BATTERIES
The question is often raised as to which of the two battery systems, lead acid or nickel
cadmium is the better? It would be appropriate to point out that both have been around
for now more than 100 years and it is evident that these two systems would continue to
dominate the storage battery market for some more years in the future too.
This indicates that neither of the two is the ‘better’. It is from application to application,
from individual requirement to requirement that either of the two systems would offer ‘a
superior solution’
A Ni-Cd cell has an open circuit voltage of only 1.2 volts whereas that of a lead-
acid is 2.0 volts. The practical consequences arising out of this are :
Without really going into much of the electrochemistry of the two systems, it
would be appropriate to point out the practical differences which arise out of them
as
a) Lead acid batteries do not require frequent equalization charge and in some
cases even require no equalization charge at least in standby application.
b) Lead acid system can reach full state of charge even at the float voltage
recharge level.
c) Ni-Cd systems can be fully charged only at an elevated recharged voltage of
1.55 volts per cell.
d) Ni-Cd systems require regular equalizing charge to maintain full capacity in
float conditions since charge retention of this system is rather poor.
e) Ni-Cd systems do not reach full capacity when recharged at elevated
temperature which is once again due to the fact that charge retention becomes
even poorer at higher temperatures.
3. Differences arising out of the difference in the role of electrolyte
A certain minimum gap has to be maintained between the pos and neg
electrodes in order to accommodate a desired amount of electrolyte which
would be sufficient to carry out the electrochemical reaction. There is
obviously no such requirement in a Ni-Cd system. This increased gap
however leads to higher internal resistance in the lead acid and therefore a
marginally lower high rate discharge performance is obtained from the
lead acid.
The principal difference in the discharge profile of the two systems can be given
as follows:
In general therefore on discharge the basic features of both the systems are similar
except that Ni-Cd gives a longer cycle life and slightly improved high rate
performance
The principal difference arises in the recharge efficiency of the two wherein the
recharge of a Ni-Cd is fraught with risks. This is because Ni-Cd batteries require
more overcharge than lead-acid batteries and therefore more heat is generated.
This means that Ni-Cd charging can only be done with very controlled charging
methods otherwise there is always a risk of thermal runaway.
5. Memory Effect
This so called memory effect can however be erased by a full discharge followed
by a full charge and is thus a temporary effect but the risk is that in between such
maintenance charge/discharge if an emergency occurs the Ni-Cd systems fails.
The question of reliability of Ni-Cd in critical applications has therefore always
remained as suspect.
6. Price : It is already mentioned that no technology is the perfect solution for all
applications. Besides other parameters as explained above, the price is also a very
important factor. We give below a comparison of cost of various types of batteries
of similar rating.