Sunteți pe pagina 1din 40

INSTALLATION INSTRUCTIONS

FOR UPFLOW/HORIZONTAL & DOWNFLOW INDUCED


DRAFT GAS FURNACES
(-)GPQ UPFLOW/HORIZONTAL SERIES
(-)GLQ DOWNFLOW SERIES

U.L. recognized fuel gas and CO (Carbon Monoxide) detectors are recommended in
all applications, and their installation should be in accordance with the manufacturer’s
recommendations and/or local laws, rules, regulations, or customs.

92-24161-51-00
Before beginning any troubleshooting procedure, complete the following installation checklist. A furnace malfunction is
sometimes caused by an improper installation. By completing this checklist, the problem may be found and corrected. Make
copies of the checklist and complete one for every Low Profile Furnace service call for your records.

INSTALLATION CHECKLIST
(Refer to this manual for specifics.)
GAS SUPPLY
Adequate pipe size
No gas leaks
Proper supply and manifold gas pressure (check with an accurate U-tube manometer with the furnace and all other gas
appliances operating.)

ELECTRICAL
Correct thermostat and subbase Thermostat model Subbase model
Correct thermostat mode and setting
Correct line supply voltage
Correct power supply polarity is required with electronic ignition
Correct furnace ground to electrical panel
DC microamp (μA) flame signal (hot surface ignition units)
Correct control voltage
Measure and set heat anticipator amperage
Air conditioning low voltage wires connected to terminals “Y” “C” - not with wire nuts

VENTING

Correct vent pipe diameter and length (according to CSA tables) Vent connection size
Correct venting material (according to CSA tables)
Correct lining for masonry chimneys
Adequate clearance from combustibles
Proper negative pressure reading in the vent
Vent pipe secured to induced draft blower housing

COMBUSTION AIR

Proper source of combustion air


Correct combustion air opening size
Optional attic combustion air pull
Non-attic combustion air pull

FURNACE INSTALLATION

Adequate clearance from combustibles


Adequate clearance for service
Proper air temperature rise (See furnace rating plate)
External static pressure inches w.c.
Correct filter(s)
Correct cooling coil or accessories (if equipped)
Adequate supply and return air ducting Return Air Duct Size Supply Air Duct Size
Air ducts sealed to prevent leakage

2
Important: All manufacturer products
meet current Federal OSHA Guidelines
CONTENTS
for safety. California Proposition 65
Installation Check List ..............................................................................................2
warnings are required for certain
products, which are not covered by the Safety Information ....................................................................................................4
OSHA standards.
General Information..................................................................................................5
California's Proposition 65 requires
warnings for products sold in California Location Requirements and Considerations ............................................................5
that contain, or produce, any of over
600 listed chemicals known to the State Combustion and Ventilation Air..............................................................................10
of California to cause cancer or birth
defects such as fiberglass insulation, Vent Pipe Installation..............................................................................................14
lead in brass, and combustion products Gas Supply and Piping...........................................................................................17
from natural gas.
All “new equipment” shipped for sale in Electrical Wiring......................................................................................................21
California will have labels stating that Thermostat .............................................................................................................21
the product contains and/or produces
Proposition 65 chemicals. Although we Accessories ............................................................................................................22
have not changed our processes,
having the same label on all our Furnace Twinning...................................................................................................22
products facilitates manufacturing and
High Altitude Installations .......................................................................................25
shipping. We cannot always know
“when, or if” products will be sold in the Start-Up Procedure ................................................................................................28
California market.
You may receive inquiries from Air Flow...................................................................................................................31
customers about chemicals found in, or Blower Performance Data ......................................................................................32
produced by, some of our heating and
air-conditioning equipment, or found in Safety Features ......................................................................................................33
natural gas used with some of our
products. Listed below are those Maintenance...........................................................................................................34
chemicals and substances commonly
Troubleshooting......................................................................................................37
associated with similar equipment in
our industry and other manufacturers. Wiring Diagram.......................................................................................................39
• Glass Wool (Fiberglass) Insulation
• Carbon Monoxide (CO)
• Formaldehyde
• Benzene
More details are available at the
Websites for OSHA (Occupational
Safety and Health Administration), at
www.osha.gov and the State of
California's OEHHA (Office of
Environmental Health Hazard
Assessment), at www.oehha.org.
Consumer education is important since
the chemicals and substances on the
list are found in our daily lives. Most
consumers are aware that products
present safety and health risks, when
improperly used, handled and
maintained.
IMPORTANT: TO INSURE PROPER INSTALLATION AND OPERATION OF
THIS PRODUCT, COMPLETELY READ ALL INSTRUCTIONS PRIOR TO
ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE, MAINTAIN OR REPAIR
THIS PRODUCT. UPON UNPACKING OF THE FURNACE, INSPECT ALL
PARTS FOR DAMAGE PRIOR TO INSTALLATION AND START-UP.

3
SAFETY INFORMATION
! WARNING ! WARNING ! WARNING
USE ONLY WITH TYPE OF GAS ALWAYS INSTALL FURNACE TO USE OF THIS FURNACE IS
APPROVED FOR THIS FURNACE. OPERATE WITHIN THE ALLOWED DURING
REFER TO THE FURNACE RATING FURNACE'S INTENDED CONSTRUCTION IF THE
PLATE. TEMPERATURE-RISE RANGE FOLLOWING TEMPORARY
WITH A DUCT SYSTEM WHICH INSTALLATION REQUIREMENTS
HAS AN EXTERNAL STATIC ARE MET. INSTALLATION MUST
! WARNING PRESSURE WITHIN THE COMPLY WITH ALL
ALLOWABLE RANGE, AS INSTALLATION INSTRUCTIONS
INSTALL THIS FURNACE ONLY IN SPECIFIED IN DUCTING SECTION INCLUDING:
A LOCATION AND POSITION AS OF THESE INSTRUCTIONS. SEE
• PROPER VENT INSTALLATION;
SPECIFIED IN THE LOCATION ALSO FURNACE RATING PLATE.
REQUIREMENTS AND • FURNACE OPERATING UNDER
CONSIDERATIONS SECTION OF THERMOSTATIC CONTROL;
THESE INSTRUCTIONS.
! WARNING
• RETURN AIR DUCT SEALED TO
WHEN A FURNACE IS INSTALLED THE FURNACE;
! WARNING SO THAT SUPPLY DUCTS CARRY
AIR CIRCULATED BY THE • AIR FILTERS IN PLACE;
PROVIDE ADEQUATE FURNACE TO AREAS OUTSIDE • SET FURNACE INPUT RATE
COMBUSTION AND VENTILATION THE SPACE CONTAINING THE AND TEMPERATURE RISE PER
AIR TO THE FURNACE SPACE AS FURNACE, THE RETURN AIR RATING PLATE MARKING;
SPECIFIED IN THE VENTING SHALL ALSO BE HANDLED BY
• MEANS FOR PROVIDING
SECTION OF THESE DUCT(S) SEALED TO THE
OUTDOOR AIR REQUIRED FOR
INSTRUCTIONS. FURNACE CASING AND
COMBUSTION;
TERMINATING OUTSIDE THE
SPACE CONTAINING THE • RETURN AIR TEMPERATURE
! WARNING FURNACE. MAINTAINED BETWEEN 55°F
COMBUSTION PRODUCTS MUST (13°C) AND 80°F (27°C); AND
BE DISCHARGED OUTDOORS. ! WARNING • CLEAN FURNACE, DUCT WORK
CONNECT THIS FURNACE TO AN AND COMPONENTS UPON
APPROVED VENT SYSTEM ONLY, WHEN THIS FURNACE IS SUBSTANTIAL COMPLETION OF
AS SPECIFIED IN VENT PIPE INSTALLED IN A RESIDENTIAL THE CONSTRUCTION
INSTALLATION SECTION OF GARAGE, IT MUST BE INSTALLED PROCESS, AND VERIFY
THESE INSTRUCTIONS. SO THE BURNERS AND IGNITION FURNACE OPERATING
SOURCE ARE LOCATED NO LESS CONDITIONS INCLUDING
THAN 18 INCHES ABOVE THE IGNITION, INPUT RATE,
! WARNING FLOOR. THIS IS TO REDUCE THE TEMPERATURE RISE AND
THE MANUFACTURER IS NOT RISK OF IGNITING FLAMMABLE VENTING, ACCORDING TO THE
RESPONSIBLE FOR EQUIPMENT VAPORS WHICH MAY INSTRUCTIONS.
THAT IS MISMATCHED OR BE PRESENT IN A GARAGE.
IMPROPERLY INSTALLED. ALSO, THE FURNACE MUST BE
LOCATED OR PROTECTED TO
! WARNING AVOID PHYSICAL DAMAGE BY
VEHICLES. FAILURE TO FOLLOW
NEVER TEST FOR GAS LEAKS THESE WARNINGS CAN CAUSE A
WITH AN OPEN FLAME. USE A FIRE OR EXPLOSION, RESULTING
COMMERCIALLY AVAILABLE IN PROPERTY DAMAGE,
SOAP SOLUTION MADE PERSONAL INJURY OR DEATH.
SPECIFICALLY FOR THE
DETECTION OF LEAKS TO CHECK
ALL CONNECTIONS, AS
SPECIFIED IN GAS SUPPLY AND
PIPING SECTION OF THESE
INSTRUCTIONS.

4
GENERAL INFORMATION
The (-)GPQ/(-)GLQ series furnaces are into a low operating cost, is not the only furnace technology and venting
design certified by CSA for use with concern that consumers have. They requirements are changing, awareness
natural and propane gases as follows: also want a furnace with a reasonable of local, state, and federal codes and
As a Category I furnace, it may be installed cost. They want a furnace that industry changes is imperative.
vented vertically with type B-1 vent provides them with comfort – their main NOTE: Always perform a proper heat
pipe and also may be common concern. And they expect a furnace with loss calculation before specifying the
vented as described in these exceptional reliability and longevity. furnace size. This ensures that the
instructions. Gas furnace manufacturers are always furnace is sized to adequately,
This furnace should be installed in striving to provide consumers with the economically, heat the building and
accordance with the American National best furnace value. The Low Profile provide the correct airflow for your
Standard Z223.1 - latest edition booklet Furnace addresses all those consumer application.
entitled “National Fuel Gas Code” needs. It gives exceptional efficiency IMPORTANT: PROPER
(NFPA 54) (in Canada, CSA B149.1 with a low installation cost. It delivers APPLICATION, INSTALLATION AND
and .2 Installation Codes for gas the comfort the customer wants along MAINTENANCE OF THIS FURNACE
burning appliances), and the with the reliability they expect. IS A MUST IF CONSUMERS ARE TO
requirements or codes of the local utility The key to all these customer benefits is RECEIVE THE FULL BENEFITS FOR
or other authority having jurisdiction the furnace's heat exchanger. The WHICH THEY HAVE PAID.
including local plumbing or waste water materials used to construct the furnace Additional helpful publications available
codes. in general and the heat exchanger in from the “National Fire Protection
The National Appliance Energy particular make it a rugged, long lasting Association” are: NFPA-90A –
Conservation Act (NAECA) of 1987 unit. The unique heat exchanger design Installation of Air Conditioning and
states that any gas furnace provides the customer with a furnace Ventilating Systems 1985 or latest
manufactured after January 1, 1992, only 34 inches high. This gives the edition. NFPA-90B – Warm Air Heating
must have a minimum Annual Fuel consumer a unit easily installed in and Air Conditioning Systems 1984.
Utilization Efficiency (AFUE) of 78%. almost every location that accepts all
customary accessories. These publications are available from:
The higher the AFUE percentage the
more usable heat energy the consumer With the introduction of higher efficiency National Fire Protection Association,
gets for every dollar of fuel purchased. furnaces, special attention must be paid Inc.
This is similar to the EPA's minimum to the venting system. Only listed Batterymarch Park
gas mileage requirement for venting systems may be used as stated Quincy, MA 02269
automobiles. It gives the consumer a in the installation instructions and the CSA-INTERNATIONAL
relatively easy way to make direct National Fuel Gas Code, ANSI Z223.1 178 Rexdale Blvd.
efficiency comparisons between (NFPA 54), or the Canadian CAN/CGA Etobicoke (Toronto), Ontario
different furnace brands and styles. B149.1 and B149.2 Installation Codes Canada M9W, 1R3
A high AFUE value, which translates for Gas Burning Appliances. Since

LOCATION REQUIREMENTS AND CONSIDERATIONS


GENERAL INFORMATION well as alcoves, utility rooms, 6. IMPORTANT: If installing in a utility
closets and crawlspaces. room, be sure the door is wide
1. NOTE: This furnace is shipped with enough to:
heat exchanger support brackets 5. IMPORTANT: Support this unit when
installed under the back of the heat installed. For attic or crawl space a. allow the largest part of the
exchanger. These may be removed installation, horizontal furnaces may furnace to pass; or
before installation, but it is not be installed on combustible wood b. allow any other appliance (such
required. flooring or by using support brackets. as a water heater) to pass.
See Figure 1.
LOCATION FIGURE 1
! WARNING HORIZONTAL FURNACE INSTALLED W/SUPPORT BRACKETS

THIS FURNACE IS NOT APPROVED


FOR INSTALLATION IN A MOBILE EXHAUST
VENT
HOME. DO NOT INSTALL THIS
FURNACE IN A MOBILE HOME.
INSTALLATION IN A MOBILE HOME
COULD CAUSE FIRE, PROPERTY
DAMAGE, PERSONAL INJURY OR
DEATH.
2. IMPORTANT: This furnace is not
approved or recommended for
installation on its back, with access
doors facing upwards.
3. This furnace is suitable for
installation in buildings constructed
on-site. This heating unit should be NOTE: Do not block furnace
centralized with respect to the heat access with support rods. Maintain
distribution system as much as clearances recommended in Figure 2.
practicable. Allow enough space for proper service
maintenance or replacement of the heat
4. NOTE: These furnaces are exchanger and blower assembly. ST-A0799-01
approved for installation in attics, as

5
6

UPFLOW/HORIZONTAL DIMENSIONS
FIGURE 2
11/4 CLEARANCE TO COMBUSTIBLE MATERIAL (INCHES)
TOP BOTTOM
UPFLOW/HORIZONTAL MODELS
REDUCED CLEARANCE (IN.)
Left Right Ship.
Model A B C D E F Back Top Front Vent
Side Side Wgts.
SUPPLY
RETURN 05 14 1227/32 105/8 ➀ 111/2 17/8 0 4➁ 0 1 3 6➂ 85 lbs.
AIR 241/2
25.406 AIR 17
23 /32 07 17 /2
1
16 /32
11
12 /8
3
➀ 15 21/2 0 3➁ 0 1 3 6➂ 105 lbs.
10(A) 171/2 1611/32 123/8 ➀ 15 21/2 0 3➁ 0 1 3 6➂ 115 lbs.
10(B) 21 19 /32
27
14 /8
1
➀ 18 /2
1
21/2 0 0 0 1 3 6➂ 120 lbs.
12 241/2 2311/32 157/8 ➀ 22 21/2 0 0 0 1 3 6➂ 140 lbs.
15 241/2 2311/32 157/8 ➀ 22 21/2 0 0 0 1 3 6➂ 150 lbs.
➀ May require 3” to 4” or 3” or 5” adapter.
➁ May be 0” with type B vent.
➂ May be 1” with type B vent.

