MALAYSIAN MS 1837:2010

STANDARD
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

INSTALLATION OF GRID-CONNECTED
PHOTOVOLTAIC (PV) SYSTEM
(FIRST REVISION)

ICS: 27.160
Descriptors: solar energy engineering, grid-connected PV system

© Copyright 2010
DEPARTMENT OF STANDARDS MALAYSIA
DEVELOPMENT OF MALAYSIAN STANDARDS

The Department of Standards Malaysia (STANDARDS MALAYSIA) is the national


standards and accreditation body of Malaysia.

The main function of STANDARDS MALAYSIA is to foster and promote standards,


standardisation and accreditation as a means of advancing the national economy,
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

promoting industrial efficiency and development, benefiting the health and safety of
the public, protecting the consumers, facilitating domestic and international trade and
furthering international cooperation in relation to standards and standardisation.

Malaysian Standards (MS) are developed through consensus by committees which


comprise balanced representation of producers, users, consumers and others with
relevant interests, as may be appropriate to the subject at hand. To the greatest
extent possible, Malaysian Standards are aligned to or are adoption of international
standards. Approval of a standard as a Malaysian Standard is governed by the
Standards of Malaysia Act 1996 [Act 549]. Malaysian Standards are reviewed
periodically. The use of Malaysian Standards is voluntary except in so far as they are
made mandatory by regulatory authorities by means of regulations, local by-laws or
any other similar ways.

STANDARDS MALAYSIA has appointed SIRIM Berhad as the agent to develop,


distribute and sell the Malaysian Standards.

For further information on Malaysian Standards, please contact:

Department of Standards Malaysia OR SIRIM Berhad


Ministry of Science, Technology and Innovation (Company No. 367474 - V)
Level 1 & 2, Block 2300, Century Square 1, Persiaran Dato’ Menteri
Jalan Usahawan Section 2
63000 Cyberjaya 40000 Shah Alam
Selangor Darul Ehsan Selangor Darul Ehsan
MALAYSIA MALAYSIA

Tel: 60 3 8318 0002 Tel: 60 3 5544 6000


Fax: 60 3 8319 3131 Fax: 60 3 5510 8095
http://www.standardsmalaysia.gov.my http://www.sirim.my

E-mail: central@standardsmalaysia.gov.my E-mail: msonline@sirim.my


MS 1837:2010

CONTENTS

Page

Committee representation ......................................................................................................... iii


Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

Foreword ................................................................................................................................iv

1 Scope ............................................................................................................................... 1

2 Normative references....................................................................................................... 1

3 Terms and definitions....................................................................................................... 2

4 General requirements ...................................................................................................... 7

5 Protection requirements................................................................................................... 7

6 Wiring requirements ....................................................................................................... 15

7 Component requirements .............................................................................................. 17

8 Earthing.......................................................................................................................... 20

9 Marking requirements .................................................................................................... 20

10 Documentation ............................................................................................................... 22

11 Commissioning............................................................................................................... 22

Table 1 Current rating of PV array circuits ........................................................................ 17

Figure 1 Schematic diagram of a grid-connected PV system (single phase)……………..…9

Figure 2 Schematic diagram of a grid-connected PV system (three phase)…….........…...10

Figure 3 PV string wiring with minimum loop area ............................................................. 15

Figure B1 Example of sign required on PV array connection box (9.2) ............................... 26

Figure B2 Example of sign required adjacent to PV array main switch (9.3.2) .................... 26

Figure B3 Example of sign required adjacent to inverter main switch (9.3.3) ...................... 26

Figure B4 Example of fire emergency information sign required on the main


switchboard (9.4.1) ............................................................................................... 27

Figure B5 Example of shutdown procedure (9.5) ................................................................. 28

© STANDARDS MALAYSIA 2010 - All rights reserved i


MS 1837:2010

CONTENTS (continued)

Page

Annex A Characteristics of PV arrays................................................................................. 24


Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

Annex B Examples of signs ................................................................................................ 26

Annex C Maintenance requirements................................................................................... 29

Annex D Changes between MS1837:2005 and MS 1837:2010 (First revision) ................. 31

ii © STANDARDS MALAYSIA 2010 - All rights reserved


MS 1837:2010

Committee representation

The Industry Standards Committee on Generation, Transmission and Distribution of Energy (ISC E) under whose
authority this Malaysian Standard was developed, comprises representatives from the following organisations:

Association of Consulting Engineers Malaysia


Department of Standards Malaysia
Federation of Malaysian Manufacturers
Jabatan Kerja Raya Malaysia
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

Malaysian Association of Standards Users


Malaysian Cable Manufacturers Association
Malaysian Electrical Appliances and Distribution Association
Malaysian Green Technology Corporation
Ministry of Domestic Trade, Co-operatives and Consumerism
Ministry of International Trade and Industry
Persatuan Kontraktor Elektrikal dan Mekanikal Melayu Malaysia
Persatuan Penjana Kuasa Bebas
SIRIM Berhad (Secretariat)
SIRIM QAS International Sdn Bhd
Suruhanjaya Komunikasi dan Multimedia Malaysia
Suruhanjaya Tenaga
Tenaga Nasional Berhad
The Electrical and Electronics Association of Malaysia
The Institution of Engineers, Malaysia
Universiti Teknologi Malaysia

The Technical Committee on Renewable Energies which supervised the development of this Malaysian Standard
consists of representatives from the following organisations:

Association of Consulting Engineers Malaysia


Bank Pembangunan Malaysia Berhad
Core Competencies Sdn Bhd
Department of Environment
Felda Palm Industries Sdn Bhd
Forest Research Institute Malaysia
Malaysian Photovoltaic Industry Association
Ministry of Energy, Green Technology and Water
National Solid Waste Management Department
Sarawak Energy Berhad
SIRIM Berhad (Renewable Energy Research Centre)
SIRIM Berhad (Secretariat)
Suruhanjaya Tenaga
Tenaga Nasional Berhad (Distribution Division)
The Institution of Engineers, Malaysia
TNB Research Sdn Bhd
Universiti Tenaga Nasional

The Working Group on Solar Photovoltaic Systems which developed this Malaysian Standard consists of
representatives from the following organisations:

Jabatan Kerja Raya Malaysia


Malaysian Photovoltaic Industry Association
Ministry of Energy, Green Technology and Water
Optimal Power Solutions Sdn Bhd
Sabah Electricity Sdn Bhd
Sarawak Energy Berhad
SIRIM Berhad (Renewable Energy Research Centre)
SIRIM Berhad (Secretariat)
Suruhanjaya Tenaga
The Electrical and Electronics Association of Malaysia
TNB Energy Services Sdn Bhd
Universiti Kebangsaan Malaysia
Universiti Malaya
Universiti Teknologi Malaysia
Universiti Teknologi MARA

© STANDARDS MALAYSIA 2010 - All rights reserved iii


MS 1837:2010

FOREWORD

This Malaysian Standard was developed by the Working Group on Solar Photovoltaic
Systems under the authority of the Industry Standards Committee on Generation,
Transmission and Distribution of Energy.
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

This Malaysian Standard is the first revision of MS 1837, Installation of grid-connected


photovoltaic (PV) system.

Major modifications in this revision are as follows:

a) incorporation of new clauses on “Terms and definitions”;

b) incorporation of new figures on “General requirements” in Clause 4;

c) incorporation of new requirements on “Over-voltage protection” in 5.8;

d) incorporation of new requirement on “PV array and PV sub-array connection boxes” in


7.3;

e) incorporation of new requirement on “Fuses” in 7.5; and

f) incorporation of Annex D on “Changes between MS 1837:2005 and MS 1837:2010 (First


revision)”.

This Malaysian Standard cancels and replaces MS 1837:2005.

Compliance with a Malaysian Standard does not of itself confer immunity from legal
obligations.

iv © STANDARDS MALAYSIA 2010 - All rights reserved


MS 1837:2010

INSTALLATION OF GRID-CONNECTED PHOTOVOLTAIC (PV) SYSTEM


(FIRST REVISION)

1 Scope
This Malaysian Standard sets out the general installation requirements for grid-connected
photovoltaic (PV) arrays with direct current (DC) open circuit voltages up to 1 000 V between
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

positive and negative conductors or up to ± 1 000 V with respect to earth.

NOTES:

1. This includes the following PV array configurations:

a) single string of modules;

b) multi-string PV array; and

c) PV array divided into several sub-arrays.

2. DC systems and photovoltaic systems in particular, pose some hazards in addition to those derived from
conventional alternate current (AC) power systems, including the ability to produce and sustain electrical arcs with
currents that are not much greater than normal operating currents. This standard addresses the safety requirements
arising from the particular characteristics of photovoltaic systems. Those characteristics are presented in Annex A.

The objective of this standard is to provide guidelines on grid-connected PV system


installation, electrical safety and fire protection requirements for:

a) uninformed persons, including owner(s)/occupier(s) and users of the premises where


photovoltaic arrays are installed;

b) informed PV service providers and workers (e.g. electricians) working on these systems;
and

c) emergency workers.

2 Normative references
The following normative references are indispensable for the application of this standard. For
dated references, only the edition cited applies. For undated references, the latest edition of
the normative reference (including any amendments) applies.

MS 589, Specification for 13 A plugs, socket-outlets, adaptors and connection units

MS 981, Specification for safety signs and colours: Colour and design

MS 982, Specification for fire safety signs, notices and graphic symbols

MS 1992, Electronic equipment for use in power installations

MS IEC 60364, Electrical installation of buildings

MS IEC 60364-7-712, Electrical installations of buildings - Part 7-712: Requirements for


special installations or locations - Solar photovoltaic (PV) power supply systems

MS IEC 60529, Degrees of protection provided by enclosures (IP code)


© STANDARDS MALAYSIA 2010 - All rights reserved 1
MS 1837:2010

MS IEC 61000-3-2, Electromagnetic compatibility (EMC) - Limits for harmonic current


emissions (equipment input current ≤ 16 A per phase)

MS IEC 61000-6-3, Electromagnetic compatibility (EMC) - Part 6-3: Generic standards -


Emission standard for residential, commercial and light-industrial environments

MS IEC 61000-6-4, Electromagnetic compatibility (EMC) - Part 6-4: Generic standards -


Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

Emission standard for industrial environments

MS IEC 61215, Crystalline silicon terrestrial photovoltaic (PV) modules - Design qualification
and type approval

MS IEC 61643-1, Low-voltage surge protective devices - Part 1: Surge protective devices
connected to low-voltage power distribution systems - Requirements and tests

MS IEC 61643-12, Low voltage surge protective devices - Part 12: Surge protective devices
connected to low voltage power distribution systems - Selection and application principles

MS IEC 61646, Thin-film terrestrial photovoltaic (PV) modules - Design qualification and type
approval

MS IEC 61727, Photovoltaic (PV) systems - Characteristics of the utility interface

MS IEC 61730-1, Photovoltaic (PV) module safety qualification - Part 1: Requirements for
construction

MS IEC 61730-2, Photovoltaic (PV) module safety qualification - Part 2: Requirements for
testing

MS IEC 62305-1, Protection against lightning - Part 1: General principles

IEEE 1547, Standard for interconnecting distributed resources with electric power systems

IEEE 1547.1, Standard for conformance tests procedures for equipment interconnectivity
distributed resources with electric power systems

3 Terms and definitions


For the purposes of this standard, the following terms, definitions and abbreviations apply.

