Documente Academic
Documente Profesional
Documente Cultură
This article was published in ASHRAE Journal, November 2016. Copyright 2016 ASHRAE. Posted at www.ashrae.org. This article may
not be copied and/or distributed electronically or in paper form without permission of ASHRAE. For more information about ASHRAE
Journal, visit www.ashrae.org.
Steven T. Taylor
The Fundamentals of
Expansion Tanks
BY STEVEN T. TAYLOR, P.E., FELLOW ASHRAE
Who would have thought such a simple piece of equipment, the expansion
tank, could be so misunderstood, including significant errors and
misunderstandings in published standards, handbooks, and manufacturer’s
installation manuals? In this month’s column, I hope to clear up some of these
issues and to provide simple advice for expansion tank sizing and piping.
I first got into the details of how expansion tanks In fact, after looking into the details and fundamen-
work when working as a commissioning agent for a tals of expansion tanks, which ultimately resulted in
mid-rise office project in the late 1990s. The building an ASHRAE Journal article, “Understanding Expansion
operator claimed the mechanical engineer made design Tanks,” published in 2003,1 I concluded there was noth-
errors because: ing at all wrong with the installation:
• The pressure at the bottom of the heating • The pressure was well below the boiler and pip-
system would rise to about 100 psig (690 kPag) ing system component limits—all were rated for over
when it warmed up each morning, higher than the 150 psig at 200°F (1034 kPag at 93°C)—so while the
operator was used to seeing. pres-
• The expansion tank, which was a precharged sure was higher than the operator was used to, it was not
bladder type tank, was not located at the pump excessive.
suction, as per the manufacturer’s installation and • The manufacturer’s IOM was simply wrong. The
operating manual (IOM), which stated, “…the expan- tank can literally be located anywhere in the system,
sion tank must be connected as close as possible to provided its precharge pressure and size are properly
the suction side of the system circulating pump for se- lected. In this case, locating the tank on the roof
proper system operation.” Instead, the tank was lo- resulted in the smallest and least expensive tank.
cated on the roof, while the pumps (and boilers) were • The sizing equation in the model mechanical
in the basement. codes, both the Uniform Mechanical Code2 and
• The tank size was too small according to the International Mechanical Code,3 do not apply to
sizing equation in the mechanical code. precharged expan-
N O V E M B E R 2016 ashrae.org A S H R A E J O U R N 1
AL
Steven T. Taylor, P.E., is a principal of Taylor Engineering in Alameda, Calif.
He is a member of SSPC 90.1.
Sizing Formulas Ewt = unit expansion ratio of water in the tank due
to temperature rise
One of the first, and still the foremost, major pub- Et = unit expansion ratio of the expansion tank
lications on expansion tank sizing was written by due to temperature rise
Lockhart and Carlson6 in 1953. The authors The last term (0.02 Vs) accounts for additional air
from desorption from dissolved air in the water.
derived the general formula for tank sizing,
Equation 1 (with variable names adjusted to This equation can be simplified to Equation 2 by
match those used in this article), from basic ignor- ing small terms and assuming tank temperature
principles assuming perfect gas laws: stays close to the initial fill temperature (typically a
good assumption, assuming no insulation on the tank or
(
Vs Ew − Ep ) piping to it, which is a common, and recommended,
Vt = PT PT −0.02Vs (1) practice):
PT sh
− Ewt1−
sc v
− sc
PmaxTs+ t
E
PiTs PmaxTs Vs −1−3 α(Th −Tc )
h
vc
V =
Where t Ps Ps (2)
Vt = tank total volume − Pmax
Pi
Vs = system volume This equation includes the credit for the expansion
Ps = starting pressure when water first starts to of the piping system. This term is also relatively
enter the tank, absolute
small and the expansion coefficients are hard to
Pi = initial (precharge) pressure, absolute deter- mine given the various materials in the
Pmax = maximum pressure, absolute
system, but
Ew = unit expansion ratio of the water in the
it is included in Equation 2 since it is included in the
sys- tem due to temperature rise
ASHRAE Handbook7 sizing equations, which in
turn were extracted from an article by Coad.8 This
term is
v
= h −1 also included in some, but not most, expansion tank
v c
manufacturers’ selection software. Most manufactur-
vh = the specific volume of water at the ers conservatively ignore this term since it is small and
maximum temperature, Th. no larger than the terms already ignored in Equation
vc = the specific volume of water at the 2. Ignoring this term results in Equation 3.
minimum temperature, Tc.
