Documente Academic
Documente Profesional
Documente Cultură
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
TEST PROCEDURE ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
Use properly insulated test lead clips and terminals to avoid contact with
unexpected hazardous voltages.
- Test clips should be attached one at a time each time a connection is
SAEP-332
A1 made.
Sec. 3 a
- A single hand should be used to make the connection, in a well
balanced body position, while the other hand should be free from resting
on any surface.
Use caution when long test leads (100 meters or longer) are extended
near overhead high voltage AC power lines, since hazardous voltages
SAEP-332
A2 can be induced into the test leads. Use rubber mats, rubber gloves, or
Sec. 3 b
both, when making measurements if induced AC potentials over 15 volts
are measured on pipelines near high voltage AC power lines.
SAEP-332
B2 Calibrate all meters annually.
Sec. 4.3.2
Page 1 of 8
Use a clamp-on-ammeter for the direct measurements of DC currents.
Meters having current measuring capacity up to 200 amps and a variety
of clamp sizes are preferred. When changing clamp sizes for the same SAEP-332
B4
meter, refer to the manufacturer's instructions for adjusting the readings. Sec. 4.3.4
Currently, the clamp-on ammeters made by William H. Swain company
are widely used in Saudi Aramco facilities.
Page 2 of 8
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) REV 3 30-Jun-08
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
SATR-X-3205
Internal Tank Bottom Testing CP-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
In the clean-up,
-Remove the oxide layer on the copper rod by using fine sand paper
-Renew the copper sulfate electrolyte.
-Fill the electrode half full, as a minimum, with a saturated water solution SAEP-332
B6
of copper sulfate. Sec. 4.3.5.1
-Use only distilled water and chemically pure copper sulfate.
-add an excess of copper sulfate crystals, equal to approximately 10%
(by weight) of the saturated solution in the cell.
For tanks with access holes from the tank roof, measure the "On"
potential measurements at three depths:
1) the tank bottom,
SAEP-332
C2 2) the midpoint, and
Sec. 4.1.7.5
3) one foot below the water level.
Note: Do not place the reference electrode close to the anodes on an
anode string but rather between anodes.
Commentary Note:
Stringent adherence to all required safety precautions, including the use SAEP-332
C5
of fall prevention devices, is required when personnel are taking Sec. 4.1.7.5 a
measurements through tank roof access holes.
Page 3 of 8
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) REV 3 30-Jun-08
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
SATR-X-3205
Internal Tank Bottom Testing CP-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
Commentary Note:
Tank internal CP system commissioning for water tanks should only be SAEP-332
C6
done when the tank is 100% full. This will ensure that the CP system is Sec. 4.1.7.5 b
set to provide protection for the full wetted surface area of the tank.
Commentary Note:
Measure potentials through the reference cell access holes that are
SAEP-332
C7 installed 150 mm from the tank shell (as shown on Standard Drawing No.
Sec. 4.1.7.5 c
AA-036353 or AA-036354). For existing tanks that do not have these
access holes, take the potentials as close to the shell as practical.
Report Forms:
Record all data relative to the commissioning and/or re-commissioning of
SAEP-332
C8 cathodic protection systems on the Commissioning Report forms
Sec. 5
attached in Appendix E of this Engineering Procedure. See Appendix E
Cathodic Protection, Tank Internal Commissioning Report
Evaluation of the Surveys -Forward the detailed data including raw data
and as-built data obtained during the commissioning surveys, to the
SAEP-332
C9 appropriate department for review. Determine the anomalies,
Sec. 4.2
discrepancies, and recommendations for upgrading or improving the
cathodic protection system (if any), and notify the appropriate agencies.
D. TEST EQUIPMENT AND MATERIALS CRITERIA FOR CP EXTERNAL TANK BOTTOM POTENTIAL SURVEY
F. CONCLUSIONS
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
SAEP-332A
F1 Result were in accordance with the Appendix D Commissioning Report.
Appendix D
Test results are acceptable and in accordance with Saudi Aramco SAEP-332A
F2
Engineering Standards and contractual requirements. Appendix D
Page 4 of 8
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) REV 3 30-Jun-08
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
SATR-X-3205
Internal Tank Bottom Testing CP-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
REMARKS:
REFERENCE DOCUMENTS:
1. Schedule Q -- Quality Requirements (Pro Forma Contract), February 2008
2. Schedule G -- Material, Tools and Equipment (Pro Forma MP-IK-LS Contract), March 2006
3. SAEP-332 Cathodic Protection Commissioning 31 May, 2005
4. SAEP-332 A Appendix A through K, 31 May, 2005
5. SAES-X-600 Cathodic Protection of Plant Facilities, 25 June, 2007
NOTES:
1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID).
2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling).
3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products
or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing
states
that the equipment, material, or services either meets appropriate designated standards or has been tested and found suitable for a specified
purpose.
4. Labeled - Equipment or materials to which has been attached a label, symbol, or other identifying mark of an approved qualified organization
concerned
with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the manufacturer
indicates compliance with appropriate standards or performance in a specified manner.
*Person Responsible for Implementation of Test and Analysis of Results Y = YES N = NO F = FAILED
Page 5 of 8
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) REV 3 30-Jun-08
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO TEST REPORT
SATR-X-3205
Internal Tank Bottom Testing CP-
Page 6 of 8
Page 7 of 8
CALIBRATION CERTIFICATE
Certification Agency:
Equipment Type, Model and Serial Number:
SURVEY DATA:
Page 8 of 8