3.1 accessible, readily

Capable of being reached quickly and without climbing over or removing obstructions,
mounting upon a chair, or using a movable ladder, and in any case not more than 2.0 m
above the ground, floor or platform.

3.2 available, readily

Capable of being reached for inspection, maintenance or repairs without necessitating the
dismantling of structural parts, cupboards, benches or the like.

2 © STANDARDS MALAYSIA 2010 - All rights reserved


MS 1837:2010

3.3 AC side

Part of the PV system from the AC terminals of the inverter until the grid connection to the
mains.

3.4 by-pass diode

A diode that is connected in parallel with a number of PV cells or the whole PV module.
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

3.5 cable

A single cable core, or two or more cable cores laid up together, either with or without fillings,
reinforcements, or protective coverings.

3.6 cable, shielded

A cable with surrounding earthed metallic layer to confine the electric field within the cable
and/or to protect the cable from external electrical influence.

NOTE. Metallic sheaths, armours and earthed concentric conductors may also serve as shields.

3.7 cable core

The conductor with its insulation but not including any mechanical protective covering.

3.8 Class II equipment

Equipment in which protection against electric shock does not rely on basic insulation only,
but in which additional safety precautions such as double insulation or reinforced insulation
are provided, there being no provision for protective earthing or reliance upon installation
conditions. Such equipment may be one of the following types:

a) Equipment having durable and substantially continuous enclosures of insulating material


which envelops all metal parts, with the exception of small parts, such as nameplates,
screw and rivets, which are isolated from live parts by insulation at least equivalent to
reinforced insulation; such equipment is called insulation-encased Class II equipment.

b) Equipment having a substantially continuous metal enclosure, in which double insulation


is used throughout, except for those parts where reinforced insulation is used, because
the application of double insulation is manifestly impracticable; such equipment is called
metal-encased Class II equipment.

c) Equipment that is a combination of the types described in 3.8 a) and 3.8 b).

NOTES:

1. The enclosure of insulation-encased Class II equipment may form part of the whole of the supplementary
insulation or of the reinforced insulation.

2. If the equipment with double insulation or reinforced insulation throughout has an earthing terminal or earthing
contact, it is considered to be of Class I construction.

3. Class II equipment may be provided with means for maintaining the continuity of protective circuits, insulated
from accessible conductive parts by double insulation or reinforced insulation.

4. Class II equipment may have parts operating at SELV (separated extra low voltage).

© STANDARDS MALAYSIA 2010 - All rights reserved 3


MS 1837:2010

3.9 connection box

An enclosure where cables are joined and/or connected to electrical equipment and/or
protective devices.

3.10 DC side

Part of the PV system from the PV cell to the DC terminals of the inverter.
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

3.11 installation earthing

When a PV array is installed on a building, the installation earthing is the earthing bar or
earthing rod of the building.

3.12 inverter

A system that converts the electrical power delivered by the PV array into the appropriate
frequency and/or voltage to be delivered to the load, and/or injected into the electricity grid.

3.13 ISC STC MOD

The short circuit current of a PV module or PV string at standard test conditions (STC), as
specified by the manufacturer on the product specification plate.

NOTE. As PV strings are a group of PV modules connected in series, the short circuit current of a string is equal to
ISC STC MOD.

3.14 ISC STC S-ARRAY

The short circuit current of a PV sub-array at STC, and is equal to:

ISC STC S-ARRAY = ISC STC MOD X NP SA

where NP SA is the number of parallel-connected PV strings in the PV sub-array.

3.15 ISC ARRAY

The short circuit current of the PV array at STC, and is equal to:

ISC STC ARRAY = ISC STC MOD x NP A

where NP A is the total number of parallel-connected PV strings in the PV array.

3.16 live part

A conductor or conductive part intended to be energised in normal use.

3.17 PARRAY STC

The nominal power of the PV array calculated as the sum of the nameplate power ratings of
all the PV modules that constitute the array.

4 © STANDARDS MALAYSIA 2010 - All rights reserved


MS 1837:2010

3.18 PVAC module

Combination of a PV module with an integrated DC/AC inverter, whereas the connection is


available on the AC side only. The DC cannot be accessed.

3.19 PV array

An electrically integrated assembly of PV modules, and other necessary components, to form


Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

a DC power supply unit. A PV array may consist of a single PV string, or several parallel-
connected strings, or several parallel-connected PV sub-arrays and their associated electrical
components. The boundary of a PV array is the connection of the PV array cable to a piece of
equipment that forms part of the inverter and which is dedicated to that particular PV array.
Two or more PV arrays, which are not interconnected in parallel on the generation side of the
inverter, is to be considered as independent PV arrays.

3.20 PV array cable

The output cable of a PV array that connects the PV array connection box to the inverter.

3.21 PV array, isolated

A PV array where there is electrical separation between the PV array output circuit and the
AC system.
NOTE. Electrical separation of power circuits is usually achieved by means of a power transformer.

3.22 PV array connection box

An enclosure where all the PV strings of a PV array or all the PV sub-arrays of a PV array are
electrically connected in parallel and where protection devices may be located, if necessary.

3.23 PV array open circuit voltage

The PV array open circuit voltage is considered to be equal to VOC STC ARRAY (see 3.39).

NOTE. The open circuit voltage is dependent on the cell temperature.

3.24 PV cell

The basic unit of photovoltaic conversion; a semiconductor device that can convert light
directly into electrical energy.

3.25 PV kWh meter

A kWh meter which records kWh units of AC electricity generated by a PV system.

3.26 PV module

An assembly of several PV cells electrically connected to form a larger photovoltaic


conversion device, and which are encapsulated together to protect them from the
environment. A PV module is the smallest ready-to-use photovoltaic conversion device.
3.27 PV module connection box

An enclosure affixed to a PV module, where the electrical connections to the PV module are
made.
© STANDARDS MALAYSIA 2010 - All rights reserved 5
MS 1837:2010

3.28 PV string

A circuit formed by one or more series connected PV modules. The series connection of PV
modules to form a PV string is intended to provide the required circuit voltage.

3.29 PV string cable

A cable connecting the modules in a PV string, or connecting the string to a junction box or to
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

the DC terminals of the inverter.

3.30 PV sub-array

A group of PV strings connected in parallel, that comprise a partial section of the PV array,
where the output current of that group of strings is carried by a dedicated output cable before
being connected in parallel with other sub-arrays.
NOTE. Not all PV arrays are divided into sub-arrays.

3.31 PV sub-array cable

The output cable of a PV sub-array that carries only the output current of its associated sub-
array in normal operation, and that connects the PV sub-array with the other PV sub-array
that constitute the PV array.

NOTE. PV sub-array cables are only relevant for PV arrays that are divided into sub-arrays.

3.32 PV sub-array connection box

An enclosure where all the PV strings of a PV are electrically connected in parallel and where
protection devices may be located if necessary.

NOTE. PV sub-array junction boxes are only relevant for PV arrays that are divided into sub-arrays.

3.33 PV system

An electrically integrated assembly of PV array, inverter (or power conditioning unit) and other
necessary components to form a power generation unit.

3.34 ripple-free DC

For sinusoidal ripple voltage, a ripple content not exceeding 10 % r.m.s.

NOTE. Therefore the maximum peak value does not exceed 140 V for a nominal 120 V ripple-free DC system and
70 V for a nominal 60 V ripple-free DC system.

3.35 SELV (separated extra-low voltage)

An extra-low voltage system which is electrically separated from earth, and from other
systems, in such a way that a single fault cannot give rise to the risk of electric shock.

3.36 SPD (surge protective device)

A device that is intended to limit transient over-voltages and divert surge currents. It contains
at least one non-linear component.

6 © STANDARDS MALAYSIA 2010 - All rights reserved


MS 1837:2010

3.37 STC (standard test conditions)

A standard set of reference conditions used for the testing and rating of photovoltaic cells and
modules. The standard test conditions are:

a) PV cell temperature of 25 °C;


Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

2
b) irradiance in the plane of the PV cell or module of 1 000 W/m ; and

c) light spectrum corresponding to an atmospheric air mass of 1.5.

3.38 VOC STC MOD

The open circuit voltage of a PV module at STC, as specified by the manufacturer in the
product specification.

3.39 VOC STC ARRAY

The open circuit voltage at STC of a PV array, and is equal to:

VOC STC ARRAY = VOC STC MOD x Ns

where Ns is the number of series-connected PV modules in any PV string of the PV array.


NOTE. This standard assumes that all strings within a PV array are connected in parallel; hence the open circuit
voltage of PV sub-arrays and PV strings is equal to VOC STC ARRAY.

3.40 voltage

Differences of potential normally existing between conductors and between conductors and
earth are as follows:

a) extra-low voltage (ELV) - Not exceeding 50 V AC or 120 V ripple-free DC; and

b) low voltage (LV) - Exceeding extra-low voltage, but not exceeding 1 000 V AC or 1 500 V
DC.
NOTE. When calculating the voltage of a PV array, VOC STC ARRAY is to be used.

4 General requirements
The installation of a grid-connected PV system shall be in accordance with Figure 1 and
Figure 2. These figures shall be extensively referred to throughout this standard.

5 Protection requirements
5.1 General

The installation of grid-connected PV systems shall comply with the requirements of MS IEC
60364 or MS IEC 60364-7-712. The provisions of this section are aimed at ensuring that
these requirements are met, taking into account a range of system topologies and earthing
arrangements.
© STANDARDS MALAYSIA 2010 - All rights reserved 7
MS 1837:2010

5.2 By-pass diodes

By-pass diodes shall be used in the PV modules. If by-pass diodes are not embedded in the
PV module encapsulation, they shall comply with all the following requirements:

a) have a voltage rating at least 2 x VOC STC MOD of the protected module;

b) have a current rating of at least 1.3 x ISC STC MOD;


Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

c) be installed according to the module manufacturer’s recommendations;

d) be installed so no live parts are exposed; and

e) be protected from degradation due to environmental factors.

