Sunteți pe pagina 1din 16

Product Bulletin

62.1:DVC6000f
D103199X012
February 2010 DVC6000f Digital Valve Controllers

Fisherr FIELDVUEt DVC6000f Digital Valve


Controllers
FIELDVUE DVC6000f digital valve controllers for DVC6000f digital valve controllers can be mounted
FOUNDATIONt fieldbus are interoperable, on sliding−stem actuators, as shown in figure 1, or
communicating, microprocessor−based, on rotary actuators, as shown in figure 2. The
digital−to−pneumatic instruments. In addition to the DVC6000f mounts on most Fisher actuators, as well
primary function of converting a digital input signal to as other manufacturers’ rotary and sliding−stem
a pneumatic output, the DVC6000f digital valve actuators.
controller, using FOUNDATION fieldbus In new or existing installations, the DVC6000f digital
communications protocol, gives easy access to valve controller’s two−wire design avoids the high
information critical to process operation as well as cost of running separate power and signal wiring by
process control. This can be done using a DeltaVt allowing you to use the existing wiring. FOUNDATION
console, another FOUNDATION fieldbus system fieldbus allows multiple instruments to operate on a
console, or with ValveLinkt software. two−wire pair, thus reducing overall installation
costs.

W9132−1
W8115−FF

Figure 1. FIELDVUE DVC6010f Digital Valve Controller Figure 2. Rotary Control Valve with FIELDVUE DVC6020f
Mounted on Fisher 585C Piston Actuator Digital Valve Controller

www.Fisher.com
Product Bulletin
62.1:DVC6000f
DVC6000f Digital Valve Controller February 2010

Specifications
Available Configurations 511—Low−power signaling, bus−powered, FISCO
DVC6010f: Sliding−stem applications I.S.
DVC6020f: Rotary and long−stroke sliding−stem
applications [over 102 mm (4 inch) travel] Fieldbus Device Capabilities
DVC6030f: Quarter−turn rotary applications
Backup Link Master capable
Remote−Mounted Instrument(1)
DVC6005f: Base unit for 2 inch pipestand or wall Output Signal(2)
mounting
Pneumatic signal as required by the actuator, up
DVC6015: Feedback unit for sliding−stem
to full supply pressure.
applications
Minimum Span: 0.4 bar (6 psig)
DVC6025: Feedback unit for rotary or long−stroke
Maximum Span: 9.5 bar (140 psig)
sliding−stem applications
Action: Double, Single direct, and Single reverse
DVC6035: Feedback unit for quarter−turn rotary
applications
DVC6000f digital valve controllers can be Supply Pressure(2)(6)
mounted on Fisher and other manufacturers’
rotary and sliding−stem actuators. Recommended: 0.3 bar (5 psi) higher than
maximum actuator requirements, up to maximum
supply pressure
Control Level
Maximum: 10 bar (145 psig) or maximum
J Standard Control (throttling control) pressure rating of the actuator, whichever is lower
Includes AO, PID, ISEL, OS, AI, MAI, DO, and
four DI function blocks Medium: Air or Natural Gas(7)
J Fieldbus Control (throttling control) Air Quality: Supply pressure must be clean, dry
AO function block air that meets the requirements of ISA Standard
J Fieldbus Logic [discrete (on/off) connectivity] 7.0.01. A maximum 40 micrometer particle size in
Includes DO, and four DI function blocks the air system is acceptable. Further filtration
down to 5 micrometer particle size is
Block Execution Times recommended. Lubricant content is not to exceed
AO Block: 15 ms AI Block: 15 ms 1 ppm weight (w/w) or volume (v/v) basis.
PID Block: 20 ms MAI BLock: 35 ms Condensation in the air supply should be
ISEL Block: 20 ms DO Block: 15 ms minimized
OS Block: 20 ms DI Block: 15 ms
Natural Gas: Natural gas must be clean, dry,
oil−free, and noncorrosive. H2S content should
Electrical Input not exceed 20 ppm.
Voltage Level: 9 to 32 volts
Maximum Current: 18 mA
Reverse Polarity Protection: Unit is not polarity Steady−State Air Consumption(2)(3)(4)
sensitive
Termination: Bus must be properly terminated Standard Relay: At 1.4 bar (20 psig) supply
per ISA SP50 guidelines pressure: Less than 0.38 normal m3/hr (14 scfh)
At 5.5 bar (80 psig) supply pressure: Less than
Digital Communication Protocol 1.3 normal m3/hr (49 scfh)
FOUNDATION fieldbus registered device Low Bleed Relay: At 1.4 bar (20 psig) supply
pressure: Average value 0.056 normal m3/hr
Physical Layer Type(s): (2.1 scfh)
121—Low−power signaling, bus−powered, Entity At 5.5 bar (80 psig) supply pressure: Average
Model I.S. value 0.184 normal m3/hr (6.9 scfh)
−continued−

