLH‐1817A ZLH1817A D43‐0WH‐007815P OP LS MOV‐1817A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
631 115‐ZLL‐1817A ZLL1817A D43‐0WH‐007815P CL LS MOV‐1817A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
632 115‐TLX‐1817A TLX1817A D43‐0WH‐007815P TRQ SW OPRTD MOV‐1817A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
633 115‐XTM‐1817A XTM1817A D43‐0WH‐007815P TRIP F/B MOV‐1817A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
634 115‐XR‐1817A XR1817A D43‐0WH‐007815P REMOTE SEL MOV‐1817A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
635 115‐ZSR‐1817BB ZSR1817BB D43‐0WH‐007815P REST POS. LS LRSB‐1817BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
636 115‐ZSF‐1817BB ZSF1817BB D43‐0WH‐007815P F/W POS. LS LRSB‐1817BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
24
28 of 35

Page 28 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
637 115‐WSF‐1817BB WSF1817BB D43‐0WH‐007815P F/W'DING F/B LRSB‐1817BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
638 115‐WSR‐1817BB WSR1817BB D43‐0WH‐007815P R/T'ING F/B LRSB‐1817BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
639 115‐XT‐1817BB XT1817BB D43‐0WH‐007815P TRIP F/B LRSB‐1817BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
640 115‐XA‐1817BB XA1817BB D43‐0WH‐007815P AUTO SEL.   LRSB‐1817BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
641 115‐ZLH‐1817B ZLH1817B D43‐0WH‐007815P OP LS MOV‐1817B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
642 115‐ZLL‐1817B ZLL1817B D43‐0WH‐007815P CL LS MOV‐1817B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
643 115‐TLX‐1817B TLX1817B D43‐0WH‐007815P TRQ SW OPRTD MOV‐1817B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
644 115‐XTM‐1817B XTM1817B D43‐0WH‐007815P TRIP F/B MOV‐1817B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
645 115‐XR‐1817B XR1817B D43‐0WH‐007815P REMOTE SEL MOV‐1817B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
646 115‐ZSR‐1817CC ZSR1817CC D43‐0WH‐007815P REST POS. LS LRSB‐1817CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
647 115‐ZSF‐1817CC ZSF1817CC D43‐0WH‐007815P F/W POS. LS LRSB‐1817CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
648 115‐WSF‐1817CC WSF1817CC D43‐0WH‐007815P F/W'DING F/B LRSB‐1817CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
649 115‐WSR‐1817CC WSR1817CC D43‐0WH‐007815P RETRCCTING F/B LRSB‐1817CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
650 115‐XT‐1817CC XT1817CC D43‐0WH‐007815P TRIP F/B LRSB‐1817CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
651 115‐XA‐1817CC XA1817CC D43‐0WH‐007815P AUTO SEL.   LRSB‐1817CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
652 115‐ZLH‐1817C ZLH1817C D43‐0WH‐007815P OP LS MOV‐1817C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
653 115‐ZLL‐1817C ZLL1817C D43‐0WH‐007815P CL LS MOV‐1817C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
654 115‐TLX‐1817C TLX1817C D43‐0WH‐007815P TRQ SW OPRTD MOV‐1817C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
655 115‐XTM‐1817C XTM1817C D43‐0WH‐007815P TRIP F/B MOV‐1817C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
656 115‐XR‐1817C XR1817C D43‐0WH‐007815P REMOTE SEL MOV‐1817C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
657 115‐ZSR‐1817DD ZSR1817DD D43‐0WH‐007815P REST POS. LS LRSB‐1817DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
658 115‐ZSF‐1817DD ZSF1817DD D43‐0WH‐007815P F/W POS. LS LRSB‐1817DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
659 115‐WSF‐1817DD WSF1817DD D43‐0WH‐007815P F/W'DING F/B LRSB‐1817DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
660 115‐WSR‐1817DD WSR1817DD D43‐0WH‐007815P R/T'ING F/B LRSB‐1817DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
661 115‐XT‐1817DD XT1817DD D43‐0WH‐007815P TRIP F/B LRSB‐1817DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
662 115‐XA‐1817DD XA1817DD D43‐0WH‐007815P AUTO SEL.   LRSB‐1817DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
663 115‐ZLH‐1817D ZLH1817D D43‐0WH‐007815P OP LS MOV‐1817D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
25
29 of 35