8 © STANDARDS MALAYSIA 2010 - All rights reserved


Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

9 © STANDARDS MALAYSIA 2010 – All rights reserved

Figure 1. Schematic diagram of a grid-connected PV system (single-phase)

MS 1837:2010
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

© STANDARDS MALAYSIA 2010 – All rights reserved 10

Figure 2. Schematic diagram of a grid-connected PV system (three-phase)

MS 1837:2010
MS 1837:2010

5.3 Over-current protection

5.3.1 Discrimination

Over-current protection within the PV string shall be graded in such a way that lower level
protection trips first in the event of fault currents flowing from higher current sections to lower
current sections of the PV array.
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

NOTE. When circuit breakers with over-current protection elements are used, they also provide the disconnecting
means required in 5.4.

5.3.2 PV strings

In cases where it applies (see Figure 1 and 2), all PV strings shall be protected with an over-
current protection device with load breaking disconnecting facilities. These over-current
protection devices shall be installed in positive active conductors. Suitably rated circuit-
breakers used for over-current protection may also provide load breaking disconnecting
facilities (see 5.4).

The rated trip current (ITRIP) of over-current protection devices for PV strings shall be as
specified by the PV module manufacturer or, ITRIP shall be determined by the following
formula:

1.5 x ISC STC MOD ≤ ITRIP ≤ 2 x ISC STC MOD

5.3.3 PV array and PV sub-arrays

Over-current protection device is not required for PV array and PV sub-arrays.

5.4 Disconnecting means

5.4.1 General

Disconnecting means shall be provided in PV arrays according to 5.4.2, to isolate the PV


array from the inverter and vice versa and to allow for maintenance and inspection tasks to be
carried out safely.

NOTE. This clause does not apply to module inverters where the inverter is an integral part of the PV module.

5.4.2 Selection and installation

Only device with DC rating which is able to extinguish electrical arc shall be used.

Suitably rated circuit-breakers used for over-current protection may also provide load
breaking disconnecting facilities.

Other disconnection and isolation devices having the characteristics described in 7.4 may be
used as a disconnection means.

Fuse systems used for string over-current protection are acceptable non-load breaking
disconnecting means if they have removable fusing elements, preferably with a disconnection
mechanism (fuse-combination unit).

© STANDARDS MALAYSIA 2010 - All rights reserved 11


MS 1837:2010

5.4.2.1 PV strings and PV sub-arrays

No separate disconnection device is required if suitably rated circuit breakers are used for the
over-current protection which also provides load breaking disconnecting facilities.

5.4.2.2 PV array

A readily available load-breaking disconnection device, which interrupts both positive and
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

negative conductors, shall be installed in the PV array cable. This device shall be lockable in
the off position.

5.4.2.3 Inverter

A suitably AC rated and readily available load-breaking disconnection device, which interrupts
both positive and negative conductors, shall be installed in the cable connected to the inverter
AC terminal. This device shall be lockable in the off position.

5.5 Emergency switching device

The PV array (DC) load-breaking disconnection device and the inverter (AC) load-breaking
disconnection device shall be used as the emergency switching devices, and therefore shall
be readily accessible and be clearly identified according to 9.4.2.

The emergency switching device shall comply with the requirements for devices for
emergency switching including emergency stopping as contained in MS IEC 60364 or MS IEC
60364-7-712.

If the emergency switching device is manually operated, the remote operating device shall be
located in a readily accessible point and be identified in accordance with 9.4.2.

5.6 Earth fault protection

All metal casings and frames shall be earthed according to MS IEC 60364 or MS IEC 60364-
7-712.

5.7 Lightning protection

Lightning protection measures may be required in some PV installations. The need for
lightning protection shall be assessed in accordance with MS IEC 62305-1.

A lightning protection system has the task of preventing severe damage caused by fire or
mechanical destruction if a direct lightning strike occurs on a building or structure. Lightning
protection systems consist of three essential components:

a) an air termination system, consisting of metallic masts or rods of sufficient height to divert
lightning currents through their structure;

b) a down conductor of sufficient cross-sectional area to conduct lightning currents to earth;


and

c) an earth termination system.

12 © STANDARDS MALAYSIA 2010 - All rights reserved


MS 1837:2010

For ground mounted or freestanding PV arrays, the need for a lightning protection system
shall be assessed in accordance with MS IEC 62305-1, and if required, it shall be installed in
compliance with that standard.

The installation of a PV array on a building has a negligible effect on the probability of direct
lightning strikes and therefore it does not necessarily imply that a lightning protection system
shall be installed if none is already present. However, if the physical characteristics or
prominence of the building do change significantly due to the installation of the PV array, it is
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

required that the need for a lightning protection system be assessed in accordance with MS
IEC 62305-1, and if required, it shall be installed in compliance with that standard.

If a lightning protection system is already installed on the building, it shall be verified that the
PV array and associated equipment are within the protection zone of the system in
accordance with MS IEC 62305-1. If the PV array is not within the protection zone of the
existing lightning protection system, additional air termination(s) shall be provided in
accordance with MS IEC 62305-1.

When a PV array is protected by a lightning protection system, the metal structure of the PV
array shall be bonded to the lightning protection system, unless the minimum safety
clearances as specified in MS IEC 62305-1, can be achieved.

5.8 Over-voltage protection

Over-voltage protection measures include:

a) equipotential bonding;

b) avoidance of wiring loops;

c) installation of SPDs; and

d) shielding.

5.8.1 Wiring loops

To reduce the magnitude of lightning induced over-voltages, the PV array wiring shall be laid
in such a way that the area of conductive loops is minimum (see example in Figure 3).

5.8.2 Surge protective device (SPD)

5.8.2.1 General guide

SPDs are a very common method of protecting electrical systems and equipment against
over-voltages. When these devices are used, the recommendations of MS IEC 61643-12
shall be observed.

Many commercial PV inverters are fitted with SPDs on the PV input (DC) terminals, and this
shall be considered when specifying the over-voltage protection of the PV array.

© STANDARDS MALAYSIA 2010 - All rights reserved 13


MS 1837:2010

5.8.2.2 Selection

The selection of SPDs shall be in accordance to MS IEC 61643-12.

5.8.2.3 Usage and installation

The usage and installation of SPDs shall be in accordance to MS IEC 61643-12. The SPDs
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

on the DC side shall be installed closest possible to the inverter.

5.8.2.4 SPD specifications to protect PV array and inverter (DC terminal)

The specifications for SPDs to protect PV arrays and inverter (DC terminal) are as follows
(refer to list of parameters for SPDs selection in MS IEC 61643-12):

a) SPDs of Class II (in this context, Class II refers to the test specifications of SPDs rather
than insulation class).

b) Have a maximum continuous operating voltage (Uc) with Uc > VOC STC GEN.

c) Have a maximum discharge current (Imax) (8/20 μs) with Imax > 40 kA (or at least 20 kA).

d) Have a nominal discharge current (In) (8/20 μs) with In > 20 kA (or at least 10 kA).

e) Have a voltage protection level (Up) with 1.3 x VOC STC GEN < Up < 1.1 kV.

f) Have a voltage protection level at In (Up) with Up (L-PE) < 2.5 kV.

5.8.2.5 SPDs specifications to protect inverter (AC terminal)

The specifications for SPD to protect inverter (AC terminal) shall be suitably rated for AC use
and in accordance to MS IEC 61643-12 and in conjunction with MS IEC 61643-1.

5.8.3 Shielding

When the PV array frame is bonded to a lightning protection system, the PV array cable shall
be shielded by one of the following methods, and the shielding conductor shall be connected
to earth at both ends:
2
a) with a metallic cable armour or shield with an equivalent cross-sectional area of 10 mm
Cu; or

b) with a metallic conduit suitable as a bonding conductor; or


2
c) with an equipotential bonding conductor with a cross-sectional area of at least 6 mm .

NOTE. 6 mm2 Cu should be able to withstand 20 kA for 1 ms.

14 © STANDARDS MALAYSIA 2010 - All rights reserved


MS 1837:2010

6 Wiring requirements
6.1 Compliance with wiring standards

The wiring to the PV array shall comply with the requirements of MS IEC 60364 or MS IEC
60364-7-712.
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

NOTE. Particular attention needs to be given to the protection of wiring systems against external influences.

6.2 System voltage

VOC STC ARRAY shall not exceed the maximum allowed system voltage of the PV modules (as
specified by the manufacturer).

6.3 Wiring Installation

6.3.1 General

Wiring of PV arrays shall be laid in such a way that the possibility of line to line and line to
earth faults occurring is minimised.

All connections shall be verified for tightness and polarity during installation to reduce the risk
of faults and possible arcs occurring during commissioning and operation.

6.3.2 Wiring loops

The PV array wiring should be laid in such a way that the area of conductive loops is
minimised (e.g. by laying cables in parallel as shown in Figure 3); see also 5.8.1.

Figure 3. PV string wiring with minimum loop area

© STANDARDS MALAYSIA 2010 - All rights reserved 15


MS 1837:2010

6.3.3 String, sub-array and array wiring

The wiring of PV strings, sub-arrays and array shall satisfy the following requirements:

a) Double insulated, DC rated, UV resistant, flex type and fire retardant shall be used.

b) Cables shall be protected from mechanical damage.


Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

c) Cables shall be clamped (to relieve tension and to prevent conductors coming free from
the connection).

6.3.4 Wiring installation in connection boxes

The following provisions apply to the installation of wiring systems in connection boxes:

a) Where conductors enter a connection box without conduit, a tension relief system shall be
used to avoid cable disconnections inside the connection box (for example by using a
gland connector).

b) All cable entries, when installed, shall maintain the IP rating of the enclosure.

NOTE. Water condensation inside connection boxes may be a problem in some locations and provision may
need to be provided to drain water build-up.

c) The wiring and its insulation particularly through the connection box including terminal
points shall maintain double insulation status over its entire length.

6.3.5 Location of PV array and PV sub-array connection boxes

PV array and PV sub-array connection boxes, where installed, shall be readily available.

6.4 Cable selection

6.4.1 Cable size

6.4.1.1 General

Cable sizes for PV string cables, PV sub-array cables and PV array cables shall not be less
2
than 2.5 mm and shall be determined with regard to both, the minimum current capacity (see
6.4.1.2) and maximum voltage drop requirements (see 6.4.1.3). The larger cable size
obtained from these two criteria shall be applied.

6.4.1.2 Current carrying capacity (CCC)

The minimum cable sizes for PV array wiring, based on CCC, shall be based upon a current
rating according to Table 1.

16 © STANDARDS MALAYSIA 2010 - All rights reserved


MS 1837:2010

Table 1. Current rating of PV array circuits

Type of cable Minimum current upon which cable cross-sectional


area should be chosen
PV string cable 2 x ISC STC MOD
PV sub-array and array 1.3 x ISC STC S-ARRAY or ARRAY (of relevant array)
cable
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

NOTE. The operating temperature of PV modules and consequently their associated wiring can be significantly
higher than the ambient temperature. A minimum temperature rise above maximum expected ambient temperature of
+40 °C should be considered for cables installed near or in contact with PV modules.