2
Product Bulletin
62.1:DVC6000f
February 2010 DVC6000f Digital Valve Controller

Specifications (continued)
Maximum Output Capacity(3)(4) ATEX—Intrinsically Safe and FISCO, Flameproof,
At 1.4 bar (20 psig) supply pressure: Type n
10.0 normal m3/hr (375 scfh) IECEx—Intrinsically Safe and FISCO,
At 5.5 bar (80 psig) supply pressure: Flameproof, Type n
29.5 normal m3/hr (1100 scfh) NEPSI—Intrinsically Safe, Flameproof
Independent Linearity(2)(5) Refer to tables 4, 5, 6, 7, and 8 for specific
approval information
±0.50% of output span
Electrical Housing.
Electromagnetic Compatibility CSA—Type 4X, IP66
Meets EN 61326−1 (First Edition) FM—NEMA 4X
Immunity—Industrial locations per Table 2 of
the EN 61326−1 standard. Performance is ATEX—IP66
shown in table 3 below IECEx—NEMA 4X, IP66
Emissions—Class A NEPSI—IP66
ISM equipment rating: Group 1, Class A
Lightning and Surge Protection—The degree of Other Classifications/Certifications
immunity to lightning is specified as Surge TIIS—Japan
immunity in table 3. For additional surge
protection commercially available transient GOST−R—Russian GOST−R
protection devices can be used. FSETAN—Russian − Federal Service of
Technological, Ecological and Nuclear
Vibration Testing Method Inspectorate
Tested per ANSI/ISA−75.13.01 Section 5.3.5. A INMETRO—Brazil
resonant frequency search is performed on all Contact your Emerson Process Management
three axes. The instrument is subjected to the ISA sales office for classification/certification specific
specified 1/2 hour endurance test at each major information
resonance, plus an additional two million cycles.
Connections
Humidity Limits
Supply Pressure: 1/4 NPT internal and integral
Tested per IEC 61514−2 pad for mounting 67CFR regulator
Output Pressure: 1/4 NPT internal
Operating Ambient Temperature Limits(6) Tubing: 3/8−inch recommended
Vent: 3/8 NPT internal
−40 to 80_C (−40 to 176_F) for most approved
Electrical: 1/2 NPT internal, M20 adapter
valve−mounted instruments
optional
−60 to 125_C (−76 to 257_F) for remote−mounted
feedback units Construction Materials
−52 to 80_C (−62 to 176_F) for valve−mounted
instruments utilizing the Extreme Temperature Housing, module base and terminal box:
option (fluorosilicone elastomers) ASTM B85 A03600 low copper aluminum alloy
(standard)
Electrical Classification CF8M (cast 316 stainless steel) (optional for
valve−mounted instruments only)
CSA—Intrinsically Safe and FISCO, Explosion Cover: Thermoplastic polyester
proof, Division 2, Dust−Ignition proof Elastomers
FM—Intrinsically Safe and FISCO, Explosion Standard: Nitrile
proof, Non−incendive, Dust−Ignition proof Optional: Fluorosilicone
−continued−

3
Product Bulletin
62.1:DVC6000f
DVC6000f Digital Valve Controller February 2010

Specifications (continued)
Stem/Shaft Travel Weight
Valve−Mounted Instruments
Linear Actuators with rated travel between 6.35
mm (0.25 inch) and 606 mm (23.375 inches) Aluminum: 3.5 Kg (7.7 lbs)
Stainless Steel: 7.7 Kg (17 lbs)
Remote−Mounted Instruments
Rotary Actuators with rated travel between 50 DVC6005f Base Unit: 4.1 Kg (9 lbs)
degrees and 180 degrees DVC6015 Feedback Unit: 1.3 Kg (2.9 lbs)
DVC6025 Feedback Unit: 1.4 Kg (3.1 lbs)
DVC6035 Feedback Unit: 0.9 Kg (2.0 lbs)

Mounting Options
J Supply and output pressure gauges or J Tire
Designed for direct actuator mounting or remote valves, J Integral mounted filter regulator,
pipestand or wall mounting. Mounting the J Stainless steel housing, module base and
instrument vertically, with the vent at the bottom terminal box (valve−mounted instruments only)
of the assembly, or horizontally, with the vent J Control Level: Standard Control, Fieldbus
pointing down, is recommended to allow drainage Control, or Fieldbus Logic
of moisture that may be introduced via the J Diagnostic Level: Performance Diagnostics,
instrument air supply. Advanced Diagnostics, or Fieldbus Diagnostics
1. 3−conductor shielded cable, 22 AWG minimum wire size, is recommended for connection between base unit and feedback unit. Pneumatic tubing between base unit output connection and
actuator has been tested to 15 meters (50 feet) maximum without performance degradation.
2. Defined in ISA Standard S51.1.
3. Normal m3/hour − Normal cubic meters per hour at 0_C and 1.01325 bar, absolute. Scfh − Standard cubic feet per hour at 60_F and 14.7 psia.
4. Values at 1.4 bar (20 psig) based on a single−acting direct relay; values at 5.5 bar (80 psig) based on double−acting relay.
5. Typical value. Not applicable for travels less than 19 mm (0.75 inch) or for shaft rotation less than 60 degrees. Also, not applicable to DVC6020f digital valve controllers in long−stroke
applications.
6. The pressure/temperature limits in this document and any applicable code or standard should not be exceeded.
7. Gas Certified DVC6000 digital valve controllers are FM and CSA Single Seal approved for use with natural gas as the supply medium.

Features D Enhanced Safety—You can check instrument


and valve operation and keep the process running
D EDD Availability—An extended device smoothly and safely from a remote location. Access
description is available for the DVC6000f digital is possible at a field junction box, marshalling panel,
valve controller. Using this file, any EDD compatible or within the safety of the control room using either a
host can provide graphic user interface to the Field Communicator, personal computer, or a
DVC6000f configuration, calibration, and diagnostic system workstation. Your exposure to hazardous
capabilities. environments is minimized and you can avoid having
to access hard−to−reach valve locations.

