YASNAC MRC ver. 3.

144B

Trouble Shooting Guide, YASNAC MRC

MOTOMAN ROBOTICS AB
a subsidiary of YASKAWA Electric Corporation
MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 1

Alarm 0010 CPU Board Insertion Error

Alarm Occurrence

Turn power OFF,


and then ON again.

Alarm
NO re-occurs? YES

Resume use Remove the SV board corresponding


to the display, and then re-install it

Alarm
YES re-occurs? NO

Remove the MCP01 Resume use


board, and then re-install it

Alarm
NO re-occurs? YES

Resume use Replace the ROM of the board


corresponding to the display

Alarm
NO re-occurs? YES

ROM failure Replace the board


corresponding to the display

Alarm
YES re-occurs? NO

Board failure
Replace all boards

Alarm
NO re-occurs? YES

Board failure Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 2 AB

Alarm 0020 CPU Communication Error

Alarm Occurrence

Turn power OFF,


and then ON again.

Alarm
NO re-occurs? YES

Resume use Remove the SV board corresponding


to the display, and then re-install it

Alarm
YES re-occurs? NO

Remove all boards, Resume use


and then re-install them

Alarm
NO re-occurs? YES

Resume use Replace the ROM of the board


corresponding to the display

Alarm
NO re-occurs? YES

ROM failure Replace the board


corresponding to the display

Alarm
YES re-occurs? NO

Board failure
Replace all boards

Alarm
NO re-occurs? YES

Board failure Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 3

Alarm 0030 ROM Error

Alarm Occurrence

Turn power OFF,


and then ON again.

Alarm
NO re-occurs? YES

Resume use Replace the ROM of the board


corresponding to the display

Alarm
NO re-occurs? YES

ROM failure Replace the board


corresponding to the display

Alarm
YES re-occurs? NO

Contact Board failure


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 4 AB

Alarm 0040 RAM Error (local)

Alarm Occurrence

Turn power OFF,


and then ON again.

Alarm
NO re-occurs? YES

Resume use Remove the board corresponding


to the display, and then re-install it

Alarm
NO re-occurs? YES

Resume use Replace the board


corresponding to the display

Alarm
YES re-occurs? NO

Contact Board failure


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 5

Alarm 0050 RTC Error)

Alarm Occurrence

Turn power OFF,


and then ON again.

Alarm
NO re-occurs? YES

Resume use Remove the board corresponding


to the display, and then re-install it

Alarm
NO re-occurs? YES

Resume use Replace the board


corresponding to the display

Alarm
YES re-occurs? NO

Contact Board failure


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 6 AB

Alarm 0060 RAM Error (A-bus Common)

Alarm Occurrence

Turn power OFF,


and then ON again.

Alarm
NO re-occurs? YES

Resume use Remove the board corresponding


to the display, and then re-install it

Alarm
YES re-occurs? NO

Remove all boards Resume use


and re-install again

Alarm
NO re-occurs? YES

Resume use Replace the board


corresponding to the display

Alarm
YES re-occurs? NO

Replace all boards Board failure

Alarm
NO re-occurs? YES

Board failure Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 7

Alarm 0070 RAM Error (D-Bus 2-Port)

Alarm Occurrence

Turn power OFF,


and then ON again.

Alarm
NO re-occurs? YES

Resume use Remove the SV board corresponding


to the display, and then re-install it

Alarm
YES re-occurs? NO

Remove all boards Resume use


and re-install again

Alarm
NO re-occurs? YES

Resume use Replace the SV board


corresponding to the display

Alarm
NO re-occurs? YES

SV board failure Replace the MCP02 board

Alarm
YES re-occurs? NO

Replace all boards Board failure

Alarm
NO re-occurs? YES

Board failure Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 8 AB

Alarm 0080 RAM Error (S-Bus 2-Port)

Alarm Occurrence

Turn power OFF,


and then ON again.

Alarm
NO re-occurs? YES

Resume use Remove the board corresponding


to the display, and then re-install it

Alarm
YES re-occurs? NO

Remove MCP01 Resume use


and re-install again

Alarm
NO re-occurs? YES

Resume use Replace the board


corresponding to the display

YES Alarm
re-occurs? NO

Replace the MCP01 board Board failure

Alarm
NO re-occurs? YES

MCP01 board failure Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 9

Alarm 0090 I/O Module Communication Error

Alarm Occurrence

Turn power OFF,


and then ON again.

Alarm
NO re-occurs? YES

Resume use Confirm the setting


of the I/O module

Alarm
YES re-occurs? NO

Check the wiring of the cable Resume use


between MIF01 and MBB02

Alarm
NO re-occurs? YES

Resume use Remove the I/O module corresponding


to the display, and then re-install it

Alarm
YES re-occurs? NO

Replace the I/O module Resume use

Alarm
NO re-occurs? YES

I/O module Replace MIF01 board


failure
Alarm
YES re-occurs? NO

Contact MIF01 board failure


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 10 AB

Alarm 0100 IAMP Communication Error

Alarm Occurrence

Turn power OFF,


and then ON again.

Alarm
NO re-occurs? YES

Resume use Remove the cable connector


between the MSV board and IAMP

Alarm
YES re-occurs? NO

Check the wiring of the cable Resume use


between MSV board and IAMP

Alarm
NO re-occurs? YES

Resume use Confirm the setting


of the servopack

Alarm NO
YES re-occurs?

Replace the servopack Resume use

Alarm
NO re-occurs? YES

Servopack failure Replace the MSV board

Alarm
YES re-occurs? NO

Contact MSV board failure


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 11

Alarm 0110 IAMP Parameter Modification Error

Alarm Occurrence

Turn power OFF,


and then ON again.

Alarm
NO re-occurs? YES

Resume use Remove the cable connector between


the MSV board and IAMP and re-install

Alarm
YES re-occurs? NO

Check the wiring of the cable Resume use


between MSV board and IAMP

Alarm
NO re-occurs? YES

Resume use Replace the servopack

Alarm
NO re-occurs? YES

Servopack failure Replace the MSV board

Alarm
YES re-occurs? NO

Contact MSV Board


MOTOMAN-service failure

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 12 AB

Alarm 0120 Encoder communication error

Alarm Occurrence

Turn power OFF,


and then ON again.

Alarm Remove the cable connector between


Resume use NO re-occurs? YES
the MSV board and IAMP and re-install

Remove the cable connector Alarm


between encoder and IAMP, YES re-occurs? NO
and then re-install it
Resume use
Alarm
Resume use NO re-occurs? YES
Remove the cable connector
between encoder and IAMP,
and then install to another axis

Check the cable ground Alarm


YES re-occurs? NO
between encoder and IAMP

Alarm Replace the


Cable failure NO re-occurs? servopack

YES Alarm
NO re-occurs?
Check the wiring of the cable Servopack
between MSV board and IAMP failure YES

Alarm Replace the


Cable failure NO re-occurs? MSV board

YES YES Alarm


re-occurs?
Reset the absolute Contact
encoder MOTOMAN-service NO

Replace the Alarm BSV Board


YES re-occurs? NO Resume use
motor failure

Alarm Contact
YES MOTOMAN-service
re-occurs?

NO

Motor failure

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 13

Alarm 0130 Encoder Overspeed

Alarm Occurrence

Turn power OFF,


and then ON again.

Alarm
NO re-occurs? YES

Resume use After the motor stops,


control power ON.

Alarm
YES re-occurs? NO

Reset the Resume use


absolute encoder

Alarm
NO re-occurs? YES

Resume use Replace


servo motor

Alarm
YES re-occurs? NO

Contact Motor failure


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 14 AB

Alarm 0131 Encoder Data Error

Alarm Occurrence

Turn power OFF,


and then ON again.

Alarm
NO re-occurs? YES

Resume use Reset the


absolute encoder

Alarm
NO re-occurs? YES

Resume use Replace the motor

Alarm
YES re-occurs? NO

Contact Motor failure


MOTOMAN-service

Alarm 0132 Encoder Back-up Error

Alarm Occurrence

Change the battery, reset the alarm


and then set home position

Alarm
NO re-occurs? YES

Resume use Reset the


absolute encoder

Alarm
NO re-occurs? YES

Resume use Replace the motor

Alarm
YES re-occurs? NO

Contact Motor failure


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 15

Alarm 0133 Encoder Checksum Error

Alarm Occurrence

Change the battery, reset the alarm


and then set home position.

Alarm
NO re-occurs? YES

Resume use Reset the


absolute encoder

Alarm
NO re-occurs? YES

Resume use Replace


servo motor

Alarm
YES re-occurs? NO

Contact Motor failure


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 16 AB

Alarm 0134 Encoder Battery Error

Alarm Occurrence

Change the battery

Alarm
NO re-occurs? YES

Resume use Check


Internal wiring

Alarm
YES re-occurs? NO

Reset the Resume use


absolute encoder

Alarm
NO re-occurs? YES

Resume use Replace the motor

Alarm
YES re-occurs? NO

Contact Motor failure


MOTOMAN-service

Alarm 0135 Encoder Overheat


Alarm Occurrence

After cooling, turn the


power ON again

Alarm
NO re-occurs? YES

Resume use Check


Internal wiring

Alarm
YES re-occurs? NO

Contact Internal wire


MOTOMAN-service failure

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 17

Alarm 0200 Fault (Parameter)

Alarm Occurrence

Turn power OFF,


and then ON again.

Alarm
NO re-occurs? YES

Resume use Contact MOTOMAN-


service before
initializing the parameter file

Alarm 0210 Fault (System Config-Data)

Alarm Occurrence

Contact MOTOMAN-
service before
initializing the parameter file

Alarm 0220 Fault (Job Management Data)

Alarm Occurrence

Turn power OFF,


and then ON agian.

