CALCULO DE CAIDA DE TENSION

PROYECTO : AMPLIACIÓN DEL SUB SISTEMA DE DISTRIBUCIÓN SECUNDARIO 440/220 V


SECCION : SUB-SISTEMA DE DISTRIBUCION SECUNDARIA MONOFASICO 440/220 V
LOCALIDAD : CHAPANGOS
DISTRITO : LANCONES
PROVINCIA : SULLANA
DEPARTAMENTO : PIURA

TENSION DEL SISTEMA : 440/220 V S.E. N° : 01

CALIFICACION ELECTRICA : 400 W/lote CIRCUITO : C-1

CONDUCTOR DE SERVICIO PARTICULAR CONDUCTOR DE ALUMBRADO PUBLICO


P PERDIDAS
U FORMACION NUMERO DE LOTES POTENCIA CAIDA DE TENSION LAMPARAS POTENCIA I CAIDA DE TENSION TOTALES
N CONDUCTOR SUMA TOTAL I A.P. A.P. I ACUMULADAS
T (mm2) SUMA C.E. C.E. S.P. Y C.E. S.P. y C.E. L SUMA (kW) (Amp) TOTAL
O OCUP. VACIOS TOTAL LOTES (KW) ( SkW ) (KW) (Amp) (m) (V) ( SV ) ( S%V ) N° (S) (V) ( SV ) ( S% V ) (Amp.) (kW) ( S%kW )

0 4 2x16+16/25 00 05 0.00 1.00 2.27 1.0 0.01 0.01 0.00 04 0.24 1.21 0.00 0.00 0.00 3.48 0.0062 0.50
1 4 2x16+16/25 00 05 0.00 1.00 2.27 30.4 0.28 0.29 0.07 04 0.24 1.21 0.12 0.12 0.06 3.48 0.0062 0.49
2 4 2x16+16/25 00 05 0.00 1.00 2.27 100.3 0.93 1.23 0.28 04 0.24 1.21 0.40 0.52 0.24 3.48 0.0057 0.46
3 4 2x16+16/25 00 05 0.00 1.00 2.27 130.1 1.21 2.44 0.55 04 0.24 1.21 0.51 1.03 0.47 3.48 0.0044 0.35
4 4 2x16+16/25 01 01 05 0.00 1.00 2.27 160.0 1.49 3.93 0.89 01 04 0.24 1.21 0.63 1.67 0.76 3.48 0.0026 0.21
5 4 2x16+16/25 01 01 03 0.00 0.60 1.36 57.4 0.32 4.25 0.97 02 0.12 0.61 0.11 1.78 0.81 1.97 0.0004 0.04
6 4 2x16+16/25 01 01 02 0.00 0.40 0.91 62.5 0.23 4.48 1.02 01 02 0.12 0.61 0.12 1.90 0.87 1.52 0.0002 0.01
7 4 2x16+16/25 01 01 01 0.00 0.20 0.45 52.9 0.10 4.58 1.04 01 01 0.06 0.30 0.05 1.96 0.89 0.76 0.0000 0.00

4 3.93
4.1 3 2x16/25 00 01 0.00 0.20 0.45 39.1 0.07 4.00 0.91 01 0.06 0.30 0.04 0.04 0.02 0.76 0.0000 0.00
4.2 3 2x16/25 01 01 01 0.00 0.20 0.45 37.4 0.07 4.07 0.93 01 01 0.06 0.30 0.04 0.08 0.03 0.76 0.0000 0.00
FORMACION FACTOR DE CAIDA DE TENSION RESISTENCIA a 40°C
MAXIMA DEMANDA = 400 W / lote CONDUCTOR (V/A x km) (ohm/km)
(mm2) 380/220 V 440/220 V 220 V A.P. FASE A.P.
FACTORES DE SIMULTANEIDAD 1 1x16/25 4.100 3.260 2.045
Servicio Particular = 0.50 2 1x16+16/25 4.100 3.260 2.045 2.045
Cargas Especiales = 1.00 3 2x16/25 4.100 3.260 2.045
Alumbrado Público = 1.00 4 2x16+16/25 4.100 3.260 2.045 2.045
5 2x25/25 2.570 2.560 1.285
FACTOR DE POTENCIA (COSØ) 6 2x25+16/25 2.570 3.270 1.285 2.045
S.Partic. y C.Espec. = 1.00 7 2x35/25 1.860 2.240 0.929
Alumbrado Público = 0.90 8 2x35+16/25 1.860 3.270 0.929 2.045
9 3x16/25 3.540 - - 2.045
TENSION DEL SISTEMA = 2 10 3x16+16/25 3.540 - 3.270 2.045 2.045
11 3x25/25 2.230 - - 1.285
1 380/220 V 12 3x25+16/25 2.230 - 3.270 1.285 2.045
2 440/220 V 13 3x35/25 1.610 - - 0.929
14 3x35+16/25 1.610 - 3.280 0.929 2.045
POTENCIA DE LA LAMPARA
Lámpara = 50.00 W
Pérdidas = 10.00 W
TOTAL = 60.00 W NOTA.- LOS CUADROS CON FONDO AZUL PUEDEN MODIFICARSE

TENSION DE LA LAMPARA = 220 V


CUADRO DE CARGAS

CUADRO DE CARGAS CARGAS A ALIMENTAR S.E. N° 01


S.E. N° SERVICIO PARTICULAR M.D. TOTAL
POTENCIA SECTORES CANT F.S.
POTENCIA (kW) (kW)
C. ESPECIALES DE
N° LOTES POTENCIA CORRIENTE TOTAL
CIRCUITO (kW) DISEÑO 1.- DOMESTICO 0.40 5 0.50 1.00
(kW) (A) (kW)
(kVA)
HAB. NO HAB. HAB. NO HAB. 2.- CARGAS ESPECIALES
C-1 5 0 0.0 0 1.00 2.27 PRONOEI 0.00
0.00
0.00
01

CIRCUITO
ALUMBRADO PUBLICO

N° LAMPARAS
POTENCIA
(kW)
CORRIENTE
(A)
1.25 5 3.- PERDIDA DE POTENCIA 0.01 1 1.00
0.00

0.01
C-1 4 0.24 1.21 4.- ALUMBRADO PUBLICO 0.06 4 1.00 0.24
SUB TOTAL 1.25
KVA PERDIDAS EN DISTRIBUCION (3%) 0.04
TOTAL (kW) 1.28
POTENCIA TOTAL (COS$=0,9) KVA 1.43