D Improved Control—Two−way digital D Hardware Savings—DVC6000f digital valve


communications give you current valve conditions. controllers, when used in an integrated system,
You can use this real−time information to make allow you to realize significant hardware and
sound process management decisions. By analyzing installation cost savings by replacing other devices
valve dynamics through ValveLink software you can in the process loop, such as positioners and limit
identify control areas needing improvement and switches, with a FIELDVUE digital valve controller.
maintain a high level of system performance.
D Travel Control−Pressure Fallback—Valve
position feedback is critical to the operation of a
D Valve and Actuator Data at your digital valve controller. Without this feedback, the
Fingertips—Accurate information is the key to valve control valve assembly traditionally goes to its fail
diagnostics. Valve and actuator spec sheet data for safe position. The DVC6000f can detect position
diagnostic use are embedded in the DVC6000f feedback problems caused by a travel sensor failure
instrument during factory mounting, providing or linkage failure and continue to operate in
up−to−date and accurate information. “pressure control” mode.

4
Product Bulletin
62.1:DVC6000f
February 2010 DVC6000f Digital Valve Controller
If a problem with the valve position feedback is Instrument Blocks
detected, the instrument will automatically disable
the travel sensor, send an alert, and control it’s The digital valve controller is a block−based device.
output pressure much like a fieldbus−to−pressure All DVC6000f digital valve controllers include the
transducer. This allows the valve assembly to resource and transducer block:
continue to operate with reduced accuracy until
maintenance can be scheduled.
Resource Block—The resource block contains the
hardware specific characteristics associated with a
D Built to Survive—Field−tough DVC6000f device; it has no input or output parameters. The
digital valve controllers have fully encapsulated resource block monitors and controls the general
printed wiring boards that resist the effects of operation of other blocks within the device. For
vibration, temperature, and corrosive atmospheres. example, when the mode of the resource block is
A separate weather−tight field wiring terminal box Out of Service, it impacts all function blocks.
isolates field−wiring connections from other areas of
the instrument. Optional stainless steel, remote
mount, and extreme temperature constructions Transducer Block—The transducer block connects
provide added durability to any application need. the analog output function block to the I/P converter,
relay, and travel sensor hardware within the digital
valve controller.
D Increased Uptime—With the self−diagnostic
capability of DVC6000f digital valve controllers, you
can answer questions about a valve’s performance,
without pulling the valve from the line. Diagnostics Control Function Blocks
that evaluate the health of the valve assembly, such
as instrument supply pressure droop, valve stuck, In addition to the resource and transducer block, the
damaged feedback, friction, deadband analysis and digital valve controller, depending on control and
trending, run continuously while the valve is in diagnostic capability, may contain the following
service and operating. You can also compare the control function blocks. See table 1 for control level
present valve/actuator signature (bench set, seat details.
load, friction, etc.) against previously stored
signatures to discover performance changes, before
they impact process control.
Note

D Faster Commissioning—The two−way The Fieldbus Foundation logo


communication capability allows you to quickly indicates that the function block is
commission loops by remotely identifying each certified as interoperable by the
instrument, verifying its calibration, reviewing stored Fieldbus Foundation.
maintenance notes, and more.
The AO function block provides analog
D Upgrades Made Easy—Using FIELDVUE output capability as defined by the Fieldbus
HotLinkt technology, firmware upgrades can be Foundation. The AO function block
downloaded to the DVC6000f instrument over the provides a connection to the positioning
fieldbus segment wiring, with minimal interruption to algorithm (transducer block).
process operations. This unique capability lets you
take advantage of firmware improvements and
increase functionality, while making the upgrade The PID function block provides
process fast and convenient right from the control proportion−plus−integral−plus−derivative
room. control for the inputs to the function block
and drives the outputs.
D Easy Maintenance—The DVC6000f is
modular in design. The single module base can be The ISEL function block selects from up to
removed from the instrument housing without four inputs and may provide the selected
disconnecting the field wiring, pneumatic signal as input to the PID function block.
connections or stem linkages. This module contains The input selection can be configured to
the critical sub−modules so component removal is select the first good input signal; a maximum,
quick and simple. minimum or average value; or a hot spare.

5
Product Bulletin
62.1:DVC6000f
DVC6000f Digital Valve Controller February 2010

Table 1. Control Level Details


CONTROL LEVEL OPTIONS
FUNCTION BLOCKS Fieldbus Logic (FL) Fieldbus Control (FC) Standard Control (SC)
On/Off Throttling Throttling
Resource n n n
Transducer n n n
Analog Output (AO) n n
Proportional/Integral/Derivative (PID) n
Input Selector (ISEL) n
Output Splitter (OS) n
Analog Input (AI) n
Multiple Analog Input (MAI) n
Discrete Output (DO) n n
Discrete Input (DI) (quantity 4) n n

The OS function block accepts the output The DI function block processes a single
from another function block (such as a PID discrete input from a field device and
block) and creates two outputs that are makes it available to other function blocks.
scaled or split, according to the user In the digital valve controller, the discrete
configuration. This block is typically used for split input function block can provide limit switch
ranging of two control valves. functionality and valve position proximity detection.

