IG-AVRi

Description
Automatic voltage Regulator interface is used for volt / PF control adjustment with galvanic separate
input output.
Every time refer to corresponding AVR manual before interface connecting. Use no droop AVR.
IG-AVRi-TRANS (AC power supply for AVRi) has to be supplied from gen-set voltage.
AVRi output can be connected as symmetrical: OUT1-OUT2 or unsymmetrical OUT1-GND or OUT2-
GND.
Potentiometer on the AVRi defines maximal OUT1, OUT2 voltage range.
Use symmetrical (OUT1,OUT2) AVRi output to connect the AVRi to AVR auxiliary voltage
input.
Use unsymmetrical output if an external AVR potentiometer has to be replaced with AVRi.
AVRi output voltage should change generator voltage typically in range 10 % of Nominal
voltage.
For more details please refer to Application guide chapter AVR interface examples.

IG-AVRi TRANS/LV is power supply unit for IG-AVRi, it is not included in package with IG-AVRi.

Dimensions

IG-AVRi unit is DIN rail mount (35mm)


IG-AVRi TRANS are DIN rail mount (35mm)

Extension Modules 95
IGS-NT, ID-DCU-Accessory Modules.pdf, February 2015
Connectors

OUT1
Output terminals for
GND

output
alternator AVR
OUT2
AC1 Power supply from IG-
AC2 AVRi TRANS/LV
AVRi+ Input signals from the
input
AVRi- controller
Output level Set output voltage bias

Wiring
Example of iG-AVRi wiring:

For more details about wiring see Installation guide.

Technical data
Dimension (WxHxD)
Output OUT1, OUT2 floating (potential free) voltage source
potentiometer adjustable
from +- 1V to +-10V DC, max 15mA
Inputs +AVR, -AVR (two wires, PWM from IG-CU)

Power supply 18V AC from IG-AVRi Trans/LV or IG-AVRi Trans/100


o
Storage temperature - 40C to + 80 C
o o
Operating temperature - 30 C to + 70 C

IG-AVRI TRANS/LV power supply unit


Dimension (WxHxD)
Output 18V AC, max 5VA
230 to 277V AC, frequency 50 to 60Hz
Inputs
400 to 480V AC, frequency 50 to 60Hz
Storage temperature - 40C to + 80oC
Operating temperature - 30oC to + 70oC

Extension Modules 96
IGS-NT, ID-DCU-Accessory Modules.pdf, February 2015
IG-AVRI TRANS/100 power supply unit
Dimension (WxHxD)
Output 18V AC, max 5VA
Inputs 100 to 120V AC, frequency 50 to 60Hz
Storage temperature - 40C to + 80oC
Operating temperature - 30oC to + 70oC