GENERAL CHARACTERISTICS
The relay UB0/A-TO64 connected to the magnetic detector TO64 allows for a very
accurate measurement of DC current (4÷20,5)A on a rated current of over 1000A.
The operation of the relay can be unidirectional or (on request) bi-directional.
The rated insulation voltage of the magnetic detector TO64 is over 5kV (dielectric
test voltage 10kV - 50Hz - 1 min (15kV on request) input against output).
On request all versions are fitted with blocking input and output or with time start
signalling relay.
SETTINGS
Settings are made on front face by means of two 8-poles DIP-SWITCHES that
allow to obtain a wide and accurate setting range for the measuring of:
Current trip level IS
Trip time delay T
SIGNALIZATION
1 Green led for signalization of auxiliary supply presence and relay regular
operation
1 Red led for trip signalization
1 Yellow led for trip memory
COMMANDS
Test spring lever switch: when pressed it simulates a current flow of 2 times
the maximum set current and allows the complete functional check of the
relay and of the trip time delay. In one position test function does not operate
the output relays; in the other it also operates the output relays.
ON-OFF switch that enables or blocks the tripping of the main output relays.
TO64
Output relays reset after trip can be:
- manual by reset push button on front face;
- manual by remote push button connected to the relevant terminals
provided on the relay; ORDERING DATA
- automatic by connecting a bridge on remote reset terminals.
The trip signal LEDS can be reset only by the front face reset push button.
• Relay type
OUTPUT RELAYS
• Rated Input Current
Two output relays are provided:
R1 with 2 form C contacts • Auxiliary Power Supply
R2, on request, with 1 C form contact
Output relay R1 is normally deenergized and it is energized on tripping. • Setting Ranges
On request it can be normally energized and deenergized on tripping.
Output relay R2 is normally deenergized and it is energized on tripping. • Output Relays Configuration
• Execution
• Options on request
16
OPTIONS
On request are provided: CAT. A4/c
12-01-99
Blocking Input (BI)
Blocking Output (BO) relay R2
Starting Time Output (TO) relay R2
OVERALL DIMENSIONS
See Overall Dimensions - 1 Module Relay.
MAGNETIC DETECTOR
ELECTRICAL CHARACTERISTICS
Rated input current : ≥ 1000A Frequency response band : 0-100 kHz
Current overload : 60kA per 1 sec. Saturation limit : 80A
Maximum sensitivity : 2A Output linearity : 2-60 A
Rated insulation voltage : 5 kV Dielectric withstand voltage : 10kV-50Hz-1min
(15kV on request)
Burden on power supply : 3W(d.c.); 6VA(a.c.)
Auxiliary Power Supply : Type 1 : 24-110 V d.c./a.c. ± 20% permanent
Type 2 : 90-220 V d.c./a.c. ± 20% permanent
Current setting : Is=[4+(0 ÷16.5)]xKa Standard: Ka=1 : Is= 4 – 20.5A Step of 0.1A
Time delay : T=[0.1+(0 ÷ 8.5)]xKt Standard: Kt=1 : T = 0,.1- 8.6s Step of 0.1s
(Definite Time)
WIRING DIAGRAM
TRIP DIRECTION
17