TAV-CCC-ARABTEC JOINT VENTURE

Midfield Terminal Building - Abu Dhabi


International Airport
Test Procedure for Switchboards
Doc No: COM-0401-AN-PR-0006 Rev: 1 Checklist No: TR-ANEL-SW-PCT-03

CONTACT RESISTANCE TEST RECORD SHEET


Module Tag Ref.: EM-MDP-W2-L1.0-1
1. General Data & Information:

Sub-System: Switchboard Feeder Designation: EM-DP-W2-L1.0-1


Temperature: 36°C Manufacturer: Schneider Electric
Humidity: 49 % Type: Powerline
Equipment Tested: EM-MDP-W2-L1.0-1 Serial No.: NA
Location / Level: PIER-4/L1.0 Rated Voltage: 400V
Room No.: 1682 Rated Current: 100A
Switchgear: UPS-W2-L1.0-1 Date: 22nd JUN 2016

2. Contact Resistance Test:

Injected Measured
From To Pass/
S. No. Current Resistance Remarks
Fail
(A) (µΩ)
R- R-
1 100 21 Pass
phase(top) phase(bottom)
Y- Y- 100 Pass
2 25
phase(top) phase(bottom)
B- B- 100 Pass
3 26
phase(top) phase(bottom)
N- N- 100 Pass
4 25
phase(top) phase(bottom)
Injected Current: 100 A Acceptable Criteria: CR < 1 mΩ [ANSI/NETA ATS-2009 – 7.4.3.2.4]

3. Testing Equipment Details:

Type / Calibration Calibration


S. No. Equipment Name Make Serial No.
Model Due Date Certificate Ref.
1 Micro Ohm Meter MEGGER MOM200A 08.11.2016 84197 1202852

Performed By:ALPHA POWER Witnessed By: ANEL Witnessed By: TCA-JV Approved By: AECOM
Name: JAYAPRAKASH Name: RAMKUMAR Name: A.KARA KAYA Name:

Signature: Signature: Signature: Signature:

Date: Date: Date: Date: