JAP006-D73/COM/D21/2162

Contract No : JAP006-D73
DESIGN & BUILD SERVICES FOR 132/11KV SUBSTATIONS FOR
THE PALM , JUMEIRAH(4 Nos.)

11kV Switchgear CT Calculation

a) General Data :-

CT CALC, 11KV - 1
1) System voltage, kV = 11 kV

2) System fault level, If = 25 kA, 3 sec.

3) CT Manufacturer = M/s.ETAH, Malaysia

b) Lead Resistance Calculation

CT CALC, 11KV - 2
2.5 Sq.mm Cable

From Manufacturer’s table,

With a size of 2.5 sq.mm cable the lead resistance = 7.41 Ohms/Km
at 20ºC
= 0.00741 Ohms/Meter

Temperature co-efficient of resistance ( 20) = 0.00393

CT CALC, 11KV - 3
RL at 75 C = R 20 [ 1 +  20 (T2 - T1) ]
= 0.009 Ohms / Metre

i) Lead length for protection relays between = 75 Meters


11kV Buszone & 11kV switchgear and
132kV Relay Panel (IDT) & 11kV
switchgear.

Therefore RL for corresponding length = 75 x 0.009


= 0.675 Ohms

CT CALC, 11KV - 4
ii) Lead length for protection relays within = 5 Meters
switchgear is considered

Therefore RL for corresponding length = 5 x 0.009


= 0.045 Ohms

iii) Lead length for protection relays between = 100 Meters


11kVswitchgear & Neutral CT

CT CALC, 11KV - 5
Therefore RL for corresponding length = 100 x 0.009
= 0.9 Ohms

Doc.No.JAP006-D73/COM/D21/2162

CT CALC, 11KV - 6
I) IDT CIRCUITS

1) T3L :-

Application : Transformer Differential & ET HV REF protection


Relay type/Make : MICOM – P632 , M/s . Alstom/-
DCD 124A ,M/s.VA Tech Reyrolle, U.K
CT Ratio : 3200/1 A

1.1) CT Requirement for Transformer Differential Protection

CT CALC, 11KV - 7
The relay for this protection application will be mounted at 132kV Relay panel.

Calculation of VK at 11kV Side

As per M/s.Alstom recommendations, the knee point voltage of CT’s is governed by the
following relation :
Vk  I thr x (R ct + 2Rl + R b)
Vk = Knee point voltage in volts

CT CALC, 11KV - 8
I thr = Through Fault Current

R ct = CT Sec. resistance at 75C in ohms = 14 Ohms

2 Rl = CT Sec. loop resistance = 2 x 0.675 = 1.35 Ohms

Rb = Relay Burden = 0.1 VA

Transformer impedance considered = 31.5%

CT CALC, 11KV - 9
Fault MVA = 50 = 158.73 MVA
0.315

The maximum through fault current = 158.73 x 103


 3 x 11

= 8331 Amps

Corresponding secondary current = 8331

CT CALC, 11KV - 10
3200

= 2.6 Amps

Doc.No.JAP006-D73/COM/D21/2162

CT CALC, 11KV - 11
Hence, the selected value of I thr = 3 Amps

Vk  3 x (14 + 2 x 0.675 + 0.1 )

 46.35 Volts

CT CALC, 11KV - 12
Therefore Vk required for transformer differential protection

= 50 Volts

CT CALC, 11KV - 13
CT CALC, 11KV - 14
CT CALC, 11KV - 15
Doc.No.JAP006-D73/COM/D21/2162

1.2) CT Requirement for Main Transformer LV REF/ Earthing Transformer


HV REF Protection :-

Relay type/Make : DCD124A, M/s.VA Tech Reyrolle, U.K


CT Ratio : 3200/1 A

CT CALC, 11KV - 16
Class of accuracy : CL X

1.2.1) Calculation of Knee Point Voltage VK :-

The calculation of knee point voltage for REF protection is carried out as per
ESI 48 – 3.

1.2.1.1) Stability Voltage Setting Vs :-

As per clause 7.3.1 & Fig. 9 of ESI 48 – 3

CT CALC, 11KV - 17
(i) Consider an external phase to earth short circuit and assume complete
saturation of a line CT, then Vs shall not be less than

Vs > IF [A+B+F+G+(T2/T3)2 (H+2K+Rb) ] T1

Where
IF = Fault current corresponding to rated stability limit.