Alarm
NO re-occurs? YES

Resume use Initialize the job file

Alarm
YES re-occurs? NO

Contact Job file destroyed


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 18 AB

Alarm 0230 Fault (CIO Ladder)

Alarm Occurrence

Initialize the
CIO Ladder

Alarm
NO YES
re-occurs?

CIO Ladder Contact


destroyed MOTOMAN-service

Alarm 0300 Verify Error (System Config-Data)

Alarm Occurrence

Contact MOTOMAN-
service before
initializing the system config.

Alarm 0310 Verify Error (CMOS Memory Size)

Alarm Occurrence

Confirm the
extension CMOS board

Alarm
NO re-occurs? YES

The extension CMOS Contact MOTOMAN-


board is not mounted service before
initializing the system config.

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 19

Alarm 0320 Verify Error (I/O module)

Alarm Occurrence

Remove the I/O-module that corresponds


to the display, then re-install the module

Alarm
NO re-occurs? YES

Resume use Confirm the setting


of the I/O module

Alarm
YES re-occurs? NO

Replace the I/O module Resume use


corresponding to the display

Alarm
NO re-occurs? YES

I/O module failure Contact


MOTOMAN-service

Alarm 0330 Illegal Parameter

Alarm Occurrence

Reset original
parameter value

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 20 AB

Alarm 0340 Verify Error (Servopack Type)

Alarm Occurrence

Set the parameter to match the


mounted servopack type

Alarm
NO re-occurs? YES

Resume use Contact MOTOMAN-


service before
initializing the system config.

Alarm 0350 Verify Error (Encoder Type)

Alarm Occurrence

Set the parameter to match the


mounted encoder type

Alarm
NO re-occurs? YES

Resume use Contact MOTOMAN-


service before
initializing the system config.

Alarm 0360 Verify Error (Application)

Alarm Occurrence

Contact MOTOMAN-service
before initializing the system config.

Alarm 0370 Verify Error (Sensor Function)

Alarm Occurrence

Contact MOTOMAN-service
before initializing the system config.

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 21

Alarm 0400 Parameter Transmission Error

Alarm Occurrence

Turn power OFF,


and then ON agian.

Alarm
NO re-occurs? YES

Resume use Replace the board


corresponding to the display

Alarm
NO re-occurs? YES

Board failure Replace


all boards

Alarm
YES re-occurs? NO

Contact Board failure


MOTOMAN-service

Alarm 0410 Mode Change Error

Alarm Occurrence

Turn power OFF,


and then ON again.

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 22 AB

Alarm 0900 - 0920 Watch Dog Timer Error

Turn power OFF,


and then ON agian. Alarm Occurrence

Alarm
re-occurs?
NO YES
Remove the board corresponding to
Resume use the display, then re-install it

Remove all boards, Alarm


then re-install them YES re-occurs?

Alarm NO
re-occurs?
NO Resume use
YES
Resume use Replace the EPROM of the board
corresponding to the display

Replace board Alarm


corresponding to the display YES re-occurs?

Alarm NO
re-occurs?
YES NO EPROM failure

Replace all Board failure


boards
Alarm
re-occurs? YES
NO
Contact
Board failure MOTOMAN-service

AL-0900 MCP02 AL-0906 MCP01 AL-0914 MSV#5


AL-0901 AL-0907 MIF01 AL-0915 MSV#6
AL-0902 MSL#1 AL-0910 MSV#1 AL-0916 MSV#7
AL-0903 MSL#2 AL-0911 MSV#2 AL-0917
AL-0904 AL-0912 MSV#3 AL-0920 MIF02
AL-0905 AL-0913 MSV#3

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 23

Alarm 0930 - 0937 Access Error

Turn power OFF,


and then ON agian. Alarm Occurrence

Alarm
re-occurs?
NO YES
Remove the board corresponding to
Resume use the display, then re-install it

Remove all boards, Alarm


then re-install them YES re-occurs?

Alarm NO
re-occurs?
NO Resume use
YES
Resume use Replace the EPROM of the board
corresponding to the display

Replace board Alarm


corresponding to the display YES re-occurs?

Alarm NO
re-occurs?
YES NO EPROM failure

Replace all Board failure


boards
Alarm
re-occurs? YES
NO
Contact
Board failure MOTOMAN-service

AL-0930 MIF02 AL-0933 MSL#2 AL-0936 MCP01


AL-0931 AL-0934 AL-0937 MIF01
AL-0932 MSL#1 AL-0935

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 24 AB

Alarm 0940 - 0947 A-Bus Error

Turn power OFF,


and then ON agian. Alarm Occurrence

Alarm
re-occurs?
NO YES
Remove the board corresponding to
Resume use the display, then re-install it

Remove all boards, Alarm


then re-install them YES re-occurs?

Alarm NO
re-occurs?
NO Resume use
YES
Resume use Replace the EPROM of the board
corresponding to the display

Replace board Alarm


corresponding to the display YES re-occurs?

Alarm NO
re-occurs?
YES NO EPROM failure

Replace all Board failure


boards
Alarm
re-occurs? YES
NO
Contact
Board failure MOTOMAN-service

AL-0940 MIF02 AL-0943 MSL#2 AL-0946 MCP01


AL-0941 AL-0944 AL-0947 MIF01
AL-0942 MSL#1 AL-0945

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 25

Alarm 0999 NMI Error

Alarm Occurrence

Turn power OFF,


and then ON agian.

Alarm
re-occurs?
NO YES

Resume use Remove all boards


and then re-install them

Alarm
re-occurs?
YES NO

Replace EPROM Resume use


of all boards

Alarm
re-occurs?
NO

EPROM failure Replace


all boards

Alarm
re-occurs?
YES NO

Contact Board failure


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 26 AB

Alarm 1010 ROM Error (Syscon)

Alarm Occurrence

Turn power OFF,


and then ON agian.

Alarm
re-occurs?
NO YES

Resume use Remove the EPROM board on the


MCP01 board and then re-install them

Alarm
re-occurs?
YES NO

Replace EPROM board Make sure connector has


on the MCP01 board no loose connections,
and then resume use
Alarm
re-occurs?
NO

MMM02 failure Replace MCP01


board

Alarm
re-occurs?
YES NO

Contact Board failure


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 27

Alarm 1020 ROM Error (Motion)

Alarm Occurrence

Turn power OFF,


and then ON agian.

Alarm
re-occurs?
NO YES

Resume use Remove the EPROM board on the


MCP02 board and then re-install them

Alarm
re-occurs?
YES NO

Replace EPROM board Make sure connector has


on the MCP02 board no loose connections,
and then resume use
Alarm
re-occurs?
NO

MMM04 failure Replace MCP02


board

Alarm
re-occurs?
YES NO

Contact Board failure


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 28 AB

Alarm 1030 ROM Error (CIO)

Alarm Occurrence

Turn power OFF,


and then ON agian.

Alarm
re-occurs?
NO YES

Resume use Remove the EPROM board on the


MIF01 board and then re-install them

Alarm
re-occurs?
YES NO

Replace EPROM board Make sure connector has


on the MCP01 board no loose connections,
and then resume use
Alarm
re-occurs?
NO

EPROM failure Replace MIF01


board

Alarm
re-occurs?
YES NO

Contact Board failure


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 29

Alarm 1040 System Error (Syscon)

Alarm Occurrence

Turn power OFF,


and then ON agian.

Alarm
re-occurs?
NO YES

Resume use Replace MCP01


board

Alarm
re-occurs?
YES NO

Contact Board failure


MOTOMAN-service

1 6 Multi Task Specification Error


2 Motion Interrupt Not Done 7 Lack of Command Saving Area
3 Syscon Error 8 EMS Error
4 Command Processing 9
5 Undefined Interrupt 10 SL Interrupt Not Done

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 30 AB

Alarm 1050 ROM Error (Sensor)

Alarm Occurrence

Turn power OFF,


and then ON agian.

Alarm
re-occurs?
NO YES

Resume use Remove the EPROM board on the


MSL board and then re-install it

Alarm
re-occurs?
YES NO

Replace EPROM board Make sure connector has


on the MSL board no loose connections,
and then resume use
Alarm
re-occurs?
NO YES

EPROM failure Replace MSL board


corresponding to the display

Alarm
re-occurs?
YES NO

Contact Board failure


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 31

Alarm 1060 System Error (CIO)

Alarm Occurrence

Turn power OFF,


and then ON agian.

Alarm
re-occurs?
NO YES

Resume use Replace MIF01


board

Alarm
re-occurs?
YES NO

Contact Board failure


MOTOMAN-service

01 05 Command Error SYSCONCIO


02 06 System Error
04 FA Communication Bus Error

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 32 AB

Alarm 1070 Fault (Parameter)

Alarm Occurrence

Turn power OFF,


and then ON agian.

Alarm
re-occurs?
NO YES

Resume use Initialize


the parameter file

Alarm
re-occurs?
YES NO

Contact MOTOMAN- Board failure


service before
initializing the system config.

0 RC parameters 8 AP parameters
1 RO parameters 9 RS parameters
2 SV paramerters 10 SP parameters
3 SVM parameters 11 CM parameters
4 SC parameters 12 SE parameters
5 SD parameters 13 VC parameters
6 CIO parameters 14 RSM parameters
7 FD parameters

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 33

Alarm 1080 Fault (Job data)

Alarm Occurrence

Turn power OFF,


and then ON agian.

Alarm
re-occurs?
NO YES

Resume use Initialize


the job file

Alarm
re-occurs?
YES NO

Contact MOTOMAN- Job file destroyed


service before
initializing the system config.

Alarm 1090 File Failure (Motion)

Alarm Occurrence

Turn power OFF,


and then ON agian.

Alarm
re-occurs?
NO YES

Resume use Contact MOTOMAN-


service before
initializing the system config.