C E
9
/16 281/16
A
19 19
19
/32 B /32 D 20 /32

2613/16
3 ALTERNATE
/4 247/16
GAS CONNECTION
SIGHT
GAS CONNECTION GLASS
15/8 DIA.
265/8
265/8
AIRFLOW 7
/8 DIA.
34
ELECTRICAL CONNECTION 11
24 /32
LOW VOLTAGE
2411/32
143/8 7
OPTIONAL RETURN AIR CUTOUT 111/2 /8 DIA. 15
(EITHER SIDE) FOR USE WITH 3
14 /8
EXTERNAL SIDE FILTER FRAME 111/2

LEFT SIDE
FRONT
RIGHT SIDE 23
IMPORTANT: This furnace is not approved or recommended for
installation on its back, with access doors facing upwards.
DOWNFLOW DIMENSIONS
FIGURE 3
CLEARANCE TO COMBUSTIBLE MATERIAL (INCHES)
DOWNFLOW MODELS
REDUCED CLEARANCE (IN.)
TOP BOTTOM Left Right Ship.
Model A B C D E Back Top Front Vent
Side Side Wgts.
05 14 1227/32 103/8 ➀ 13 1/8 0 4➁ 0 1 3 6➂ 85 lbs.
07 17 /2
1
16 /32
11
12 /8
1
➀ 16 5/8 0 3➁ 0 1 3 6➂ 105 lbs.
10(A) 171/2 1611/32 121/8 ➀ 16 5/8 0 3➁ 0 1 3 6➂ 115 lbs.
10(B) 21 19 /32
27
13 /8
7
➀ 20 1/8 0 0 0 1 3 6➂ 120 lbs.
193/4
12 241/2 2311/32 155/8 ➀ 23 5/8 0 0 0 1 3 6➂ 140 lbs.
241/2
15 241/2 2311/32 155/8 ➀ 23 5/8 0 0 0 1 3 6➂ 150 lbs.
➀ May require 3” to 4” or 3” or 5” adapter.
➁ May be 0” with type B vent.
➂ May be 1” with type B vent.

S.A.
E

281/16
C A
5 R.A. 5
/8 B /8 D 201/8 5
/8

3
/4 265/8
7
265/8 /8 DIA.
7
SIGHT /8 DIA.
GLASS
LOW VOLTAGE

34
ELECTRIC CONNECTION
233/8
13
233/8
26 /16
203/8 203/8 247/16
AIRFLOW

GAS CONNECTION 63/16 15/8 DIA.


63/16

NOTE: IN DOWNFLOW CONFIGURATION, OPTIONAL AIR CUTOUT IS NOT PERMITTED.


7
CLEARANCE – TABLE 1 DUCTING
ACCESSIBILITY FURNACE BASE BASE Proper air flow is required for the
WIDTH PLATE NO. PLATE SIZE correct operation of this furnace. Too
The design of forced air furnaces with 14” RXGB-D14 115/8” x 239/16”
input ratings as listed in the tables on little air flow can cause erratic
171/2” RXGB-D17 151/8” x 239/16” operation and can damage the heat
the following pages are certified by 21” RXGB-D21 185/8” x 239/16” exchanger. The duct system must
CSA for the clearances to combustible 241/2” RXGB-D24 255/8” x 239/16” carry the correct amount of air for
materials shown in inches.
heating and cooling. Position the unit
See name/rating plate and clearance minimize long runs or runs with many
label for specific model number and
SITE SELECTION turns and elbows.
clearance information. 1. Select a site in the building near the Size the ducts according to acceptable
center of the proposed, or existing, industry standards and methods. The
Service clearance of at least 24 inches
duct system. total static pressure drop (including
is recommended in front of all furnaces.
2. Give consideration to the vent system evaporator coil, if used) of the entire
ACCESSIBILITY CLEARANCES, system should not exceed 0.5” w.c. Be
piping when selecting the furnace
WHERE GREATER, MUST TAKE sure to have adequate space for unit
location. Be sure the venting system
PRECEDENCE OVER FIRE filter. NOTE: Airflow external static
can travel from the furnace to the
PROTECTION CLEARANCES. pressure measurements do not include
termination with minimal length and
elbows. filter or coil.
! WARNING
IMPORTANT: Some high efficiency
UPFLOW AND HORIZONTAL 3. Locate the furnace near the existing
filters have a greater than normal
FURNACES MUST NOT BE gas piping. Or, if running a new gas
resistance to air flow. This can
INSTALLED DIRECTLY ON line, locate the furnace to minimize
adversely affect furnace operation. BE
CARPETING, TILE OR OTHER the length and elbows in the gas SURE TO CHECK AIR FLOW if using
COMBUSTIBLE MATERIAL OTHER piping. any filter other than the factory-
THAN WOOD FLOORING. 4. Locate the furnace to maintain proper provided filter.
INSTALLATION ON A clearance to combustibles as shown NOTE: DO NOT take return air from
COMBUSTIBLE MATERIAL CAN in Figures 2 and 3. bathrooms, kitchens, furnace rooms,
RESULT IN FIRE CAUSING garages, utility or laundry rooms, or
PROPERTY DAMAGE, SEVERE ! CAUTION cold areas.
PERSONAL INJURY OR DEATH. WHEN COILS ARE USED WITH AIR
A gas-fired furnace for installation in a HANDLERS OR FURNACES AND IMPORTANT: When using outside air,
residential garage must be installed so INSTALLED ABOVE A FINISHED design and adjust the system to
CEILING OR LIVING AREA, IT IS maintain a return air temperature
that the burner(s) and the ignition
RECOMMENDED THAT AN above 50°F during the heating season.
source are located not less than 18” AUXILIARY SHEET METAL
above the floor and the furnace is CONDENSATE DRAIN PAN BE
located or protected to avoid physical
! WARNING
FABRICATED AND INSTALLED
damage by vehicles. UNDER ENTIRE UNIT. FAILURE TO NEVER ALLOW PRODUCTS OF
DO SO CAN RESULT IN PROPERTY COMBUSTION OR THE FLUE
! WARNING DAMAGE. RUN CONDENSATE TO A PRODUCTS TO ENTER THE
DOWNFLOW UNIT DESIGN IS LOCATION WHERE IT IS RETURN AIR DUCTWORK, OR THE
CERTIFIED FOR INSTALLATION ON NOTICEABLE. CIRCULATING AIR SUPPLY. ALL
NON-COMBUSTIBLE FLOOR. A RETURN DUCTWORK MUST BE
SPECIAL COMBUSTIBLE FLOOR ! WARNING ADEQUATELY SEALED AND
SUB-BASE IS REQUIRED WHEN COMBUSTIBLE MATERIAL MUST SECURED TO THE FURNACE WITH
INSTALLING ON A COMBUSTIBLE NOT BE PLACED ON OR AGAINST SHEET METAL SCREWS, AND
FLOOR. FAILURE TO INSTALL THE THE FURNACE JACKET OR WITHIN JOINTS TAPED. WHEN A FURNACE
SUB-BASE MAY RESULT IN FIRE, THE SPECIFIED CLEARANCES OF IS MOUNTED ON A PLATFORM,
PROPERTY DAMAGE, PERSONAL THE VENT PIPE. THE AREA AROUND WITH RETURN THROUGH THE
THE FURNACE MUST BE KEPT BOTTOM, IT MUST BE SEALED
INJURY OR DEATH. THIS SPECIAL
CLEAR AND FREE OF ALL AIRTIGHT BETWEEN THE FURNACE
BASE IS OFFERED AS AN COMBUSTIBLE MATERIALS AND THE RETURN AIR PLENUM.
ACCESSORY FROM THE FACTORY. INCLUDING GASOLINE AND OTHER THE RETURN AIR PLENUM MUST
SEE THE CLEARANCE LABEL FLAMMABLE VAPORS AND LIQUIDS. BE PERMANENTLY ENCLOSED.
LOCATED INSIDE THE FURNACE PLACEMENT OF COMBUSTIBLE NEVER USE A DOOR AS A PART OF
FOR THE APPROPRIATE MODEL MATERIALS ON, AGAINST OR THE RETURN AIR PLENUM. THE
NUMBER. AROUND THE FURNACE JACKET FLOOR OR PLATFORM MUST
CAN CAUSE AN EXPLOSION OR PROVIDE SOUND PHYSICAL
THE SPECIAL BASE IS NOT FIRE RESULTING IN PROPERTY
REQUIRED WHEN THE FURNACE IS SUPPORT OF THE FURNACE,
DAMAGE, PERSONAL INJURY OR
INSTALLED ON TOP OF AN AIR WITHOUT SAGGING, CRACKS,
DEATH. THE FURNACE OWNER
CONDITIONING PLENUM. SHOULD BE CAUTIONED THAT THE GAPS, ETC., AROUND THE BASE AS
FURNACE AREA MUST NOT BE TO PROVIDE A SEAL BETWEEN
USED AS A BROOM CLOSET OR THE SUPPORT AND THE BASE.
FOR ANY OTHER STORAGE
PURPOSES.

8
FAILURE TO PREVENT PRODUCTS b. If summer air conditioning is
OF COMBUSTION FROM BEING
! WARNING
desired, position the indoor coil on
CIRCULATED INTO THE LIVING A SOLID METAL BASE PLATE, (SEE the bottom of the unit. Insure that
SPACE CAN CREATE POTENTIALLY TABLE 1) MUST BE IN PLACE no air can bypass this coil.
HAZARDOUS CONDITIONS, WHEN THE FURNACE IS
INSTALLED WITH SIDE AIR 2. Connect the return air ducting to the
INCLUDING CARBON MONOXIDE return air opening at the top of the
POISONING THAT COULD RESULT RETURN DUCTS. FAILURE TO
INSTALL A BASE PLATE COULD unit. Make the connection air tight to
IN PERSONAL INJURY OR DEATH. prevent entraining combustion
CAUSE PRODUCTS OF
DO NOT, UNDER ANY COMBUSTION TO BE CIRCULATED gases from an adjacent fuel-burning
CIRCUMSTANCES, CONNECT INTO THE LIVING SPACE AND appliance.
RETURN OR SUPPLY DUCTWORK CREATE POTENTIALLY
TO OR FROM ANY OTHER HEAT HAZARDOUS CONDITIONS, HORIZONTAL UNITS
PRODUCING DEVICE SUCH AS A INCLUDING CARBON MONOXIDE 1. Unit can be mounted left or right
FIREPLACE INSERT, STOVE, ETC. POISONING OR DEATH.
side airflow configuration.
DOING SO MAY RESULT IN FIRE, 2. If summer air conditioning is desired,
CARBON MONOXIDE POISONING, 2. Position the unit on adequate
position the indoor coil on the supply
EXPLOSION, PERSONAL INJURY supports or by using support
air side of the furnace. Insure that no
OR PROPERTY DAMAGE. brackets (see Figure 1) and connect
air can bypass this coil.
supply plenum.
! WARNING 3. Connect the supply air plenum to the
3. If summer air conditioning is desired,
furnace plenum opening.
BLOWER AND BURNERS MUST position the indoor coil on the supply
NEVER BE OPERATED WITHOUT air side of the unit. Insure that no air
THE BLOWER DOOR IN PLACE.
DOWNFLOW UNITS can bypass this coil.
THIS IS TO PREVENT DRAWING
GAS FUMES (WHICH COULD
! WARNING 4. Secure the four angle brackets
THE DOWNFLOW FURNACE shipped with the unit to the return air
CONTAIN HAZARDOUS CARBON opening. See Figure 5. Connect the
MONOXIDE) INTO THE HOME THAT DESIGN IS CERTIFIED FOR
INSTALLATION ON A NON- return air ducting to the return air
COULD RESULT IN PERSONAL opening at the top of the unit. Make
INJURY OR DEATH. COMBUSTIBLE FLOOR. IF
INSTALLED ON A COMBUSTIBLE the connection air tight to prevent
FLOOR, USE THE SPECIAL BASE entraining combustion gases from
UPFLOW UNITS an adjacent fuel-burning appliance.
SPECIFIED ON THE FURNACE
1. Set furnace in place and connect the CLEARANCE LABEL. FAILURE TO NOTE: Do not block furnace access
return duct or return air cabinet to INSTALL THE SPECIAL BASE MAY with support rods. Maintain clearances
unit. Make the connection air-tight to RESULT IN FIRE, PROPERTY recommended in Figure 2. Allow
prevent entraining combustion DAMAGE, PERSONAL INJURY OR enough space for proper service
gases from any adjacent fuel- DEATH. THIS SPECIAL BASE IS maintenance or replacement of the
burning appliances. Unit return air SHIPPED FROM THE FACTORY AS heat exchanger and blower assembly.
may be connected on the sides or AN ACCESSORY.
bottom of the return air
compartment. 1. Position the unit over the supply air
plenum and connect.
a. Openings in the side must be cut a. If installing on a combustible floor
out the full width of the knockouts and not using an evaporator
on the unit. If using side return air, coil box, install the special
THE BOTTOM base plate must combustible floor base. See
be installed. Figure 4.
NOTE: Where the maximum
airflow is 1800 CFM or more, both
sides or the bottom must be used FIGURE 4
for return air. COMBUSTIBLE FLOOR BASE

b. If using bottom return air, place


furnace over return air plenum and
seal furnace bottom to return air
plenum.