Page 29 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
664 115‐ZLL‐1817D ZLL1817D D43‐0WH‐007815P CL LS MOV‐1817D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
665 115‐TLX‐1817D TLX1817D D43‐0WH‐007815P TRQ SW OPRTD MOV‐1817D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
666 115‐XTM‐1817D XTM1817D D43‐0WH‐007815P TRIP F/B MOV‐1817D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
667 115‐XR‐1817D XR1817D D43‐0WH‐007815P REMOTE SEL MOV‐1817D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
668 115‐ZSR‐1817EE ZSR1817EE D43‐0WH‐007815P REST POS. LS LRSB‐1817EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
669 115‐ZSF‐1817EE ZSF1817EE D43‐0WH‐007815P F/W POS. LS LRSB‐1817EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
670 115‐WSF‐1817EE WSF1817EE D43‐0WH‐007815P F/W'DING F/B LRSB‐1817EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
671 115‐WSR‐1817EE WSR1817EE D43‐0WH‐007815P R/T'ING F/B LRSB‐1817EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
672 115‐XT‐1817EE XT1817EE D43‐0WH‐007815P TRIP F/B LRSB‐1817EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
673 115‐XA‐1817EE XA1817EE D43‐0WH‐007815P AUTO SEL.   LRSB‐1817EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation and will return to PLC as a DI.

SB PLC
674 115‐ZLH‐1817E ZLH1817E D43‐0WH‐007815P OP LS MOV‐1817E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
675 115‐ZLL‐1817E ZLL1817E D43‐0WH‐007815P CL LS MOV‐1817E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
676 115‐TLX‐1817E TLX1817E D43‐0WH‐007815P TRQ SW OPRTD MOV‐1817E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
677 115‐XTM‐1817E XTM1817E D43‐0WH‐007815P TRIP F/B MOV‐1817E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
678 115‐XR‐1817E XR1817E D43‐0WH‐007815P REMOTE SEL MOV‐1817E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
679 115‐ZSR‐1818AA ZSR1818AA D43‐0WH‐007815P REST POS. LS LRSB‐1818AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
680 115‐ZSF‐1818AA ZSF1818AA D43‐0WH‐007815P F/W POS. LS LRSB‐1818AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
681 115‐WSF‐1818AA WSF1818AA D43‐0WH‐007815P F/W'DING F/B LRSB‐1818AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
682 115‐WSR‐1818AA WSR1818AA D43‐0WH‐007815P R/T'ING F/B LRSB‐1818AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
683 115‐XT‐1818AA XT1818AA D43‐0WH‐007815P TRIP F/B LRSB‐1818AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
684 115‐XA‐1818AA XA1818AA D43‐0WH‐007815P AUTO SEL.   LRSB‐1818AA DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

SB PLC
685 115‐ZLH‐1818A ZLH1818A D43‐0WH‐007815P OP LS MOV‐1818A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
686 115‐ZLL‐1818A ZLL1818A D43‐0WH‐007815P CL LS MOV‐1818A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
687 115‐TLX‐1818A TLX1818A D43‐0WH‐007815P TRQ SW OPRTD MOV‐1818A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
688 115‐XTM‐1818A XTM1818A D43‐0WH‐007815P TRIP F/B MOV‐1818A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
689 115‐XR‐1818A XR1818A D43‐0WH‐007815P REMOTE SEL MOV‐1818A DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
690 115‐ZSR‐1818BB ZSR1818BB D43‐0WH‐007815P REST POS. LS LRSB‐1818BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation and will return to PLC as a DI.