6.4.1.3 Voltage drop

The voltage drop between the PV array and the inverter shall be less than 5 %.

NOTE. Voltage drop in cables is a measure of the losses in PV array wiring and hence affects the efficiency of the
PV power system.

6.4.2 Insulation

The insulation of cables used within the PV array shall:

a) have a voltage rating of at least 1.2 x VOC STC ARRAY;

NOTE. The use of double insulated and shielded cable is required for wiring of PV arrays where VOC STC ARRAY ≥
120 V DC, to minimise the risk of faults within the wiring.

b) have a temperature rating according to the application; and

NOTE. PV modules frequently operate at temperatures of the order of 40 °C above ambient temperature. Cable
insulation of wiring installed in contact with, or near, PV modules needs to be rated accordingly.

c) be UV resistant, or be protected from UV light by appropriate protection (e.g. installed in


UV resistant conduit).

6.5 Wiring identification

Appropriate identification shall be provided for PV array cabling where it can be confused with
other wiring systems.

7 Component requirements
7.1 PV modules

7.1.1 Reliability

Crystalline silicon PV modules shall comply with MS IEC 61215. Thin film PV modules shall
comply with MS IEC 61646.

7.1.2 Equipment class

PV modules shall be Class II. PV modules shall comply with MS IEC 61730-1 and MS IEC
61730-2.
© STANDARDS MALAYSIA 2010 - All rights reserved 17
MS 1837:2010

7.1.3 Reverse current

PV modules shall be capable of conducting continuously a reverse current equal to 2.6 x ISC
MOD without damage.

7.2 Inverter requirements

Inverters shall comply with requirements in accordance to MS IEC 61000-3-2, MS IEC 61000-
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

6-3, MS IEC 61000-6-4, MS IEC 60364-7-712 and MS 1992 or IEEE 1547 and IEEE 1547.1
or other equivalent standard. Inverters shall be isolated in the event of mains supply failure.

7.3 PV array and PV sub-array connection boxes

7.3.1 Environmental effects

PV array and PV sub-array connection boxes exposed to the environment shall be at least IP
56 compliant in accordance with MS IEC 60529, and shall be UV resistant.

7.4 Switching devices

7.4.1 General

All switching devices shall comply with all the following requirements:

a) be rated for AC side as AC and be rated for DC side as DC use and able to extinguish
electrical arcs;

b) have a voltage rating greater than VOC STC ARRAY;

c) not have exposed metallic live parts in connected or disconnected state; and

d) interrupt all poles.

7.4.2 Current breaking devices

In addition to the requirements of 7.4.1, circuit breakers and any other load breaking
disconnection devices used for protection and/or disconnecting means shall comply with the
following requirements:

a) not be polarity sensitive (as fault currents in a PV array may flow in the opposite direction
of normal operating currents);

b) be rated to interrupt full load and prospective fault currents from the PV array and any
other connected power sources such as batteries, generators and the grid, if present; and

c) when over-current protection is incorporated, the trip current shall be rated according to
5.3.

7.4.3 Plugs, sockets and couplers

Plugs, sockets and couplers shall comply with all the following requirements:

a) be rated for AC side for AC use and be rated for DC side for DC use;

18 © STANDARDS MALAYSIA 2010 - All rights reserved


MS 1837:2010

b) have a voltage rating greater than VOC STC ARRAY;

c) be protected from contact with live parts in both the connected and disconnected state
(i.e. be shrouded);

d) have a current rating equal to, or greater than, the cable to which they are fitted;

e) require a deliberate force to disconnect;


Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

f) have a temperature rating suitable for their installation location;

g) if multipolar, be polarised;

h) comply with Class II; and

i) if exposed to the environment, be rated for outdoor use, be UV resistant and be at least
IP 56 compliant.

Plugs and socket outlets normally used for connection to AC mains power as described in MS
589, shall not be used in PV arrays wiring.

7.5 Fuses

Fuses used in PV arrays shall comply with all the following requirements:

a) be rated for AC for AC use and be rated for DC for DC use;

b) have a voltage rating equal to, or greater than VOC STC ARRAY;

c) be rated to interrupt full load and prospective fault currents from the PV array and
connected power sources such as batteries, generators and the grid, if present; and

d) have a current rating of ≥ 1.5 and ≤ 2 time ISC STC String.

NOTE. When fuses are provided for over-current protection, the use of fused load break switch-disconnectors (fuse-
combination units) is recommended.

7.5.1 Fuse holders

Fuse holders shall comply with all the following requirements:

a) have a voltage rating equal to, or greater than VOC STC ARRAY;

b) have a current rating equal to, or greater than, the corresponding fuse; and

c) provide a degree of protection not less than IP 2X.

7.6 PV kWh meter

The PV kWh meter is used to record kWh units of AC generated electricity by a PV system.
The meter shall be connected between the AC breaker and the AC grid isolator main switch
(AC load breaking disconnection device).

© STANDARDS MALAYSIA 2010 - All rights reserved 19


MS 1837:2010

The PV kWh meter shall be suitable to record kWh units of AC electricity. The meter accuracy
shall be of Class 2 (± 2 %).

8 Earthing
8.1 General

There are three possible reasons for earthing a PV array:


Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

a) equipotential bonding to avoid uneven potentials across and installation;

b) protective earthing to provide a path for fault currents to flow; and

c) lightning protection.

An earth conductor may perform one or more of these functions in an installation. The
dimensions and location of the conductor are very dependent on its function.

8.2 Earthing electrode

If a separate earthing electrode is provided for the PV array, this electrode shall be bonded to
the installation earthing.

8.3 Equipment earthing

8.3.1 Earthing of equipment

Equipment earthing refers to the bonding to earth of all frames of the PV array including any
2
structural metalwork. Equipment earthing shall be done with at least a 10 mm earthing
conductor.

8.3.2 Earthing conductors

All PV array earthing conductors shall comply with the material, type, insulation, identification,
installation and connection requirements as specified in MS IEC 60364 or MS IEC 60364-7-
712.

9 Marking requirements
9.1 General

All signs required by 9.2 to 9.4 shall:

a) comply with MS 981 and MS 982;

b) be indelible;

c) be legible from at least 0.8 m unless otherwise specified in the relevant clauses; and

d) be constructed and affixed to remain legible for the life of the equipment it is attached or
related to.

NOTE. Examples of signs are given in Annex B.

20 © STANDARDS MALAYSIA 2010 - All rights reserved


MS 1837:2010

9.2 PV array and PV sub-array connection boxes

A sign containing the text 'PV DC' shall be attached to PV array and PV sub-array connection
boxes.

9.3 Disconnection devices

9.3.1 General
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

Disconnection devices shall be marked with an identification name or number in accordance


with the PV array wiring diagram.

All switches shall have the ON and OFF positions clearly indicated.

9.3.2 PV array main switch

The PV array main switch (DC load breaking disconnection device) shall be provided with a
sign affixed in a prominent location with the following text: ‘PV DC MAIN SWITCH’.

9.3.3 Inverter main switch

The inverter main switch (AC load breaking disconnection device) shall be provided with a
sign affixed in a prominent location with the following text: ‘PV AC MAIN SWITCH’.

9.4 Fire emergency information

9.4.1 General

For PV arrays that are installed on buildings and have a rated power greater than 500 W or
with VOC STC ARRAY greater than 50 V, a sign next to the building main switchboard shall be
provided. This sign shall specify the procedure for the fire brigade to enter the building without
the risk of electric shock from the PV array and the operation of the emergency switching
device, if relevant. This sign shall be legible from at least 1.5 m.

9.4.2 Manually operated emergency switching device

When a manually operated switching device is used, the means of operating such device,
such as handles or push-buttons for emergency switching, shall be clearly indicated. The
signs to identify the switching devices (see 9.3.2 and 9.3.3) shall be placed next to them and
shall be legible from at least 1.5 m.

9.5 Shutdown procedure

A sign, that contains shutdown instructions for the PV system, shall be located in a prominent
location. The sign shall include the name and location of the relevant disconnection devices.

The sign shall also include the following PV array information:

a) open circuit voltage at STC; and

b) short circuit current at STC.

© STANDARDS MALAYSIA 2010 - All rights reserved 21


MS 1837:2010

10 Documentation
The PV system installer shall prepare the following documents and a copy shall be handed to
the PV system owner:

a) a basic circuit diagram that includes the electrical ratings of the PV array, including the
information required by 9.4;
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

b) a copy of the emergency shutdown procedure including the location of relevant switching
devices;

c) as-built drawing that includes the PV array, the inverter and the major components;

d) PV system or parts certification as required by relevant authorities and provided by


manufacturer;

e) all specifications of the PV array, the inverter and the system components; and

f) PV system maintenance requirements (see Annex C).

11 Commissioning
11.1 General

Commissioning tests are required to ensure that the PV array complies with the safety
requirements of this standard.

11.2 Wiring and installation integrity

The PV array wiring shall be inspected for compliance with the wiring requirements of MS IEC
60364 or MS IEC 60364-7-712, and the wiring requirements set out in Clause 4 of this
standard, and corrected if necessary.

11.3 Open circuit voltage

11.3.1 General

This test is intended to ensure that wiring polarity and continuity of the PV array are correct.

11.3.2 Procedure

The open circuit voltage of every string shall be measured before connecting to other strings.
All PV string open circuit voltages shall be within 5 % variation; otherwise the connections
shall be verified for polarity, continuity and possible faults and repaired. Once the verification
is complete and satisfactory, the PV strings can be connected in parallel.

The same procedure shall be carried out to verify PV sub-array open circuit voltages (if
relevant) and PV array open circuit voltage before connecting the PV array to the inverter.

NOTE. It is recommended that all measurements are made under irradiance conditions (during the daytime with no
rain).

22 © STANDARDS MALAYSIA 2010 - All rights reserved


MS 1837:2010

11.4 PV kWh meter

The meter shall be tested for functionality and the initial value shall be recorded.

11.5 Commissioning records

The following commissioning records shall be given to the owner, and if necessary to the
relevant authorities:
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

a) a certificate stating that the work done on the installation meets the requirements of this
standard;

b) a record of the final open circuit voltage measurements;

c) a record of the measured values of current and/or resistance before and after any
adjustments to the earth fault protection system (if relevant); and

d) a record of the initial value of the PV kWh meter.

© STANDARDS MALAYSIA 2010 - All rights reserved 23


MS 1837:2010

Annex A
(informative)

Characteristics of PV arrays
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

A1 PV arrays
A1.1 DC versus AC behavior

One of the most important characteristics of direct current (DC) in relation to safety is that DC
arcs, caused by switching or faults, are much more difficult to extinguish than AC arcs. This
implies that all switchgear and over-current protection devices in the PV array need to be
rated for used in DC circuits (DC switchgear is less readily available and its cost increases
significantly, as the DC operating voltages increase).