9
• Commercial buildings
FIGURE 5 • Buildings with indoor pools
HORIZONTAL RETURN AIR DUCT
(LEFT-HAND AIRFLOW POSITION SHOWN) • Furnaces installed in laundry rooms
• Furnaces in hobby or craft rooms
• Furnaces installed near chemical
storage areas.
AIRFLOW
Exposure to the following substances
in the combustion air supply may also
require OUTDOOR AIR for
combustion:
• Permanent wave solutions
• Chlorinated waxes and cleaners
RETURN • Chlorine-based swimming pool
chemicals
• Water softening chemicals
REAR VIEW • De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as
perchloroethylene)
FOUR ANGLE BRACKETS ARE SHIPPED WITH EACH
UNIT THAT CAN BE INSTALLED HORIZONTALLY. THESE
• Printing inks, paint removers,
BRACKETS MAY BE USED TO SECURE THE RETURN varnishes, etc.
AIR DUCT TO A HORIZONTAL UNIT. • Hydrochloric acid
• Cements and glues
COMBUSTION AND VENTILATION AIR • Antistatic fabric softeners for clothes
dryers
IMPORTANT: This is not a direct vent furnace. Review venting instructions • Masonry acid washing materials
before installing.

! WARNING COMBUSTION AIR


THIS FURNACE AND ANY OTHER
REQUIREMENTS
FUEL-BURNING APPLIANCE MUST IMPORTANT: Air for combustion and
BE PROVIDED WITH ENOUGH ventilation must not come from a
FRESH AIR FOR PROPER corrosive atmosphere. Any failure due
COMBUSTION AND VENTILATION to corrosive elements in the
OF THE FLUE GASES. MOST atmosphere is excluded from warranty
HOMES WILL REQUIRE THAT coverage.
OUTSIDE AIR BE SUPPLIED INTO The following types of installation may
THE FURNACE AREA. FAILURE TO require OUTDOOR AIR for
DO SO CAN CAUSE DEATH FROM combustion, due to chemical
CARBON MONOXIDE POISONING. exposures:
Adequate facilities for providing air for
combustion and ventilation must be FIGURE 6
provided in accordance with section AIR FROM HEATED SPACE
5.3, Air for Combustion and
Ventilation, of the National Fuel Gas
Code, ANSI, Z223.1 latest edition or
CSA B149.1 and .2 or, applicable
provisions for the local building codes,
and not obstructed so as to prevent the
flow of air to the furnace.

10
Combustion air must be free of acid
forming chemicals; such as sulphur, FIGURE 7
AIR FROM ATTIC/CRAWL SPACE
fluorine and chlorine. These elements
are found in aerosol sprays,
detergents, bleaches, cleaning
solvents, air fresheners, paint and
varnish removers, refrigerants and
many other commercial and household
products. Vapors from these products
when burned in a gas flame form acid
compounds. The acid compounds
increase the dew point temperature of
the flue products and are highly
corrosive after they condense.

! WARNING
ALL FURNACE INSTALLATIONS
MUST COMPLY WITH THE
NATIONAL FUEL GAS CODE AND
LOCAL CODES TO PROVIDE
ADEQUATE COMBUSTION AND
VENTILATION AIR FOR THE
FURNACE. FAILURE TO DO SO CAN
CREATE HAZARDOUS CONDITIONS
RESULTING IN PROPERTY
DAMAGE, BODILY INJURY OR EXAMPLE 2. AIR INTAKE PIPE CONNECTION
DEATH FROM SMOKE, FIRE OR FURNACE LOCATED IN A (GPQ ONLY)
CARBON MONOXIDE. CONFINED SPACE A double-elbow may be installed to
Combustion air requirements are A confined space (any space smaller top inlet air opening, BUT IS NOT
determined by whether the furnace is than shown above as “unconfined”) REQUIRED. This will help to prevent
in an open (unconfined) area or in a must have openings into the space accidental blockage of the intake
confined space such as a closet or which are located in accordance with opening. Reference Figure 8 for
small room. See Figures 6 and 7. the requirements set forth in the proper elbow diameter.
following subsections A and B. Size the NOTE: Inlet is specifically designed to
EXAMPLE 1.
openings by how they are connected to prevent material from being pulled into
FURNACE LOCATED IN AN
the heated area or to the outside, and furnace. If elbows are not used, the
UNCONFINED SPACE by the input of all appliances in the intake opening must be kept clean and
Using indoor air for combustion. space. free of debris.
An unconfined space must have at If confined space is within a building It is also acceptable to run the
least 50 cubic feet for each 1,000 with tight construction, combustion air condensate drain (or refrigerant) line
BTUH of the total input for all must be taken from outdoors or area access over the air intake hole as
appliances in the space. Here are a freely communicating with the long as a 1" minimum clearance is
few examples of the room sizes outdoors. maintained.
required for different inputs. The sizes A. USING INDOOR AIR FOR B. USING OUTDOOR AIR FOR
are based on 8 foot ceilings. COMBUSTION, ALL OF THE COMBUSTION, ALL OF THE
BTUH Minimum Sq. Feet Typical Room Size
MODELS (GPQ, GLQ) MODELS (GPQ, GLQ)
Input With 8' Ceiling With 8' Ceiling IMPORTANT: Air should not be taken IMPORTANT: Never take
50,000 312 14*x24* or 18*x18* from a heated space with a fireplace, combustion air from an attic space
75,000 469 15*x31* or 20*x24* exhaust fan or other device that may that is equipped with power
100,000 625 20*x31* or 25*x25* produce a negative pressure. ventilation.
125,000 833 23*x34* or 26*x30* If combustion air is taken from the
150,000 938 25*x38* or 30*x31* The confined space must
heated area, the openings must
communicate with the outdoors
If the open space containing the each have at least 100 square
according to Methods 1 and 2. The
furnace is in a building with tight inches of free area. Each opening
minimum air opening dimension
construction (contemporary must have at least one square inch
of free area for each 1,000 Btuh of shall not be less than 3 inches.
construction), outside air may still be When using ducts, they shall be of
required for the furnace to operate and total input in the space. Here are
some examples of typical openings the same cross-sectional area as
vent properly. Outside air openings the free area of the openings to
should be sized the same as for a required.
which they connect.
confined space. Btuh Free Area
Input Each Opening
100,000 100 Square Inches
150,000 150 Square Inches

11
FIGURE 8
COMBUSTION AIR FITTING – NON-ATTIC COMBUSTION AIR PULL, GPQ ONLY

ATTACH OPTIONAL DOUBLE ELBOW TO TOP INLET


AIR OPENING TO PREVENT ACCIDENTAL BLOCKAGE
OF INTAKE OPENING. THIS IS NOT A REQUIREMENT.
(SEE PREVIOUS PAGE.) SINGLE ELBOW IS ALLOWED
BUT MAY NOT PREVENT DEBRIS FROM BEING
DROPPED INTO THE FURNACE.
EXHAUST

PVC
DOUBLE
ELBOW
METAL FLUE
PIPE ONLY
6" MININUM
CLEARANCE

#8 SCREWS #8 SCREWS

6" MIN.

GROUND OR
SHELF SURFACE

B: Method 1 b. Where communicating with a. One square inch for each 3000
Provide two permanent openings, outdoors through HORIZONTAL BTUH of the total input rating of all
DUCTS, each opening shall have equipment located in the enclosure,
one located within 12 inches of the
a minimum free area of 1 square AND
top and one located within 12
inches of the bottom of the inch for each 2000 BTUH of total b. Not less than the sum of the areas
enclosure. Each opening shall input rating for all equipment in of all vent connectors in the confined
communicate directly, or by ducts, the enclosure. Here are typical space.
with the outdoors or spaces (crawl duct sizes:
IMPORTANT: If the furnace is in a
or attic) that freely communicate location with an exhaust fan, there
with the outdoors. HORIZONTAL OUTDOOR AIR must be sufficient ventilation to prevent
OPENING DIMENSIONS the exhaust fan from creating a
a. Where directly communicating
BTUH Free Area Round negative pressure in the room.
with the outdoors or where Input Each Opening Pipe Size
communicating to the outdoors Combustion air openings must NOT
50,000 25.00 sq. inches 6” BE RESTRICTED in any manner.
through VERTICAL DUCTS,
75,000 37.50 sq. inches 7”
each opening shall have a CONSULT LOCAL CODES FOR
100,000 50.00 sq. inches 8”
minimum free area of 1 square SPECIAL REQUIREMENTS.
inch for each 4000 BTUH of 125,000 62.50 sq. inches 9”
total appliance input rating in the 150,000 75.00 sq. inches 10”
enclosure. Here are typical duct
sizes:
B: Method 2
One permanent opening, located within
VERTICAL OUTDOOR AIR 12 inches of the top of the enclosure,
OPENING DIMENSIONS
shall be permitted where the
BTUH Free Area Round equipment has clearances of at least 1
Input Each Opening Pipe Size
inch from the sides and back and 6
50,000 12.50 sq. inches 4” inches from the front of the appliance.
75,000 18.75 sq. inches 5” The opening shall directly
100,000 25.00 sq. inches 6” communicate with the outdoors or
125,000 31.25 sq. inches 7” communicate through a vertical or
150,000 37.50 sq. inches 7” horizontal duct to the outdoors or
spaces (crawl or attic) that freely
communicate with the outdoors and
have a minimum free area of:

12
FIGURE 9
OUTSIDE AIR USING A HORIZONTAL INLET & OUTLET

B: Method 3, GPQ only


For the optimum in quiet operation,
attic air may be brought directly to the
furnace.
IMPORTANT: In applications using
Method 3 for combustion air, the attic
must be ventilated by gable or soffit If attic combustion air is used, the inlet than 10 feet can result in nuisance
vents. See Figure 7. air opening at the furnace must be pressure switch trips.
protected from accidental blockage.
! CAUTION Install a 90° elbow pointing horizontally
COMBUSTION AIR INTAKES at the top of inlet air pipe. See Figure
CANNOT BE TERMINATED 10 (maximum of 2, 45° or 90° elbows,
OUTSIDE. DOING SO CAN CAUSE allowed).
IMPROPER OPERATION OF THE NOTE: Maximum length of pipe that
FURNACE. may be used for combustion air is 10
feet with two elbows. Lengths of more

FIGURE 10
COMBUSTION AIR FITTING – OPTIONAL ATTIC COMBUSTION AIR PULL, GPQ ONLY
ATTACH A 90° ELBOW TO TOP INLET AIR
OPENING TO PREVENT ACCIDENTAL BLOCKAGE
OF INTAKE OPENING.

PVC
ELBOW
EXHAUST

ATTIC SPACE
12" MIN. FROM INSULATION
TOP OF INSULATION

METAL FLUE PIPE ONLY

10 FT. MAX.
INDOOR SPACE
INCLUDING 6" MINIMUM
HORIZONTAL DIRECTION CLEARANCE
#8 SCREW PVC
COUPLER
#8 SCREWS

! CAUTION
USE OF SHEET METAL
AIR INTAKE PIPE INSTEAD
OF PVC MAY RESULT IN
NOISE ISSUES.

13
VENTING FIGURE 11
ATTACHING TO DRAFT INDUCER COLLAR
GENERAL INFORMATION
The furnace must be vented in
accordance with these instructions,
National Fuel Gas Code, ANSI Z223.1
and/or the Natural Gas Installation
Code, CSA-B149.1 & .2 and
requirements or codes of the local utility
or other authority having jurisdiction.