14-OCT-2019
TANEJA JUHI (MS) (C283)
26
30 of 35

Page 30 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
691 115‐ZSF‐1818BB ZSF1818BB D43‐0WH‐007815P F/W POS. LS LRSB‐1818BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
692 115‐WSF‐1818BB WSF1818BB D43‐0WH‐007815P F/W'DING F/B LRSB‐1818BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
693 115‐WSR‐1818BB WSR1818BB D43‐0WH‐007815P R/T'ING F/B LRSB‐1818BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
694 115‐XT‐1818BB XT1818BB D43‐0WH‐007815P TRIP F/B LRSB‐1818BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
695 115‐XA‐1818BB XA1818BB D43‐0WH‐007815P AUTO SEL.   LRSB‐1818BB DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
696 115‐ZLH‐1818B ZLH1818B D43‐0WH‐007815P OP LS MOV‐1818B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
697 115‐ZLL‐1818B ZLL1818B D43‐0WH‐007815P CL LS MOV‐1818B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
698 115‐TLX‐1818B TLX1818B D43‐0WH‐007815P TRQ SW OPRTD MOV‐1818B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
699 115‐XTM‐1818B XTM1818B D43‐0WH‐007815P TRIP F/B MOV‐1818B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
700 115‐XR‐1818B XR1818B D43‐0WH‐007815P REMOTE SEL MOV‐1818B DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+10650 Elevation

SB PLC
701 115‐ZSR‐1818CC ZSR1818CC D43‐0WH‐007815P REST POS. LS LRSB‐1818CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
702 115‐ZSF‐1818CC ZSF1818CC D43‐0WH‐007815P F/W POS. LS LRSB‐1818CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
703 115‐WSF‐1818CC WSF1818CC D43‐0WH‐007815P F/W'DING F/B LRSB‐1818CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
704 115‐WSR‐1818CC WSR1818CC D43‐0WH‐007815P RETRCCTING F/B LRSB‐1818CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
705 115‐XT‐1818CC XT1818CC D43‐0WH‐007815P TRIP F/B LRSB‐1818CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
706 115‐XA‐1818CC XA1818CC D43‐0WH‐007815P AUTO SEL.   LRSB‐1818CC DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
707 115‐ZLH‐1818C ZLH1818C D43‐0WH‐007815P OP LS MOV‐1818C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
708 115‐ZLL‐1818C ZLL1818C D43‐0WH‐007815P CL LS MOV‐1818C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
709 115‐TLX‐1818C TLX1818C D43‐0WH‐007815P TRQ SW OPRTD MOV‐1818C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
710 115‐XTM‐1818C XTM1818C D43‐0WH‐007815P TRIP F/B MOV‐1818C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
711 115‐XR‐1818C XR1818C D43‐0WH‐007815P REMOTE SEL MOV‐1818C DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
712 115‐ZSR‐1818DD ZSR1818DD D43‐0WH‐007815P REST POS. LS LRSB‐1818DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
713 115‐ZSF‐1818DD ZSF1818DD D43‐0WH‐007815P F/W POS. LS LRSB‐1818DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
714 115‐WSF‐1818DD WSF1818DD D43‐0WH‐007815P F/W'DING F/B LRSB‐1818DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation 24 VDC +ve will go to SB PDB pot. free contact 
and will return to PLC as a DI.
SB PLC
715 115‐WSR‐1818DD WSR1818DD D43‐0WH‐007815P R/T'ING F/B LRSB‐1818DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
716 115‐XT‐1818DD XT1818DD D43‐0WH‐007815P TRIP F/B LRSB‐1818DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
717 115‐XA‐1818DD XA1818DD D43‐0WH‐007815P AUTO SEL.   LRSB‐1818DD DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

14-OCT-2019
TANEJA JUHI (MS) (C283)
27
31 of 35

Page 31 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC
718 115‐ZLH‐1818D ZLH1818D D43‐0WH‐007815P OP LS MOV‐1818D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
719 115‐ZLL‐1818D ZLL1818D D43‐0WH‐007815P CL LS MOV‐1818D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
720 115‐TLX‐1818D TLX1818D D43‐0WH‐007815P TRQ SW OPRTD MOV‐1818D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation and will return to PLC as a DI.