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 34 AB

Alarm 1100 File Total Checksum Error (Motion)

Turn power OFF,


and then ON agian. Alarm Occurrence

Alarm
re-occurs?
NO YES

Resume use Replace MCP02


board

Alarm
re-occurs?
YES NO

Contact Board failure


MOTOMAN-service

Alarm 1110 Set-up Process Error (Syscon)

Turn power OFF,


and then ON agian. Alarm Occurrence

Alarm
re-occurs?
NO YES

Resume use Replace MCP02


board

Alarm
re-occurs?
YES NO

Contact Board failure


MOTOMAN-service

1 Motion Section Set-up incomplete

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 35

Alarm 1120 Wrong Segment Clock Value

Turn power OFF,


and then ON agian. Alarm Occurrence

Alarm
re-occurs?
NO YES

Resume use Reset phase offset


data file

Alarm
re-occurs?
YES NO

Contact CMOS file breakdown


MOTOMAN-service

Alarm 1130 MMM Error

Turn power OFF,


and then ON agian. Alarm Occurrence

Alarm
re-occurs?
NO YES

Resume use Contact


MOTOMAN-service

0 3 Process Not Set


1 Process Definition Table Not Set 4 Process Control Code Not Set
2 Entry Table Overflow

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 36 AB

Alarm 1140 MMM Error

Alarm Occurrence

Turn power OFF,


and then ON agian.

Alarm
re-occurs?
NO YES

Resume use Contact


MOTOMAN-service

Alarm 1150 Fault

Alarm Occurrence

Turn power OFF,


and then ON agian.

Alarm
re-occurs?
NO YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 37

Alarm 1160 High Temperature (in Control Box)

Alarm Occurrence

Turn power OFF,


and then ON agian.

Alarm
re-occurs?
NO YES

Resume use Turn the power off, let the controller


cool inside, and then turn power on again

Alarm
re-occurs?
YES NO

Check movement of cooling fan Resume use

Alarm
re-occurs?
NO YES

Check wiring cooling fan

Faulty?

NO YES

Replace fan Contact


MOTOMAN-service
Replace power unit Alarm
YES re-occurs?
(CPS-18F)
NO
Alarm
re-occurs? Fan failure
NO

YES Power unit failure

Contact
MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 38 AB

Alarm 1170 Overrun Limit Switch Released

Alarm Occurrence

Turn power OFF,


and then ON agian.

Alarm
re-occurs?
NO YES

Resume use Check the


OVERRUN RECOVERY
switch

Alarm
re-occurs?
YES NO

Contact Switch failure


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 39

Alarm 1180 - 1186 Servo Monitor System Error

Alarm Occurrence

Turn power OFF,


and then ON agian.

Alarm
re-occurs?
NO YES

Resume use Replace MSV board


corresponding to the display

Alarm
re-occurs?
YES NO

Board failure
Replace MCP01 board

Alarm
re-occurs?
NO YES

Board failure
Replace MCP02 board

Alarm
re-occurs?
YES NO

Contact Board failure


MOTOMAN-service

AL-1180 MSV#1 AL-1183 MSV#4 AL-1186 MSV#7


AL-1181 MSV#2 AL-1184 MSV#5
AL-1182 MSV#3 AL-1185 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 40 AB

Alarm 1190 - 1196 Servo System Error

Alarm Occurrence

Turn power OFF,


and then ON agian.

Alarm
re-occurs?
NO YES

Resume use Replace MSV board


corresponding to the display

Alarm
re-occurs?
YES NO

Board failure
Replace MCP01 board

Alarm
re-occurs?
NO YES

Board failure
Replace MCP02 board

Alarm
re-occurs?
YES NO

Contact Board failure


MOTOMAN-service

AL-1190 MSV#1 AL-1193 MSV#4 AL-1196 MSV#7


AL-1191 MSV#2 AL-1194 MSV#5
AL-1192 MSV#3 AL-1195 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 41

Alarm 1200 - 1206 Overcurrent

Alarm Occurrence

Condition
At control at the time At servo
power ON power ON
of alarm?

Replace servopack
corresponding to the display Running
Check first
grounding terminal
Alarm
re-occurs?
Go to
NO point Faulty
YES A grounding

Contact Servopack NO YES


MOTOMAN-service failure
Replace servopack
corresponding
to the display
B

Check second Alarm


ground terminal re-occurs?

Faulty NO YES
grounding
YES NO Servopack
failure
Check
internal wiring Replace motor Contact
corresponding MOTOMAN-service
Alarm to the display
re-occurs?
Alarm
NO YES re-occurs?
NO
Internal wiring YES
failure Servomotor
failure
Contact
MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 42 AB

Alarm 1200 - 1206 Overcurrent (...continued)

Check movement of
servopack cooling fan

Abnormal?
YES NO

Replace Check
cooling fan robot load

Alarm Fan Load


re-occurs? NO failure condition?
OK
YES Overload
Alarm
Contact occurs at a Decrease
MOTOMAN-service specific point? weight
NO
YES
Check first
grounding terminal

Faulty Go to
YES grounding NO point
B

Replace servopack
corresponding
to the display

Alarm Servopack
re-occurs? NO failure

YES Contact
MOTOMAN-service

AL-1200 MSV#1 AL-1203 MSV#4 AL-1206 MSV#7


AL-1201 MSV#2 AL-1204 MSV#5
AL-1202 MSV#3 AL-1205 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 43

Alarm 1210 - 1216 MCCB Tripped

Alarm Occurrence

At control
power ON
Condition
At servo
at the time power ON
Turn ON the of alarm?
MCCB

Alarm
re-occurs? NO Running
Check first
grounding terminal
YES Resume use
Go to
Replace servopack point Faulty
corresponding to the display A grounding

Alarm Servopack NO YES


re-occurs? NO failure
Replace servopack
YES corresponding
to the display
B
Contact
MOTOMAN Check second Alarm
service ground terminal re-occurs?

Faulty NO YES
grounding
YES NO Servopack
failure
Replace
internal wiring Replace motor Contact
corresponding MOTOMAN-service
Alarm to the display
re-occurs?
Alarm
NO YES re-occurs?
NO
Internal wiring YES
failure Motor failure

Contact
MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 44 AB

Alarm 1210 - 1216 MCCB Tripped (...continued)

Check
robot load

Load
condition?
OK
Overload
Alarm
occurs at a Decrease
specific point? weight
NO
YES
Check first
grounding terminal

Faulty Go to
YES grounding NO point
B

Replace servopack
corresponding
to the display

Alarm Servopack
re-occurs? NO failure

YES Contact
MOTOMAN-service

AL-1210 MSV#1 AL-1213 MSV#4 AL-1216 MSV#7


AL-1211 MSV#2 AL-1214 MSV#5
AL-1212 MSV#3 AL-1215 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 45

Alarm 1220 - 1226 Ground Fault

Alarm Occurrence

Condition
At control at the time At servo
power ON power ON
of alarm?

Replace servopack
corresponding to the display Running
Check first
grounding terminal
Alarm
re-occurs?
Go to
NO point Faulty
YES A grounding

Contact Servopack NO YES


MOTOMAN-service failure
Replace servopack
corresponding
to the display

Check second Alarm


ground terminal re-occurs?

Faulty NO YES
grounding
YES NO Servopack
failure
Check
internal wiring Replace motor Contact
corresponding MOTOMAN-service
Alarm to the display
re-occurs?
Alarm
NO YES re-occurs?
NO
Internal wiring YES
failure Servo motor
failure
Contact
MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 46 AB

Alarm 1220 - 1226 Ground Fault (...continued)

Alarm
occurs at a
NO
specific point?
Check first YES
grounding terminal

Faulty Check second


grounding NO ground terminal

YES Faulty
grounding
Replace servopack YES NO
corresponding
to the display Check
internal wiring

Alarm
re-occurs?
NO
YES
Internal wiring Replace motor
failure Contact corresponding
MOTOMAN-service to the display
Alarm
re-occurs? Alarm
re-occurs?
YES NO
NO YES

Contact Servopack Motor Contact


MOTOMAN-service failure failure MOTOMAN-service

AL-1220 MSV#1 AL-1223 MSV#4 AL-1226 MSV#7


AL-1221 MSV#2 AL-1224 MSV#5
AL-1222 MSV#3 AL-1225 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 47

Alarm 1230 - 1236 Defective Current Offset

Alarm Occurrence

Replace servopack
corresponding to the display

Alarm
re-occurs?
NO YES

Servopack Contact
failure MOTOMAN-service

AL-1230 MSV#1 AL-1233 MSV#4 AL-1236 MSV#7


AL-1231 MSV#2 AL-1234 MSV#5
AL-1232 MSV#3 AL-1235 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 48 AB

Alarm 1240- 1246 Encoder Transmission Error

Turn power OFF,


and then ON again. Alarm Occurrence

Alarm Remove the cable between MSV


re-occurs? YES
board and IAMP, then re-install it
NO
Remove the cable between Alarm
YES re-occurs?
Resume use encoder and IAMP, then re-install it

Alarm NO
Resume use NO re-occurs?
YES Resume use
Check the cable ground
between encoder and IAMP Remove the cable between the
encoder and IAMP, then
Alarm install connector from another axis
re-occurs?
YES NO Alarm
YES re-occurs?
Check the cable
between encoder and IAMP NO

Alarm Cable failure Replace the servopack


re-occurs? NO
Alarm
Servopack failure NO re-occurs?
Reset absolute
encoder
YES
Alarm Replace the
re-occurs? YES servomotor Replace MSV board

NO Alarm Alarm
re-occurs? NO re-occurs?
Resume use NO
YES Board failure YES
Motor failure
Contact
MOTOMAN-service

AL-1240 MSV#1 AL-1243 MSV#4 AL-1246 MSV#7


AL-1241 MSV#2 AL-1244 MSV#5
AL-1242 MSV#3 AL-1245 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 49

Alarm 1250 - 1256 Defective Encoder Internal Data

Alarm Occurrence

Turn power OFF,


and then ON again.

Alarm
re-occurs?
NO YES

Resume use Reset absolute encoder


corresponding to the displayed axis

Alarm
re-occurs?
YES NO

Replace motor corresponding Resume use


to the displayed axis

Alarm
re-occurs?
NO YES

Motor failure Contact


MOTOMAN-service

AL-1250 MSV#1 AL-1253 MSV#4 AL-1256 MSV#7


AL-1251 MSV#2 AL-1254 MSV#5
AL-1252 MSV#3 AL-1255 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 50 AB

Alarm 1260 - 1266 Defective Encoder Absolute Data

Alarm Occurrence

Turn power OFF,


and then ON again.

Alarm
re-occurs?
NO YES

Resume use Reset absolute encoder


corresponding to the displayed axis

Alarm
re-occurs?
YES NO

Replace motor corresponding Resume use


to the displayed axis

Alarm
re-occurs?
NO YES

Motor failure Contact


MOTOMAN-service

AL-1260 MSV#1 AL-1263 MSV#4 AL-1266 MSV#7


AL-1261 MSV#2 AL-1264 MSV#5
AL-1262 MSV#3 AL-1265 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 51

Alarm 1270 - 1276 Encoder Overheat

Alarm Occurrence

Condition
At control at the time Running
power ON
of alarm?

If motor has cooling


fan check if fan is
A working

Check
NO Abnormal?
Robot load
Reset absolute encoder
corresponding to the Load YES
displayed axis condition?
Check
Alarm Overload wiring
re-occurs?
Decrease
YES NO weight

Resume use Faulty


wiring?
NO
Replace internal
Replace motor wiring

Alarm Replace Alarm


re-occurs? cooling fan YES re-occurs?

YES NO Alarm NO
re-occurs?
YES Internal wiring
Motor failure NO failure
Go to
Contact Fan point
MOTOMAN-service failure A

AL-1270 MSV#1 AL-1273 MSV#4 AL-1276 MSV#7


AL-1271 MSV#2 AL-1274 MSV#5
AL-1272 MSV#3 AL-1275 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 52 AB

Alarm 1280- 1286 Servo Monitor Transmission Error

Alarm Occurrence

Turn power OFF,


and then ON again.

Alarm
re-occurs?
NO YES

Resume use Remove the cable between MSV


board and IAMP, then re-install it

Alarm
re-occurs?
YES NO

Check the cable wiring Resume use


between MSV board and IAMP

Faulty
wiring
YES NO

Replace cable Replace the


servopack
Alarm
re-occurs? YES
Alarm
re-occurs? YES
NO
NO
Cable failure Replace MSV board

Servopack failure Alarm


re-occurs?
YES NO

Contact Board failure


MOTOMAN-service

AL-1280 MSV#1 AL-1283 MSV#4 AL-1286 MSV#7


AL-1281 MSV#2 AL-1284 MSV#5
AL-1282 MSV#3 AL-1285 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 53

Alarm 1290 -1296 Servo CPU Synchronizing Error

Alarm Occurrence

Replace MSV board

Alarm
re-occurs?
NO YES

Board failure Contact


MOTOMAN-service

AL-1290 MSV#1 AL-1293 MSV#4 AL-1296 MSV#7


AL-1291 MSV#2 AL-1294 MSV#5
AL-1292 MSV#3 AL-1295 MSV#6

Alarm 1300 -1306 DSP Program Checksum Error

Alarm Occurrence

Replace MSV board

Alarm
re-occurs?
NO YES

Board failure Contact


MOTOMAN-service

AL-1300 MSV#1 AL-1303 MSV#4 AL-1306 MSV#7


AL-1301 MSV#2 AL-1304 MSV#5
AL-1302 MSV#3 AL-1305 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 54 AB

Alarm 1310 -1316 Mon Pgrm Total Checksum Error

Alarm Occurrence

Replace MSV board

Alarm
re-occurs?
NO YES

Board failure Contact


MOTOMAN-service

AL-1310 MSV#1 AL-1313 MSV#4 AL-1316 MSV#7


AL-1311 MSV#2 AL-1314 MSV#5
AL-1312 MSV#3 AL-1315 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 55

Alarm 1320- 1326 Servopack Failure

Alarm Occurrence

Turn power OFF,


and then ON again.

Alarm
re-occurs?
NO YES

Resume use Remove the cable between MSV


board and IAMP, then re-install it

Alarm
re-occurs?
YES NO

Check the cable wiring Resume use


between MSV board and IAMP

Faulty
wiring
YES NO

Replace cable Replace the


servopack
Alarm
re-occurs? YES
Alarm
re-occurs? YES
NO
NO
Cable failure Replace MSV board

Servopack failure Alarm


re-occurs?
YES NO

Contact Board failure


MOTOMAN-service

AL-1320 MSV#1 AL-1323 MSV#4 AL-1326 MSV#7


AL-1321 MSV#2 AL-1324 MSV#5
AL-1322 MSV#3 AL-1325 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 56 AB

Alarm 1330- 1336 Position Error

Alarm Occurrence

Condition
At control Go to
at the time Running point
power ON
of alarm? A

At servo
power ON
Replace the cable between
encoder and IAMP with a
cable from another axis

Moved to
another axis? NO
Replace MSV board
YES
Alarm
Check wiring re-occurs?
NO YES

Board failure
Faulty
wiring

YES NO

Replace cable

Alarm Replace the


re-occurs? YES servo motor

NO Alarm Contact
re-occurs? YES MOTOMAN-service
Cable failure
NO

Motor failure

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 57

Alarm 1330- 1336 Position Error (... continued)

Is there a
A noise source NO
around?

YES

Remove the
noise source

Alarm
re-occurs? YES

NO

Resume use Check wiring

Faulty
wiring
YES

Replace cable

Replace the Alarm


servo motor YES re-occurs?
NO
Alarm NO
Motor failure re-occurs?
Cable failure
YES

Replace MSV board

Alarm Contact
re-occurs? YES MOTOMAN-service

NO

Board failure

AL-1330 MSV#1 AL-1333 MSV#4 AL-1336 MSV#7


AL-1331 MSV#2 AL-1334 MSV#5
AL-1332 MSV#3 AL-1335 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 58 AB

Alarm 1340- 1346 Overload 1

Alarm Occurrence

Condition
At control at the time Running
power ON
of alarm?

Replace MSV board How long


Right away after Servo ON After several
does alarm minutes
occur?
Check for Check
interference Robot load

Load
Interference? condition?
YES
NO OK Overload
Modify
teaching Reduce
load
Alarm Check
re-occurs? YES motor wiring

NO Faulty
wiring NO
Teaching error
YES Go to
Alarm point
re-occurs? Replace wiring A
NO
Alarm
re-occurs? YES
YES Board failure

Contact NO
MOTOMAN-service
Cable failure

AL-1340 MSV#1 AL-1343 MSV#4 AL-1346 MSV#7


AL-1341 MSV#2 AL-1344 MSV#5
AL-1342 MSV#3 AL-1345 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 59

Alarm 1340- 1346 Overload 1 (...continued)

Is brake
NO release A
audiable?
Check
brake circuit
YES
Input voltage Abnormal NO
abnormal condition?

Input voltage Check brake


Replace MTU board normal lead wiring

Replace SVM Faulty


wiring
Alarm NO
re-occurs? YES
NO Check
YES Replace wiring motor brake
Resume use
Alarm
Alarm re-occurs?
re-occurs? NO
YES YES
NO Resume use
Contact
Resume use MOTOMAN-service

NO Defective?

Check if YES
mechanically locked
Replace the
servo motor
NO Movable?

Alarm
Fix mechanical re-occurs?
problem YES YES
NO
Alarm Contact
re-occurs? YES MOTOMAN-service Resume use

NO

Resume use

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 60 AB

Alarm 1350- 1356 Overload 2

Alarm Occurrence

Condition
At control at the time Running
power ON
of alarm?

Replace MSV board How long


Right away after Servo ON After several
does alarm minutes
occur?
Check for Check
interference robot load

Load
Interference? condition?
YES
NO OK Overload
Modify
teaching Reduce
load
Alarm Check
re-occurs? YES motor wiring

NO Faulty
wiring NO
Teaching error
YES Go to
Alarm point
re-occurs? Replace wiring A
NO
Alarm
re-occurs? YES
YES Board failure

Contact NO
MOTOMAN-service
Cable failure

AL-1350 MSV#1 AL-1353 MSV#4 AL-1356 MSV#7


AL-1351 MSV#2 AL-1354 MSV#5
AL-1352 MSV#3 AL-1355 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 61

Alarm 1350- 1356 Overload 2 (...continued)

Is brake
NO release A
audiable?
Check
brake circuit
YES
Input voltage Abnormal NO
abnormal condition?

Output voltage Check brake


Replace MTU board abnormal lead wiring

Replace SVM Faulty


wiring
Alarm NO
re-occurs? YES
NO Check
YES Replace wiring motor brake
Resume use
Alarm
Alarm re-occurs?
re-occurs? NO
YES YES
NO Resume use
Contact
Resume use MOTOMAN-service

NO Defective?

Check if YES
mechanically locked
Replace the
servo motor
NO Movable?

Alarm
Fix mechanical re-occurs?
problem YES YES
NO
Alarm Contact
re-occurs? YES MOTOMAN-service Resume use

NO

Resume use

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 62 AB

Alarm 1360-1366 Broken PG Line

Alarm Occurrence

Condition
At control at the time Running
power on 1
of alarm?