! WARNING
DEVICES ATTACHED TO THE FLUE
OR VENT FOR THE PURPOSE OF
REDUCING HEAT LOSS UP THE
CHIMNEY HAVE NOT BEEN TESTED
AND HAVE NOT BEEN INCLUDED
IN THE DESIGN CERTIFICATION OF
THIS FURNACE. WE, THE
MANUFACTURER, CANNOT AND
WILL NOT BE RESPONSIBLE FOR
INJURY OR DAMAGE CAUSED BY A0991-01

THE USE OF SUCH UNTESTED


AND/OR UNCERTIFIED DEVICES, FURNACE CATEGORY IMPORTANT APPLICATION
ACCESSORIES OR COMPONENTS.
INFORMATION NOTES
This furnace is shipped as a Category I When the furnace is used as a
DRAFT INDUCER type induced draft furnace. A Category replacement, the existing vent system
! WARNING I furnace operates with a nonpositive should be inspected to assure that
vent pressure and has a vent gas there are no obstructions, blockage, or
VENT PIPE ATTACHING HOLES
temperature at least 140°F above the any signs of corrosion and is properly
MUST BE PREDRILLED IN THE
dew point of the vent gases. A sized for use with this furnace.
DRAFT INDUCER COLLAR TO
Category I type may be a draft hood NOTE: When the vent table permits
PREVENT DAMAGING THE
equipped furnace or have a fan more than one diameter of pipe for a
INDUCER. DRILL 1/8” DIAMETER
assisted combustion system (induced connector or vent, the smallest
HOLES THROUGH THE VENT PIPE
draft). The inducer is used to pull flue permitted diameter must be used.
AND COLLAR AND USE #8 SCREWS
products through the combustion
TO ATTACH. SEE FIGURE 11. Vent pipe may be type “B-1,” either
chamber and as they leave the
FAILURE TO FOLLOW THIS rigid or suitable flexible construction
furnace, most of the energy has been
WARNING CAN CAUSE that carries a u.l. listing.
dissipated. The buoyant effect of the
RECIRCULATION OF FLUE
flue gases provides venting to the Common venting is allowed with
PRODUCTS CAUSING CARBON
outdoors. vertical B-1 vent systems, and lined
MONOXIDE POISONING
During the off cycle, the inducer is off masonry chimneys. Follow the National
RESULTING IN PERSONAL INJURY
and there is very little flow through the Fuel Gas Code, ANSI Z223.1 and/or
OR DEATH.
vent, cooling the vent. During the on the Natural Gas Installation Code,
cycle there is no dilution airflow, as CSA-B149.1 & .2 for proper installation
with a draft hood type furnace. practices.
Although the vent heats up rapidly NOTE: Follow combustion air
without dilution air, the flue products instructions as outlined in this manual.
contain more water vapor, which
Single wall vent connectors to “B-1
results in a higher dew point
vent or masonry chimneys” may be
temperature. It is most important that
used under the guidelines of the
you follow the guidelines in these
National Fuel Gas Code, ANSI Z223.1
instructions to prevent the possible
and/or the Natural Gas Installation
formation of condensation in the
Code, CSA-B149.1 & .2.
venting system.
The entire length of the vent
As a Category I furnace it may be connector shall be readily
vented vertically with type B-1 vent accessible for inspection, cleaning
pipe and also may be common vented, and replacement.
as described in these instructions.

14
“B-1” VERTICAL VENTING FIGURE 12
TYPICAL VENTING WITH “B-1” VENT
Type “B-1” vents must be installed in
accordance with the terms of their
listings and the vent manufacturer’s
instructions.
“B-1” vents must be supported and
spaced in accordance with their listings
and the manufacturer’s instructions. All
vents must be supported to maintain
their minimum clearances from
combustible material.
VERTICAL VENTING
Categorized
Furnace Vent
Input Size Required
50K 3”
75K *4”
100K *4”
125K *5”
150K *5”

*NOTE: All furnaces have a 3” vent


connection as shipped from the factory. A 3”
to 4” or 3” to 5” vent transition is required on
all but the 50,000 BTUH models when
vertically vented or common vented with
metal vent pipes. THE VENT TRANSITION
CONNECTION MUST BE MADE AT THE
FURNACE VENT EXIT. It must originate
with an adapter if required, at the furnace
flue collar and terminate either in a listed
cap or roof assembly. When common
venting, the vent connector size may differ
from the above diameters depending on
application. See ANSI Z21.47-1993/CSA- These shall be assembled in
2.3-M93 or latest edition tables. ! WARNING
accordance with the manufacturer’s
VERTICAL VENT SYSTEMS: instructions. See Figure 11. DO NOT CONNECT THIS FURNACE
1. A gas vent shall terminate above the TO A CHIMNEY USED TO VENT A
5. Any angle greater than 45 degrees SOLID FUEL APPLIANCE (WOOD
roof surface with a listed cap or from the vertical is considered
listed roof assembly. Gas vents 12 OR COAL). VENTING WITH A SOLID
horizontal. The total horizontal FUEL APPLIANCE CAN LEAD TO
inches in size or smaller with listed distance of a vent plus the horizontal
caps shall be permitted to be IMPROPER FUNCTIONING OF THE
vent connector serving draft-hood UNIT, AND DUE TO SOOTING, THE
terminated in accordance with equipped appliances shall not be
Figure 12, provided they are at least POSSIBILITY OF FIRE RESULTING
greater than 75 percent of the IN PROPERTY DAMAGE,
8 feet from a vertical wall or similar vertical height of the vent.
obstruction. All other gas vents shall PERSONAL INJURY OR DEATH.
terminate not less than 2 feet above NOTE: Refer to the National Fuel Gas
the highest point where they pass Code, ANSI Z223.1 and/or the Natural
through the roof and at least 2 feet Gas Installation Code, SPECIAL VENT SYSTEMS (SVS)
higher than any portion of a building CSA-B149.1 & .2. IMPORTANT: It is THE FURNACE
within 10 feet. Single appliance venting of a fan MANUFACTURER’s position now that
assisted furnace into a tile-lined new installations of any HTPV pipe
2. A type B-1 gas vent shall terminate
masonry chimney is prohibited. The used in a category III vent application,
at least 5 feet in vertical height including Selkirk’s Selvent™ II HTPV
above the highest connected chimney must be lined with either Type
B vent or with a listed, single wall, product, should cease immediately.
equipment draft hood or flue collar.
metal lining system. Reference
3. Must rise 1/4” per foot away from the National Fuel Gas Code, ANSI Z223.1
furnace on horizontal runs and be and/or the Natural Gas Installation
supported with straps or hangers so Code, CSA-B149.1 & .2. See Figure 13
it has no sags or dips. Supports at 4 for typical B-1 vent chase.
foot intervals and at all elbows are
recommended.
4. The vent connector must be
mechanically fastened to the outlet
collar of the furnace with at least (2)
sheet metal screws except vent
connectors that are B-1 material.
15
POWER VENT SYSTEMS EXISTING VENT SYSTEMS the common venting system are
located. Turn on clothes dryers and
When vertical venting is not possible, IMPORTANT RETROFIT any appliance not connected to the
the only acceptable method for VENTING INSTRUCTIONS common venting system. Turn on
horizontal venting is with the use of
If this furnace is a replacement any exhaust fans, such as range
Tjernlund model GPAK-1TR or Field
installation, ALWAYS INSPECT the hoods and bathroom exhausts, so
Controls models SWG-4R power
existing vent system to be sure there they will operate at maximum speed.
venter. Type B vent pipe and fittings
must be used. Common venting is not are no obstructions, blockages, or Do not operate a summer exhaust
permitted signs of corrosion. fan. Close fireplace dampers.

All application and installation When the existing furnace is removed 3. Follow the lighting instructions.
instructions supplied with the power from a venting system serving other Place the appliance being inspected
venter must be followed. appliances, the venting is likely to be into operation. Adjust the thermostat
too large to properly vent the remaining so the appliance will operate
Please address all questions regarding continuously.
power venter installation, agency attached appliances.
listings and furnace model compatibility 4. Test for spillage at the draft hood
The following steps shall be followed
to: relief opening after 5 minutes of
with each appliance that remains
main burner operation. Use the
Tjernlund Products, Inc. connected to the common venting
flame of a match or candle, or
(800) 255-4208 or (612) 426-2993 system, while the other appliances that smoke from a cigarette, cigar, or
remain connected to the common pipe.
Field Controls L.L.C. venting systems are not in operation.
(800) 742-8368 or (919) 522-0214 5. After it has been determined that
NOTE: When the vent table permits each appliance that remains
more than one diameter of pipe for a
CHIMNEY-FRIENDLY connector or vent, the smallest
connected to the common venting
system properly vents (when tested
ADAPTER SYSTEM permitted diameter must be used.1. as outlined above) return doors,
This furnace can be used with chimney Seal any unused openings in the windows, exhaust fans, fireplace
adapter RXGW-B01. common venting system. dampers and any other gas-burning
1. Visually inspect the venting system appliance to their previous
conditions of use.
for proper size and horizontal pitch
and determine that there is no 6. If improper venting is observed
blockage, restriction, leakage, during any of the above tests, the
corrosion or other deficiencies which common venting system must be
could cause an unsafe condition. resized. Refer to National Fuel Gas
Code, ANSI Z223.1 and/or the
2. Insofar as is practical, close all Natural Gas Installation Code,
building doors, windows and all CSA-B149.1 & .2.
doors between the space where the
appliances remaining connected to

FIGURE 13
DEDICATED VENTING THROUGH
CHIMNEY WITH “B-1” VENT

16
GAS SUPPLY AND PIPING
GAS SUPPLY FIGURE 14
GAS PIPING INSTALLATION
! WARNING GAS PIPE INSTALLATION
THIS FURNACE IS EQUIPPED AT GROMMET
THE FACTORY FOR USE ON (IN NORMAL POSITION)
NATURAL GAS ONLY. CONVERSION MANUAL GAS VALVE UPFLOW & DOWNFLOW
(IN CLOSED POSITION)
TO LP GAS REQUIRES A SPECIAL
KIT AVAILABLE FROM THE GAS VALVE
DISTRIBUTOR. FAILURE TO USE
THE PROPER CONVERSION KIT CAN
CAUSE FIRE, CARBON MONOXIDE 4 TO 5 FEET MANIFOLD
ABOVE FLOOR
POISONING, EXPLOSION, REQ'D BY SOME
PROPERTY DAMAGE, PERSONAL UTILITIES
INJURY OR DEATH.
See the conversion kit index supplied
with the furnace. This index identifies DRIP LEG DIRECT SPARK
the proper LP Gas Conversion Kit BURNERS IGNITOR
UNION
required for each particular furnace. FLAME SENSOR
IMPORTANT: Any additions, changes
or conversions required for the furnace
to satisfactorily meet the application
should be made by a qualified installer, HORIZONTAL
service agency or the gas supplier,
4 TO 5 FEET MANUAL GAS VALVE (IN CLOSED POSITION)
using factory-specified or approved ABOVE FLOOR DUCT GROMMET
parts. In the commonwealth of REQ'D BY SOME UNION (IN NORMAL
UTILITIES POSITION)
Massachusetts, installation must be
performed by a licensed plumber or gas
fitter for appropriate fuel.
IMPORTANT: Connect this furnace DRIP LEG
only to gas supplied by a commercial FLAME
utility. SENSOR

IMPORTANT: A U.L. recognized


fuel gas and CO detector(s) are
recommended in all applications, BURNERS
and their installation should be in
accordance with the detector
manufacturer’s recommendations
and/or local laws, rules, regulations or
DIRECT SPARK IGNITOR GAS VALVE
customs. MANIFOLD

GAS PIPING (SEE FIGURE 14) a piece of black pipe. If local codes IMPORTANT: When making gas pipe
allow the use of a flexible gas appliance connections, use a back-up wrench to
Install the gas piping according to all
local codes, state codes and regulations
connector, always use a new listed prevent any twisting of the control
of the utility company, whichever holds connector. Do not use a connector assembly and gas valve. Do not
jurisdiction. which has previously serviced another overtighten the connection.
gas appliance. Massachusetts law Any strains on the gas valve can
If possible, run a separate gas supply limits flexible gas connectors to a
line directly from the meter to the change the position of the gas orifices
maximum of 36”. in the burners. This can cause erratic
furnace. Consult the local gas company
for the location of the manual main shut- Install a ground joint union outside furnace operation.
off valve. The gas line and manual gas the cabinet to easily remove the IMPORTANT: ENSURE that the
valve must be adequate in size to control valve assembly. Install a furnace gas control valve not be
prevent undue pressure drop and manual shut-off valve in the gas line subjected to high gas line supply
never smaller than the pipe size to outside the furnace casing. The valve pressures.
the combination gas valve on the should be readily accessible to turn the
furnace. Refer to Table 2 for the recom- gas supply on or off. Install a drip leg in DISCONNECT the furnace and its
mended pipe size for natural gas and the gas supply line as close to the individual shut-off valve from the gas
Table 3 for LP gas pipe sizes. furnace as possible. Always use a pipe supply piping during any pressure
compound resistant to the action of testing that exceeds 1/2 PSIG
IMPORTANT: It is permissible to run
liquefied petroleum gases on all (3.48 kPa).
flexible gas connector inside the unit to
threaded connections.

17
GAS PRESSURE LP CONVERSION NOx MODELS
IMPORTANT: The maximum gas NOTE: For installation, see specific LP When converting furnaces equipped
supply pressure to the furnace should kit installation instructions. with NOx inserts to LP gas, remove the
be 10.5” w.c. for natural gas and 13” NOx insert assemblies. Steps for
The valve can be converted to use removal are listed below:
w.c. for LP gas. liquefied petroleum (LP) gas by
Natural gas supply pressure should replacing the pressure regulator spring 1. Turn off all electrical power and the
operate between 5" to 10.5” w.c. LP with the conversion kit spring. This LP gas supply to the furnace.
gas supply pressure should be 11” to kit spring allows the regulator to 2. Remove the burner door from the
13” w.c. This pressure must be maintain the proper adjusted manifold furnace.
maintained with all other gas-fired pressure for LP gas. The correct burner 3. Remove the igniter assembly –
appliances in operation. LP orifices are included in the kit. handle with care.
NOTE: Do not exceed a gas pressure NOTE: Order the correct LP conversion 4. Remove the two screws attaching
of 13” w.c. kit from the local distributor. Furnace the NOx insert retainer brackets to
conversion to LP gas must be the center panel. Pull the retainer
! CAUTION performed by a qualified technician. rod.
ELEVATIONS ABOVE 2000 FT
REQUIRE THAT THE FURNACE ! CAUTION 5. Put the two screws back into the
INPUT RATING BE ADJUSTED AND ELEVATIONS ABOVE 2000 FT holes in the center panel.
THAT THE SIZE OF THE BURNER REQUIRE THAT THE FURNACE 6. Re-install the igniter and burner
ORIFICES BE RE-CALCULATED INPUT RATING BE ADJUSTED AND assemblies.
BASED ON ELEVATION AND GAS THAT THE SIZE OF THE BURNER 7. Replace burner door.
HEATING VALUE. THE BURNER ORIFICES BE RE-CALCULATED
ORIFICES MAY (OR MAY NOT) NEED BASED ON ELEVATION AND GAS 8. Turn on electrical power and gas
TO BE CHANGED. SEE THE HEATING VALUE. THE BURNER supply to the unit.
SECTION TITLED “HIGH ALTITUDE ORIFICES MAY (OR MAY NOT) NEED NOTE: Some NOx models may have
INSTALLATIONS” OF THIS BOOK TO BE CHANGED. SEE THE one less NOx insert.
FOR INSTRUCTIONS. SECTION TITLED “HIGH ALTITUDE
INSTALLATIONS” OF THIS BOOK
! WARNING FOR INSTRUCTIONS.
NEVER PURGE A GAS LINE INTO
THE COMBUSTION CHAMBER.
NEVER USE MATCHES, FLAME OR
ANY IGNITION SOURCE FOR
CHECKING LEAKAGE. FAILURE TO
FOLLOW THIS WARNING CAN
CAUSE AN EXPLOSION OR FIRE
RESULTING IN PROPERTY
DAMAGE, PERSONAL INJURY OR
DEATH.
To check for gas leakage, use an
approved chloride-free soap and water
solution, an electronic combustible gas
detector, or other approved method.