Ep = unit expansion ratio of the piping and other vh
−
1 V s
system components in the system due to =v
tem- Vt Ps
c Ps (3)
perature rise
−
= 3 α(Th −Tc ) Pi Pmax
= coefficient of expansion of piping and
The numerator is the volume of the expanded
other system components, per degree
water, Ve, as it warms from minimum to
Th = maximum average water temperature in the maximum tempera- tures, so the equation can be
written:
system, degrees absolute Ps
Ve
Vt =
Tc = minimum average water temperature in the Ps
−
(4)
system, degrees absolute Pi Pmax
flexible membrane, to eliminate air migration) and that 4. Bladder tanks. Bladder tanks use a balloon-like
was designed to be precharged (to reduce tank size). bladder to accept the expanded water. Bladders are
The flexible diaphragm typically is attached to the side often sized for the entire tank volume, called a “full
of the tank near the middle and is not field replaceable; acceptance” bladder, to avoid damage to the bladder
if the diaphragm ruptures, the tank must be replaced. in case they become waterlogged. Bladders are
gener-
Where either a special order can be made from the fac-
Ve = (vh/vc – 1)Vs tory or the contractor must increase the pressure
Equation 4 can be further simplified based on the with compressed air or a hand pump. But it is not
style uncommon for this to be overlooked. This oversight
of tank used. For vented tanks, the pressures are all can be compensated for by sizing the tank using
the same and the dominator limits to 1, so the tank Equation 8 (assuming atmospheric pressure at sea
size is simply the volume of expanded water:† level):
Vented Tank Vt = Ve (5) Closed Tank
(12 psig/26.7 psia [83 kPag/184 kPaa] precharge)
For unvented plain steel tanks, the starting
pres-
sure is typically atmospheric pressure with the tank Ve
Vt =
empty (no precharge). The tank is then connected 26.7 (8)
26.7−
to
Pi Pmax
the makeup water, which pressurizes the tank to the
fill pressure by displacing air in the system,
This will increase the tank size vs. a properly pre-
essentially wasting part of the tank volume. So the
charged tank.
sizing equa- tion‡ is: ASME Boiler and Pressure Vessel Code-2015, Section
VI,
Ve includes sizing equations (as do the UMC and IMC,
Vt = which extract the equations verbatim), as shown in
Closed Tank (no precharge) Pa Pa (6
Pi − ) Equation 10, with variables revised to match those
used in this article:
Where Pmax
Pa = atmospheric pressure Vs (0.00041Th −0.0466)
V=
For any tank that is precharged to the required initial t Pa Pa (9)
pressure, including properly charged diaphragm and − Pmax
Pi
bladder tanks, but also including closed plain steel Comparing the denominator of Equation 9 to
tanks if precharged, Ps is equal to Pi so the sizing Equation 6, this formula is clearly for sizing a non-
equa- tion reduces to: precharged tank; it will overestimate the size of a pre-
Ve charged tank.
Precharged Tank Vt = (7) The numerator is a curve fit of Ve; it assumes a mini-
Pi
1−
Pmax mum temperature of 65°F (18°C) and is only
accurate in the range of about 170°F to 230°F (77°C
Note that this equation only applies when the to 110°C) average operating temperature. Therefore,
tank is precharged to the required Pi. Tanks are fac- this equa- tion cannot be used for very high
tory charged to a standard precharge of 12 psig (83 temperature hot water (e.g. 350°F [177°C]), closed-
kPag).§ For higher desired precharge pressures, circuit condenser water, or chilled water systems.
† In the 2016 ASHRAE Handbook—Systems and Equipment, Chapter 13, the analogous equation includes a factor of 2,
doubling tank size. This is a common, but unnecessarily conservative, safety factor to ensure the tank does not overflow.