Replace cable between encoder & At servo


IAMP with cable from another axis power on

Move to NO Replace MSV


other axis? board

YES Alarm
re-occurs? YES
Check wiring
NO Replace servopack

MSV board failure Alarm


re-occurs? NO
Faulty
wiring? YES Replace cable
YES Servopack failure

NO Replace cable between


IAMP and MSV
Alarm
Replace motor YES re-occurs?
Alarm
re-occurs? NO
NO
YES Cable failure
Cable failure
Replace motor
Alarm
re-occurs? NO
Alarm
re-occurs? NO
Motor failure
YES
YES Motor failure
Contact
MOTOMAN-service Contact
MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 63

Alarm 1360-1366 Broken PG Line (...continued)

Is there a noise Remove noise


YES
source around? source

NO
Alarm
Check wiring YES re-occurs? NO Resume use

Faulty
wiring? YES Replace cable

NO
Alarm
Replace motor YES re-occurs? NO Cable failure

Alarm
re-occurs? YES MSV board failure

NO Alarm
NO re-occurs? YES

Motor failure

MSV board failure Replace servopack

Alarm
YES re-occurs? NO

Replace cable between Servopack failure


IAMP and MSV

Alarm
NO re-occurs? YES Replace motor

Cable failure Alarm


YES re-occurs? NO

Contact Motor failure


MOTOMAN-service

AL-1360 MSV#1 AL-1363 MSV#4 AL-1366 MSV#7


AL-1361 MSV#2 AL-1364 MSV#5
AL-1362 MSV#3 AL-1365 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 64 AB

Alarm 1370-1376 Over Speed

Alarm Occurrence

Is there a noise Remove noise


NO source around? YES source

Alarm
Check wiring YES re-occurs? NO

Faulty Resume use


wiring? NO

At servo Condition at the


1 Running
YES power on time of alarm

Replace cable At servo


power on
Alarm
re-occurs? NO Cable failure
Alarm occurs
1 NO
at specific point?
YES
YES
1
Point of alarm
NO taught by MOVJ?
Replace MSV board

Alarm YES
re-occurs? NO MSV board failure

Multiple axes
YES Reduce speed YES moving at the
same time?
Replace motor
NO
Alarm
re-occurs? NO Motor failure
Alarm
re-occurs? YES 1
YES
NO
Contact
MOTOMAN-service Resume use

AL-1370 MSV#1 AL-1373 MSV#4 AL-1376 MSV#7


AL-1371 MSV#2 AL-1374 MSV#5
AL-1372 MSV#3 AL-1375 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 65

Alarm 1380-1386 Servo Tracking Error

Alarm Occurrence

Condition at the Running


time of alarm?
Check if robot interferes
At control with work or fixture
power on

Modify teaching YES Interference? NO Check load

Alarm Check motor Load


re-occurs? YES OK
wiring condition?

NO
Overload
Teaching error
Decrease weight
Replace MSV board
Faulty
wiring? NO 1
Alarm
re-occurs? NO
YES
YES MSV board failure
Replace wiring
Contact harness
MOTOMAN-service
Alarm
re-occurs? YES 1

NO

Wiring failure

AL-1380 MSV#1 AL-1383 MSV#4 AL-1386 MSV#7


AL-1381 MSV#2 AL-1384 MSV#5
AL-1382 MSV#3 AL-1385 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 66 AB

Alarm 1380-1386 Servo Tracking Error (...continued)

Is brake
NO release audible? YES

Check brake
circuit

Input voltage Abnormal


NO
abnormal condition?

Replace Output voltage Check brake


MTU board abnormal lead wiring

Replace SVM Faulty Check motor


wiring? NO brake
Alarm
NO re-occurs? YES

Resume use YES Replace wiring


harness
Alarm Contact
re-occurs? YES MOTOMAN Alarm
re-occurs? NO
service

NO
YES Resume use
Resume use
Contact
MOTOMAN-service

Check if mechanically NO Defective?


locked

YES
NO Movable?

Fix mechanical Replace motor


problem YES

Alarm Contact Alarm


re-occurs? YES MOTOMAN-service YES re-occurs?

NO NO

Resume use Resume use

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 67

Alarm 1390-1396 Speed (Monitor)

Alarm Occurrence

NO Is there a noise YES Remove noise


source around? source

Alarm
Check wiring YES re-occurs? NO

Faulty Resume use


NO
wiring?
At control Condition at the Running
1 power on time of alarm?
YES

Replace cable At servo


power on
Alarm
re-occurs? NO Cable failure
Alarm occurs
1 NO at specific point?
YES
YES
1
Point of alarm
NO taught by MOVJ
Replace
MSV board
YES
Alarm MSV board
re-occurs? NO
failure Multiple axes
Reduce speed YES moving at the
YES same time?

Replace motor NO

Alarm Alarm
re-occurs? NO Motor failure re-occurs? YES 1

YES NO

Contact Resume use


MOTOMAN
service

AL-1390 MSV#1 AL-1393 MSV#4 AL-1396 MSV#7


AL-1391 MSV#2 AL-1394 MSV#5
AL-1392 MSV#3 AL-1395 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 68 AB

Alarm 3000-3006 Not Ready For Servo System

Alarm Occurrence

Turn the power off


and then on again

Alarm
Resume use NO re-occurs?

YES

Check Is SVM Check primary


NO YES
MTU board working? power voltage

Defective? NO Replace SVM Defective? YES

YES Alarm Primary power


re-occurs? YES 1
failure
Replace
MTU board NO NO

Resume use Check cable between


servopack and MSV board

Alarm
re-occurs? YES 1 YES Defective? NO 1

NO Replace cable

Resume use Alarm


re-occurs? YES 1

NO

Cable failure

AL-3000 MSV#1 AL-3003 MSV#4 AL-3006 MSV#7


AL-3001 MSV#2 AL-3004 MSV#5
AL-3002 MSV#3 AL-3005 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 69

Alarm 3000-3006 Not Ready For Servo System (...continued)

Check cable between


servopack and SVM

Defective? YES Replace cable

NO

Replace Alarm
servopack YES re-occurs? NO Cable failure

Alarm Replace
re-occurs? YES MSV board

NO Alarm Contact
re-occurs? YES MOTOMAN
service
Servopack
failure NO

MSV board
failure

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 70 AB

Alarm 3010-3016 Servo Defective Speed

Alarm Occurrence

Are you trying to Try power on while


turn power on while YES
axis is moving axis is stopped

NO

Replace Alarm
MSV board YES re-occurs? NO Resume use

Alarm MSV board


re-occurs? NO
failure

YES

Contact
MOTOMAN
service

AL-3010 MSV#1 AL-3013 MSV#4 AL-3016 MSV#7


AL-3011 MSV#2 AL-3014 MSV#5
AL-3012 MSV#3 AL-3015 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 71

Alarm 3020-3026 Servo Defective DB

Alarm Occurrence

Turn the power off


and then on again

Alarm
re-occurs? YES Replace servopack

NO Alarm Servopack
re-occurs? NO failure
Resume use
YES

Replace
MSV board

Alarm MSV board


re-occurs? NO
failure

YES

Contact
MOTOMAN
service

AL-3020 MSV#1 AL-3023 MSV#4 AL-3026 MSV#7


AL-3021 MSV#2 AL-3024 MSV#5
AL-3022 MSV#3 AL-3025 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 72 AB

Alarm 3030-3036 Regenerative Trouble

Alarm Occurrence

Condition at the At servo


time of alarm? power on

At control Check regeneration


power on resistor

Replace Replace regeneration


NO Defective? YES
servopack resistor

Alarm Contact Alarm


re-occurs? YES YES re-occurs?
MOTOMAN-service

NO NO

Servopack Regeneration
failure resistor failure

AL-3030 MSV#1 AL-3033 MSV#4 AL-3036 MSV#7


AL-3031 MSV#2 AL-3034 MSV#5
AL-3032 MSV#3 AL-3035 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 73

Alarm 3040-3046 Overvoltage

Alarm Occurrence

Condition at the At servo


time of alarm? power on

At control Check primary


power on power voltage

Primary power
Abnormal? YES
failure

NO

Check regeneration
resistor

Replace Replace regeneration


NO Defective? YES
servopack resistor

Alarm Contact Alarm


re-occurs? YES YES re-occurs?
MOTOMAN-service

NO NO

Servopack Regeneration
failure resistor failure

AL-3040 MSV#1 AL-3043 MSV#4 AL-3046 MSV#7


AL-3041 MSV#2 AL-3044 MSV#5
AL-3042 MSV#3 AL-3045 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 74 AB

Alarm 3050-3056 Voltage Drop

Alarm Occurrence

Condition at the At servo


time of alarm? power on

At control Check primary


power on power voltage

Replace Primary power


NO Abnormal? YES
servopack failure

Alarm Contact
re-occurs? YES MOTOMAN-service

NO

Servopack
failure

AL-3050 MSV#1 AL-3053 MSV#4 AL-3056 MSV#7


AL-3051 MSV#2 AL-3054 MSV#5
AL-3052 MSV#3 AL-3055 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 75

Alarm 3060-3066 Heat sink overheat

Alarm Occurrence

Condition at the At servo


time of alarm? power on

At control Check primary


power on power voltage

Replace Primary power


NO Abnormal? YES
servopack failure

Alarm Contact
re-occurs? YES MOTOMAN-service

NO

Servopack
failure

AL-3060 MSV#1 AL-3063 MSV#4 AL-3066 MSV#7


AL-3061 MSV#2 AL-3064 MSV#5
AL-3062 MSV#3 AL-3065 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 76 AB

Alarm 3070-3076 Servo Blown Fuse

Alarm Occurrence

Condition at the At servo


time of alarm? power on

At control Check motor


power on cable

Replace Replace wiring


NO Abnormal? YES
servopack harness

Alarm Contact Alarm


re-occurs? YES YES re-occurs?
MOTOMAN-service

NO NO

Servopack Wiring failure


failure

AL-3070 MSV#1 AL-3073 MSV#4 AL-3076 MSV#7


AL-3071 MSV#2 AL-3074 MSV#5
AL-3072 MSV#3 AL-3075 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 77

Alarm 3080-3086 Broken Current Ref Cable

Alarm Occurrence

Check cable between


servopack and MSV board

Defective? YES Replace cable

NO

Replace Alarm
YES re-occurs? NO Cable failure
servopack

Alarm Replace
re-occurs? YES
MSV board

NO Alarm Contact
re-occurs? YES MOTOMAN-service
Servopack
failure NO

MSV board
failure

AL-3080 MSV#1 AL-3083 MSV#4 AL-3086 MSV#7


AL-3081 MSV#2 AL-3084 MSV#5
AL-3082 MSV#3 AL-3085 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 78 AB

Alarm 3090-3096 Open Phase

Alarm Occurrence

Check primary
power voltage

Abnormal? Check if contactor


YES
is stuck or not

NO Replace
Abnormal? YES
contactor
Primary power
failure NO

Check cable for Alarm


YES re-occurs?
SVM contactor

NO
Replace cable YES Abnormal?