18
SETTING GAS PRESSURE FIGURE 15
The maximum gas supply pressure to TYPICAL HOSE CONNECTION TO LINE PRESSURE TAP
the furnace should be 10.5” w.c.
natural gas, or 13” w.c. LP gas. The
minimum supply gas pressure to the
gas valve should be 5" w.c. natural gas
or 11" w.c. LP gas. A properly
calibrated manometer is required for
accurate gas pressure measurements.
! CAUTION
ELEVATIONS ABOVE 2000 FT
REQUIRE THAT THE FURNACE
INPUT RATING BE ADJUSTED AND
THAT THE SIZE OF THE BURNER
ORIFICES BE RE-CALCULATED
BASED ON ELEVATION AND GAS
HEATING VALUE. THE BURNER
ORIFICES MAY (OR MAY NOT)
NEED TO BE CHANGED. SEE THE
SECTION TITLED “HIGH ALTITUDE
INSTALLATIONS” OF THIS BOOK
FOR INSTRUCTIONS.
Supply Gas Pressure Measurement.
A line pressure tap is on the inlet side
of the gas valve.
1. With gas shut off to the furnace at
the manual gas valve outside the
unit, remove the input pressure tap
plug.
TABLE 2
2. Connect a U-Tube manometer to NATURAL GAS PIPE CAPACITY TABLE (CU. FT./HR.)
the pressure tap. See Figure 15.
Capacity of gas pipe of different diameters and lengths in cu. ft. per hr. with pressure drop of 0.3 in. and specific
3. Turn on the gas supply and gravity of 0.60 (natural gas).
operate the furnace and all other Nominal Length of Pipe, Feet
gas-fired units on the same gas Iron Pipe
line as the furnace. Size, Inches 10 20 30 40 50 60 70 80
1/2 132 92 73 63 56 50 46 43
4. Adjust the line gas pressure to 3/4 278 190 152 130 115 105 96 90
supply: 1 520 350 285 245 215 195 180 170
1-1/4 1,050 730 590 500 440 400 370 350
A. 5” - 10.5” w.c. for natural gas. 1-1/2 1,600 1,100 890 760 670 610 560 530
B. 11” - 13” w.c. for LP gas. After the length of pipe has been determined, select the pipe size which will provide the minimum cubic feet per hour
required for the gas input rating of the furnace. By formula:
5. Shut off the gas at the manual gas Gas Input of Furnace (BTU/HR)
valve and remove the Cu. Ft. Per Hr. Required =
Heating Value of Gas (BTU/FT3)
U-Tube manometer. The gas input of the furnace is marked on the furnace rating plate. The heating value of the gas (BTU/FT3) may be
6. Replace the pressure tap plug determined by consulting the local natural gas utility or the LP gas supplier.
before turning on the gas.
NATURAL GAS:
If the supply gas line pressure is above TABLE 3
the operating range, install an in-line LP GAS PIPE CAPACITY TABLE (CU. FT./HR.)
gas regulator to the furnace. If supply
gas line pressure is below the Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water
column inlet pressure).
operating range, either remove any
(Based on a Pressure Drop of 0.5 Inch Water Column)
restrictions in the gas supply piping or
enlarge the gas pipe. See Table 2. Nominal Length of Pipe, Feet
Iron Pipe
LP GAS:
Size, Inches 10 20 30 40 50 60 70 80 90 100 125 150
If the supply gas line pressure is above
the operating range, have the LP 1/2 275 189 152 129 114 103 96 89 83 78 69 63
supplier reduce the line pressure at the 3/4 567 393 315 267 237 217 196 182 173 162 146 132
regulator. If supply gas line pressure is 1 1,071 732 590 504 448 409 378 346 322 307 275 252
below operating range, have the LP 1-1/4 2,205 1,496 1,212 1,039 913 834 771 724 677 630 567 511
supplier adjust the line pressure at the 1-1/2 3,307 2,299 1,858 1,559 1,417 1,275 1,181 1,086 1,023 976 866 787
regulator. See Table 3.
2 6,221 4,331 3,465 2,992 2,646 2,394 2,205 2,047 1,921 1,811 1,606 1,496
NOTE: Depending on the amount of LP
vapor and the outdoor ambient Example (LP): Input BTU requirement of unit, 150,000
temperature, the LP storage tank may Equivalent length of pipe, 60 ft. = 3/4" IPS required.
require supplemental heat to maintain
proper pressure levels. Ensure LP
storage tank does not drop below 15%
capacity during heating season.

19
ADJUSTING OR CHECKING LP GAS:
Furnaces for use on LP gas, the LP gas
Check of input is important to prevent
over firing of the furnace beyond its
FURNACE INPUT supply pressure must be set between design-rated input. NEVER SET INPUT
11.0” and 13.0” W.C. by means of the ABOVE THAT SHOWN ON THE
! CAUTION tank or branch supply regulators. The RATING PLATE.
ELEVATIONS ABOVE 2000 FT furnace manifold pressure should be set TO CHECK FURNACE INPUT:
REQUIRE THAT THE FURNACE at 10” W.C. at the gas control valve. For
INPUT RATE BE ADJUSTED AND elevations up to 8,000 feet, rating plate 1. Make certain that all other gas
THAT THE SIZE OF THE BURNER input ratings apply. For high altitudes appliances are shut off, with the
ORIFICES BE RE-CALCULATED (elevations 8,000 and over) and for any exception of pilot burners.
BASED ON ELEVATION AND GAS necessary major changes in the gas 2. Start the furnace
HEATING VALUE. THE BURNER flow rate the orifice spud must be
changed. 3. Time the meter to measure the time
ORIFICES MAY (OR MAY NOT) NEED
required to burn one cubic foot of
TO BE CHANGED. SEE THE SECTION TO CHANGE ORIFICE SPUDS: gas.
TITLED “HIGH ALTITUDE
INSTALLATIONS” OF THIS BOOK 1. Shut off the manual main gas valve 4. Use Table 4 to determine input rate.
FOR INSTRUCTIONS. and remove the gas manifold.
NATURAL GAS: 2. Replace the orifice spuds.
The maximum gas supply pressure to 3. Reassemble in reverse order.
the furnace should be 10.5” W.C. for
4. Turn the gas supply back on and
natural gas. The minimum gas supply
check for leaks.
pressure for purposes of input
adjustment to the furnace should be 5” 5. Check for proper operation and
W.C. manifold pressure.
A properly calibrated manometer or
gauge is required for accurate gas
pressure readings.
The manifold pressure should be set at
3.5” W.C. for natural gas. Only small
variations in the gas flow should be
made by means of the pressure
regulator adjustment. TABLE 4
To adjust the pressure regulator: METER TIME IN MINUTES AND SECONDS FOR NORMAL
INPUT RATING OF FURNACES EQUIPPED FOR NATURAL OR LP GAS
1. Remove the regulator cap.
METER HEATING VALUE OF GAS BTU PER CU. FT.
2. Turn the adjustment screw clockwise INPUT
SIZE 900 1000 1040 1100 2500
BTU/HR
to increase pressure or CU. FT. MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC.
counterclockwise to decrease ONE 1 5 1 12 1 15 1 18 3 20
50,000
pressure. TEN 10 50 12 00 12 30 13 12 30 00
3. Replace the regulator cap securely. 75,000 ONE 0 44 0 48 0 50 0 53 2 0
TEN 7 12 8 0 8 19 8 48 20 0

100,000 ONE 0 33 0 36 0 38 0 40 1 30
TEN 5 24 6 0 6 15 6 36 15 0

125,000 ONE 0 26 0 29 0 30 0 32 1 12
TEN 4 19 4 48 5 0 5 17 12 0

150,000 ONE 0 31 0 24 0 25 0 26 1 0
TEN 3 36 4 0 4 10 4 20 10 0
Heating Value of Gas (BTU/Ft3) x 3600 x correction factor
Input BTU/HR =
Time in Seconds (for 1 cu.ft.) of Gas

20
ELECTRICAL WIRING FIGURE 16
ISOLATION RELAY

! WARNING
TURN OFF ELECTRIC POWER AT
THE FUSE BOX OR SERVICE PANEL
BEFORE MAKING ANY
ELECTRICAL CONNECTIONS.

TWIN Y
ALSO, THE GROUND CONNECTION
MUST BE COMPLETED BEFORE
MAKING LINE VOLTAGE
CONNECTIONS. FAILURE TO DO

G
SO CAN RESULT IN ELECTRICAL
SHOCK, SEVERE PERSONAL

R W2 W 1 C
INJURY OR DEATH.
IMPORTANT: The furnace must be
installed so that the electrical
components are protected from water
due to improper flue installation or
evaporator condensate drain run-off,
etc.
ELECTRICAL CONNECTIONS
! WARNING ST-A0804-01

THE CABINET MUST BE


PERMANENTLY GROUNDED. A
GROUND SCREW IS PROVIDED IN
THE JUNCTION BOX FOR THIS THERMOSTAT
PURPOSE. FAILURE TO DO SO CAN
RESULT IN FIRE, ELECTRICAL The room thermostat must be drafts, concealed hot or cold water
SHOCK, PERSONAL INJURY OR compatible with the integrated furnace pipes, lighting fixtures, radiation from
DEATH. control on the furnace. Generally, all fireplace, rays of sun, lamps, television,
The electrical supply requirements are thermostats that are not of the “current radios or air streams from registers.
listed on the furnace rating plate. robbing” type are compatible with the Refer to the instructions packed with
integrated furnace control used. the thermostat for best anticipator
Use a separate fused branch electrical adjustment or selection or see below.
circuit containing a properly sized fuse NOTE: An isolation relay (part number
or circuit breaker. Run this circuit 42-25104-01) may assist with “current HEAT ANTICIPATOR SETTINGS
directly from the main switch box to an robbing” type thermostat compatibility For adjusting the thermostat heat
electrical disconnect which must be problems. Use a single-pole, single- anticipator setting; (a) add the current
readily accessible and located within throw relay with a 24-volt AC coil. The draw of the various components in the
sight of the furnace. Connect from the contacts should be rated for .5 amps system or (b) using jumper wire,
disconnect to the junction box on the minimum at 24 volts. See Figure 16.
left side of the furnace, inside the measure the current flow between the
control compartment. See appropriate Install the room thermostat in R and W thermostat circuits. Set the
wiring diagram. accordance with the instruction sheet thermostat heat anticipator according
in the box with the thermostat. Run the to the current flow measured.
NOTE: The electrical junction box thermostat lead wires inside the control
inside the furnace control compartment compartment. Connect the thermostat
may be relocated to the right side if as shown on the wiring diagram. Never
necessary. A knockout is provided.
install the thermostat on an outside
NOTE: L1 (hot) and neutral polarity wall or where it will be influenced by
must be observed when making field
connections to the furnace. The
ignition control on electric ignition
models will not sense flame if L1 and
neutral are reversed.
Installation of the electric supply line TABLE 5
should be in accordance with the FIELD WIRE SIZE FOR 24 VOLT CONTROL CIRCUITS
National Electric Code ANSI/NFPA No. SOLID COPPER WIRE - AWG
70, latest edition, or Canadian
Electrical Code Part 1 - CSA Standard 3.0 16 14 12
THERMOSTAT
LOAD - AMPS

C22.1 and local building codes. 2.5 16 14 12

This can be obtained from: 2.0 18 16 14


50 100 150
National Fire Protection Association
Batterymarch Park LENGTH OF RUN - FEET ➀
Quincy, MA 02269 ➀ Wire length equals twice the run distance
Canadian Standards Association NOTE: Do not use 24 volt control wiring smaller than No. 18.
178 Rexdale Blvd.
Etobicoke (Toronto), Ontario
Canada M9W, 1R3