SB PLC
721 115‐XTM‐1818D XTM1818D D43‐0WH‐007815P TRIP F/B MOV‐1818D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
722 115‐XR‐1818D XR1818D D43‐0WH‐007815P REMOTE SEL MOV‐1818D DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+7000 Elevation

SB PLC
723 115‐ZSR‐1818EE ZSR1818EE D43‐0WH‐007815P REST POS. LS LRSB‐1818EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
724 115‐ZSF‐1818EE ZSF1818EE D43‐0WH‐007815P F/W POS. LS LRSB‐1818EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
725 115‐WSF‐1818EE WSF1818EE D43‐0WH‐007815P F/W'DING F/B LRSB‐1818EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
726 115‐WSR‐1818EE WSR1818EE D43‐0WH‐007815P R/T'ING F/B LRSB‐1818EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
727 115‐XT‐1818EE XT1818EE D43‐0WH‐007815P TRIP F/B LRSB‐1818EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC 24 VDC +ve will go to SB PDB pot. free contact 
728 115‐XA‐1818EE XA1818EE D43‐0WH‐007815P AUTO SEL.   LRSB‐1818EE DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation and will return to PLC as a DI.

SB PLC
729 115‐ZLH‐1818E ZLH1818E D43‐0WH‐007815P OP LS MOV‐1818E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
730 115‐ZLL‐1818E ZLL1818E D43‐0WH‐007815P CL LS MOV‐1818E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
731 115‐TLX‐1818E TLX1818E D43‐0WH‐007815P TRQ SW OPRTD MOV‐1818E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
732 115‐XTM‐1818E XTM1818E D43‐0WH‐007815P TRIP F/B MOV‐1818E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC
733 115‐XR‐1818E XR1818E D43‐0WH‐007815P REMOTE SEL MOV‐1818E DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Interrogation Voltage 24V DC, 2A
+4200 Elevation

SB PLC Interrogation Voltage 24V DC, 2A 
734 115‐HSO‐1801 HSO1801 D43‐0WH‐007815P SB'ING SEQ STR PB  Push Button DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+4200 Elevation from SB PLC

SB PLC Interrogation Voltage 24V DC, 2A 
735 115‐HS‐1801 HS1801 D43‐0WH‐007815P SB'ING SEQ RESET PB  Push Button DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+4200 Elevation from SB PLC

SB PLC Interrogation Voltage 24V DC, 2A 
736 115‐HSC‐1801 HSC1801 D43‐0WH‐007815P SB'ING SEQ STP  PB Push Button DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ YES ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS  These are Push Buttons on Soot Blower PLC.
+4200 Elevation from SB PLC

SB PLC Interrogation Voltage 24V DC, 2A 
737 115‐XS‐1801 XS1801 D43‐0WH‐007815P SB Hooter Test PB Push Button DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ MTS D84‐4WH‐000237 Non IS 
+4200 Elevation from SB PLC

SB PLC Interrogation Voltage 24V DC, 2A 
738 115‐XAA‐1801 XAA1801 D43‐0WH‐007815P HOOTER/ALARM ACCEPT PB Push Button DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+4200 Elevation from SB PLC

SB PLC Interrogation Voltage 24V DC, 2A 
739 115‐HSO‐1801‐1 HSO1801‐1 D43‐0WH‐007815P SB'ING SEQ STR PB  From DCS DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+4200 Elevation from SB PLC 24 VDC +ve will go to DCS pot. free contact 
and will return to SB PLC as a DI. (Note‐c)
SB PLC Interrogation Voltage 24V DC, 2A 
740 115‐HSC‐1801‐1 HSC1801‐1 D43‐0WH‐007815P  SB'ING SEQ STP  PB From DCS DI‐POT. FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NC D84‐4WH‐000237 Non IS 
+4200 Elevation from SB PLC

741 115‐HS‐1801‐1 HS1801‐1 D43‐0WH‐007815P SB'ING SEQ RESET PB From DCS ‐ DI‐SERIAL Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 NA Communication through Modbus
Refer Modbus Mapping List for details. (Note‐
c)
742 115‐XAA‐1801‐1 XAA1801‐1 D43‐0WH‐007815P HOOTER/ALARM ACCEPT PB From DCS ‐ DI‐SERIAL Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 NA Communication through Modbus