The AI function block monitors device The DO and DI function blocks in a DVC6000f
measurements from a DVC6000f and instrument can also provide dribble control using 5%
provides it as an output to another block. positioning. In a batch environment, vessels are
filled through on−off valves for speed, but there can
be a problem at shutoff. The amount of material may
The MAI function block has the ability to not be “close enough” for the recipe and additional
process up to eight device measurements material may have to be added. This addition can be
from a DVC6000f and make them available tricky and/or time consuming for the operator. The
to other function blocks. capability of being able to “crack” the valve to 5 to
10% and “dribble” in the correct amount either
The DO function block processes a manually or automatically through recipe control can
discrete set point and sends it to a provide significant reduction in variability, and
specified output channel. In the digital reduction in “FDA−like” reporting and certification. In
valve controller, the discrete output block addition, it can eliminate the need for a second
provides both normal open/closed control and the smaller on−off valve or the operator climbing up and
ability to position the valve in 5% increments for dumping in a pail of material to add “just the right
course throttling applications. amount.”

6
Product Bulletin
62.1:DVC6000f
February 2010 DVC6000f Digital Valve Controller

W9210−1

Figure 3. PlantWeb Alerts, Displayed on a DeltaV Host System

Table 2. FIELDVUE DVC6000f Diagnostic Level Capabilities Additional Performance Diagnostic testing that can
DIAGNOSTIC LEVEL be scheduled or run manually during on−line
CAPABILITY operation include:
FD AD PD
Auto Calibration n n n
Custom Characterization n n n
Alerts n n n
D On−Line Friction and Deadband Analysis
Step Response, Drive Signal Test & (see figure 4)
Dynamic Error Band, Valve n n
Signature
Travel Control—Pressure Fallback n n D Friction and Deadband Trending
Performance Diagnostics n

While all diagnostics can be run while the valve is


inline, Performance Diagnostics can be performed
while the valve is in service and operating.
Diagnostic Capabilities (see table 2)

Performance Diagnostics
Advanced Diagnostics
The latest generation of Fisher FIELDVUE
diagnostics, Performance Diagnostics (PD), are now Advanced Diagnostics include the following dynamic
built right into the DVC6000f. These diagnostics scan tests:
allow the DVC6000f to continuously perform checks
on the valve assembly without disturbing or
interrupting the control valve while it is in the D Valve Signature (see figure 5)
process. Actuator/tubing leakage, air supply
availability, calibration shift, and other issues are
continuously reviewed and evaluated. The D Dynamic Error Band
DVC6000f can then automatically trigger PlantWeb
alerts, as shown in figure 3, that forewarn the user of
issues before they impact process operation. D Instrument Drive Signal

7
Product Bulletin
62.1:DVC6000f
DVC6000f Digital Valve Controller February 2010

W7468/IL

Figure 5. Valve Signature Display

Fieldbus Diagnostics
Figure 4. Valve Friction and Deadband Analysis Fieldbus Diagnostics capabilities include the
following diagnostics:

D Key Valve Parameters

These diagnostics are run while the control valve is The key valve parameters allow you to monitor the
blocked out and not controlling the process. The total valve stem travel (travel accumulation) and the
diagnostic scans vary the positioner set point at a number of stem travel reversals (cycles).
controlled rate and plot valve operation to determine
valve dynamic performance. The valve signature test D Instrument Health Parameters
allows you to determine the valve/actuator friction,
bench set, spring rate, and seat load. The Dynamic The instrument health parameters alert you if there
Error Band test is a combination of hysteresis and are any problems with the instrument memory,
deadband plus “slewing.” Hysteresis and deadband processor, or sensors. Should a problem occur, you
are static measurements. However, because the can define how the instrument will react to the
valve is moving, a dynamic error, or “slewing” error problem. You can also select which problems will
is introduced. cause the instrument to shutdown. These indicators
may be reported as alerts. Monitoring these alerts
can give you an instant indication of any problems
with the instrument or the valve assembly.
Dynamic scan tests give a better indication of how
the valve will operate under process conditions
which are dynamic, not static. PlantWeb Alerts
The DVC6000f provides two levels of alerts;
Instrument alerts and PlantWeb alerts.
The Step Response Test checks the valve Instrument alerts, when enabled, detect many
assembly’s response to a changing input signal and operational and performance issues that may be of
plots travel versus time. The end results of this test interest. To view these alerts, the user must open
allow you to evaluate the dynamic performance of the appropriate status screen for a specific device
the valve. The Performance Step Test provides a host such as DeltaV, ValveLink software or a Field
standardized step test with which to evaluate your Communicator.
valve performance. It utilizes small, medium and
Some instrument alerts can also be used to trigger
large changes.
PlantWeb alerts that will be reported in Failed,
Maintenance or Advisory categories, as configured
by the user (refer to figure 3). PlantWeb alerts, when
Advanced Diagnostics are performed with ValveLink enabled, are visible through the DeltaV alarm
software. The valve must be out of service for interface tools, such as the alarm banner and the
Advanced Diagnostics to be performed. alarm summary object.

8
Product Bulletin
62.1:DVC6000f
February 2010 DVC6000f Digital Valve Controller
When a PlantWeb alert occurs, the DVC6000f sends
an event notification and waits a specified period of
time for an acknowledgment to be received. This
occurs even if the condition that caused the alert no
longer exists. If the acknowledgment is not received
within the pre−specified time−out period, the event
notification is retransmitted. This reduces the
possibility of alert messages getting lost.