21
boards must be in phase with each
FIGURE 17 other.
LINE VOLTAGE CONNECTIONS
UTEC 1095-101 CONTROL BOARD b. Control board “ONE” is on the
furnace connected to the thermostat.
c. Connect the “W”, “W2”, “C” and
“TWIN” terminals from one control to
the “W”, “W2”, “C” and “TWIN”
terminals of the second control
respectively.
d. Both control boards must have
“Twin” switch #3 in “ON” position.
(MAY BE CAPPED) ST-A0761-01
e. Adjust the heat anticipator current to
0.15 amps.
NOTE: Leave Switch #4 in the “OFF”
position. It does not affect the
FIELD INSTALLED OPTION FURNACE TWINNING twinning operation.
ACCESSORIES INSTALLATIONS
ELECTRONIC AIR CLEANER NOTE: Limit of two furnaces per
Electronic air cleaner line voltage thermostat.
power can be supplied from the screw IMPORTANT: No more than two
terminal “EAC” and a line voltage furnaces can share the same supply
neutral screw terminal on the control and return. Furnaces must have same
board. Power is on any time the blower heating and blower capacity. Twinning
is activated. See Figure 17. furnaces must operate off the same
phase of power.
HUMIDIFIER
Twinning operation of two furnaces,
Humidifier line voltage power can be
installed side-by-side, connected by a
supplied from screw terminal “HUM” to common duct system with main power
a line voltage neutral screw terminal on supplied by the same source, and
the control board. See Figure 17. This controlled by a common thermostat can
will power the humidifier whenever the be done with the UTEC 1095-101
inducer is operating in the heating integrated control boards.
mode. The Status LED will flash 5 times if the
NOTE: There is no “HUM” terminal on twinning is not set up properly.
GPP models. Single Stage Thermostat
NOTE: Maximum current –1.0 amps (See Figure 17)
for each option. a. Control board “ONE” is on furnace
connected to the thermostat.
FOSSIL FUEL KIT
Refer to specification sheet for b. The 24 VAC supply to both control
approved fossil fuel kit number. boards must be in phase with each
other.
c. Connect the “W2”, “C” and “TWIN”
RXGW-B01 CHIMNEY terminals to counterparts on each
ADAPTER control.
IMPORTANT: CHIMNEY ADAPTER d. Both control boards must have
IS CERTIFIED FOR USE ON switch #3 in “ON” position.
UPFLOW (-GPN AND -GPP) ONLY. e. Adjust the heat anticipator current to
0.15 amps.
This appliance is CSA certified for use
with RXGW-B01 Chimney Adapter. Two Stage Thermostat
Refer to Kit Installation Instructions (See Figure 18)
92-101682-01. a. The 24 VAC supply to both control

22
FIGURE 18
UT ELECTRONIC CONTROLS NO. 1095-100 CONTROL BOARD
TWINNING CONNECTION SINGLE STAGE OPERATION

I685

23
FIGURE 19
UT ELECTRONIC CONTROLS NO. 1095-100 CONTROL BOARD
TWINNING CONNECTION TWO STAGE OPERATION

I684

24
80+ HIGH ALTITUDE Orifice required at 5000 ft. elevation
(4% de-rate per thousand ft.): #45
The recommended LP Gas high
altitude orifice selections differ slightly
INSTRUCTIONS Orifice required at 8000 ft elevation (4% in that the NFGC LP orifice chart, as
(TABLES 6 & 9) de-rate per thousand ft): #47 they are not accurate for Rheem
products. The National Fuel Gas Code
! CAUTION LP orifices are based on an 11" of
THE NATIONAL FUEL GAS CODE
LP GAS (TABLE 7) water column pressure at the orifice,
(NFGC) GUIDELINES SHOULD BE NOTE: Keep any parts removed during which differs from products that use 10"
FOLLOWED WHEN CONVERTING LP conversion procedure stored with of water column at the orifice. This
THESE FURNACES FOR HIGH the product literature for future use. difference requires a deviation from the
ALTITUDE OPERATION. NFGC orifice size recommendations.
LP Gas is a manufactured gas that has
The Sea Level input should still be
34" 80 Plus furnaces installed above consistent heating value across most
reduced by 4% per thousand ft. and the
2,000 ft. require the furnace to be de- regions.
orifice size must be selected based on
rated 4% per thousand feet. The NFGC guidelines are used with the the reduced input in Table 7.
IMPORTANT: Factory installed orifices following exception:
are calculated and sized based on a sea
level Natural Gas heating value of 1075
BTU per cubic ft.
TABLE 6
NOTE: Orifices are available through
your local distributor. Natural Gas Orifice Drill Size (4% per 1000 ft. De-Rate)
IMPORTANT: 80+ Models only. Do not use this chart for any 90+ Models.
Reference Tables 6 and 9 for
appropriate orifice sizing. Burner Input (per burner) 25,000 BTU @ Sea Level
The following are examples of orifice Annual Avg. Heat Sea level 2000 to 3000 to 4000 to 5000 to 6000 to 7000 to 8000 to
Value (btu per ft3) to 1999 ft 2999 ft 3999 ft 4999 ft 5999 ft 5999 ft 7999 ft 8999 ft
sizing using the National Fuel Gas Code
Appendix F: 850 38 39 40 41 41 42 42 43
900 40 41 42 42 42 43 43 44
For a simplified estimation of orifice size
based on gas heating value and 975 41 42 42 42 43 43 44 44
elevation, Tables 6 and 9 may be used. 1075 42 42 43 43 43 44 44 45
However, calculations are the best 1170 43 44 44 44 45 45 46 47
method.
Example: 900 BTU/ft3 Regional
Natural Gas Heating Value
I/H = Q TABLE 7
LP GAS
25000 / 900 = 27.78 ft3 IMPORTANT: 80+ MODELS ONLY! DO NOT
USE THIS CHART WITH ANY 90+ MODELS.
I = Sea Level input (per burner): 25000
H = Sea Level Heating Value: 900 Input (per Orifice
Q = 27.78 ft3 Natural Gas per hour. Altitude burner) 25000 Size
0 to 2000 ft. 25000 #54
From Table F.1 of National Fuel Gas
Code Handbook, 2002 (3.5 w.c. 2000-3000 24000 #54
column). 3000-4000 23000 #54
Orifice required at Sea Level: #40 4000-5000 22000 #54
5000-6000 21000 #54
From Table F.4 of National Fuel Gas
Code Handbook, 2002 6000-7000 20000 #54
Orifice required at 5000 ft. elevation (4% 7000-8000 19000 #55
de-rate per thousand ft): #42 8000-9000 18000 #55
Orifice required at 8000 ft. elevation (4% 9000-10000 17000 #55
de-rate per thousand ft.): #44
Example: 1050 BTU/ft3 Regional
Natural Gas Heating Value
FIGURE 20
I/H=Q MANIFOLD PRESSURE-CHANGE LABEL
25000 / 1050 = 23.81ft3
THE MANIFOLD PRESSURE OF THIS APPLIANCE HAS
I = Sea Level input (per burner): 25000 BEEN FIELD ADJUSTED TO OBTAIN THE CORRECT
H = Sea Level Heating Value: 1050 INPUT RATING FOR INSTALLATION AT ALTITUDES
Q = 23.81 ft3 Natural Gas per hour. BETWEEN 2,000 FEET AND 4,500 FEET ELEVATION.
From Table F.1 of Natural Fuel Gas
Code Handbook, 2002 (3.5 w.c. LA PRESSION DU DISTRIBUTEUR D'ALIMENTATION
column). DE CET APPAREIL A ÉTÉ AJUSTÉ SUR LES LIEUX AFIN
D'OBTENIR LA BONNE PUISSANCE D'ENTRÉE POUR
Orifice required at Sea Level: #43
UNE INSTALLATION ENTRE 2000 ET 4500 PIEDS
From Table F.4 of National Fuel Gas D'ALTITUDE.
Code Handbook, 2002 92-24399-01-01

25
ORIFICE ORDERING ALTERNATE METHOD FOR
INFORMATION CANADIAN HIGH-ALTITUDE
Orifice sizes are selected by adding the DERATE
2-digit drill size required in the orifice
In Canada, unless an orifice change is
part number. Drill sizes available are 39 specifically mandated by local codes,
through 64; metric sizes available an alternate method of altitude deration
1.10mm (-90) and 1.15mm (-91): through a reduction in manifold
Orifice Part Number 62-22175-(drill size) pressure is acceptable as described in
Table 8. This information is based on a
Example 1: heating value of 1000 BTU per cubic
# 60 drill size orifice required feet of natural gas, and 2500 BTU per
Part # 62-22175-60 cubic feet of LP gas.
Example 2: IMPORTANT: Actual input rates must
1.15mm drill size orifice required be measured onsite with manifold
Part # 62-22175-91 pressure adjustment to ensure that an
actual 10% reduction in input rate is
achieved.
Once this field adjustment has been
made, the label shown in Figure 20
must be affixed in a conspicuous
location on the front of the furnace
cabinet.
NOTE: This label is supplied in the
information packet shipped with each
furnace.

TABLE 8
ALTERNATE METHOD FOR CANADIAN HIGH-ALTITUDE DERATE
IMPORTANT: 80+ MODELS ONLY! DO NOT USE THIS CHART WITH ANY 90+ MODELS.
NATURAL GAS LP GAS
ORIFICE MANIFOLD ORIFICE MANIFOLD
ALTITUDE INPUT OUTPUT ALTITUDE INPUT OUTPUT
SIZE PRESSURE SIZE PRESSURE

50,000 40,000 50,000 40,000


75,000 60,000 75,000 60,000
0’ - 2000’ 100,000 80,000 #42 3.5” W.C. 0’ - 2000’ 100,000 80,000 #54 10” W.C.
125,000 100,000 125,000 100,000
150,000 120,000 150,000 120,000

45,000 36,000 45,000 36,000


67,500 54,000 67,500 54,000
2001’ - 4500’ 90,000 72,000 #42 2.9” W.C. 2001’ - 4500’ 90,000 72,000 #54 8.1” W.C.
112,500 90,000 112,500 90,000
135,000 108,000 135,000 108,000

26
TABLE 9
SUPPLEMENTAL ORIFICE SIZE CHART

80 Plus Models only with 25,000 Btu's per Burner. Do not use this chart for any 90+ models.
NATURAL GAS QUICK REFERENCE CHART FOR ORIFICE SELECTION, AT 3.5" W.C. AND APPROXIMATE FINAL FIRING RATES
Sea Level 80 Plus ELEVATION CHART (NFG recommended orifice based on 4% derate for each 1000 foot of elevation, based on the intersection of the
Sea Level Cubic Heat orifice required at Sea Level and the elevation required below)
Orifice Foot at Value at
Size 3.5" W.C. 25,000 0-999 1000-1999 2000-2999 3000-3999 4000-4999 5000-5999 6000-6999 7000-7999 8000-8999 9000-9999
37 30.63 816 37 37 38 39 39 40 41 42 42 43
38 29.25 855 38 38 39 40 41 41 42 42 43 43
39 28.2 887 39 39 40 41 41 42 42 43 43 44
40 27.03 925 40 40 41 42 42 42 43 43 44 44
41 25.98 962 41 41 42 42 42 43 43 44 44 45
42 24.95 1002 42 42 42 43 43 43 44 44 45 46
43 22.39 1117 43 43 44 44 44 45 45 46 47 47
44 21.01 1190 44 44 45 45 45 46 47 47 48 48
Final Firing Rate per Burner 25,000 24,000 23,000 22,000 21,000 20,000 19,000 18,000 17,000 16,000

All calculations are performed by using the first three columns of information only. Before beginning any calculations, determine the individual burner Btu size
and heating value at Sea Level for the installation site. Each value shown in the Heat Value column is per burner at 3.5" W.C.

NOTE:
Heat Value at Sea Level, for the location of the installation, is available from the Natural Gas Supplier to that site. Orifices for all altitudes are based on Sea Level values.

Divide the individual burner capacity (25,000 for 80 plus) by the Heat Value for the site to determine the Cubic Foot value at Sea Level, or divide burner capacity by the Cubic
Foot value for the Heat Value. Once you have either the Cubic Foot Value or the Heat Value you can estimate the Sea Level orifice for the site. To select the corresponding
high altitude orifice, locate the site elevation on the chart above and the orifice required at Sea Level from your calculation in the first column. The correct high
altitude orifice that must be installed in each individual burner is the intersection of these two points on the chart above.