14-OCT-2019
TANEJA JUHI (MS) (C283)
1
32 of 35

Page 32 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

DIGITAL OUTPUT

SB PLC Interrogation Voltage 24V DC from 
1 115‐HSO‐1819 HSO1819 D43‐0WH‐007815P SB‐PLC OP CMD MOV‐1819 DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Relay ‐ Pot. Free Dry DO
+4200 Elevation MOV

SB PLC Interrogation Voltage 24V DC from 
2 115‐HSC‐1819 HSC1819 D43‐0WH‐007815P SB‐PLC CL CMD MOV‐1819 DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Relay ‐ Pot. Free Dry DO
+4200 Elevation MOV

SB PLC Interrogation Voltage 24V DC from 
3 115‐HSO‐1820 HSO1820 D43‐0WH‐007815P SB‐PLC OP CMD MOV‐1820 DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Relay ‐ Pot. Free Dry DO
+4200 Elevation MOV

SB PLC Interrogation Voltage 24V DC from 
4 115‐HSC‐1820 HSC1820 D43‐0WH‐007815P SB‐PLC CL CMD MOV‐1820 DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Relay ‐ Pot. Free Dry DO
+4200 Elevation MOV

SB PLC Interrogation Voltage 24V DC from 
5 115‐HSO‐1821 HSO1821 D43‐0WH‐007815P SB‐PLC OP CMD MOV‐1821 DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Relay ‐ Pot. Free Dry DO
+4200 Elevation MOV

SB PLC Interrogation Voltage 24V DC from 
6 115‐HSC‐1821 HSC1821 D43‐0WH‐007815P SB‐PLC CL CMD MOV‐1821 DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  Relay ‐ Pot. Free Dry DO
+4200 Elevation MOV

SB PLC DO Relay; Pot. Free Dry contact / 
7 115‐HSO‐1806A HSO1806A D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1806AA DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
8 115‐HSO‐1806B HSO1806B D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1806BB DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC
240VAC Phase will come from SB MCC to DO 
SB PLC DO Relay; Pot. Free Dry contact /  Relay pot free contact and will return to SB 
9 115‐HSO‐1806C HSO1806C D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1806CC DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC MCC through DO for actuating the auxilary 
contactor.
SB PLC DO Relay; Pot. Free Dry contact / 
10 115‐HSO‐1806D HSO1806D D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1806DD DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
11 115‐HSO‐1806E HSO1806E D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1806EE DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+4200 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
12 115‐HSO‐1807A HSO1807A D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1807AA DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
13 115‐HSO‐1807B HSO1807B D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1807BB DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC
240VAC Phase will come from SB MCC to DO 
SB PLC DO Relay; Pot. Free Dry contact /  Relay pot free contact and will return to SB 
14 115‐HSO‐1807C HSO1807C D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1807CC DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC MCC through DO for actuating the auxilary 
contactor.
SB PLC DO Relay; Pot. Free Dry contact / 
15 115‐HSO‐1807D HSO1807D D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1807DD DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
16 115‐HSO‐1807E HSO1807E D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1807EE DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+4200 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
17 115‐HSO‐1808A HSO1808A D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1808AA DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
18 115‐HSO‐1808B HSO1808B D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1808BB DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC
240VAC Phase will come from SB MCC to DO 
SB PLC DO Relay; Pot. Free Dry contact /  Relay pot free contact and will return to SB 
19 115‐HSO‐1808C HSO1808C D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1808CC DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC MCC through DO for actuating the auxilary 
contactor.
SB PLC DO Relay; Pot. Free Dry contact / 
20 115‐HSO‐1808D HSO1808D D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1808DD DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
21 115‐HSO‐1808E HSO1808E D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1808EE DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+4200 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact /  240VAC Phase will come from SB MCC to DO 