ValveLink Software

ValveLink software is a WindowsR−based software


package that allows easy access to the information
available from DVC6000f digital valve controllers.

W9128
Using ValveLink software, you can monitor the
performance characteristics of the valve and obtain
Figure 6. 375 Field Communicator
vital information without having to pull the valve from
the line. Performance Diagnostic tests, including
On−Line Friction, Deadband Analysis and Trending
can be run while the valve is in service and
operating. Valve Signature, Dynamic Error Band,
and Step Response are displayed in an intuitive Installation
user−friendly environment that allows easy
The DVC6010f digital valve controller is designed for
interpretation of data.
yoke mounting to sliding stem actuators. DVC6020f
digital valve controllers are designed for mounting to
rotary actuators or long stroke sliding stem actuators
Diagnostic graphs can be superimposed over those
(over 4 inches travel). DVC6030f digital valve
previously stored to view areas of valve degradation.
controllers are designed for mounting on virtually
This allows plant personnel to concentrate efforts on
any quarter−turn actuator.
equipment that needs repair, avoiding unnecessary
maintenance. This diagnostic capability is readily
accessible and available to you either in the control The DVC6005f digital valve controller base unit may
room or on the plant floor. In addition to the be remote mounted on a 2 inch pipestand or a wall.
diagnostic features, ValveLink software contains an The remote−mounted DVC6005f base unit connects
Audit Trail, Batch Runner for automating repetitive to the DVC6015, DVC6025, or DVC6035 feedback
tasks, and Trending to view valve performance. unit mounted on the actuator. Feedback wiring and
pneumatic tubing to the control valve assembly must
be connected in the field.
ValveLink software provides integration into AMSt
and DeltaV systems, with HARTt and fieldbus Refer to Fisher bulletin 62.1:DVC6000(S1)
communications. (D103308X012) for DVC6000f digital valve controller
dimensional information

The digital valve controllers are loop powered and


Field Communicator do not require additional power. Electrical
You can perform configuration and calibration at the connections are made in the terminal box.
valve or anywhere on the two−wire loop via a Field
Communicator (figure 6). Powerful tools such as the All pressure connections on the digital valve
Setup Wizard and Auto Travel Calibration automate controllers are 1/4 NPT internal connections.
the tasks of commissioning DVC6000f digital valve Remote venting is available and tubing with a
controllers. These automation tools not only save minimum outside diameter of 3/8−inch (9.5 mm) is
time, but also provide accurate and repeatable recommended for connecting the digital valve
results. controller output to the actuator input.

9
Product Bulletin
62.1:DVC6000f
DVC6000f Digital Valve Controller February 2010

Table 3. EMC Summary Results—Immunity


Port Phenomenon Basic Standard Test Level Performance Criteria(1)
4 kV contact
Electrostatic discharge (ESD) IEC 61000−4−2 A
8 kV air
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
Enclosure Radiated EM field IEC 61000−4−3 1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80% A
2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
Rated power frequency
IEC 61000−4−8 60 A/m at 50 Hz A
magnetic field
Burst IEC 61000−4−4 1 kV A
I/O signal/control Surge IEC 61000−4−5 1 kV (line to ground only, each) B
Conducted RF IEC 61000−4−6 150 kHz to 80 MHz at 3 Vrms A
1. A = No degradation during testing. B = Temporary degradation during testing, but is self−recovering.

Ordering Information d. Diagnostic Level


When ordering, specify:
D Performance Diagnostics
1. Type number

2. Actuator type and size D Advanced Diagnostics

3. Maximum actuator travel or rotation


D Fieldbus Diagnostics
4. Options

a. Supply pressure regulator


Note
b. Supply and output gauges
Neither Emerson, Emerson Process
c. Function Block Suite Management, nor any of their affiliated
entities assumes responsibility for the
D Standard Control selection, use, or maintenance of any
product. Responsibility for the
D Fieldbus Control selection, use, and maintenance of any
product remains with the purchaser
D Fieldbus Logic and end user.

10
Product Bulletin
62.1:DVC6000f
February 2010 DVC6000f Digital Valve Controller

Table 4. Hazardous Area Classifications—CSA (Canada)