27
START-UP PROCEDURE
DIRECT SPARK IGNITION seconds), and then changes to low
speed. After a 30 second pre-purge,
gas valve is de-energized, the draft
inducer continues to run, and control
LIGHTING INSTRUCTIONS the spark ignitor energizes and the begins timing the inter-purge delay.
This appliance is equipped with a direct low stage of the gas valve opens, The indoor blower motor will be
spark ignition device. This device lights lighting the burners. energized and/or remain energized
the main burners each time the room d. After the gas valve opens, the on low speed for low fire and heat
thermostat (closes) calls for heat. See remote flame sensor must prove speed for high fire for the selected
lighting instructions on the furnace. ignition for one second using the delay off time.
process of flame rectification. If the When the inter-purge delay is over,
TO START FURNACE burners do not light, the system the control initiates another ignition
goes through another ignition trial period. The control will recycle
! WARNING sequence. It does this up to 4 times. up to 5 flame losses (4 re-cycles)
(2 tries on low fire and 2 tries on within a single call for heat before
1. BE SURE THAT THE MANUAL high fire.) going into lockout.
GAS CONTROL HAS BEEN IN THE
“OFF” POSITION FOR AT LEAST e. The main blower starts on low Sequence of operation with two
FIVE MINUTES. DO NOT speed 30 seconds after the burners stage thermostat
ATTEMPT TO MANUALLY LIGHT light. The furnace operates on low Connect W1 and W2 terminals on the
THE MAIN BURNERS. FAILURE fire for 12 minutes and then, if the thermostat to W and W2 terminals on
TO FOLLOW THIS WARNING CAN thermostat is not satisfied, shifts to the control board.
CAUSE A FIRE OR AN high fire, causing the draft inducer to
EXPLOSION RESULTING IN go to high speed, the gas valve to Call for 1st stage heat
PROPERTY DAMAGE, PERSONAL 100% and the main blower goes to a. R and W thermostat contacts close
INJURY OR DEATH. heat speed. and the control module runs a self-
2. Set the room thermostat to the f. When the thermostat cycle ends, the check routine. After the control
lowest setting. gas valve closes, and the burners module verifies that both sets of
go out. pressure switch contacts are open,
3. Turn the gas control knob to the the induced draft motor starts on
“On” position, or move the gas g. The draft inducer will continue high until the low pressure switch
control lever to the “On” position. running for a 10 second (low speed) contacts close (a maximum of 60
or 5 second (high speed) post seconds), then changes to low
4. Replace the control access door. purge. speed.
5. Turn on the electrical power. h. The main blower will run for 90 b. After a 30 second pre-purge the
6. Set the room thermostat to a point seconds on high speed or 120 spark igniter energizes and the gas
above room temperature to light the seconds on low speed. (This timing valve (low stage) opens, lighting the
main burners. After the burners are is field adjustable, for 60, 90, 120 or burners.
lit, set room thermostat to a desired 150 seconds). See Figure 20 for
temperature. switch settings. c. After the burners light, the remote
flame sensor must prove ignition. If
TO SHUT DOWN FURNACE Sequence if the system doesn’t light the burners do not light, the system
or doesn’t sense flame: goes through another ignition
1. Set the room thermostat to its lowest
setting. a. If flame is not sensed within 8 sequence. It does this up to 4 times
seconds after the gas valve opens, (2 tries on low fire and 2 tries on
2. Shut off the gas to main burners by the valve closes and the ignitor is high fire).
turning the gas control knob to the de-energized. The induced draft
“Off” position, or by depressing the d. The main blower starts on low
motor will run for 60 seconds on low, speed 30 seconds after the gas
gas control lever and moving it to stop momentarily, and then restart.
the “Off” position. valve opens. The furnace continues
b. The ignition process goes through to run on low until the call for heat is
! WARNING one more try on low fire. If this fails, satisfied or the 2nd stage contacts
there are two tries on high fire with a close. If the 1st stage call for heat is
SHOULD OVERHEATING OCCUR 30 second interpurge between trials. satisfied the gas valve closes and
OR THE GAS SUPPLY FAIL TO During high fire ignition attempts, the induced draft motor continues
SHUT OFF, SHUT OFF THE MANUAL the inducer steps to high speed, the running for a 10 second post purge
GAS VALVE TO THE APPLIANCE high pressure switch closes (both time. the main blower runs for 120
BEFORE SHUTTING OFF THE pressure switch closes (both seconds (this timing is field
ELECTRICAL SUPPLY. FAILURE TO pressure switches are now closed), adjustable). See Figure 20 for switch
DO SO CAN CAUSE AN EXPLOSION and the gas valve steps to 100%. settings.
OR FIRE RESULTING IN PROPERTY
DAMAGE, PERSONAL INJURY OR c. If there is no ignition after the 2nd Call for 2nd stage heat after 1st
DEATH. trial on high fire, the furnace goes stage
into soft lockout for one hour. R and W2 thermostat contacts close,
Sequence of operation with a single
stage thermostat d. The sequence repeats after a one calling for 2 stage heat. The induced
hour delay and continues repeating draft motor then switches to high
a. Connect the “W” terminal on the until ignition is successful or the call speed and the high pressure switch
thermostat to the W2 terminal on the for heat is terminated. contacts will close. The gas valve to
control board. switches to high fire and the main
e. To reset the lockout, make and
b. When there is a call for heat, the “R” break power either at the thermostat blower to switch to heating speed.
and “W2” contacts close and the IFC or at the unit disconnect switch for 5 2nd stage heat satisfied, 1st stage
runs a self check routine to verify to 10 seconds. The furnace will then heat still required.
that the pressure switch contacts are go through another set of trials for
open. The limit switch contacts are R and W2 thermostat contacts open.
ignition. The induced draft motor switches to
constantly monitored.
f. If flame is established and low speed, the main blower motor
c. The induced draft motor starts on maintained during the trial for switches to low speed and the gas
high until the low pressure switch ignition period and flame is lost, the valve changes to low fire. The furnace
contacts close (a maximum of 60

28
continues to run in this mode until the seconds after the thermostat is maintain the proper rise range.
1st stage heat call is satisfied. The satisfied in cooling. This timing can be Reconnect the unused lead to the M1
system will shut down as noted in “c,” field adjusted. To change the blower off or M2 terminal. Check motor lead for
under 1st stage call for heat. timing, set DIP switches 1 and 2 as speed designation. Do not reduce the
shown in Figure 20. heating speeds where it could cause
FAN CONTROL GAS FURNACE (DIRECT
the furnace air temperature rise to
exceed the maximum outlet air
The furnace is equipped with an
integrated furnace control which DRIVE) INSTRUCTIONS FOR temperatures specified for the unit.
automatically starts the main blower 30 CHANGING BLOWER SPEED IMPORTANT: Always check air
seconds after the gas valve opens. It temperature rise after changing the
stops the main blower a set time after heating speed for any reason.
! WARNING
the heat call ends. The off timing is It is recommended to use the next
controlled by the first two dip switches DISCONNECT THE ELECTRICAL higher blower speed tap, if the main
on the control board. See Figure 20. SUPPLY TO THE FURNACE BEFORE limit tripped at a premature condition.
ATTEMPTING TO CHANGE THE
The blower runs on low speed when the BLOWER SPEED. FAILURE TO DO
furnace is in the low fire mode and on
the HEAT speed in the high fire mode.
SO CAN CAUSE ELECTRICAL
SHOCK RESULTING IN SEVERE
ADJUSTING OR CHECKING
The integrated control board also PERSONAL INJURY OR DEATH. FURNACE INPUT
contains the low voltage terminals for The blower motor is wired for blower The maximum gas supply pressure to
the thermostat connection, and is speeds required for normal operation. the furnace should be 10.5 W.C. for
located in the blower compartment. The LOW speed, which is for the low natural gas. The minimum gas supply
fire operation should never be pressure for purposes of input
SETTING BLOWER TIMINGS increased. The HEAT speed is factory adjustment to the furnace should be 5
The control board has six quick connect wired for the regular high fire speed. W.C.
terminals for connecting motor speed This may be changed if required to
leads. These are:
1. LOW – This is low speed. The
motor runs on low when the furnace FIGURE 22
TYPICAL GAS VALVE
is in the low fire mode or when the
thermostat is in the “FAN” position.
2. COOL – Factory wired at high
speed. This may be changed if a
lower cooling speed is desired.
3. HEAT – Factory wired at the normal
high input blower speed. HIGH FIRE
MANIFOLD
4. HEAT/COOL – Connect here if the PRESSURE
required HEAT and COOL speeds ADJUSTMENT
are the same. INLET
PRESSURE OUTLET
IMPORTANT: Do not connect any TAP PRESSURE
TAP
leads to the HEAT or COOL terminals if
the HEAT/COOL terminal is used.
5. M1 – Connect unused motor lead. LOW FIRE
PRESSURE
6. M2 – Connect unused motor lead. MANIFOLD
ADJUSTMENT
The unit comes from the factory set to
stop the blower 120 seconds after the
thermostat is satisfied in heating and 45 TABLE 8
METER TIME IN MINUTES AND SECONDS FOR NORMAL
INPUT RATING OF FURNACES EQUIPPED FOR NATURAL
FIGURE 21 OR LP GAS
BLOWER OFF TIMINGS
METER HEATING VALUE OF GAS BTU PER CU. FT.
UTEC 1095 - 101 CONTROL BOARD INPUT
SIZE 900 1000 1040 1100 2500
BTU/HR
TWIN

CU. FT. MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC. MIN. SEC.
ICM

ONE 1 5 1 12 1 15 1 18 3 20
50,000
ON TEN 10 50 12 00 12 30 13 12 30 00
ONE 0 44 0 48 0 50 0 53 2 0
75,000 TEN 7 12 8 0 8 19 8 48 20 0
NOTE: SWITCH NO. 3 IS FOR
A076201 ONE 0 33 0 36 0 38 0 40 1 30
TWINNING APPLICATIONS 100,000 TEN 5 24 6 0 6 15 6 36 15 0
(NORMAL (ICM ONE 0 26 0 29 0 30 0 32 1 12
125,000
MODE) MODE) TEN 4 19 4 48 5 0 5 17 12 0
SW4 SW4
LOW HIGH OFF ON ONE 0 31 0 24 0 25 0 26 1 0
SW1 SW2 HEAT HEAT COOL COOL 150,000 TEN 3 36 4 0 4 10 4 20 10 0
*OFF OFF 110 80 40 30
OFF ON 80 50 30 0 Heating Value of Gas (BTU/Ft3) x 3600 x correction factor
ON OFF 150 120 60 20 Input BTU/HR =
ON ON 170 140 90 50 Time in Seconds (for 1 cu.ft.) of Gas
*FACTORY SETTING

29
A properly calibrated manometer or NOTE: Use a 3/32 allen wrench for Check of input is important to prevent
gauge is required for accurate gas making the pressure adjustment. over firing of the furnace beyond its
pressure readings. design-rated input. NEVER SET
On furnaces using LP gas, the LP gas
1. When adjusting the furnace input, supply pressure must be set between INPUT ABOVE THAT SHOWN ON
the high fire input should be 11.0 and 13.0 W.C. by means of the THE RATING PLATE.
checked. The high fire manifold
tank or branch supply regulators. Set To check furnace input:
pressure should be 3.5’ W.C. Follow
these steps to be sure the furnace is the furnace manifold pressure at 10 1. Make certain that all other gas
high fire mode: W.C. at the gas control valve. appliances are shut off, with the
a. With a single stage thermostat, To change orifice spuds: exception of pilot burners.
the furnace runs for 12 minutes 1. Shut off the manual main gas valve 2. Start the furnace
on low fire before shifting to high and remove the gas supply piping
fire. To be certain that it is on high 3. Time the meter to measure the time
from the gas valve. required to burn one cubic foot of
fire, jump terminals “W” and “W2”
on the control board in the blower 2. Remove the four screws securing gas.
compartment. the manifold assembly and remove 4. Use Table 8 to determine input rate.
b. With a two stage thermostat, set the assembly.
the thermostat to its highest 3. Replace the orifice spuds.
setting to keep the furnace
operating in the high fire mode. 4. Reassemble in reverse order.
2. To adjust high fire manifold 5. Turn the gas supply back on and
pressure, remove the adjustment check for proper operation and
cover screw on the outlet end of the manifold pressure.
gas valve and turn the adjustment
screw clockwise to increase the
pressure and counterclockwise to
reduce the pressure. Replace the
cover screw securely. See Figure
21.
3. The low fire manifold pressure
should be 1.7 W.C. As mentioned
above, the furnace remains in the
low fire mode for 12 minutes upon a
heat call with a single stage
thermostat. With a two stage
thermostat, disconnect the
thermostat lead to the “W2” terminal
on the control board and the furnace
will remain in the low fire mode. To
adjust the pressure, remove the
regulator cover, on top of the valve,
and adjust as noted under Step 2,
above. After the adjustment replace
the screw cover securely.

30
AIR FLOW FIGURE 23
TEMPERATURE RISE MEASUREMENT
The importance of proper air flow over
the heat exchanger cannot be over
emphasized.
! CAUTION
IT IS IMPORTANT THAT EACH DUCT
SYSTEM BE SIZED AND INSTALLED
FOR THE SPECIFIC APPLICATION
BY PROPERLY APPLYING THE
APPROPRIATE INDUSTRY
ACCEPTED STANDARD. IF LESS
THAN MINIMUM STANDARDS ARE
APPLIED, THE EQUIPMENT USER
COULD EXPECT TO EXPERIENCE
HIGHER UTILITY BILLS, MAJOR
COMPONENT FAILURE, VARYING
DEGREES OF AIR NOISE OR OTHER
UNSATISFACTORY ISSUES, OVER
WHICH THE MANUFACTURER HAS
NO CONTROL.

TEMPERATURE RISE CHECK


To determine if the air flow is correct,
make a temperature rise check.
1. Insert a thermometer in the supply
air duct as close to the furnace as
possible yet out of a direct line
FIGURE 24
from the heat exchanger. See TYPICAL FURNACE NAME PLATE
Figure 22.
2. Insert a thermometer in the return
air duct as close to the furnace as
possible.
3. Operate the furnace.
4. When the thermometer in the
supply air duct stops rising
(approximately five minutes),
subtract the return air temperature
from the supply air temperature.
The difference is the temperature
rise.
5. Compare the measured
temperature rise to the approved
temperature rise range listed on
the furnace name plate. See
Figure 23.
If the measured temperature rise is
above the approved range, the air flow
is too low. More air must be moved by
speeding up the blower, by removing
restrictions in the duct system, or by
adding more supply or return air duct. If
the measured temperature rise is below
the approved range, the air flow is too
much. Use lower speed tap on the
multi-speed blower.
Ideally the measured temperature rise
should be in the middle of the range.
The rise range is the same for high and
low inputs.

