COAL FEEDER
Allow Startup conditions for coal feeder (must satisfy all the condition)
1. Sealing air of coal feeder is already open
2. Coal mill outlet valves are opened
3. Coal mill is running
4. Coal feeder outlet valve is opened
5. Coal feeder control is on “remote” position
6. Coal mill outlet primary air temperature should be 60 – 70 oC
7. Coal mill roller is rised to the position
8. No coal feeder trip condition
Local Control panel for coal feeder : Rotary Scraper Control Cabinet
1. Remote Button (if press it, we control from control panel)
2. REMOTE BUTTON push = cannot control on loadNote position,
: air but it on control
compress roomcircuit
bag main
breakeroninREMOTE
3. OFF button = Local condition can use (cannot function on this control cabinet.
condition)
4. LOCAL button = to switch the operating condition in cal feeder to local position
5. JOG button = to check motor operation (to try motor operation good/not)
Running JOG button for short time for trial n must get permission from supervisor
Using JOG button will influence the boiler
6. TOTAL button = to show the total coal quantity feed to coal mill
Signals on the coal feeder control panel :
1. RUNNING = when startup running lamp will on, normal = running lamp will on
2. FEEDING = Coal on belt n coal belt is running to feed coal to coal mill
3. ALARM = Alarm lights is on, it means there are some problem in coal feeder
4. TRIP = When a serious problem on coal feeder/coal mill, coal feeder will trip and the TRIP
lamp is ON
5. VOLUMETRIC = When the weighing system have some problem, coal feeder will running
under the coal feeder stack
6. REMOTE = ON – operating condition in remote
7. OFF = On is shutdown
8. LOCAL = if in local condition, local signals will on
COAL mill system :
Interlock protections between the coal mill and coal feeder :
1. Coal Feeder trip = coal mill will not trip immediately, but will take a delay trip (15 s – 30
s) (when coal feeder trip = to start up, immediately get permission)
2. Coal feeder inlet valve is not fully opened,coal feeder cannot startup
3. Coal feeder sealing air valve is not fully opened, coal feeder cannot start up
4. Coal mill trip, coal feeder will trip immediately after coal mill trip. The following valves
will be act by interlock :
a. Fire Fighting steam valve will be act by interlock
b. Outlet valves (4) will close automatically
c. Cold primary air valve and hot primary air valve will close automatically
5. If coal feeder is running, coal feeder belt have no coal due tocoal jamming, “no coal”
signal is sent out and coal mill current decrease then coal mill system will tripped after a
certain time (thermal dynamic protection)
6. Coal mill outlet lose flame signals (3VS4)then coal mill trip
7. Other electrical problems will also cause coal mill system trip