14.

CP-300 Processor Board


On the Processor Board CP-300 the function block diagrams and the station bus protocols are processed. Data is
exchanged via the HIPASE internal process bus with the other modules in the HIPASE device. It is necessary to
provide exactly one CP-300 in a HIPASE device. Please also refer to Device Features.

Top view of board CP-300

14.1. Features

 Stationsbus IEC 60870-5-104 Ed. 2.0 elektrisch und optisch


 Station bus IEC 60870-5-104 Ed. 2.0 electrical
 Station bus IEC 61850 Ed. 2.0 electrical
 IRIG-A/-B/-AM input
 Second pulse input
 Separate Touch Panel connection via Ethernet with HIPASE-PoE (Power over Ethernet)
 32-bit Processors with 400 MHz
 4 LEDs (V1 .. V4) and one accept button (S1)

DGB-004-1.03 HIPASE Data Sheets Page 175 of 429


14.3. Interfaces

Port X01 IEC60870-5-103

Connection type RS485 electrical, each wire pair up to 32 interfaces in half duplex operation are possible in parallel

Plug type D-Sub 9 Female

Pin assignment Pin 2: RX+, Pin 3: RX-, Pin 4: TX-, Pin 5: TX+

Galvanic isolation Yes

Isolation voltage
500 V
(Connection - Ground)

EMC immunity IEC 60255-26, EN 61131-2, IEC 61850-3 Ed.2.0

Special wiring
Shielded cable up to 100 m length at 9600 baud
recommendations

Port X02 IEC60870-5-103 optical - Receive

Connection type RS232C optical

Plug type Fiber optic ST/BFOC 2.5 mm (IEC 61754-2), Receiver 820 nm

Galvanic isolation Yes

Isolation voltage
Optical connection
(Connection - Ground)

EMC immunity IEC 60255-26, EN 61131-2, IEC 61850-3 Ed.2.0

Simplex or Duplex full core HCS-fiber (core diameter: 50/125 μm, 62.5/125 μm, 100/140 μm, and 200 μm) with
Special wiring
ST/BFOC-plug; Length up to 2 km
recommendations
Note bending radius: e.g. short-term 50 x core diameter, long-term 400 x core diameter

Port X03 IEC60870-5-103 optical - Transmit

Connection type RS232C optical

Plug type Fiber optic ST/BFOC 2.5 mm (IEC 61754-2), Transmitter 820 nm

Galvanic isolation Yes

Isolation voltage
Optical connection
(Connection - Ground)

EMC immunity IEC 60255-26, EN 61131-2, IEC 61850-3 Ed.2.0

Simplex or Duplex full core HCS-fiber (core diameter: 50/125 μm, 62.5/125 μm, 100/140 μm, and 200 μm) with
Special wiring
ST/BFOC-plug; Length up to 2 km
recommendations
Note bending radius: e.g. short-term 50 x core diameter, long-term 400 x core diameter

DGB-004-1.03 HIPASE Data Sheets Page 177 of 429


Port X04 USB-connection to PC (for future purpose)

Connection type USB 2.0 electrical

Plug type USB Type-B

Galvanic isolation Yes

Isolation voltage
500 V
(Connection - Ground)

EMC immunity IEC 60255-26, EN 61131-2, IEC 61850-3 Ed.2.0

Special wiring
Up to 5 m USB A to B Printer Cable
recommendations

Port X05 Second pulse (e. g. IEC 61850 Ed.2.0) (for future purpose)

Connection type electrical

Plug type SMB Sub-miniature coaxial socket, not terminated

Signal Input Rising edge 1 Hz, 3 .. 24 VDC @ 1 µs

Galvanic isolation Yes

Isolation voltage
500 V
(Connection - Ground)

EMC immunity IEC 60255-26, EN 61131-2, IEC 61850-3 Ed.2.0

Special wiring
Coaxial cable 50 ohms, length max. 10 m
recommendations

Port X06 For Touch panel with PoE ONLY !

Connection type Ethernet electrical

Plug type RJ45

Baud rate 10/100 Mbit/s

Cable connection on The PoE-enabled Ethernet cable (up to 5 m in length!) has to be plugged on the external touch panel in RJ45
Touch panel socket X10.

10.0.0.1 (IPv4 dotted decimal notation)


(10.99.20.1 deliveries up to beginning of November 2015)
CAUTION: If there are several HIPASE devices in a network different IP addresses for each device have to be
IP address (factory default assigned!
setting, changeable)
Net mask: 255.255.255.0 (“Class C”-size, /24)
Standard gateway: 10.0.0.254

Alias-IP address (factory 10.99.20.1 (static) (IPv4 dotted decimal notation)


default setting, not
changeable) Net mask: 255.255.255.0 (“Class C”-size, /24)

Page 178 of 429 DGB-004-1.03 HIPASE Data Sheets


Port X06 For Touch panel with PoE ONLY !