22 115‐HSO‐1809A HSO1809A D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1809AA DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC Relay pot free contact and will return to SB 
MCC through DO for actuating the auxilary 
SB PLC DO Relay; Pot. Free Dry contact / 
23 115‐HSO‐1809B HSO1809B D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1809BB DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  contactor.
+10650 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
24 115‐HSO‐1809C HSO1809C D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1809CC DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC
240VAC Phase will come from SB MCC to DO 
SB PLC DO Relay; Pot. Free Dry contact /  Relay pot free contact and will return to SB 
25 115‐HSO‐1809D HSO1809D D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1809DD DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC MCC through DO for actuating the auxilary 
contactor.
SB PLC DO Relay; Pot. Free Dry contact / 
26 115‐HSO‐1809E HSO1809E D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1809EE DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+4200 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
27 115‐HSO‐1810A HSO1810A D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1810AA DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC
240VAC Phase will come from SB MCC to DO 
SB PLC DO Relay; Pot. Free Dry contact /  Relay pot free contact and will return to SB 
28 115‐HSO‐1810B HSO1810B D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1810BB DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
14-OCT-2019 +10650 Elevation suitable for 230 VAC MCC through DO for actuating the auxilary 
contactor.
TANEJA JUHI HSO1810C
(MS) (C283)D43‐0WH‐007815P SB PLC DO Relay; Pot. Free Dry contact / 
29 115‐HSO‐1810C SB‐PLC STR CMD LRSB‐1810CC DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC
29
33 of 35

Page 33 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 

SB PLC DO Relay; Pot. Free Dry contact /  240VAC Phase will come from SB MCC to DO 


30 115‐HSO‐1810D HSO1810D D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1810DD DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC Relay pot free contact and will return to SB 
MCC through DO for actuating the auxilary 
SB PLC DO Relay; Pot. Free Dry contact / 
31 115‐HSO‐1810E HSO1810E D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1810EE DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  contactor.
+4200 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
32 115‐HSO‐1811A HSO1811A D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1811AA DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
33 115‐HSO‐1811B HSO1811B D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1811BB DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC
240VAC Phase will come from SB MCC to DO 
SB PLC DO Relay; Pot. Free Dry contact /  Relay pot free contact and will return to SB 
34 115‐HSO‐1811C HSO1811C D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1811CC DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC MCC through DO for actuating the auxilary 
contactor.
SB PLC DO Relay; Pot. Free Dry contact / 
35 115‐HSO‐1811D HSO1811D D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1811DD DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
36 115‐HSO‐1811E HSO1811E D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1811EE DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+4200 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
37 115‐HSO‐1812A HSO1812A D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1812AA DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
38 115‐HSO‐1812B HSO1812B D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1812BB DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC
240VAC Phase will come from SB MCC to DO 
SB PLC DO Relay; Pot. Free Dry contact /  Relay pot free contact and will return to SB 
39 115‐HSO‐1812C HSO1812C D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1812CC DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC MCC through DO for actuating the auxilary 
contactor.
SB PLC DO Relay; Pot. Free Dry contact / 
40 115‐HSO‐1812D HSO1812D D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1812DD DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
41 115‐HSO‐1812E HSO1812E D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1812EE DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+4200 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
42 115‐HSO‐1813A HSO1813A D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1813AA DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
43 115‐HSO‐1813B HSO1813B D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1813BB DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC
240VAC Phase will come from SB MCC to DO 
SB PLC DO Relay; Pot. Free Dry contact /  Relay pot free contact and will return to SB 
44 115‐HSO‐1813C HSO1813C D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1813CC DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC MCC through DO for actuating the auxilary 
contactor.
SB PLC DO Relay; Pot. Free Dry contact / 
45 115‐HSO‐1813D HSO1813D D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1813DD DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
46 115‐HSO‐1813E HSO1813E D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1813EE DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+4200 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
47 115‐HSO‐1814A HSO1814A D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1814AA DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
48 115‐HSO‐1814B HSO1814B D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1814BB DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC
240VAC Phase will come from SB MCC to DO 
SB PLC DO Relay; Pot. Free Dry contact /  Relay pot free contact and will return to SB 
49 115‐HSO‐1814C HSO1814C D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1814CC DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC MCC through DO for actuating the auxilary 
contactor.
SB PLC DO Relay; Pot. Free Dry contact / 
50 115‐HSO‐1814D HSO1814D D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1814DD DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
51 115‐HSO‐1814E HSO1814E D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1814EE DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+4200 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
52 115‐HSO‐1815A HSO1815A D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1815AA DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
53 115‐HSO‐1815B HSO1815B D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1815BB DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC
240VAC Phase will come from SB MCC to DO 
SB PLC DO Relay; Pot. Free Dry contact /  Relay pot free contact and will return to SB 
54 115‐HSO‐1815C HSO1815C D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1815CC DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC MCC through DO for actuating the auxilary 
contactor.
SB PLC DO Relay; Pot. Free Dry contact / 
55 115‐HSO‐1815D HSO1815D D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1815DD DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
56 115‐HSO‐1815E HSO1815E D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1815EE DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+4200 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
57 115‐HSO‐1816A HSO1816A D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1816AA DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
58 115‐HSO‐1816B HSO1816B D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1816BB DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
14-OCT-2019 +10650 Elevation suitable for 230 VAC
240VAC Phase will come from SB MCC to DO
TANEJA JUHI (MS) (C283)
30
34 of 35