Certification
Type Certification Obtained Entity Rating Temperature Code Enclosure Rating
Body
FIELDBUS
Vmax = 24 VDC
Imax = 380 mA
Ci = 5 nF
Ex ia—Intrinsically Safe & FISCO Li = 0 mH T4(Tamb v 80_C)
Class I,II,III Division 1 GP A,B,C, Type 4X, IP66
FISCO T5(Tamb v 77_C)
D,E,F,G per drawing GE42818 Single Seal Device
Natural Gas Approved Vmax = 17.5 VDC T6(Tamb v 62_C)
Imax = 380 mA
DVC60x0F
Ci = 5 nF
DVC60x0FS
Li = 0 mH
(x = 1,2,3)
Pi = 5.32 W
Explosion Proof
Type 4X, IP66
Class I Division 1 GP B,C,D T6 −−− T6(Tamb v 80_C)
Single Seal Device
Natural Gas Approved
Class I Division 2 GP A,B,C,D T6
Class II Division 1,2 GP E,F,G T6 Type 4X, IP66
−−− T6(Tamb v 80_C)
Class III Single Seal Device
Natural Gas Approved
FIELDBUS
Vmax = 24 VDC Voc = 24 VDC
Imax = 380 mA Isc = 17.5 mA
Ci = 5 nF Ca = 121 nF
Ex ia—Intrinsically Safe & FISCO Li = 0 mH La = 100 mH
Pi = 1.4 mW Po = 105 mW T4(Tamb v 80_C)
Class I,II,III Division 1 GP A,B,C, Type 4X, IP66
CSA T5(Tamb v 77_C)
D,E,F,G per drawing GE42818 FISCO Single Seal Device
T6(Tamb v 62_C)
Natural Gas Approved Vmax = 17.5 VDC Voc = 24 VDC
Imax = 380 mA Isc = 17.5 mA
DVC6005F Ci = 5 nF Ca = 121 nF
Li = 0 mH La = 100 mH
Pi = 5.32 mW Pi = 105 mW
Explosion Proof
Type 4X, IP66
Class I Division 1 GP B,C,D T6 −−− T6(Tamb v 80_C)
Single Seal Device
Natural Gas Approved
Class I Division 2 GP A,B,C,D T6
Class II Division 1,2 GP E,F,G T6 Type 4X, IP66
−−− T6(Tamb v 80_C)
Class III Single Seal Device
Natural Gas Approved
Vmax = 30 VDC
Ex ia— Intrinsically Safe Imax = 17.5 mA T4(Tamb v 125_C)
Class I,II,III Division 1 GP A,B,C, Ci = 0 uF T5(Tamb v 95_C) Type 4X, IP66
D,E,F,G per drawing GE42818 Li = 0 mH T6(Tamb v 80_C)
Pi = 105 mW
DVC60x5 T4(Tamb v 125_C)
(x = 1,2,3) Explosion Proof
−−− T5(Tamb v 95_C) Type 4X, IP66
Class I Division 1 GP B,C,D
T6(Tamb v 80_C)
T4(Tamb v 125_C)
Class I Division 2 GP A,B,C,D
−−− T5(Tamb v 95_C) Type 4X, IP66
Class II Division 1,2 GP E,F,G
T6(Tamb v 80_C)

11
Product Bulletin
62.1:DVC6000f
DVC6000f Digital Valve Controller February 2010

Table 5. Hazardous Area Classifications—FM (United States)


Certification
Type Certification Obtained Entity Rating Temperature Code Enclosure Rating
Body
FIELDBUS
Vmax = 24 VDC
Imax = 380 mA
Ci = 5 nF
Intrinsically Safe & FISCO Li = 0 mH
Pi = 1.4 W T4(Tamb v 80_C)
Class I,II,III Division 1 GP A,B,C,
T5(Tamb v 77_C) NEMA 4X
D,E,F,G per drawing GE42819 FISCO
T6(Tamb v 62_C)
Natural Gas Approved Vmax = 17.5 VDC
Imax = 380 mA
DVC60x0F
Ci = 5 nF
DVC60x0FS
Li = 0 mH
(x = 1,2,3)
Pi = 5.32 W
Explosion Proof
Class I, Division 1 GP B,C,D T6 −−− T6(Tamb v 80_C) NEMA 4X
Natural Gas Approved
Class I Division 2 GP A,B,C,D T6
Class II Division 1 GP E,F,G T6
Class II Division 2 GP F,G T6 −−− T6(Tamb v 80_C) NEMA 4X
Class III
Natural Gas Approved
FIELDBUS
Vmax = 24 VDC Voc = 24 VDC
Imax = 380 mA Isc = 17.5 mA
Ci = 5 nF Ca = 121 nF
Intrinsically Safe & FISCO Li = 0 mH La = 100 mH
FM Class/Division Pi = 1.4 W Po = 105 mH T4(Tamb v 80_C)
Class I,II,III Division 1 GP A,B,C, T5(Tamb v 77_C) NEMA 4X
FISCO
D,E,F,G per drawing GE42819 T6(Tamb v 62_C)
Natural Gas Approved Vmax = 17.5 VDC Voc = 24 VDC
Imax = 380 mA Isc = 17.5 mA
DVC6005F Ci = 5 nF Ca = 121 nF
Li = 0 mH La = 100 mH
Pi = 5.32 W Po = 105 mW
Explosion Proof
Class I Division 1 GP B,C,D T6 −−− T6(Tamb v 80_C) NEMA 4X
Natural Gas Approved
Class I Division 2 GP A,B,C,D
Class II,III Division 1 GP E,F,G
−−− T6(Tamb v 80_C) NEMA 4X
Class II,III Division 2 GP F,G
Natural Gas Approved
Vmax = 30 VDC
Intrinsically Safe Imax = 17.5 mA T4(Tamb v 125_C)
Class I,II,III Division 1 GP A,B,C, Ci = 0 nF T5(Tamb v 95_C) NEMA 4X
D,E,F,G per drawing GE42819 Li = 0 mH T6(Tamb v 80_C)
Pi = 105 mW
DVC60x5 T4(Tamb v 125_C)
(x = 1,2,3) Explosion Proof
−−− T5(Tamb v 95_C) NEMA 4X
Class I Division 1 GP A,B,C,D
T6(Tamb v 80_C)
Class I Division 2 GP A,B,C,D T4(Tamb v 125_C)
Class II,III Division 1 GP E,F,G −−− T5(Tamb v 95_C) NEMA 4X
Class II,III Division 2 GP F,G T6(Tamb v 80_C)