Contactor
NO failure

Alarm Replace
re-occurs? YES
servopack

NO Alarm Replace
re-occurs? YES
MSV board
Cable failure
NO
Abnormal? NO

Servopack
failure MSV board
YES failure

Contact
MOTOMAN-service

AL-3090 MSV#1 AL-3093 MSV#4 AL-3096 MSV#7


AL-3091 MSV#2 AL-3094 MSV#5
AL-3092 MSV#3 AL-3095 MSV#6

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 79

Alarm 4000 Not Ready

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4010 Current Position Set Program Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4020 Servo Power On Sequence Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 80 AB

Alarm 4030 Servo Power Off Sequence Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4040 Home Calibration Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4050 Absolute Data Change Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 81

Alarm 4060 Segment Data Output Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4070 Axis Parameter Error

Alarm Occurrence

Initialize parameter
setting

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4080 Table Parameter Error For Actual Axis

Alarm Occurrence

Initialize parameter
setting

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 82 AB

Alarm 4090 Sequence Task Control Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4100 Data Refresh Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4110 Undefined Command (Arith)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 83

Alarm 4120 System Error (Arith)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4130 Arithmetic Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4140 Select Error (Parameter)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 84 AB

Alarm 4150 Group Axis Control Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4160 Two Steps Same Position (Circle)

Alarm Occurrence

Confirm the taught program, and


then input three different points

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4170 Two Steps Same Position (Spline)

Alarm Occurrence

Confirm the taught program, and


then input three different points

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 85

Alarm 4180 Two Steps Same Position (3 steps)

Alarm Occurrence

Confirm the taught program, and


then input three different points

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4190 Two Steps Same Position (weave)

Alarm Occurrence

Confirm the taught program, and


then input three different points

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4200 Teach Error (Spline)

Alarm Occurrence

Confirm the taught program,


and then provide instructions to
position taught points correctly

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 86 AB

Alarm 4210 Impossible Linear Motion (L/U)

Alarm Occurrence

Confirm the taught


program so the pattern
of L and U axes is the same

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4220 Impossible Linear Motion (S/L)

Alarm Occurrence

Confirm the taught


program so the pattern
of S and L axes is the same

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 87

Alarm 4230 Excessive Segment (Low speed)

Alarm Occurrence

Decrease the speed of the step


where the alarm occured

Alarm
NO re-occurs? YES

Resume use Set form of axes S and L,


and provide a new instruction

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4240 Excessive Segment (High speed)

Alarm Occurrence

Decrease the speed of the step


where the alarm occured

Alarm
NO re-occurs? YES

Resume use Set form of axes S and L,


and provide a new instruction

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 88 AB

Alarm 4250-4300 Soft Limit Over

Alarm Occurrence

Reset alarm using soft-limit-over


reset method, and then provide
another instruction

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

AL-4250 Pulse limit over: minimum AL-4280 Cube limit over: maximum
AL-4260 Pulse limit over: maximum AL-4290 Special soft limit over: minimum
AL-4270 Cube limit over: minimum AL-4300 Special soft limit over: maximum

Alarm 4310-4340 Mechanical Interference

Alarm Occurrence

Reset alarm using soft-limit-over


reset method, and then provide
another instruction.

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

AL-4310 Mechanical interference: AL-4330 Special mechanical interference:


minimum maximum
AL-4320 Mechanical interference: AL-4340 Special mechanical interference:
maximum minimum

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 89

Alarm 4350-4360 Pulse Mechanical limit

Alarm Occurrence

Reset alarm using soft-limit-over


reset method, and then provide
another instruction.

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

AL-4350 Pulse mechanical limit: minimum AL-4360 Pulse mechanical limit: maximum

Alarm 4370 Station Axis Data Input Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 90 AB

Alarm 4380 Segment Control Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4390 Sub-segment Control Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4400 Wrong Specified Control Group

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 91

Alarm 4410 CPU Communication Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4420 Failed To Select Over SP Level

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Turn the power off,


and then on again

Alarm
YES re-occurs? NO

Replace MSV board Resume use

Alarm
NO re-occurs? YES

MSV board failure Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 92 AB

Alarm 4430 Averaging Number Change Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Turn the power off,


and then on again

Alarm
YES re-occurs? NO

Replace MSV board Resume use

Alarm
NO re-occurs? YES

MSV board failure Contact


MOTOMAN-service

Alarm 4440 Torque Limit Change Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Turn the power off,


and then on again

Alarm
YES re-occurs? NO

Replace MSV board Resume use

Alarm
NO re-occurs? YES

MSV board failure Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 93

Alarm 4450 JMS Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

1/255 Parameter 11/245 Sequence number error


2/254 Access time over 12/244 Step numer error
3/253 Access error 13/243
4/252 Job name error 14/242 Code error
5/251 Existing job open 15/241
6/250 Memory over 16/240 Lack of handle
7/249 Not existing 17/239 Write Protected
8/248 Acess not permitted 18/238 Maximum instruction
9/247 Handling number error 19/237 Maximum step
10/246 System error 99/157 Job failure

Alarm 4460 JHM Error

Alarm Occurrence

Turn the power off,


and then on again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 94 AB

Alarm 4470 Instruction Interpreter Error

Alarm Occurrence

Turn the power off,


and then on again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4480 Undefined Global Variable

Alarm Occurrence

Reset the parameter, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4490 Var-Scoreboard Control Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 95

Alarm 4500 Undefined Local Variable

Alarm Occurrence

Set the local variable to the job heade


and then execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4510 Less Than 3 Steps (circular)

Alarm Occurrence

Confirm the taught program, and


then input instructions to provide
more than three steps continuously

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4520 Cannot Interpolate Circular Motion

Alarm Occurrence

Confirm the taught program, and


then input instructions to provide
more than three steps continuously

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 96 AB

Alarm 4530 Undefined Job

Alarm Occurrence

Reset alarm, end then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4540 Undefined Label

Alarm Occurrence

Check the taught point, and


then teach the point again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4550 Undefined Return Job

Alarm Occurrence

Start from the original job

Alarm
NO re-occurs? YES
Resume use Check the taught point, and
then teach the point again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 97

Alarm 4560 Lack Of Local-Variable Area

Alarm Occurrence

Decrease the use


of local variables

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4570 Local-Variable Control Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4580 Job Call Stack Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 98 AB

Alarm 4590 Feedback Pulse Making Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4600 Unsuccessful Fine Positioning

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Turn the power off,


and then on again

Alarm
YES re-occurs? NO

Replace MSV board Resume use

Alarm
NO re-occurs? YES

MSV board failure Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 99

Alarm 4610 Pending Block-End Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4620 Data Preset Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4630 Variable Data Type Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 100 AB

Alarm 4640 Over Variable Limit


(B**) ‘0-255
Alarm Occurrence (I**) -32768~32767
(D**) -2147483648
~214748
Change value of variable type that (R**) -1.70141E+38
exceeds numerical range limits. ~1.70141E

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4650 Defective Taught Point (circular)

Alarm Occurrence

Check taught point, and then teach


three points not in a straight line

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4660 Weaving Control Error

Alarm Occurrence

Reset alarm, and then check


weave file and REFP points

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 101

Alarm 4670-4671 Overrun In Axis

Alarm Occurrence

Recover from overtravel


then try again

Alarm
NO re-occurs? YES Check short switch on MBB02

Resume use
Set the swith again YES Abnormal?

NO

Alarm Check the over


NO re-occurs? YES
run limit switch

Swith setting failure


Replace switch YES Defective?

NO

Alarm Check the wiring of the


NO re-occurs? YES
overrun limit switch

Switch failure Alarm Replace wiring


re-occurs? YES
harness

NO

Replace MTU Alarm


YES re-occurs?
board

Replace MBB02 Alarm NO


YES re-occurs?
(IOBB) board
Lead failure
Alarm NO
NO re-occurs? YES
Board failure
MBB02 (IOBB)
failure Contact
MOTOMAN-service

AL-4670 At robot axes occurrence AL-4671 At external axes occurrence

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 102 AB

Alarm 4680-4730 File Fault

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm Load the file corresponding to


NO re-occurs? YES
the screen, and then try again

Resume use Alarm


NO re-occurs? YES

Resume use Contact


MOTOMAN-service

AL-4680 Tool file AL-4710 Weaving file


AL-4690 User frame file AL-4720 Home position absolute data file
AL-4700 Servo monitor signal file AL-4730 Second home position data file

Alarm 4740 Posn File Data Read-Out Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 103

Alarm 4750 Unmatched Posn Var Data Type

Alarm Occurrence

Change position variable data


type (pulse - XYZ).

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4760 File No. Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4770 Undefined Reference Point

Alarm Occurrence

Register the reference point

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 104 AB

Alarm 4780 Stack More Than 8 (job call)

Alarm Occurrence

Check program, and modify so that


stack does not exceed 8 calls

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4790 Arithmetic Section Request Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4800 Request-To-Send Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 105

Alarm 4810 Over Variable No.