A1.2 Series parallel configuration

To reduce mismatch and improve PV array yield, all PV strings within a PV array should be of
the same technology and have the same number of series connected PV modules. Also, all
PV modules within the PV array should have similar rated electrical characteristics including
short circuit current, open circuit voltage, maximum power current, maximum power voltage
and rated power (all at STC).

A1.3 Low fault levels

PV cells (and consequently PV arrays) behave like current sources under low impedance
faults. Thus in PV arrays without battery storage, currents much greater than normal full load
currents will not flow even under short circuit fault conditions, making short circuit detection
impossible. Therefore, electric arcs can be formed in a PV array with fault currents that will
not trip an over-current device. The implications for PV array design that arise from these PV
array characteristics are:

a) the chances of line to line faults, earth faults and inadvertent wire disconnections in the
system need to be minimised; and

b) earth fault detection and disablement could be required as part of the system protection
functions depending on the array size and location, to eliminate the risk of fire.

A1.4 Operating temperature

PV modules can operate well above ambient temperature under normal operating conditions.
A common steady state temperature rise for silicon modules operating at the maximum power
2
point under 1 000 W/m solar irradiance and with adequate ventilation is 25 °C. This
temperature rise can go up by 35 °C when modules are open circuited (i.e. the PV array has
been put out of operation due to a grid failure in the case of grid connected systems). The
2
temperature rise can be even higher when irradiance levels are greater than 1 000 W/m and
when modules have poor ventilation. The following are two main requirements on the PV
array design derived from this operating characteristic of PV modules:

24 © STANDARDS MALAYSIA 2010 - All rights reserved


MS 1837:2010

a) PV module efficiency reduces as their operating temperature increases (for crystalline


silicon solar cells the maximum power decreases between 0.4 % and 0.5 % per each
degree C rise in operating temperature). Therefore adequate ventilation of the PV array
should be a design goal, in order to ensure optimum performance for both modules and
associated components.

b) All the components and equipment that may be in direct contact or near the PV array
(conductors, inverters, connectors, etc.) need to be capable of withstanding the expected
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

maximum operating temperature of the PV array.

A2 Grid-connected photovoltaic (PV) systems


The systems have the following characteristics:

a) Generally they do not use batteries for energy storage because the grid behaves as an
infinite bus that can receive or supply power.

b) PV arrays in these systems tend to be low voltage.

c) A wide range of inverter topologies can be found on the market. Some of them include an
isolation transformer, and some of them are transformerless; some of them require the
PV array to be earthed and some of them require it not to be earthed.

© STANDARDS MALAYSIA 2010 - All rights reserved 25


MS 1837:2010

Annex B
(informative)

Examples of signs
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

B1 Overview
This annex provides examples of appropriate signs as specified in Clause 9.

PV DC

Figure B1. Example of sign required on PV array connection box (9.2)

PV DC
MAIN SWITCH

Figure B2. Example of sign required adjacent to PV array main switch (9.3.2)

PV AC
MAIN SWITCH

Figure B3. Example of sign required adjacent to inverter main switch (9.3.3)

26 © STANDARDS MALAYSIA 2010 - All rights reserved


MS 1837:2010

FIRE EMERGENCY
INFORMATION
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

DISCONNECT THE GRID MAINS


POWER INTO THE BUILDING BEFORE
ENTERING THE PREMISE. THIS WILL
ALSO DISCONNECT THE PV SYSTEM
POWER SUPPLY INTO THE BUILDING

FOLLOW THE PV SYSTEM SHUTDOWN


PROCEDURE TO FULLY DISCONNECT
THE PV SYSTEM
Figure B4. Example of fire emergency information sign required on the main
switchboard (9.4.1)

© STANDARDS MALAYSIA 2010 - All rights reserved 27


MS 1837:2010

PV SYSTEM SHUTDOWN PROCEDURE

STEP 1: Turn off the ‘PV AC MAIN SWITCH’ located


next to the AC terminals of the inverter.
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

STEP 2: Turn off the ‘PV DC MAIN SWITCH’ located


next to the DC terminals of the inverter.

Warning: Do not open plug and socket


connectors or PV string isolators under load

PV Array Open Circuit Voltage at STC: VDC

PV Array Short Circuit Current at STC: ADC

Figure B5. Example of shutdown procedure (9.5)

28 © STANDARDS MALAYSIA 2010 - All rights reserved


MS 1837:2010

Annex C
(informative)

Maintenance requirements

C1 Safety
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

Attention should be given in the maintenance procedures to the following safety requirements:

a) emergency shutdown procedure;

b) obey all warning signs;

c) shut system down and interrupt PV array according to the manual shutdown procedure;

d) split strings into extra low voltage sections (if relevant); and

e) warn of the live parts that cannot be de-energised during daylight.

C2 Periodic maintenance
The following maintenance activities should be considered for inclusions in the maintenance
procedures, according to the location, size and design of the PV array.

a) Cleaning of the PV array might be periodically required in locations where it is likely to


collect dust or other shading materials.

b) Periodic inspections should be carried out to check wiring integrity, electrical connections,
corrosion and mechanical protection of wiring.

c) Verify open circuit voltage, and if possible short circuit current values.

d) Verify functioning of earth fault protection (if relevant).

e) Measure wet insulation resistance.

f) Check PV array mounting structure(s).

g) Test operation of switches regularly.

h) Check for module defects (fracture, moisture penetration, browning, etc.).

i) Verify status of SPDs (if relevant).

© STANDARDS MALAYSIA 2010 - All rights reserved 29


MS 1837:2010

C3 Operation and maintenance procedures


Operation and maintenance procedures should include the following:

a) a short description of the function and operation of all installed equipment. More detailed
information should be available from the manufacturer’s documentation [see C3 d)];
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

b) emergency and maintenance shutdown procedures;

c) periodic maintenance requirements including procedures and schedule; and

d) equipment manufacturer’s documentation (data sheets, handbooks, etc.) for all


equipment supplied.

30 © STANDARDS MALAYSIA 2010 - All rights reserved


Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

© STANDARDS MALAYSIA 2010 - All rights reserved

Annex D
(informative)

Changes between MS 1837:2005 and MS 1837:2010 (First revision)

Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision)

MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.
Foreword Foreword A+D This Malaysian Standard was developed by the Working Group
on Utility Interfaced Solar Photovoltaic System under the
authority of the Electro technical Industry Standards Committee

Compliance with a Malaysian Standards does not of itself


confer immunity from legal obligations.

This Malaysian Standard was developed by the Working Group


on Solar Photovoltaic Systems under the authority of the
Industry Standards Committee on Generation, Transmission
and Distribution of Electrical Energy.

This Malaysian Standard is the first revision of MS 1837,

MS 1837:2010
Installation of grid-connected photovoltaic (PV) system.

Major modifications in this revision are as follows:

a) incorporation of new clauses on “Terms and definitions”;


31
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

32 Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)

MS 1837:2010
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.
b) incorporation of new figures on “General requirements” in
Clause 4;

c) incorporation of new requirements on “Over-voltage


protection” in 5.8;

d) incorporation of new requirement on “PV array and PV


sub-array connection boxes” in 7.3;

e) incorporation of new requirement on “Fuses” in 7.5; and

f) incorporation of Annex D on “Changes between MS


1837:2005 and MS 1837:2010 (First revision)”.

This Malaysian Standard cancels and replaces MS 1837:2005.

Compliance with a Malaysian Standard does not of itself confer


© STANDARDS MALAYSIA 2010 - All rights reserved

immunity from legal obligations.

SECTION 1 1 Scope
1.1 Scope Merged sub clause 1.1 & 1.2
1.2 Objective
1.3 Normative 2 Normative references A+D MS 589, Specification for 13 A plugs, socket-outlets, adaptors
references and connection units

MS 981, Specification for safety signs and colours: Colour and


design

MS 982, Specification for fire safety signs, notices and graphic


symbols

32
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

© STANDARDS MALAYSIA 2010 - All rights reserved


Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued) 1
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.
MS 1992, Electronic equipment for use in power installations

MS IEC 60364, Electrical installation of buildings

MS IEC 60364-7-712, Electrical installations of buildings - Part


7-712: Requirements for special installations or locations -
Solar photovoltaic (PV) power supply systems

MS IEC 60529, Degrees of protection provided by enclosures


(IP code)

MS IEC 61000-3-2, Electromagnetic compatibility (EMC) -


Limits for harmonic current emissions (equipment input current
≤ 16 A per phase)

MS IEC 61000-6, Electromagnetic compatibility (EMC) - Part 6:


Generic standards

MS IEC 61024-1, Protection of structures against lightning -


Part 1: General principles

MS IEC 61215, Crystalline silicon terrestrial photovoltaic (PV)


modules - Design qualification and type approval

MS IEC 61643-1, Low-voltage surge protective devices - Part


1: Surge protective devices connected to low-voltage power

MS 1837:2010
distribution systems - Requirements and tests

MS IEC 61643-12, Low voltage surge protective devices - Part


12: Surge protective devices connected to low voltage power
distribution systems - Selection and application principles
33
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
34

MS 1837:2010
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.

MS IEC 61646, Thin-film terrestrial photovoltaic (PV) modules -


Design qualification and type approval

MS IEC 61727, Photovoltaic (PV) systems - Characteristics of


the utility interface

MS IEC 61730-1, Photovoltaic (PV) module safety qualification


- Part 1: Requirements for construction

MS IEC 61730-2, Photovoltaic (PV) module safety qualification


- Part 2: Requirements for testing

MS IEC 62305-1, Protection against lightning - Part 1: General


principles

IEEE 1547, Standard for interconnecting distributed resources


© STANDARDS MALAYSIA 2010 - All rights reserved

with electric power systems

IEEE 1547.1, Standard for conformance tests procedures for


equipment interconnectivity distributed resources with electric
power systems

34
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

© STANDARDS MALAYSIA 2010 - All rights reserved


Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
1
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.
1.4 Definitions 3 Terms and definitions - -

1.4.1 Accessible, 3.1 Accessible, readily - -


readily

1.4.2 Available, 3.2 Available, readily - -


readily

- 3.3 AC side A Part of the PV system from the AC terminals of the inverter until
the grid connection to the mains.

1.4.3 By Pass diode 3.4 By Pass diode A A diode that is connected in parallel with a number of PV cells
or the whole PV module.

1.4.4 Cable 3.5 Cable - -

1.4.5 Cable, shielded 3.6 Cable, shielded - -

1.4.6 Cable core 3.7 Cable core - -

1.4.7 Class II 3.8 Class II equipment - -


equipment

1.4.8 Connection box 3.9 Connection box - -

MS 1837:2010
- 3.10 DC Side A Part of the PV system from the PV cell to the DC terminals of
the inverter.

