OVERVOLTAGE RELAY FOR

SUPERVISION OF CTs’ CIRCUITS


UB3/59-S
CAT. B7-98
12-01-99

GENERAL CHARACTERISTICS
Three-phase three-elements sensitive overvoltage relay with adjustable definite time
trip delay complete with time start output relay.
The UB3/59-S is used for supervision of the Current Transformers Secondary circuits
in Busbar differential protection.

SETTINGS
Settings are made on front face by means of two 4-poles DIP-SWITCH that allow to
obtain a wide and accurate setting range for the trip level as well as for the trip time
delay.

SIGNALIZATIONS
! 1 Green led for signalization of auxiliary power supply presence and relay
regular operation.
! 1 Red led for trip signalization.
! 1 Yellow led for start time monitoring.

COMMANDS
! Test spring lever switch: when pressed it simulates a voltage beyond the trip
level and allows the complete functional check of the relay. In one position the
test function does not operate the output relays; in the other it also operates the
output relays.
! Reset after trip of the time delayed output relays R1, R2, R3 can be:
- manual by reset push button on front face
- manual by remote push button connected to the relevant terminals provided ORDERING DATA
on the relay
- automatic with differential by connecting a bridge on remote reset terminals.
• Relay Type
OUTPUT RELAYS
! 3 Trip signal relays with one Change-over contacts rating 5A. • Rated Input Voltage
! 1 Time start signal relay with one Change-over contact rating 5A. • Auxiliary Power Supply
The output relays are normally deenergized (energized on trip).
• Setting Ranges

• Execution

40
OVERALL DIMENSIONS
See Overall Dimensions - 1 Module Relay.

ELECTRICAL CHARACTERISTICS CAT. B7-98


12-01-99
Rated input voltage : 100 V Burden on Input voltage : 0,03VA @ Vn = 100/√3 V
Auxiliary power : Type 1 : 24-110V d.c./a.c. ±
supply 20% 3W(d.c.);
Burden on supply voltage :
Type 2 : 90-220V d.c./a.c. ± 6VA(a.c.)
20%

STANDARD SETTING RANGES (Different on request)


VOLTAGE REGULATION TRIP TIME DELAY
! Vs = [a0 + (0 ÷ 15)] V ! T = [1+(0 ÷ 15)] x Kt(s)
! a0 = 2 : Vs = (2 ÷ 17) V step 1 V ! Kt = 1 : T = (1 ÷ 16) s step 1s

WIRING DIAGRAM

Vn (phase-to-phase)

100V