(B000~B039)
Alarm Occurrence (I000~I039)
D000~D039)
R000~R039)
Check program, and change P000~P127)
variable number within limit BP000~BP127)
EX000~EX127)
Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4820 Position Data Management Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

1 Not enough area 9 Control information destroyed


2 Number of axis zero 10 Irregular position number
3 Position not kept 11 Position data not set
4 Number of position over 12 Undefined position
5 Area not specified 13 Undefined control group
6 File destroyed 14 Initialization not done
7 Memory over 15 Number of axis over
8 Position data destroyed

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 106 AB

Alarm 4830-4850 Undefined Condition File

Alarm Occurrence

Complete the
setting of the file

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

AL-4830 Welder condition file AL-4850 Arc end condition file


AL-4840 Arc start condition file

Alarm 4860 Wrong Welder Selection

Alarm Occurrence

Match unit of voltage


selection to welder type

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 107

Alarm 4870-4900 Condition File Fault

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Load file, and the try again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

AL-4870 Welder condition file AL-4890 Arc end condition file


AL-4880 Arc start condition file AL-4900 Arc condition supp. file

Alarm 4910 AX-CPU Command Area Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 108 AB

Alarm 4920-4950 File Fault

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Load file, and then try again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

AL-4920 COM-ARC 3 Condition file AL-4940 Correction condition file


AL-4930 COM-ARC 3 Data file AL-4950 Phase offset data file

Alarm 4960 System Change

Alarm Occurrence

Turn the power off,


and then on again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 109

Alarm 4970 Equation Exception Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4980 Excessive Instruction Equation

Alarm Occurrence

Check the program, and


make the expression short

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 4990 Encoder Battery Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm Replace battery


NO re-occurs? YES
board for encoder

Battery failure Alarm


NO re-occurs? YES

MFC board failure Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 110 AB

Alarm 5000 Encoder Overheat

Alarm Occurrence

Turn the power off, let encoder


cool, and then turn the power on

Alarm
re-occurs?

YES

If motor has cooling fan, check


if fan is working properly

Is fan
YES
working?

NO

Check the wiring of fan

Defective? NO

YES

Replace fan wiring Check load

Alarm Load
re-occurs? YES Replace fan OK
condition?

NO Alarm Overload
re-occurs? YES
Lead failure Decrease weight
NO

Fan failure Replace motor

Contact Alarm
MOTOMAN-service YES re-occurs?

NO

Motor failure

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 111

Alarm 5010 Illegal Parameter

Alarm Occurrence

Change the parameter


back to original

Alarm
NO re-occurs? YES

Resume use Load parameter file,


and then try again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5020 Zero Divisor Occurrence

Alarm Occurrence

Change the program so that the


number will not be divided by zero

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 112 AB

Alarm 5030 Global-Variable Area Parameter Error

Alarm Occurrence

Change the parameter


back to original value

Alarm
NO re-occurs? YES

Resume use Load parameter file,


and then try again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5040 Out Of Range (abso data)

Alarm Occurrence

Reset alarm by checking


second home position

Alarm Check battery wiring


re-occurs? YES
to encodeers

NO
Defective? YES Replace battery
Resume use
NO
Alarm
Replace motor YES re-occurs?

Alarm
Motor failure NO re-occurs? NO

YES Battery failure

Contact
MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 113

Alarm 5060 Undefined Auto-Weld Release Cond

Alarm Occurrence

Set welding release condition


time, and then try again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5070 Undefined Position For Arc Retry

Alarm Occurrence

Add step, and then try again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5080 Overspeed Limit

Alarm Occurrence

Check setting for MFC04


board, and then try again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 114 AB

Alarm 5090 DC 24V Power Supply Failure

Alarm Occurrence

Check 24V power voltage


supplied to IOBB

Replace DC 24V
Defective? YES
power supply

NO
Alarm Power supply
Check fuse on IOBB YES re-occurs? NO failure

Defective? YES Replace fuse

NO
Alarm
Replace IOBB YES re-occurs? NO Fuse failure

Alarm
re-occurs? NO Board failure

YES

Contact
MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 115

Alarm 5100 Shock Sensor Action

Alarm Occurrence

Remove interference between


the tool and the fixture, etc

Remove interference, YES Interference?


and then try again

NO

Alarm Check the shock


re-occurs? YES
sensor cable

NO
Defective? YES Replace cable
Resume use
NO

Check the shock Alarm


YES re-occurs? NO
sensor operation

Check the setting of Cable failure


NO Abnormal? YES
IOBB short pin switch

Set the short Replace shock sensor


Abnormal? YES
pin switch
Alarm
re-occurs? NO
NO

Replace MTU Alarm YES Sensor failure


YES re-occurs?
board
Contact
NO MOTOMAN-service
Alarm
re-occurs? YES
Setting failure

MTU board Replace MRY


failure board Replace IOBB

Alarm Alarm
YES re-occurs? NO IOBB failure
re-occurs?

NO YES

MRY board failure Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 116 AB

Alarm 5110 Brake Fuse Blown

Alarm Occurrence

Check the brake lead wiring


for short to ground

YES Replace lead


Short? wire for brake

Check the Alarm


YES re-occurs?
brake fuse

Replace the NO
YES Fuse blown?
brake fuse
Lead wire failure
NO

Alarm Replace the


re-occurs? YES
MTU board

NO Alarm
re-occurs? NO Board failure
Fuse failure
YES

Contact
MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 117

Alarm 5120 Parity Error

Alarm Occurrence

Check the parameter for


parity check function

Invalid Set the parameter


YES
parameter? correctly

NO

Alarm
Check input YES re-occurs?

Check the NO
input program YES Abnormal?

Parameter setting
NO failure

Alarm Replace the MTU


re-occurs? YES
board

NO Alarm
re-occurs? NO Board failure
Abnormal input
YES

Contact
MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 118 AB

Alarm 5130 Over BCD Range

Alarm Occurrence

Check the BCD


function parameter

Invalid Set the parameter


YES
parameter? correctly

NO

Check Alarm
input/output YES re-occurs?

Check the input/ NO


YES Abnormal?
output program
Parameter setting
NO failure

Alarm Replace IO
re-occurs? YES
module board

NO Alarm
re-occurs? NO Board failure

Input/output
failure YES

Contact
MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 119

Alarm 5140 Over Binary Range (parity check)

Alarm Occurrence

Check parity check - BCD


function parameter

Invalid Set the parameter


YES
parameter? correctly

NO

Alarm
Check output YES re-occurs?

Check the NO
output program YES Abnormal?

Parameter setting
NO failure

Alarm Replace IO
re-occurs? YES
module board

NO Alarm
re-occurs? NO Board failure

Output failure
YES

Contact
MOTOMAN-service

Alarm 5150 Offline Undefined Command (Arith)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 120 AB

Alarm 5160 Offline System Error (Arith)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5170 Robot Calibration Data Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5180 Robot Calibration Frame Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 121

Alarm 5190 Arithmetic Section Init Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5200 Set-Up Process Error (motion)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5210 System Error (motion)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 122 AB

Alarm 5220 Servo Ready Monitoring Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5230 Calibration Data Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5240 Tool Calibration Data Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 123

Alarm 5250-5300 File Fault

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Load the file corresponding to


the display, and then try again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

AL-5250 Robot calibration file AL-5280 Arc end cond guide file
AL-5260 Tool calibration file AL-5290 Welder user-defined file
AL-5270 Arc start cond guide file AL-5300 Ladder program file

Alarm 5310 Arithmetic Alarm Reset Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 124 AB

Alarm 5320 Wrong Control Group Axis

Alarm Occurrence

Check program and modify it (include


control group to the original job).

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5330 Cannot Execute Job (no robot)

Alarm Occurrence

Check program and modify it (include


control group to the original job).

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5340 Sensing Data Request Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 125

Alarm 5350 Main Contactor On Reply Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Check if main contactor


is working or not

NO Working? YES

Check voltage for


main contactor coil

NO Abnormal? YES

Replace main
contactor

Alarm
re-occurs? YES Check MTU board

Defective? YES Replace MTU board


NO

Contactor failure NO

Contact Alarm
YES re-occurs?
MOTOMAN-service

NO

MTU board failure

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 126 AB

Alarm 5360 Main Contactor Off Reply Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Check if main contactor


is working or not

NO Working? YES

Check voltage for


main contactor coil

NO Abnormal? YES

Replace main
contactor

Alarm
re-occurs? YES Check MTU board

Defective? YES Replace MTU board


NO

Contactor failure NO

Contact Alarm
YES re-occurs?
MOTOMAN-service

NO

MTU board failure

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 127

Alarm 5370 Braking Lock Reply Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Check if main contactor


is working or not

NO Working? YES

Check voltage for


main contactor coil

NO Abnormal? YES

Replace main
contactor

Alarm
re-occurs? YES Check MTU board

Defective? YES Replace MTU board


NO

Contactor failure NO

Contact Alarm
YES re-occurs?
MOTOMAN-service

NO

MTU board failure

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 128 AB

Alarm 5380 Braking Release Reply Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Check if main contactor


is working or not

NO Working? YES

Check voltage for


main contactor coil

NO Abnormal? YES

Replace main
contactor

Alarm
re-occurs? YES Check MTU board

Defective? YES Replace MTU board


NO

Contactor failure NO

Contact Alarm
YES re-occurs?
MOTOMAN-service

NO

MTU board failure

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 129

Alarm 5390 Servo-Ready On Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Check if main contactor


is working or not

NO Working? YES 1

Check voltage for


main contactor coil

NO Abnormal? YES

Replace main
contactor

Alarm
re-occurs? YES Check MTU board

Defective? YES Replace MTU board


NO

Contactor failure NO

Contact Alarm
YES re-occurs?
MOTOMAN-service

NO

MTU board failure

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 130 AB

Alarm 5390 Servo-Ready On Error (...continued)

Check change LED


on servopack

YES Lit?