1.4.9 Installation 3.11 Installation earthing - -


earthing
35
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
36

MS 1837:2010
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.

1.4.10 Inverter 3.12 inverter - -

1.4.11 ISC MOD 3.13 ISC STC MOD - -

1.4.12 ISC S-ARRAY 3.14 ISC STC-S-ARRAY A+D The short circuit current of a PV sub-array at STC, and is equal
to:

ISC STC S-ARRAY = ISC STC MOD X SSA NP SA

where SSA NP SA is the number of parallel-connected PV strings


in the PV sub-array.

1.4.13 ISC ARRAY 3.15 ISC STC ARRAY A+D The short circuit current of the PV array at STC, and is equal
to:
© STANDARDS MALAYSIA 2010 - All rights reserved

ISC STC ARRAY = ISC STC MOD x SA NP A

where SA NP A is the total number of parallel-connected PV


strings in the PV array.

1.4.14 Live Part 3.16 ISC ARRAY - -

1.4.15 PARRAY 3.17 PARRAY STC - -

- 3.18 PV AC module
A Combination of a PV module with an integrated DC/AC
inverter, whereas the connection is available on the AC side
only. The DC cannot be accessed.

1.4.16 PV array 3.19 PV array - -

36
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

© STANDARDS MALAYSIA 2010 - All rights reserved


Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
1
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.

1.4.17 PV array cable 3.20 PV array cable - -

1.4.18 PV array, 3.21 PV array, isolated - -


isolated

1.4.19 PV array 3.22 PV array connection - -


connection box box

1.4.20 PV array 3.23 PV array open circuit A+D The PV array open circuit voltage is considered to be equal to
voltage voltage VOC STC ARRAY (see 1.4.36) (see 3.39).

NOTE. The open circuit voltage is dependent on the cell temperature.

1.4.21 PV cell 3.24 PV cell - -

1.4.22 PV kWh meter 3.25 PV kWh meter - -

1.4.23 PV module 3.26 PV module - -

1.4.24 PV module 3.27 PV module connection -


-
connection box box
- -
1.4.25 PV string 3.28 PV string

MS 1837:2010
1.4.26 PV string 3.29 PV string cable -
-
cable
- -
1.4.27 PV sub-array 3.30 PV sub-array
37
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
38

MS 1837:2010
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.
1.4.28 PV sub-array 3.31 PV sub-array cable - -
cable

1.4.29 PV sub-array 3.32 PV sub-array - -


connection box connection box

1.4.30 PV system 3.33 PV system - -

1.4.31 Ripple-free 3.34 ripple free DC - -


d.c.

1.4.32 SELV 3.35 SELV (separated extra- - -


(separated extra-low low voltage)
voltage)

1.4.33 SPD (surge 3.36 SPD(surge protective - -


© STANDARDS MALAYSIA 2010 - All rights reserved

protective device) device

1.4.34 STC 3.37 STC (standards test - -


(standards test conditions)
conditions)

1.4.35 VOC MOD 3.38 VOC STC MOD - -

1.4.36 VOC ARRAY 3.39 VOC STC ARRAY A+D The open circuit voltage at STC of a PV array, and is equal to:

VOC STC ARRAY = VOC STC MOD x M Ns

where M Ns is the number of series-connected PV modules in


any PV string of the PV array.

38
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

© STANDARDS MALAYSIA 2010 - All rights reserved


Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
1
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.
NOTE. This standard assumes that all strings within a PV array are connected
in parallel; hence the open circuit voltage of PV sub-arrays and PV strings is
equal to VOC STC ARRAY.

1.4.37 Voltage 3.40 voltage A+D Differences of potential normally existing between conductors
and between conductors and earth are as follows:

a) extra-low voltage (ELV) - Not exceeding 50 V a.c. AC or


120 V ripple-free d.c. DC; and

b) low voltage (LV) - Exceeding extra-low voltage, but not


exceeding 1 000 V a.c. AC or 1 500 V d.c. DC.
NOTE. When calculating the voltage of a PV array, VOC STC ARRAY is to be used.

SECTION 2 : 4 General Requirements The installation of a grid-connected PV system shall be in


GENERAL A accordance with Figure 1 and Figure 2. These figures shall be
REQUIREMENTS extensively referred to throughout this standard.
SECTION 3 : 5 Protection Requirements
PROTECTION
REQUIREMENTS

3.1 General 5.1 General - -

3.2 By-pass diodes 5.2 By-pass diodes A By-pass diodes shall be used in the PV modules. If by-pass
diodes are not embedded in the PV module encapsulation, they

MS 1837:2010
shall comply with all the following requirements:

a) have a voltage rating at least 2 x VOC STC MOD of the


protected module;

b) have a current rating of at least 1.3 x ISC STC MOD;


39
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
40

MS 1837:2010
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.

c) be installed according to the module manufacturer’s


recommendations;

d) be installed so no live parts are exposed; and

e) be protected from degradation due to environmental factors.


© STANDARDS MALAYSIA 2010 - All rights reserved

Figure 1. Schematic diagram of a grid-connected PV system


(single-phase)

a) removed PV string overcurrent protection device from


negative string cable;
2
b) PV string cable : minimum 2.5 mm ;
c) removed SPD between – ve & + ve cable before and after

40
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

© STANDARDS MALAYSIA 2010 - All rights reserved


Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
1
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.
inverter; and
2
d) earthing : minimum 10 mm .

Figure 2. Schematic diagram of a grid-connected PV system


(three-phase) - New figure included to reflect 3 phase
connection to grid
3.3 Over-current 5.3 Over-current protection

MS 1837:2010
protection

3.3.1 Discrimination 5.3.1 Discrimination A Over-current protection within the PV string shall be graded in
such a way that lower level protection trips first in the event of
fault currents flowing from higher current sections to lower
current sections of the PV array.
41
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
42

MS 1837:2010
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.

NOTE. When circuit breakers with over-current protection elements are used,
they also provide the disconnecting means required in 3.4 5.4.

3.3.2 PV Strings 5.3.2 PV Strings A+D In all cases, where it applies (refer to figure), all PV strings shall
be protected with an over-current protection device with load
breaking disconnecting facilities. These over-current protection
devices shall be installed in (both) positive active conductors.
Suitably rated circuit-breakers used for over-current protection
may also provide load breaking disconnecting facilities (see
3.4) (see 5.4).

The rated trip current (ITRIP) of over-current protection devices


for PV strings shall be as specified by the PV module
manufacturer or, ITRIP shall be determined by the following
formula:
© STANDARDS MALAYSIA 2010 - All rights reserved

1.3 1.5 x ISC STC MOD ≤ ITRIP ≤ 2 x ISC STC MOD

3.3.3 PV array and 5.3.3 PV array and PV sub- - -


PV sub-arrays arrays
3.4 Disconnecting 5.4 Disconnecting means
means

3.4.1 General 5.4.1 General A+D Disconnecting means shall be provided in PV arrays according
to 3.4.2 5.4.2, to isolate the PV array from the inverter and vice
versa and to allow for maintenance and inspection tasks to be
carried out safely.

NOTE. This clause does not apply to module inverters where the inverter is an
integral part of the PV module.

42
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

© STANDARDS MALAYSIA 2010 - All rights reserved


Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
1
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.

3.4.2 Selection and 5.4.2 Selection and A + D, para 1 and 3 Only device with d.c. DC rating which is able to extinguish
installation installation electrical arc shall be used.

Other disconnection and isolation devices having the


characteristics described in 5.4 7.4 may be used as a
disconnection means.
3.4.2.1 PV Strings 5.4.2.1 PV Strings and PV -
and PV sub arrays sub arrays -

3.4.2.2 PV array 5.4.2.2 PV array -


-
3.4.2.3 Inverter 5.4.2.3 Inverter -
-
3.5 Emergency 5.5 Emergency switching A+D The PV array (d.c. DC) load-breaking disconnection device and
switching device device the inverter (a.c. AC) load-breaking disconnection device shall
be used as the emergency switching devices, and therefore
shall be readily accessible and be clearly identified according to
7.4.2 9.4.2.

The emergency switching device shall comply with the


requirements for devices for emergency switching including
emergency stopping as contained in MS IEC 60364 or MS IEC
60364-7-712.The emergency switching device shall open all
active conductors of the PV array cable and shall prevent

MS 1837:2010
further supply by the PV array to its associated d.c wiring

If the emergency switching device is manually operated, the


remote operating device shall be located in a readily accessible
point and be identified in accordance with 7.4.2 9.4.2.
43
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
44

MS 1837:2010
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.

NOTE : This clause is intended to eliminate the shock risk to fire brigade
personnel in the event of a fire emergency in the premises, by disconnecting
otherwise potentially live d.c wiring inside the premises or in readily accessible
areas outside the building.
3.6 Earth fault 5.6 Earth fault protection A All metal casings and frames shall be earthed according to MS
protection IEC 60364 or MS IEC 60364-7-712.

3.7 Lightning 5.7 Lightning protection A+D Lightning protection measures may be required in some PV
protection installations. The need for lightning protection shall be
assessed in accordance with MS IEC 61024-1 62305-1.

A lightning protection system has the task of preventing severe


damage caused by fire or mechanical destruction if a direct
lightning strike occurs on a building or structure. Lightning
protection systems consist of three essential components:

e) an air termination system, consisting of metallic masts or


© STANDARDS MALAYSIA 2010 - All rights reserved

rods of sufficient height to divert lightning currents through


their structure;

f) a down conductor of sufficient cross-sectional area to


conduct lightning currents to earth; and

g) an earth termination system.

For ground mounted or freestanding PV arrays, the need for a


lightning protection system shall be assessed in accordance
with MS IEC 61024-1 62305-1, and if required, it shall be
installed in compliance with that standard.

The installation of a PV array on a building has a negligible

44
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

© STANDARDS MALAYSIA 2010 - All rights reserved


Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
1
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.
effect on the probability of direct lightning strikes and therefore
it does not necessarily imply that a lightning protection system
shall be installed if none is already present. However, if the
physical characteristics or prominence of the building do
change significantly due to the installation of the PV array, it is
required that the need for a lightning protection system be
assessed in accordance with MS IEC 61024-1 62305-1, and if
required, it shall be installed in compliance with that standard.

If a lightning protection system is already installed on the


building, it shall be verified that the PV array and associated
equipment are within the protection zone of the system in
accordance with MS IEC 61024-1 62305-1. If the PV array is
not within the protection zone of the existing lightning protection
system, additional air termination(s) shall be provided in
accordance with MS IEC 61024-1 62305-1.