12
Product Bulletin
62.1:DVC6000f
February 2010 DVC6000f Digital Valve Controller

Table 6. Hazardous Area Classifications—ATEX


Temperature
Certificate Type Certification Obtained Entity Rating Enclosure Rating
Code
II 1 G D FIELDBUS
Gas Ui = 24 VDC , Ii = 380 mA ,
Ci = 5 nF , Li = 0 mH , Pi = 1.4 W T4(Tamb v 80_C)
Ex ia IIC T4/T5/T6—Intrinsically Safe
Dust T5(Tamb v 77_C) IP66
FISCO
Ex iaD 20 T100_C (Tamb v 80_C) T6(Tamb v 62_C)
Ui = 17.5 VDC , Ii = 380 mA ,
Ex iaD 20 T85_C (Tamb v 75_C) Ci = 5 nF , Li = 0 mH , Pi = 5.32 W
II 2 G D
DVC60x0F Gas
DVC60x0FS Ex d IIB+H2 T5/T6—Flameproof T5(Tamb v 85_C)
Dust −−− IP66
(x = 1,2,3) T6(Tamb v 75_C)
Ex tD A21 IP66 T90_C (Tamb v 85_C)
Ex tD A21 IP66 T80_C (Tamb v 75_C)
II 3 G D
Gas
Ex nCL IIC T5/T6—Type n T5(Tamb v 80_C)
−−− IP66
Dust T6(Tamb v 75_C)
Ex tD A22 IP66 T85_C (Tamb v 80_C)
Ex tD A22 IP66 T80_C (Tamb v 75_C)
FIELDBUS
Ui = 24 VDC Uo = 24 VDC
Ii = 380 mA Io = 17.5 mA
II 1 G D Ci = 5 nF Co = 121 nF
Gas Li = 0 mH Lo = 100 mH
Pi = 1.4 W Po = 105 mW T4(Tamb v 80_C)
Ex ia IIC T4/T5/T6—Intrinsically Safe
Dust T5(Tamb v 77_C) IP66
FISCO
Ex iaD 20 T100_C (Tamb v 80_C) T6(Tamb v 62_C)
Ui = 17.5 VDC Uo = 24 VDC
Ex iaD 20 T85_C (Tamb v 75_C) Ii = 380 mA Io = 17.5 mA
Ci = 5 nF Co = 121 nF
Li = 0 mH Lo = 100 mH
DVC6005F Pi = 5.32 W Po = 105 mW
II 2 G D
ATEX Gas
Ex d IIB T5/T6—Flameproof T5(Tamb v 80_C)
Dust −−− IP66
T6(Tamb v 70_C)
Ex tD A21 IP66 T85_C (Tamb v 80_C)
Ex tD A21 IP66 T75_C (Tamb v 70_C)
II 3 G D
Gas
Ex nL IIC T5/T6—Type n T5(Tamb v 80_C)
−−− IP66
Dust T6(Tamb v 75_C)
Ex tD A22 IP66 T85_C (Tamb v 80_C)
Ex tD A22 IP66 T80_C (Tamb v 75_C)
II 1 G D
Gas Ui = 30 VDC
Ex ia IIC T4/T5/T6—Intrinsically Safe Ii = 17.5 mA T4(Tamb v 125_C)
Dust Ci = 0 μF T5(Tamb v 95_C) IP66
Ex iaD 20 T135_C (Tamb v 125_C) Li = 0 mH T6(Tamb v 80_C)
Ex iaD 20 T100_C (Tamb v 95_C) Pi = 105 mW
Ex iaD 20 T85_C (Tamb v 80_C)
II 2 G D
Gas
Ex d IIC T4/T5/T6—Flameproof T4(Tamb v 125_C)
DVC60x5 Dust −−− T5(Tamb v 95_C) IP66
(x = 1,2,3) Ex tD A21 IP66 T130_C (Tamb v 125_C) T6(Tamb v 80_C)
Ex tD A21 IP66 T100_C (Tamb v 95_C)
Ex tD A21 IP66 T85_C (Tamb v 80_C)
II 3 G D
Gas
Ex nA IIC T4/T5/T6—Type n T4(Tamb v 125_C)
Dust −−− T5(Tamb v 95_C) IP66
Ex tD A22 IP66 T130_C (Tamb v 125_C) T6(Tamb v 80_C)
Ex tD A22 IP66 T100_C (Tamb v 95_C)
Ex tD A22 IP66 T85_C (Tamb v 80_C)