NO

Turn off power, and


then turn it on again

Alarm
re-occurs? NO Resume use

YES

Check wiring between


contactor and servopack

Replace wiring between


Defective? YES contactor and servopack

NO

Check wiring between MSV Alarm


YES re-occurs? NO Wiring failure
board and servopack

Replace wiring between


Defective? YES MSV board and servopack

NO
Alarm
Replace servopack YES re-occurs? NO Wiring failure

Alarm
re-occurs? YES Replace MSV board

NO Alarm MSV board


re-occurs? NO
failure
Servopack failure
YES

Contact
MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 131

Alarm 5400 Servo-Ready Off Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Check if main contactor


is working or not

NO Working? YES 1

Check voltage for


main contactor coil

NO Abnormal? YES

Replace main
contactor

Alarm
re-occurs? YES Check MTU board

Defective? YES Replace MTU board


NO

Contactor failure NO

Contact Alarm
YES re-occurs?
MOTOMAN-service

NO

MTU board failure

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 132 AB

Alarm 5400 Servo-Ready Off Error (...continued)

Check change LED


on servopack

YES Lit?

NO

Turn off power, and


then turn it on again

Alarm
re-occurs? NO Resume use

YES

Check wiring between


contactor and servopack

Replace wiring between


Defective? YES contactor and servopack

NO

Check wiring between MSV Alarm


YES re-occurs? NO Wiring failure
board and servopack

Replace wiring between


Defective? YES MSV board and servopack

NO
Alarm
Replace servopack YES re-occurs? NO Wiring failure

Alarm
re-occurs? YES Replace MSV board

NO Alarm MSV board


re-occurs? NO
failure
Servopack failure
YES

Contact
MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 133

Alarm 5410 Base-Block On Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
re-occurs? NO Resume use

YES

Turn off power, and


then turn it on again

Alarm
re-occurs? NO Resume use

YES

Check wiring between MSV


board and servopack

Replace wiring between


Defective? YES
MSV board and servopack

NO
Alarm
Replace servopack YES re-occurs? NO Wiring failure

Alarm
re-occurs? YES Replace MSV board

NO Alarm MSV board


re-occurs? NO
failure
Servopack failure
YES

Contact
MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 134 AB

Alarm 5420 Base-Block Off Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
re-occurs? NO Resume use

YES

Turn off power, and


then turn it on again

Alarm
re-occurs? NO Resume use

YES

Check wiring between MSV


board and servopack

Replace wiring between


Defective? YES
MSV board and servopack

NO
Alarm
Replace servopack YES re-occurs? NO Wiring failure

Alarm
re-occurs? YES Replace MSV board

NO Alarm MSV board


re-occurs? NO
failure
Servopack failure
YES

Contact
MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 135

Alarm 5430 Dynamic Brake On Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
re-occurs? NO Resume use

YES

Turn off power, and


then turn it on again

Alarm
re-occurs? NO Resume use

YES

Check wiring between MSV


board and servopack

Replace wiring between


Defective? YES
MSV board and servopack

NO
Alarm
Replace servopack YES re-occurs? NO Wiring failure

Alarm
re-occurs? YES Replace MSV board

NO Alarm MSV board


re-occurs? NO
failure
Servopack failure
YES

Contact
MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 136 AB

Alarm 5440 Dynamic Brake Off Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
re-occurs? NO Resume use

YES

Turn off power, and


then turn it on again

Alarm
re-occurs? NO Resume use

YES

Check wiring between MSV


board and servopack

Replace wiring between


Defective? YES
MSV board and servopack

NO
Alarm
Replace servopack YES re-occurs? NO Wiring failure

Alarm
re-occurs? YES Replace MSV board

NO Alarm MSV board


re-occurs? NO
failure
Servopack failure
YES

Contact
MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 137

Alarm 5450 Unused (on)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5460 Unused (off)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5470 Cannot Edit (edit lock job)

Alarm Occurrence

Release Edit-lock, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 138 AB

Alarm 5480 Select Error (application 1)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5490 Select Error (application 2)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5500 Select Error (sensor 1)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 139

Alarm 5510 Select Error (sensor 2)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5520 Wrong Port Out (analog output)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Data 1 Application 1 Data 2 Application 2

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 140 AB

Alarm 5530 Pass Over

Alarm Occurrence

Is COM-ARC III’s Check workpiece


YES
function normal? deviation

NO

Check the cable between


the current detection unit Small Deviation? Large Position a workpiece
and the sensor board

Defective? Check the current


NO detection unit

YES Replace the current


Defective? YES detection unit
Change the cable
NO

Replace the Alarm


YES re-occurs?
sensor board

Alarm NO
Sensor board failure NO re-occurs?
Current detection
YES unit failure

Contact
MOTOMAN-service

Alarm 5540 Wrong Selection (sensor)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 141

Alarm 5550 Wrong Mech Parameter File

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5560 Incompleted PT Frame

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5570 Defective Taught Point (cutting)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Data 1 CW axis position is not 0. Data 2 Cutting radius is 0.

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 142 AB

Alarm 5580 Defective Taught Point (endless)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Data 1 Linear motion error (MRESET Data 3 Endless not selected on T-axis.
not executed.
Data 2 Endless on base axes Data 4 Command position exceeds limit
(214748367 pulse).

Alarm 5590 Correctional Direction Data

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5600 Position Correction Data

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 143

Alarm 5610 Over Tool File No.

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5620 Defective Taught Point (weav)

Alarm Occurrence

Check the REFP, and then


teach the REFP again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Data 1 Weaving atart point and end Data 2 Weaving REFP 1 or 2 is on the path
point is the same

Alarm 5630 Undefined Robot Calibration

Alarm Occurrence

Execute robot calibration

Alarm
NO re-occurs YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 144 AB

Alarm 5640 Parameter Error

Alarm Occurrence

Reset the parameter


with the original data

Alarm
NO re-occurs? YES

Resume use Load the parameter file


and then try again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5650 Defective Taught Point (Calib)

Alarm Occurrence

Check the taught point, and


then teach the point again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Data 3 Data for station 2nd axis is not Data 5 Data for station 2nd axis is not
same 3, 4, 5 points. same 1, 2, 3 points.
Data 4 Data for station 1st axis is not Data 6 Data for station 1st axis is not same
same 1, 2, 3 points. 3, 4, 5 points.

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 145

Alarm 5660 DM-Bank Transmission Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5670 Cannot Execute Job (no grp axis)

Alarm Occurrence

Set group axes

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5680 Univ Data Preset Request Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 146 AB

Alarm 5690 Braking Sequence Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5700 Process Error (Syscon - axis)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5710 Illegal Sv Parameter (online)

Alarm Occurrence

Reset the parameter


with the original data.

Alarm
NO re-occurs? YES

Resume use Load the parameter file


and then try again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 147

Alarm 5720 Illegal Sv Parameter (online)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Replace the MSV board,


and then try again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5730 Sv Parameter Change Error (online)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Replace the MSV board,


and then try again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 148 AB

Alarm 5740 Illegal Max Speed Parameter

Alarm Occurrence

Reset the parameter


with the original data

Alarm
NO re-occurs? YES

Resume use Load the parameter file


and then try again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5750 Undefined Position Variable

Alarm Occurrence

Set the position variable

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5760 Undefined User Frame

Alarm Occurrence

Set the user frame

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 149

Alarm 5770 Out Of Range (parallel process)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5780 SL Board On-Line Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5790 Interrupt Error (sensor)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Trouble Shooting YASNAC MRC MOTOMAN
ROBOTICS
Page: 150 AB

Alarm 5800 Out Of Current Detector Range

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5810 Command Error (sensor)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5820 Process Error (sensor)

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


MOTOMAN
ROBOTICS
Trouble Shooting YASNAC MRC
AB Page: 151

Alarm 5830 Parallel Start Instruction Error

Alarm Occurrence

Check the program,


and then modify it.

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5840 Cannot Execute Job (grp axis)

Alarm Occurrence

Set group axes

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Alarm 5850 Measure Inst Execute Error

Alarm Occurrence

Reset alarm, and then


execute the operation again

Alarm
NO re-occurs? YES

Resume use Contact


MOTOMAN-service

Skapad: 98-10-09 Ändrad: 98-11-26 Filnamn: T:\M-ROBOT\ENGELSK\TROUBLE_SHOOTING.FM


Headquarters:
MOTOMAN ROBOTICS AB
Box 504 l 385 25 Torsås l Sweden
Tel: +46-486-48800l Fax: +46-486-41410

Subsidiary:
MOTOMAN ROBOTICS UK LTD
1 Swan Industrial Estate l Banbury l OXON OX16 8DJ l England
Tel: +44-1295-272755 l Fax: +44-1295-267127

MOTOMAN ROBOTICS ITALIA SRL


Via Emilia 1420/16 l I-41100 Modena l ITALY
Tel: +39-59280496 l Fax: +39-59280602

MOTOMAN ROBOTICS FRANCE S.A.


Rue Nungesser et Coli l D2A Nantes-Atlantique l F-44860 Saint-Aignan-de-Grand-Lieu l France
Tel: +33-2-40131919 l Fax: +33-40754147

MOTOMAN ROBOTICS ESPAÑA S.L.


Avenida Marina 56 l Parcela 90 l ES-08830 ST. Boi de Llobregat l Spain
Tel: +34-36303478 l Fax: +34-36543459

Distributors:
ELECTRO-ARCO S.A.
Rua Vice Almirante Azevedo Coutinho, 4 l Venda Nova l PT-2700 Amadora l Portugal
Tel: +351-14968160 l Fax: +351-14990696

HN AUTOMATIC A/S
Hjulmagervej 4 l DK-7100 Vejle l Denmark
Tel: +45-79428000 l Fax: +45-79428001

LINCOLN-KD S.A.
Ctra, Laureà Miró 396-398 l E-08980 Sant Feliu de Llobregat l Spain
Tel: +34-36859600 l Fax: +34-36859633

MOTOMAN ROBOTIT OY
Kärsämäentie 8 l SF-20300 Turku l Finland
Tel: +358-22145600 l Fax: +358-22145660