31
BLOWER PERFORMANCE DATA – (-)GPQ UPFLOW/HORIZONTAL MODELS

CFM AIR DELIVERY


BLOWER M O T O R BLOWER EXTERNAL STATIC PRESSURE INCHES WATER COLUMN
MODEL (BTU)
SIZE H.P. SPEED
.1 .2 .3 .4 .5 .6 .7
L OW 675 655 635 610 585 555 520
50,000 11 x 6 1/2 MED-LO 950 930 905 880 860 830 800
M ED-HI 1115 1090 1070 1040 1015 985 945
HI 1270 1250 1225 1200 1165 1130 1085
LOW 921 897 872 845 818 795 746
75,000 11 x 7 1/2 MED-LO 1093 1066 1039 1008 977 941 905
MED-HI 1241 1212 1183 1150 1118 1076 1033
HI 1393 1359 1326 1293 1259 1214 1169
LOW 1245 1220 1195 1165 1135 1105 1065
75,000 11 x 7 3/4 MED-LO 1555 1515 1475 1435 1395 1350 1300
MED-HI 1810 1755 1705 1645 1585 1530 1470
HI 2050 1985 1915 1845 1785 1715 1655
LOW 925 890 865 835 810 775 745
100,000 11 x 7 1/2 MED-LO 1050 1040 1030 990 960 920 890
MED-HI 1220 1195 1160 1140 1105 1065 1020
HI 1360 1327 1295 1263 1231 1179 1128
LOW 1295 1275 1250 1225 1195 1165 1135
100,000 11 x 10 3/4 MED-LO 1645 1615 1580 1550 1510 1465 1425
MED-HI 2045 2000 1955 1905 1845 1785 1720
HI 2320 2260 2200 2130 2060 1985 1910
LOW 1280 1275 1265 1245 1215 1185 1145
125,000 11 x 10 3/4 MED-LO 1645 1635 1615 1590 1560 1520 1470
MED-HI 2050 2015 1960 1935 1885 1835 1775
HI 2365 2310 2250 2185 2115 2035 1950
LOW 1270 1250 1220 1195 1165 1135 1105
150,000 11 x 10 3/4 MED-LO 1620 1595 1570 1545 1515 1480 1440
MED-HI 2010 1985 1960 1915 1850 1800 1730
HI 2340 2275 2215 2145 2080 2010 1940
*NOT TO BE USED AS A HEATING SPEED! 92-23671-06-02

BLOWER PERFORMANCE DATA – (-)GLQ DOWNFLOW MODELS

CFM AIR DELIVERY


BLOWER M O T O R BLOWER EXTERNAL STATIC PRESSURE INCHES WATER COLUMN
MODEL (BTU)
SIZE H.P. SPEED
.1 .2 .3 .4 .5 .6 .7
L OW 655 630 600 565 532 500 467
50,000 11 x 6 1/2 MED-LO 975 943 915 886 852 813 770
M ED-HI 1180 1140 1105 1067 1027 980 924
HI 1335 1290 1250 1202 1157 1110 1060
LOW 910 887 863 839 814 776 738
75,000 11 x 7 1/2 MED-LO 1074 1054 1034 1007 979 944 908
MED-HI 1229 1207 1184 1159 1134 1099 1063
HI 1409 1385 1361 1329 1297 1260 1223
LOW 1180 1170 1153 1141 1125 1108 1083
75,000 11 x 7 3/4 MED-LO 1438 1420 1400 1380 1348 1320 1281
MED-HI 1730 1697 1660 1620 1575 1530 1480
HI 1842 1805 1761 1713 1664 1615 1560
LOW 895 874 852 825 798 766 734
100,000 11 x 7 1/2 MED-LO 1052 1033 1013 991 968 930 891
MED-HI 1238 1217 1196 1169 1143 1094 1044
HI 1383 1366 1348 1317 1286 1245 1203
LOW 1374 1356 1339 1323 1286 1249 1212
100,000 11 x 10 3/4 MED-LO 1709 1686 1663 1635 1607 1562 1516
MED-HI 2132 2085 2038 1988 1937 1882 1827
HI 2362 2300 2237 2173 2108 2036 1964
LOW 1315 1292 1269 1250 1231 1194 1157
125,000 11 x 10 3/4 MED-LO 1618 1597 1576 1552 1528 1486 1443
MED-HI 2065 2025 1984 1938 1891 1824 1756
HI 2275 2219 2163 2103 2042 1982 1921
LOW 1300 1280 1230 1205 1170 1115 1030
150,000 11 x 10 3/4 MED-LO 1675 1650 1620 1570 1545 1485 1425
MED-HI 2105 2075 2035 1990 1955 1900 1815
HI — 2340 2290 2215 2145 2080 1995
*NOT TO BE USED AS A HEATING SPEED! 92-23671-07-01

32
SAFETY FEATURES
LIMIT CONTROL FLAME ROLL-OUT PRESSURE SWITCH
The high limit cut-off temperature is set SAFETY SWITCHES This furnace is equipped with a
at the factory and cannot be adjusted. Furnaces are equipped with safety normally-open pressure switch that
The temperature setting prevents the switches to protect against flame roll- monitors pressure conditions within the
air temperature leaving the furnace out conditions in the burner furnace vent system during the heating
from exceeding the maximum outlet air compartment, which, if tripped, will cycle.
temperature, which, if exceeded, will terminate the heating cycle. In the There are several reasons for the
shut the furnace down. event of a flame roll-out condition, the pressure switch not to close.
There are several reasons for a limit switch will shut the furnace down. 1. An inoperative induced draft blower.
switch to open and almost always Switches for the (-)GPQ furnaces are
involve low airflow through the furnace. located on either side of the burner 2. A loose or leaky pressure switch
cover plate and just above the burners hose.
1. A dirty or restricted air filter.
on the blower divider panel. The (-)GLQ 3. A blockage in the vent.
2. A dirty or restricted cooling coil. requires only one switch on the left side
of burner cover plate. If a switch is 4. Severe downdrafts canceling the
3. Undersized or restricted return air draft from the inducer fan.
system. tripped, it must be manually reset. DO
NOT jumper or reset this switch. If this 5. A leaky gasket at the induced draft
4. Undersized or restricted supply air switch should trip, a qualified installer, blower.
system. service agency or the gas supplier 6. Improperly sized or installed vent.
5. A problem affecting the main should be called to diagnose and/or
blower: correct the source of tripping. If this The pressure switch contacts must
unit is mounted in a closet, the door open before the unit can go through
A. A wrong speed tap selection. another heating cycle.
must be closed when making this
B. Failing motor bearings. check. See troubleshooting chart in this book
C. Low voltage to the motor. for troubleshooting recommendations.
D. Dirty blower wheel.
E. Wrong motor rotation.
F. Blower wheel slipping on the
F. motor shaft.
6. Overfiring the furnace with too much
gas pressure.
7. Ventilation problems.

33
MAINTENANCE TABLE 10 FILTER SIZES
UPFLOW FILTER SIZES AS SHIPPED
! WARNING FURNACE INPUT BOTTOM SIDE
QUANTITY
WIDTH BTUH SIZE SIZE
DISCONNECT MAIN ELECTRICAL
POWER TO THE UNIT BEFORE 14 50 12 /4" X 25"
1
15 /4" X 25"
3
1
ATTEMPTING ANY MAINTENANCE. 171/2" 75 & 100 153/4" X 25" 153/4" X 25" 1 *NOTE: Some filters must be
21" 100 191/4" X 25" 153/4" X 25" 1 ordered or resized to fit certain
FAILURE TO DO SO CAN CAUSE 241/2" 125 & 150 223/4" X 25" 153/4" X 25" 1 units and applications.
ELECTRICAL SHOCK RESULTING
IN SEVERE PERSONAL INJURY OR
DEATH. reduced to maximize system IMPORTANT: Do not operate the
performance and life. Always verify that system for extended periods without
FILTERS the systems airflow is not impaired by filters. A portion of the dust entrained
the filtering system that has been in the air may temporarily lodge in the
Filter application and placement are
installed, by performing a temperature air duct runs and at the supply
critical to airflow, which may affect the
rise and temperature drop test. registers. Any circulated dust particles
heating and cooling system
Keep the air filters clean at all times. will be heated and charred by contact
performance. Reduced airflow can
Vacuum dirt from filter, wash with with the furnace heat exchanger. This
shorten the life of the systems major
detergent and water, air dry thoroughly sooty residue will soil ceilings, walls,
components, such as motor, limits,
and reinstall. drapes, carpets, and other household
elements, heat exchanger, evaporator
articles. Soot damage may also result
coil or compressor. Consequently, we See Table 10 and Figures 26 and 27 for with, or without, filters in place, when
recommend that the return air duct proper filter sizes and locations. certain types of candles are burned, or
system have only one filter location.
1. 14”- 50,000 BTUH unit requires candlewicks are left untrimmed.
The most common location will be
removal of 31/2” segment of filter and
inside the furnace or air handler or a
frame to get proper width for a
filter base. For systems with a return
bottom filter.
air filter grill or multiple filter grills, can
have a filter installed at each of the 2. 21”-100,000 BTUH unit requires
return air openings. DO NOT DOUBLE removal of 31/2” segment of filter and
FILTER THE RETURN AIR DUCT frame to get proper width for a side
SYSTEM. DO NOT FILTER THE filter.
SUPPLY AIR DUCT SYSTEM. 3. 241/2”-125,000 and 150,000 BTUH
If high efficiency filters or electronic air units require removal of 7” segment
cleaners are used in the system, it is of filter and frame to get proper
important that the airflow is not width for a side filter.

FIGURE 25
FILTER RETAINING ROD

FILTER
ROD
45-24095-01

34
FIGURE 26
UPFLOW FILTER RETAINING ROD (SIDE RETURN)

FILTER
ROD
45-24095-01
FILTER ROD
SUPPORT
ANGLE
AE-60520-01

FILTER
SUPPORT
ANGLE
AE-61883-01

FILTER AND ROD ASSEMBLY


CUT-OUT AND DRILL DETAIL

FILTER ROD
SUPPORT
ANGLE
AE-60520-01

FILTER SUPPORT
ANGLE
(SEE ANGLE DETAIL)
AE-61883-01

ROD & FILTER SUPPORT ANGLE ASSEMBLY

SOLID BOTTOM MAY BE ORDERED FROM THE FACTORY.

FIGURE 27
DOWNFLOW FILTER INSTALLATION

35
SYSTEM OPERATION FUMES TO ENTER THE HOME
RESULTING IN CARBON
LUBRICATION
INFORMATION MONOXIDE POISONING OR DEATH. The indoor blower motor and induced
THE VENT PIPE OR HEAT draft motor are prelubricated by the
Advise The Customer To: EXCHANGER MUST BE REPLACED motor manufacturer and do not require
1. Keep the air filters clean. The heating IF THEY LEAK. further attention.
system will operate better, more
• IMPORTANT: It is recommended The motors must be cleaned
efficiently and more economically. periodically by a qualified installer,
that at the beginning of the heating
2. Arrange the furniture and drapes so season and approximately midway service agency, or the gas supplier to
that the supply air registers and the in the heating season a visual prevent the possibility of overheating
return air grilles are unobstructed. inspection be made of the main due to an accumulation of dust and dirt
3. Close doors and windows. This will burner flames for the desired flame on the windings or on the motor
reduce the heating load on the appearance by a qualified installer, exterior. Air filters should be kept
system. service agency, or the gas supplier. clean. Dirty filters can restrict airflow
and results in motor overheating.
4. Avoid excessive use of kitchen & • IMPORTANT: It is also
bathroom exhaust fans. recommended that at the beginning Reference Figure 28 for proper
of the heating season, the flame removal of the blower assembly on
5. Do not permit the heat generated by sensor be cleaned with steel wool downflow models.
television, lamps or radios to by a qualified installer, service
influence the thermostat operation. agency, or the gas supplier. REPLACEMENT PARTS
6 Except for the mounting platform, • IMPORTANT: It is recommended
keep all combustible articles three Contact your local distributor for a
that an annual inspection and complete parts list.
feet from the furnace and vent cleaning of all furnace markings be
system. made to assure legibility. Attach a
7. IMPORTANT: Replace all blower replacement marking, which can be NOx MODELS
doors and compartment covers after obtained through the distributor, if When converting furnaces equipped
servicing the furnace. Do not operate any are found to be illegible or with NOx inserts to LP gas, remove the
the unit without all panels and doors missing. NOx insert assemblies.
securely in place. IMPORTANT: FOR Nox MODELS –
8. Proper operation of the system with At the beginning of the heating season TROUBLESHOOTING
constant air circulation. a visual inspection of the Nox device
should be made to ensure they have Refer to Figure 29 for determining
not become obstructed by insects cause of unit problems.
! WARNING nests or anything else which may
COMBUSTIBLE MATERIAL MUST effect performance. WIRING DIAGRAM
NOT BE PLACED ON OR AGAINST Figures 30 and 31 are complete wiring
THE FURNACE JACKET OR WITHIN
diagrams for the furnace and power
THE SPECIFIED CLEARANCES OF
THE VENT PIPE. THE AREA AROUND sources.
THE FURNACE MUST BE KEPT
CLEAR AND FREE OF ALL FIGURE 28
COMBUSTIBLE MATERIALS DOWNFLOW BLOWER REMOVAL
INCLUDING GASOLINE AND OTHER
FLAMMABLE VAPORS AND LIQUIDS.
PLACEMENT OF COMBUSTIBLE
MATERIALS ON, AGAINST OR
AROUND THE FURNACE JACKET
CAN CAUSE AN EXPLOSION OR
FIRE RESULTING IN PROPERTY
DAMAGE, PERSONAL INJURY OR
DEATH. THE FURNACE OWNER
SHOULD BE CAUTIONED THAT THE
FURNACE AREA MUST NOT BE
USED AS A BROOM CLOSET OR FOR
ANY OTHER STORAGE PURPOSES.

ANNUAL INSPECTION
The furnace should operate for many
years without excessive scale build-up
in the flue passageways, however, it is
recommended that a qualified installer,
service agency, or the gas supplier
actually inspect the flue passageways,
the vent system and the main burners
for continued safe operation paying
particular attention to deterioration from
corrosion or other sources.
! WARNING
HOLES IN THE VENT PIPE OR HEAT
EXCHANGER CAN CAUSE TOXIC

36
➤ FIGURE 29
INTEGRATED FURNACE CONTROL (IFC) TROUBLESHOOTING GUIDE
FOR UTEC 1095-101

37
FIGURE 30
TROUBLESHOOTING FLOWCHART (CONTINUED)

38
FIGURE 31
FOR MODELS WITH UT ELECTRONIC CONTROLS 1028-928 INTEGRATED FURNACE CONTROL AND DIRECT SPARK IGNITION

39
40 CM 1105

S-ar putea să vă placă și