When a PV array is protected by a lightning protection system,


the metal structure of the PV array shall be bonded to the
lightning protection system, unless the minimum safety
clearances as specified in MS IEC 61024-1 62305-1, can be
achieved.
3.8 Over-voltage 5.8 Over-voltage protection - -
protection

3.8.1 Wiring loops 5.8.1 Wiring loops A+D To reduce the magnitude of lightning induced over-voltages,

MS 1837:2010
the PV array wiring shall be laid in such a way that the area of
conductive loops is minimum (see example in Figure 2 3).
3.8.2 Surge 5.8.2 Surge protective
protective device device (SPD) - -
(SPD)
45
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
46

MS 1837:2010
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.
3.8.2.1 General guide 5.8.2.1 General guide - -

3.8.2.2 Selection 5.8.2.2 Selection - -

3.8.2.3 Usage and 5.8.2.3 Usage and A The usage and installation of SPDs shall be in accordance to
installation installation MS IEC 61643-12. The SPDs on the DC side shall be installed
closest possible to the inverter.

3.8.2.4 SPD 5.8.2.4 SPD specifications to A+D The specifications for SPDs to protect PV arrays and inverter
specifications to protect PV array and inverter (d.c. DC terminal) are as follows (refer to list of parameters for
protect PV array and (DC terminal) SPDs selection in MS IEC 61643-12):
inverter (d.c terminal)
a) SPDs of Class II (in this context, Class II refers to the test
specifications of SPDs rather than insulation class).

b) Have a maximum continuous operating voltage (Uc) with Uc


> 1.3 x VOC STC GEN.
© STANDARDS MALAYSIA 2010 - All rights reserved

c) Have a maximum continuous operating current (Ic) with Ic >


1.3 x ISC STC GEN
Have a maximum discharge current (Imax) (8/20 μs) with Imax
> 40 kA (or at least 20 kA)

d) Have a nominal discharge current (In) (8/20 μs) with In > 20


kA (or at least 10 kA)

e) Have a voltage protection level (Up) with 1.3 x VOC STC GEN <
Up < 1.1 kV.

f) Have a voltage protection level at In (Up) with Up (L-PE) <


1.1 2.5 kV

46
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

© STANDARDS MALAYSIA 2010 - All rights reserved


Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
1
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.

3.8.2.5 SPDs 5.8.2.5 SPDs specifications A+D The specifications for SPD to protect inverter (a.c. AC terminal)
specifications to to protect inverter (AC shall be suitably rated for a.c. AC use and in accordance to MS
protect inverter (a.c terminal) IEC 61643-12 and in conjunction with MS IEC 61643-1.
terminal)

3.8.3 Shielding 5.8.3 Shielding A+D When the PV array frame is bonded to a lightning protection
system, the PV array cable shall be shielded by one of the
following methods, and the shielding conductor shall be
connected to earth at both ends:

a) with a metallic cable armour or shield with an equivalent


2 2
cross-sectional area of 6 mm 10 mm Cu; or
b) with a metallic conduit suitable as a bonding conductor; or
c) with an equipotential bonding conductor with a cross-
2
sectional area of at least 6 mm .

NOTE. 6 mm2 Cu should be able to withstand 20 kA for 1 ms

SECTION 4 : 6 Wiring requirements


WIRING
REQUIREMENTS

4.1 Compliance with 6.1 Compliance with wiring - -


wiring standards standards

MS 1837:2010
4.2 System voltage 6.2 System voltage - -

4.3 Wiring Installation 6.3 Wiring Installation - -

4.3.1 General 6.3.1 General - -


47
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
48

MS 1837:2010
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.
4.3.2 Wiring loops 6.3.2 Wiring loops A+D The PV array wiring should be laid in such a way that the area
of conductive loops is minimised (e.g. by laying cables in
parallel as shown in Figure 2 Figure 3); see also 5.8.1.

Figure 2 Figure 3. PV string wiring with minimum loop


area
© STANDARDS MALAYSIA 2010 - All rights reserved

4.3.3 String, sub- 6.3.3 String, sub-array and A The wiring of PV strings, sub-arrays and array shall satisfy the
array and array wiring array wiring following requirements:

a) Double insulated, DC rated, UV resistant, flex type and fire


retardant shall be used.

b) Cables shall be protected from mechanical damage.

c) Cables shall be clamped (to relieve tension and to prevent


conductors coming free from the connection).

4.3.4 Wiring 6.3.4 Wiring installation in A+D The following provisions apply to the installation of wiring
installation in connection boxes systems in connection boxes:
connection boxes

48
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

© STANDARDS MALAYSIA 2010 - All rights reserved


Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
1
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.
a) Where conductors enter a connection box without conduit,
a tension relief system shall be used to avoid cable
disconnections inside the connection box (for example by
using a gland connector).

b) All cable entries, when installed, shall maintain the IP rating


of the enclosure.

NOTE. Water condensation inside connection boxes may be a problem in


some locations and provision may need to be provided to drain water
build-up.

c) For LV PV arrays, where a return conductor is routed


through module connection boxes, such retirn conductors
shall be double-insulated cables, and the cable and its
insulation shall maintain double insulation status over its
entire length, particularly through connection boxes (i.e
these provisions also apply to the joints)

c) The wiring and its insulation particularly through the


connection box including terminal points shall maintain
double insulation status over its entire length.

34.3.5 Location of PV 3 6.3.5 Location of PV array - -


array and PV sub- and PV sub-array
array connection connection boxes

MS 1837:2010
boxes

4.4 Cable selection 6.4 Cable selection - -


4.4.1 Cable size 6.4.1 Cable size - -
49
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
50

MS 1837:2010
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.
4.4.1.1 General 6.4.1.1 General A+D Cable sizes for PV string cables, PV sub-array cables and PV
2
array cables shall not be less than 2.5 mm and shall be
determined with regard to both, the minimum current capacity
(see 4.4.1.2 ) (see 6.4.1.2) and maximum voltage drop
requirements (see 4.4.1.3) (see 6.4.1.3). The larger cable size
obtained from these two criteria shall be applied.
© STANDARDS MALAYSIA 2010 - All rights reserved

4.4.1.2 Current 6.4.1.2 Current carrying - -


carrying capacity capacity (CCC)
(CCC)

4.4.1.3 Voltage drop 6.4.1.3 Voltage drop - -

4.4.2 Insulation 6.4.2 Insulation A+D a) have a voltage rating of at least 1.2 x VOC STC ARRAY;
NOTE. The use of double insulated and shielded cable is required for
wiring of PV arrays where VOC STC ARRAY ≥ 120 V d.c. DC, to minimise the
risk of faults within the wiring.

4.5 Wiring 6.5 Wiring identifications - -


identifications

50
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

© STANDARDS MALAYSIA 2010 - All rights reserved


Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
1
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.
SECTION 5 : 7 Component requirements
COMPONENT
REQUIREMENTS

5.1 PV modules 7.1 PV modules - -

5.1.1 Reliability 7.1.1 Reliability A Crystalline silicon PV modules shall comply with MS IEC
61215. Thin film PV modules shall comply with MS IEC 61646.

5.1.2 Equipment 7.1.2 Equipment class A PV modules shall be Class II. PV modules shall comply with
class MS IEC 61730-1 and MS IEC 61730-2.

5.1.3 Reverse current 7.1.3 Reverse current - -


5.2 Inverter 7.2 Inverter requirements A+D Inverters shall comply with requirements in accordance to MS
requirements IEC 61000-3-2, MS IEC 61000-6, MS IEC 60364-7-712 and BS
EN 50178 MS 1992 or IEEE 1547 and IEEE 1547.1 or other
equivalent standard. Inverters shall be isolated in the event of
mains supply failure.

5.3 PV array and PV 7.3 PV array and PV sub- - -


sub-array connection array connection boxes
boxes

5.3.1 Environmental 7.3.1 Environmental effects A+D PV array and PV sub-array connection boxes exposed to the
effects environment shall be at least IP 65 56 compliant in accordance
with MS IEC 60529, and shall be UV resistant.

MS 1837:2010
5.4 Switching devices 7.4 Switching devices - -

5.4.1 General 7.4.1 General A+D All switching devices shall comply with all the following
requirements:
51
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
52

MS 1837:2010
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.

a) be rated for d.c. use and able to extinguish electrical arcs


be rated for AC side as AC and be rated for DC side as DC
use and able to extinguish electrical arcs;

b) have a voltage rating equal to greater than, 1.2 x VOC ARRAY


VOC STC ARRAY;

c) not have exposed metallic live parts in connected or


disconnected state; and

d) interrupt all poles.

5.4.2 Current 7.4.2 Current breaking A+D In addition to the requirements of 5.4.1 7.4.1, circuit breakers
breaking devices devices and any other load breaking disconnection devices used for
protection and/or disconnecting means shall comply with the
© STANDARDS MALAYSIA 2010 - All rights reserved

following requirements:

a) not be polarity sensitive (as fault currents in a PV array


may flow in the opposite direction of normal operating
currents);

b) be rated to interrupt full load and prospective fault currents


from the PV array and any other connected power sources
such as batteries, generators and the grid, if present; and

c) when over-current protection is incorporated, the trip


current shall be rated according to 3.3 5.3.

52
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

© STANDARDS MALAYSIA 2010 - All rights reserved


Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
1
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.
5.4.3 Plugs, sockets 7.4.3 Plugs, sockets and A+D Plugs, sockets and couplers shall comply with all the following
and couplers couplers requirements:

a) be rated for d.c. use AC side for AC use and be rated for
DC side for DC use;

b) have a voltage rating equal or greater than 1.2 x VOC ARRAY


VOC STC ARRAY;

c) be protected from contact with live parts in both the


connected and disconnected state (i.e. be shrouded);

d) have a current rating equal to, or greater than, the cable to


which they are fitted;

e) require a deliberate force to disconnect;

f) have a temperature rating suitable for their installation


location;

g) if multipolar, be polarised;

h) comply with Class II; and

i) if exposed to the environment, be rated for outdoor use, be


UV resistant and be at least IP 65 56 compliant.

MS 1837:2010
Plugs and socket outlets normally used for connection to AC
mains power as described in MS 589, shall not be used in PV
arrays wiring.
53
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
54

MS 1837:2010
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.
5.5 Fuses 7.5 Fuses A+D Fuses used in PV arrays shall comply with all the following
requirements:

a) be rated for d.c. use AC for AC use and be rated for DC for
DC use;

b) have a voltage rating equal to, or greater than, 1.2 x VOC


ARRAY VOC STC ARRAY;

c) be rated to interrupt full load and prospective fault currents


from the PV array and connected power sources such as
batteries, generators and the grid, if present; and

d) have a current rating of ≥ 1.5 and ≤ 2 time ISC STC String.