13
Product Bulletin
62.1:DVC6000f
DVC6000f Digital Valve Controller February 2010

Table 7. Hazardous Area Classifications—IECEx


Temperature
Certificate Type Certification Obtained Entity Rating Enclosure Rating
Code
FIELDBUS
Vmax = 24 VDC
Imax = 380 mA
Ci = 5 nF
Li = 0 mH
Intrinsically Safe Pi = 1.4 W T4(Tamb v 80_C)
Gas T5(Tamb v 77_C) IP66
FISCO
Ex ia IIC T4/T5/T6 T6(Tamb v 62_C)
Vmax = 17.5 VDC
DVC60x0F
DVC60x0FS Imax = 380 mA
(x = 1,2,3) Ci = 5 nF
Li = 0 mH
Pi = 5.32 W
Flameproof T5(Tamb v 80_C)
Gas −−− IP66
Ex d IIB+H2 T5/T6 T6(Tamb v 75_C)
Type n
T5(Tamb v 80_C)
Gas −−− IP66
T6(Tamb v 75_C)
Ex nC IIC T5/T6
FIELDBUS
Vmax = 24 VDC Voc = 24 VDC
Imax = 380 mA Isc = 17.5 mA
Ci = 5 nF Ca = 121 nF
Li = 0 mH La = 100 mH
Intrinsically Safe Pi = 1.4 W Po = 105 mH T4(Tamb v 80_C)
IECEx Gas T5(Tamb v 77_C) IP66
FISCO
Ex ia IIC T4/T5/T6 T6(Tamb v 62_C)
Vmax = 17.5 VDC Voc = 24 VDC
DVC6005F Imax = 380 mA Isc = 17.5 mA
Ci = 5 nF Ca = 121 nF
Li = 0 mH La = 100 mH
Pi = 5.32 W Po = 105 mH
Flameproof T5(Tamb v 80_C)
Gas −−− IP66
Ex d IIB T5/T6 T6(Tamb v 75_C)
Type n
T5(Tamb v 80_C)
Gas −−− IP66
T6(Tamb v 75_C)
Ex nC IIC T5/T6
Ui = 30 VDC
Intrinsically Safe Ii = 17.5 mA T4(Tamb v 125_C)
Gas Ci = 0 uF T5(Tamb v 95_C) IP66
Ex ia IIC T4/T5/T6 Li = 0 mH T6(Tamb v 80_C)
Pi = 105 mW
DVC60x5 Flameproof T4(Tamb v 125_C)
(x = 1,2,3) Gas −−− T5(Tamb v 95_C) IP66
Ex d IIC T4/T5/T6 T6(Tamb v 80_C)
Type n T4(Tamb v 125_C)
Gas −−− T5(Tamb v 95_C) IP66
Ex nA IIC T4/T5/T6 T6(Tamb v 80_C)

14
Product Bulletin
62.1:DVC6000f
February 2010 DVC6000f Digital Valve Controller

Table 8. Hazardous Area Classifications—NEPSI


Temperature
Certificate Type Certification Obtained Entity Rating Enclosure Rating
Code
FIELDBUS
Ui = 24 VDC
Ii = 226 mA
Ci = 5 nF
Intrinsically Safe Li = 0 mH
Gas Pi = 1.4 W T5(Tamb v 80_C)
Ex ia IIC T5/T6 IP66
Dust FISCO T6(Tamb v 75_C)
DVC60x0f DIP A21 T5 Ui = 17.5 VDC
(x = 1,2,3) Ii = 380 mA
Ci = 5 nF
Li = 0 mH
Pi = 5.32 W
Flameproof
Gas
T5(Tamb v 80_C)
Ex d IIB+H2 T5/T6 −−− IP66
Dust T6(Tamb v 75_C)
DIP A21 T5
FIELDBUS
Ui = 24 VDC Uo = 8.6 VDC
NEPSI Ii = 226 mA Io = 2.3 mA
Ci = 5 nF Co = 8.2 uF
Li = 0 mH Lo = 100 mH
Intrinsically Safe Pi = 1.4 W Po = 5 mW T5(Tamb v 80_C)
IP66
Ex ia IIC T5,T6 FISCO T6(Tamb v 75_C)
DVC6005f
Ui = 17.5 VDC Uo = 8.6 VDC
Ii = 380 mA Io = 2.3 mA
Ci = 5 nF Co = 8.2 uF
Li = 0 mH Lo = 100 mH
Pi = 5.32 W Po = 5 mW
Flameproof T5(Tamb v 80_C)
−−− IP66
Ex d IIB T5,T6 T6(Tamb v 75_C)
Ui = 10 VDC
Ii = 5 mA T4(Tamb v 125_C)
Intrinsically Safe
Ci = 0 uF T5(Tamb v 95_C) IP66
DVC60x5 Ex ia IIC T4,T5,T6
Li = 0 mH T6(Tamb v 80_C)
(x = 1,2,3) Pi = 10 mW
T4(Tamb v 125_C)
Flameproof
−−− T5(Tamb v 95_C) IP66
Ex d IIC T4,T5,T6
T6(Tamb v 80_C)

15
Product Bulletin
62.1:DVC6000f
DVC6000f Digital Valve Controller February 2010

Fisher, FIELDVUE, DeltaV, ValveLink, HotLink, and AMS are marks owned by one of the companies in the Emerson Process Management
business division of Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of
Emerson Electric Co. FOUNDATION and the Fieldbus Foundation logo are marks owned by Fieldbus Foundation. HART is a mark owned by HART
Communication Foundation. All other marks are the property of their respective owners.

The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they
are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or
applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the
designs or specifications of such products at any time without notice. Neither Emerson, Emerson Process Management, nor any of their affiliated
entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of
any product remains solely with the purchaser and end user.

Emerson Process Management


Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Chatham, Kent ME4 4QZ UK
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com

EFisher
16 Controls International LLC 2005, 2010; All Rights Reserved

S-ar putea să vă placă și