‡ In the 2016 ASHRAE Handbook Systems and Equipment, Chapter 13, the analogous equation is said to apply to all closed
plain steel tanks. In fact, it only applies to any tank that is not precharged.
§ The 12 psig (83 kPag) standard precharge comes from old residential construction where the boiler and expansion tank are
typically in the basement. This results in a slight positive pressure at the top of the system in a typical two-story house.
ally field replaceable. This is now the most common type of large commercial expansion tank. (See sidebar,
“Typical Expansion Tank Piping,” for a typical piping above work by allowing water to compress a cham-
diagram.) ber of air as the water expands with increasing tem-
The three closed type expansion tanks described perature (Figure 1). When the system is cold and
the water in the tank is at minimum level (which
may be no water at all), the tank pressure is at its
initial
Typical Expansion 4. A bypass around the PRV is recommended to
reduce the time required to fill the system. Higher
Tank Piping fill velocities also tend to help the water entrain
air
bubbles and carry them toward the manual air vents
Figure 2 shows how bladder expansion tanks are at high points.
typi- cally piped. Notes corresponding to numbers in 5. Makeup water must be protected with backflow
the figure are as follows: preventers, per code. The available pressure must be
1. Vertical tanks are most common for
above the PRV setpoint. For high-rise buildings with
commercial projects and mounted on the floor for multiple domestic (or reclaimed) water pressure zones
ease of construc- tion and maintenance access. and where the tank is located low in the building, it is
Horizontal tanks are usually necessary to connect to the high pressure zone
also available for suspension from the structure above riser rather than the low pressure zone serving plumb-
where floor space is inadequate. ing fixtures at the tank location. This requirement is
2. If makeup water is located at the expansion tank
commonly overlooked.
as shown, the pressure reducing valve (PRV) setpoint 6. A pressure relief valve must be located between
may conveniently be the same as the precharge the tank isolation valve (Note 11) and the system
pressure of con- nection, so it is available even when the tank is
the tank (Pi ) so the two are coordinated regardless of valved off for maintenance. On hot water systems,
pump operation. It is possible, and sometimes neces-
this valve will be located at the boiler (per code), so
sary, to have the two separated. For instance, there it cannot be valved off from the heat source.
may not be a convenient makeup water source near 7. A gauge pressure sensor or switch connected to
the preferred tank location (see Note 5, for example). the building automation system is recommended to
In this case, the PRV setpoint must be adjusted to gener- ate an alarm when the pressure drops below
account for the elevation difference between the the mini-
PRV and tank. In this case, however, the pressure at
mum pressure (Pi ), indicating either the system needs
the PRV will vary depending on pump operation. To refilling (see Note 3) or a major leak has occurred.
avoid overfilling the system, the makeup water 8. Expansion tank installation and operating manuals
connection must be valved off once the system is (IOMs) generally recommend connecting to the side of
filled and air removed (see Note 3). In addition, the system main piping, rather than the bottom (where
because some over- filling will inevitably occur, the debris might migrate to the tank) or top (where air
tank should be sized conservatively. may result in an air lock). If a bottom connection
3. Once the system is filled and air is removed, the
cannot be avoided, a dirt leg with drain should be
makeup water connection should be valved off. This installed.
prevents “feeding a flood” should there be a major 9. Sizing of the piping from the tank to the system
leak in the system.# When the system has small is somewhat controversial. In normal operation, the
normal water losses, e.g., at automatic air vents and flow rate of water as it moves back and forth to and
pump seals, the valve will have to be reopened from the tank is very low. Even after a cold start, the
occasionally. A low-pressure alarm (Note 7) can be water temperature and volume in the system
used to indicate when a refill is needed. generally rise slowly so the flow rate, and resulting
pressure drop, are low. A 0.75 in. (19 mm) line
should be more than
# On one of our early high-rise projects in the late ‘80s, an improperly supported pipe caused a pump casing to crack, causing
a ma- jor leak. Naturally, the break occurred over a weekend when no one was around. The pump was located on the 30th
floor. A security guard in the lobby noticed the leak when water poured onto his desk after leaking through all 29 stories of
office space. The damage would have been minimal if the makeup water valve had been closed.