Documente Academic
Documente Profesional
Documente Cultură
Principle of Operation
Construction
Types of Transformers
emf Equation
Ideal Transformer
Transformer Losses
Transformer on Load
Equivalent Circuit of Transformer
Open circuit & Short Circuit Tests
Transformer Efficiency
Instrument Transformers
Auto Transformer
Introduction - Transformer
The main advantage of a.c generation, transmission and distribution over d.c
is that a.c. voltage can be increased or reduced dependent on the purpose of
use.
Under practical conditions electrical power is generated at voltage levels
from 3.3kV to 33kV.
As the requirement arises for use of power at distant load points the
voltage is stepped-up with the help of transformers and then transmitted
over long distances, 66kV, 132kV, 220kV, 330kV, 400kV
Depending on requirements of the loads voltage is further stepped down to
ensure supply at pre-determined voltages for loads. Such transformers are
commonly power transformers. 11kV, 400V, 220V
Transformers are also applied for low power to light power usages such as
electronic and telecommunications systems
In addition transformers are also used with measuring instruments to
facilitate transformation on measurements.
What is a Transformer?
A transformer is an electro-static device which
consists of two windings coupled through a
magnetic medium.
The two windings work at different voltage level.
One winding is referred to as High voltage and the
other Low voltage winding.
Yoke
𝐿𝑖𝑑 − 𝑜𝑛 𝑡𝑜𝑝 𝑜𝑓 𝑐𝑜𝑣𝑒𝑟
𝐻 𝑉 𝑏𝑢𝑠ℎ𝑖𝑛𝑔𝑠 𝐶𝑇𝑠
𝐶𝑜𝑖𝑙𝑠
T𝑎𝑝 𝐶ℎ𝑎𝑛𝑔𝑒𝑟 𝐷𝑟𝑖𝑣𝑒
1
2
3
4
5
6
7
8
9
10
11
12
n/n Name of Transformer Part Location on Transformer Purpose
13
14
15
16
17
18
19
20
21
22
23
24
n/n Name of Transformer Part Location on Transformer Purpose
25
26
27
28
29
30
31
32
33
34
35
36
Types of Transformer
The construction of transformers varies greatly, depending on their
applications, winding voltage, current ratings and operating
frequencies, cooling methods greatly influence their catergorisation.
High mechanical strength Has low mechanical strength due to nonbracing of windings
Reduction of leakage reactance is highly possible Reduction of leakage reactance is not easily possible
It cannot be easily dismantled for repair work The assembly can be easily dismantled for repair work
Has longer mean length of core and shorter mean length of coil turn.
It is not suitable for EHV (Extra High Voltage) requirements
Hence best suited for EHV (Extra High Voltage) requirements
Types of Transformers
w.r.t. Cooling Methods
n/n Type of Label Full Name [Detail)
5 ONAN [ONAN+A] Oil Immersed, Combination of Self Cooled and Air blast
Current Transformer
Potential Transformer
𝑵𝟏 𝑵𝟐 f𝜱𝒎 = 𝑩𝑨
o 𝐵
o 𝑨
𝜱𝒎
expressed as: 𝟏 = 𝟒𝒇𝜱𝒎 [Web/sec].
𝟒𝒇
e = 𝟒𝒇𝜱𝒎
e = 𝟒𝒇𝜱𝒎 𝑵
Transformer – emf Equation
The rms value for this induced emf will as E = 𝟒𝒇𝜱𝒎 𝑵,
considering that the form factor is 1.11. NB form factor is
the ratio of the rms value to the average value.
Therefore for the whole primary windings the rms value for With consideration that 𝜱𝒎 = 𝑩𝑨 the
the induced emf is 𝑬𝟏 = 𝟒. 𝟒𝟒𝑵𝟏 𝒇𝑩𝒎 𝑨 and for the whole equation for the induced emf in N-turns
of the windings becomes 𝐸 =
secondary windings it will be 𝑬𝟐 = 𝟒. 𝟒𝟒𝑵𝟐 𝒇𝑩𝒎 𝑨
4.44𝑁𝑓𝐵 𝐴. This is the emf equation
From the emf equation of a transformer it is evident for the transformer.
the ratios = = 4.44𝑓𝐵 𝐴
𝑬 𝑽
This indicates the emf per turn in each winding of a
The ratio 𝑲 = 𝟐 = 𝟐 . Is an indication of a
𝑬𝟏 𝑽𝟏
transformer are the same or equal. This is why for an constant by how much the voltage in the primary is
ideal transformer on no-load 𝑬𝟏 = 𝑽𝟏 and 𝑬𝟐 = 𝑽𝟐 . changed to attain the secondary voltages.
Transformation ratio
𝑵𝟐
K can also be expressed as 𝑲 = . This
𝐾= > 1 the transformer is called a step-up or if 𝑵𝟏
is when it’s also referred to as the turn’s
𝐾= > 1, this will imply that 𝐸 > 𝐸 or 𝑁 > 𝑁 ratio of a transformer.