Page 34 of 35
PLANT: DRPP, LEKKI FREE TRADE ZONE, NIGERIA 4 17/9/2019 TJB NVK NVK DRAWING NO

CLIENT: M/S DANGOTE OIL REFINING COMPANY LTD. 3 24/5/2019 TJB NVK NVK


DORC DOC. No.: 
DIVISION : ENGINEERING
A545‐7950‐5043‐VD‐LW1001 & LW1002‐3007
ENGINEERS INDIA LIMITED    CONSULTANT: EIL  2 12/2/2019 TJB NVK NVK

NEW DELHI EIL JOB No.: A545 1 23/05/2016 TJB NVK NVK ElL Doc. No.: DORL‐FGSG‐7940‐059

PACKAGE / UNIT NO.: 115‐LW‐1001 & 1002 0 18/3/2016 TJB NVK NVK TL Doc. No.: D65‐WH‐CS‐00661


DEPT :
INSTRUMENTATION
SUPPLY: FLUE GAS STEAM GENERATOR PACKAGE REVISION DATE PREPARED BY CHECKED BY APP. BY REV. 3

POINT DATA BASE FOR  SB‐PLC
LOCATION: SB‐PLC (Located at Field on FGSG Structure)

Tag No. DISPLAY RANGE SET POINT FOR ALARM    TEMP SENSOR


 CONTROL  ROOM /  LOOP TYPE LINEAR /   CONTROL  CONT.  FAILURE CONTACT  FUNCTIONAL /   IS/ 
 SI No    PID No TAG COMMENT  SIGNAL TYPE  ENGG UNIT  REMARK NOTES ID
 SRR NO  (OPEN / CLOSE) SQ. ROOT ACTION  ALGORITHM  POS  STATUS  LOGIC DIAG Non‐IS
HIGH LOW BURNOUT
INSTRUMENT  SYSTEM MIN MAX HIGH LOW TYPE
HIGH  LOW  STATUS 
240VAC Phase will come from SB MCC to DO 
SB PLC DO Relay; Pot. Free Dry contact /  Relay pot free contact and will return to SB 
59 115‐HSO‐1816C HSO1816C D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1816CC DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC MCC through DO for actuating the auxilary 
contactor.
SB PLC DO Relay; Pot. Free Dry contact / 
60 115‐HSO‐1816D HSO1816D D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1816DD DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
61 115‐HSO‐1816E HSO1816E D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1816EE DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+4200 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
62 115‐HSO‐1817A HSO1817A D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1817AA DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
63 115‐HSO‐1817B HSO1817B D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1817BB DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC
240VAC Phase will come from SB MCC to DO 
SB PLC DO Relay; Pot. Free Dry contact /  Relay pot free contact and will return to SB 
64 115‐HSO‐1817C HSO1817C D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1817CC DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC MCC through DO for actuating the auxilary 
contactor.
SB PLC DO Relay; Pot. Free Dry contact / 
65 115‐HSO‐1817D HSO1817D D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1817DD DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
66 115‐HSO‐1817E HSO1817E D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1817EE DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+4200 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
67 115‐HSO‐1818A HSO1818A D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1818AA DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
68 115‐HSO‐1818B HSO1818B D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1818BB DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+10650 Elevation suitable for 230 VAC
240VAC Phase will come from SB MCC to DO 
SB PLC DO Relay; Pot. Free Dry contact /  Relay pot free contact and will return to SB 
69 115‐HSO‐1818C HSO1818C D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1818CC DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC MCC through DO for actuating the auxilary 
contactor.
SB PLC DO Relay; Pot. Free Dry contact / 
70 115‐HSO‐1818D HSO1818D D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1818DD DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+7000 Elevation suitable for 230 VAC

SB PLC DO Relay; Pot. Free Dry contact / 
71 115‐HSO‐1818E HSO1818E D43‐0WH‐007815P SB‐PLC STR CMD LRSB‐1818EE DO‐POT FREE Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS 
+4200 Elevation suitable for 230 VAC

SB PLC These Signals are Lamp Indications on Soot 
72 115‐ASR‐1801 ASR1801 D43‐0WH‐007815P ALL SB IN REST POS. Lamp DO‐WET Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  DO Relay: Wet 24 V DC
+4200 Elevation Blower PLC Panel.

SB PLC These Signals are Lamp Indications on Soot 
73 115‐SBA‐1801 SBA1801 D43‐0WH‐007815P SB IN AUTO Lamp DO‐WET Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  DO Relay: Wet 24 V DC
+4200 Elevation Blower PLC Panel.

SB PLC These Signals are Lamp Indications on Soot 
74 115‐ASO‐1801 ASO1801 D43‐0WH‐007815P AUTO SEQ ON Lamp DO‐WET Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  DO Relay: Wet 24 V DC
+4200 Elevation Blower PLC Panel.

SB PLC These Signals are Lamp Indications on Soot 
75 115‐ASC‐1801 ASC1801 D43‐0WH‐007815P AUTO SEQ COMPLETED Lamp DO‐WET Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  DO Relay: Wet 24 V DC
+4200 Elevation Blower PLC Panel.

SB PLC These Signals are Lamp Indications on Soot 
76 115‐MF‐1801 MF1801 D43‐0WH‐007815P MECHNICAL FAULT Lamp DO‐WET Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  DO Relay: Wet 24 V DC
+4200 Elevation Blower PLC Panel.

SB PLC These Signals are Lamp Indications on Soot 
77 115‐TO‐1801 TO1801 D43‐0WH‐007815P MP STM TEMP OK Lamp DO‐WET Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  DO Relay: Wet 24 V DC
+4200 Elevation Blower PLC Panel.

SB PLC These Signals are Lamp Indications on Soot 
78 115‐PO‐1801 PO1801 D43‐0WH‐007815P MP STM PRESS OK Lamp DO‐WET Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  DO Relay: Wet 24 V DC
+4200 Elevation Blower PLC Panel.

SB PLC These Signals are Lamp Indications on Soot 
79 115‐PO‐1802 PO1802 D43‐0WH‐007815P SA PRESS OK Lamp DO‐WET Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4WH‐000237 Non IS  DO Relay: Wet 24 V DC
+4200 Elevation Blower PLC Panel.

MECHNICAL FAULT ALARM ‐  SB PLC
80 681‐HTR‐1801 HTR1801 D43‐0WH‐007815P Hooter DO‐WET Open ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ ‐ NO D84‐4HR‐000172 Non IS  DO Relay: Wet 24 V DC Hooter located on SB PLC Panel.
HOOTER +4200 Elevation

Note:
1. Soot Blower PLC & Soot Blower PDB shall be kept side‐by‐side in Field on FGSG Structure. All SB PLC Panels and SB PDB Panels are distributed through‐out Elevation +4200, +7000, +10650 (Refer Annexure‐I for typical represenattion of distribution of Panels). Communication from SB PLC to Customer DCS shall be through Modbus (Modbus cable from SB PLC to DCS shall be in customer's scope).