Power over Ethernet HIPASE-PoE (30V)

Galvanic isolation Data isolated, supply HIPASE-PoE not isolated

Isolation voltage
500 V data lines only
(Connection - Ground)

EMC immunity IEC 60255-26, EN 61131-2, IEC 61850-3 Ed.2.0

Special wiring
Min. CAT5, Length max. 5 m with HIPASE-PoE
recommendations

PC with HIPASE Engineering Tool / Station Bus (IEC 60870-5-104 Ed. 2.0 / MODBUS TCP / IEC 61850
Port X07
Ed. 2.0)

Connection type Ethernet electrical

Plug type RJ45

Baud rate 10/100 Mbit/s

10.0.0.1 (IPv4 dotted decimal notation)


(10.99.20.1 deliveries up to beginning of November 2015)
CAUTION: If there are several HIPASE devices in a network different IP addresses for each device have to be
IP address (factory default assigned!
setting, changeable)
Net mask: 255.255.255.0 (“Class C”-size, /24)
Standard gateway: 10.0.0.254

Alias-IP address (factory 10.99.20.1 (static) (IPv4 dotted decimal notation)


default setting, not
changeable) Net mask: 255.255.255.0 (“Class C”-size, /24)

Power over Ethernet –

Galvanic isolation Yes

Isolation voltage
500 V data lines only
(Connection - Ground)

EMC immunity IEC 60255-26, EN 61131-2, IEC 61850-3 Ed.2.0

Special wiring
Min. CAT5, Length max. 100 m
recommendations

Port X08 Station Bus (IEC 60870-5-104 Ed. 2.0 / MODBUS TCP / IEC 61850 Ed. 2.0)

Connection type Ethernet optical

Plug type SFF, Small form-factor pluggable (for SFP, Mini-GBIC)

Baud rate 10/100 Mbit/s provided, actually depending on equipped SFP module

Galvanic isolation Yes

DGB-004-1.03 HIPASE Data Sheets Page 179 of 429


Port X08 Station Bus (IEC 60870-5-104 Ed. 2.0 / MODBUS TCP / IEC 61850 Ed. 2.0)

10.0.0.1 (IPv4 dotted decimal notation)


(10.99.20.1 deliveries up to beginning of November 2015)
CAUTION: If there are several HIPASE devices in a network different IP addresses for each device have to be
IP address (factory default assigned!
setting, changeable)
Net mask: 255.255.255.0 (“Class C”-size, /24)
Standard gateway: 10.0.0.254

Alias-IP address (factory 10.99.20.1 (static) (IPv4 dotted decimal notation)


default setting, not
changeable) Net mask: 255.255.255.0 (“Class C”-size, /24)

Power over Ethernet –

Isolation voltage
optical connection
(Connection - Ground)

EMC immunity IEC 60255-26, EN 61131-2, IEC 61850-3 Ed.2.0

Special wiring
Refer to SFP Module manufacturer
recommendations

Connection with further HIPASE devices (for future purpose)


Port X09
PLEASE DO NOT PLUG ANYTHING!

Connection type Ethernet electrical

Plug type RJ45

Baud rate 10/100 Mbit/s

Power over Ethernet –

Galvanic isolation Yes

Isolation voltage
500 V
(Connection - Ground)

EMC immunity IEC 60255-26, EN 61131-2, IEC 61850-3 Ed.2.0

Special wiring
Min. CAT5, Length max. 5 m
recommendations

Port X10 Time Input via IRIG-A/-B or Meinberg telegram

Standard IRIG 200-98, formats A002, A132, B002, B122

Connection type DC-Level shift codes, AM, RS232, TTL

Plug type SMB Subminiature coaxial socket, not terminated

Supported Carrier
1 kHz or 10 kHz
frequency IRIG

Page 180 of 429 DGB-004-1.03 HIPASE Data Sheets


Port X10 Time Input via IRIG-A/-B or Meinberg telegram

Supported baud rates


1200 .. 115200 baud
Meinberg telegram

Logic High Level 3 .. 10 V

Logic Low Level 1 .. 3 V

Input voltage level 1 .. 10 V

Input impedance Non-linear, approx. 4 kOhms @ 3.5 VDC, 3 kOhms @ 10 VDC

Galvanic isolation Yes

Isolation voltage
500 V
(Connection - Ground)

EMC immunity IEC 60255-26, EN 61131-2, IEC 61850-3 Ed.2.0

Special wiring
Coaxial cable 50 ohms, length max. 10 m
recommendations

DGB-004-1.03 HIPASE Data Sheets Page 181 of 429


14.4. Indication and operating elements (HMI): LEDs and Button

Element Color Symbol Function Description

LED V1 GREEN O OPERATION CP-300 is in operation and functional

LED V2 RED F FAULT CP-300 has a malfunction, and can meet limited or no services

A
LED V3 YELLOW (‘S’ until beginning ALARM A function of the function block diagram changed to status "Alarm"
of year 2016)

LED V4 RED T TRIP A function of the function block diagram changed to status "Trip"

Accept button Accepting of latched LED status “Alarm” and "Trip" (yellow LED V3
R RESET
S1 and red LED V4), if it is no longer active

For further details please refert to chapter ‘Indication and operating elements’.

Page 182 of 429 DGB-004-1.03 HIPASE Data Sheets