NOTE. When fuses are provided for over-current protection, the use of fused
load break switch-disconnectors (fuse-combination units) is recommended.
© STANDARDS MALAYSIA 2010 - All rights reserved

5.5.1 Fuse holders 7.5.1 Fuse holders A+D a) have a voltage rating equal to, or greater than 1.2 x VOC STC
ARRAY;

5.6 PV kWh meter 7.6 PV kWh meter A+D The PV kWh meter is used to record kWh units of a.c. AC
generated electricity by a PV system. The meter shall be
connected between the a.c. AC breaker and the a.c. AC grid
isolator main switch (a.c. AC load breaking disconnection
device).

The PV kWh meter shall be suitable to record kWh units of a.c.


AC electricity. The meter accuracy shall be of Class 2 (± 2 %).

54
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

© STANDARDS MALAYSIA 2010 - All rights reserved


Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
1
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.
SECTION 6 : 8 Earthing
EARTHING

6.1 General 8.1 General - -

6.2 Earthing 8.2 Earthing electrode - -


electrode

6.3 Equipment 8.3 Equipment earthing - -


earthing

6.3.1 Earthing of 8.3.1 Earthing of equipment A+D Equipment earthing refers to the bonding to earth of all frames
equipment of the PV array including any structural metalwork. Equipment
2
earthing shall be done with at least a 6 10 mm earthing
conductor.

6.3.2 Earthing 8.3.2 Earthing conductors A All PV array earthing conductors shall comply with the material,
conductors type, insulation, identification, installation and connection
requirements as specified in MS IEC 60364 or MS IEC 60364-
7-712.

SECTION 7 : 9 Marking requirements


MARKING
REQUIREMENTS

7.1 General 9.1 General A+D All signs required by (7.2) 9.2 to (7.4) 9.4 shall:

MS 1837:2010
7.2 PV array and PV 9.2 PV array and PV sub- A+D A sign containing the text 'PV D.C. DC' shall be attached to PV
sub-array connection array connection boxes array and PV sub-array connection boxes.
boxes
55
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
56

MS 1837:2010
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.
7.3 Disconnection 9.3 Disconnection devices - -
devices

7.3.1 General 9.3.1 General - -

7.3.2 PV array main 9.3.2 PV array main switch A+D The PV array main switch (d.c. DC load breaking disconnection
switch device) shall be provided with a sign affixed in a prominent
location with the following text: ‘PV D.C DC MAIN SWITCH’.

7.3.3 Inverter main 9.3.3 Inverter main switch A+D The inverter main switch (a.c. AC load breaking disconnection
switch device) shall be provided with a sign affixed in a prominent
location with the following text: ‘PV A.C AC MAIN SWITCH’.

7.4 Fire emergency 9.4 Fire emergency - -


information information

7.4.1 General 9.4.1 General - -


© STANDARDS MALAYSIA 2010 - All rights reserved

7.4.2 Manually 9.4.2 Manually operated A+D When a manually operated switching device is used, the
operated emergency emergency switching device means of operating such device, such as handles or push-
switching device buttons for emergency switching, shall be clearly indicated. The
signs to identify the switching devices (see 7.3.2 9.3.2 and
7.3.3 9.3.3) shall be placed next to them and shall be legible
from at least 1.5 m.

7.5 Shutdown 9.5 Shutdown procedure A A sign, that contains shutdown instructions for the PV system,
procedure shall be located in a prominent location. The sign shall include
the name and location of the relevant disconnection devices.

56
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

© STANDARDS MALAYSIA 2010 - All rights reserved


Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
1
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.
The sign shall also include the following PV array information:

a) open circuit voltage at STC; and

b) short circuit current at STC.

SECTION 8 : 10 Documentation A+D a) a basic circuit diagram that includes the electrical ratings of
DOCUMENTATION the PV array, including the information required by 7.4 9.4;
SECTION 9 : 11 Commissioning
COMMISSIONING

9.1 General 11.1 General - -

9.2 Wiring and 11.2 Wiring and installation A+D The PV array wiring shall be inspected for compliance with the
installation integrity integrity wiring requirements of MS IEC 60364 or MS IEC 60364-7-712,
and the wiring requirements set out in Section Clause 4 of this
standard, and corrected if necessary.

9.3 Open circuit 11.3 Open circuit voltage - -


voltage

9.3.1 General 11.3.1 General - -

9.3.2 Procedure 11.3.2 Procedure A+D NOTE. All measurements should be made when practicable under irradiance
conditions. Conditions close to noon are preferable.

NOTE. It is recommended that all measurements are made under irradiance

MS 1837:2010
conditions (during the daytime with no rain).

-
9.4 PV kWh meter 11.4 PV kWh meter -

9.5 Commissioning 11.5 Commissioning records -


records -
57
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
58

MS 1837:2010
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.
Annex A (informative) Annex A (informative)
Characteristic of PV Characteristic of PV arrays
arrays

A1. PV arrays A1 PV arrays - -

A1.2 Series parallel A1.2 Series parallel - -


configuration configuration

A1.3 Low fault levels A1.3 Low fault levels - -

-
A1.4 Operating A1.4 Operating temperature -
temperature

A2 Grid-connected A2 Grid-connected - -
© STANDARDS MALAYSIA 2010 - All rights reserved

photovoltaic (PV) photovoltaic (PV) systems


systems

Annex B (informative) Annex B (informative)


Examples of signs Examples of signs

B1. Overview B1 Overview A+D This annex provides examples of appropriate signs as specified
in Section 7 Clause 9.

PV D.C. DC

Figure B1. Example of sign required on PV array


connection box (7.2) (9.2)

58
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

© STANDARDS MALAYSIA 2010 - All rights reserved


Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
1
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.

PV D.C. DC
MAIN SWITCH

Figure B2. Example of sign required adjacent to PV array


main switch (7.3.2) (9.3.2)

PV A.C. AC
MAIN SWITCH

Figure B3. Example of sign required adjacent to inverter


main switch (7.3.3) (9.3.3)

MS 1837:2010
59
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (continued)
60

MS 1837:2010
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.

FIRE EMERGENCY INFORMATION

DISCONNECT THE GRID MAINS


POWER INTO THE BUILDING
BEFORE ENTERING THE PREMISE.
THIS WILL ALSO DISCONNECT THE
PV SYSTEM POWER SUPPLY INTO
THE BUILDING
FOLLOW THE PV SYSTEM
SHUTDOWN PROCEDURE TO
FULLY DISCONNECT THE PV
SYSTEM

Figure B4. Example of fire emergency information sign


required on the main switchboard (7.4.1) (9.4.1)
© STANDARDS MALAYSIA 2010 - All rights reserved

PV SYSTEM SHUTDOWN PROCEDURE


STEP 1: Turn off the ‘PV A.C. AC MAIN SWITCH’
located next to the a.c. terminals of the
inverter.

STEP 2: Turn off the ‘PV D.C. DC MAIN SWITCH’


located next to the d.c. DC terminals of the
inverter.

Warning: Do not open plug and socket connectors


or PV string isolators under load

PV Array Open Circuit Voltage at STC: Vdc DC


PV Arry Short Circuit Current at STC: Adc DC

Figure B5. Example of shutdown procedure (7.5) (9.5)

60
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking

© STANDARDS MALAYSIA 2010 - All rights reserved


Table D1. Changes between MS 1837:2005 and MS 1837:2010 (First revision) (concluded)
1
MS 1837 : 2010
MS 1837 : 2005 Additional (A)
(First revision) Amended Text
Clause No. Or Deletion (D)
Clause No.
Annex C (informative)
Maintenance Annex C (informative)
requirements Maintenance requirements

C1. Safety C1 Safety - -

C2. Periodic C2. Periodic maintenance - -


maintenance

C3. Operation and C3. Operation and - -


maintenance maintenance procedures
procedures

MS 1837:2010
61
Acknowledgements

Members of Technical Committee on Renewable Energies

Ir Ahmad Hadri Haris (Chairman) Ministry of Energy, Green Technology and Water
Mr Mohammad Nazmin Noh (Secretary) SIRIM Berhad
Ir Wong Kian Lon Association of Consulting Engineers Malaysia
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

Mr Azman Ahmad Bank Pembangunan Malaysia Berhad


Mr Abdul Nasir Adnan Core Competencies Sdn Bhd
Mr Mohd Rashdan Topa Department of Environment
Mr Mokhtar Mat Min Felda Palm Industries Sdn Bhd
Dr Wan Asma Ibrahim Forest Research Institute Malaysia
Mr Sivaganthan R.Jayasingam Malaysian Photovoltaic Industry Association
Mr Abdul Nasir Abdul Aziz National Solid Waste Management Department
Dr Chen Shiun Sarawak Energy Berhad
Ir Dr Ahmad Zainal Abidin SIRIM Berhad
(Renewable Energy Research Centre)
Ir Francis Xavier Jacob Suruhanjaya Tenaga
Mr Sansubari Che Mud Tenaga Nasional Berhad (Distribution Division)
Ir Kok Yen Kwan The Institution of Engineers, Malaysia
Mr Mohammed Azrin Ali TNB Research Sdn Bhd
Prof Ir Dr Abd Halim Shamsudin Universiti Tenaga Nasional

© STANDARDS MALAYSIA 2010 - All rights reserved


Acknowledgements (continued)

Members of Working Group on Solar Photovoltaic Systems

Assoc Prof Dr Sulaiman Shaari Universiti Teknologi MARA


(Chairman)
Mr Mohammad Nazmin Noh (Secretary) SIRIM Berhad
Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

Ms Rozina Sudin Jabatan Kerja Raya Malaysia


Mr Sivaganthan R.Jayasingam Malaysian Photovoltaic Industry Association
Ms Azah Ahmad Ministry of Energy, Green Technology and Water
Mr Jeyaram Subramaniam/ Optimal Power Solutions Sdn Bhd
Ms Khairunnisa Shan
Mr Benjamin Tan Sabah Electricity Sdn Bhd
Mr Goh Wei Chiun Sarawak Energy Berhad
Mr Hamdan Mokhtar SIRIM Berhad
(Renewable Energy Research Centre)
Mr Jamari Ibrahim Suruhanjaya Tenaga
Mr Yap Ching Kiat The Electrical and Electronics Association of
Malaysia
Mr Khairul Anuar Abd Aziz TNB Energy Services Sdn Bhd
Ms Suhaila Sepeai Universiti Kebangsaan Malaysia
(Solar Energy Research Institute)
Dr Jeyraj Selvaraj Universiti Malaya
Dr Naziha Ahmad Azli Universiti Teknologi Malaysia
Assoc Prof Dr Ahmad Maliki Omar Universiti Teknologi MARA

© STANDARDS MALAYSIA 2010 - All rights reserved


Licensed to UNIVERSITI MALAYSIA PERLIS (UNIMAP) / Downloaded on : 21-Feb-2014 12:34:02 PM / Single user license only, copying and networking prohibited

© Copyright 2010
All rights reserved. No part of this publication may be reproduced or utilised in any form
or by any means, electronic or mechanical, including photocopying and microfilm, without
permission in writing from the Department of Standards Malaysia.