CT CALC, 11KV - 18
= 16 times rated current of power transformer
considered for phase fault

= 16 x 50 x 103
3 x 11

= 41990 Amps (for phase fault)

= 2000 Amps (for earth fault based on earthing


transformer rating)

CT CALC, 11KV - 19
T1 = Turns ratio of line and neutral CTs

= 1__
3200

A = Resistance of wiring plus CT secondary winding for


line CT

= RCT + RL

CT CALC, 11KV - 20
Where, RL = Lead resistance for 75 Meters length = 0.675 Ohms

Doc.No.JAP006-D73/COM/D21/2162

CT CALC, 11KV - 21
Therefore A = 14 + 0.675

= 14.675 Ohms

N = Resistance of wiring plus CT secondary winding for


neutral CT

= RCT + RL

CT CALC, 11KV - 22
Where, RL = Lead resistance for 100 Meters length = 0.9 Ohms

Therefore N = 14 + 0.9 = 14.9 Ohms

B = Resistance of wiring = RL
= 0.675 Ohms

F, G, K, H = Resistance of wiring

= Already included in A, B, N above

CT CALC, 11KV - 23
= 0

Rb = Resistance of bias coil

= 0 (Not applicable)

T2/T3 = Turns ratio of interposing CTs

= 0 (Not applicable)

CT CALC, 11KV - 24
Vs  2000 x (14.675 + 0.675 + 0)
3200

 9.594 Volts

(ii) Consider an external phase to earth short circuit and assume complete
saturation of Neutral CT, then Vs shall not be less than

Vs  IF (N) T1

CT CALC, 11KV - 25
 2000 x 14.9
3200

 9.3125 Volts

Doc.No.JAP006-D73/COM/D21/2162

CT CALC, 11KV - 26
(iii) Consider an external phase to phase short circuit and assume complete
saturation of a line CT, then Vs shall not be less than

Vs  IF (A+G+(T2/T3)2 (H + 3k + 3Rb/2) T1 Volts

 41990 x 14.675
3200
 192.56 Volts

CT CALC, 11KV - 27
(iv) Consider an external three-phase short circuit and assume complete
saturation of a line CT, then Vs shall not be less than

Vs  IF (A+G+(T2/T3)2 (H + 3k + 3Rb/2) T1 Volts

 41990 (14.675 + 0)
3200
 192.56 Volts

CT CALC, 11KV - 28
From (i), (ii), (iii) & (iv) above, consider the stability voltage setting of

Vs = 210 Volts

1.2.1.2) Knee Point Voltage VK :-

As per ESI 48 – 3, the knee point voltage of CTs for REF protection shall be
atleast twice that of stability voltage setting

Vk  2 Vs

CT CALC, 11KV - 29
 2 x 210

 420 Volts

However as per item 1.1, the Vk required for transformer differential protection is
50 V.

Hence the required Vk  420 Volts

CT CALC, 11KV - 30
CT CALC, 11KV - 31
Doc.No.JAP006-D73/COM/D21/2162

1.3) Magnetising Current Imag :-

As per ESI 48-3 when the protected winding of the transformer is not connected
to a solidly earthed power system, the fault setting shall be between 10% and 25%
of the minimum current available for earth fault at the transformer terminals.

CT CALC, 11KV - 32
Minimum fault current at 11kV bus = 2000 A

The fault setting shall be between 200 to 500 A

Primary operating current Iop = (Is + In + 3 I1 + Im) / T1

Where

Is = Relay setting current

CT CALC, 11KV - 33
= 0.1 A

In = Neutral CT magnetizing
current at Vk/2

= 3 mA at Vk/2

I1 = Line CT magnetizing
current at Vk/2

CT CALC, 11KV - 34
= 3 mA at Vk/2

T = Turns ratio

= 1_
3200

Im = Metrosil current

= 5 mA (Assumed)

CT CALC, 11KV - 35
Iop = [0.1+0.003+(3x0.003)+
0.005]x3200

= 374.4 Amps

= 18.7%

Approximately 19% of the minimum earth fault current.

CT CALC, 11KV - 36
Doc.No.JAP006-D73/COM/D21/2162

CT CALC, 11KV - 37
Since the fault setting is between 10% and 25% of the rated current of the
protected winding, as per ESI 48 – 3, the selected magnetizing current 3 mA is
suitable for the system protection.

1.4) Stabilising Resistor :-

Relay voltage setting Vs = 210 Volts

Relay current setting Is = 0.1A

CT CALC, 11KV - 38
Relay burden VA = 0.2 VA

Stabilising resistor Rsr = Vs - VA


Is Is2

= 210 - 0.2_
0.1 0.12

= 2080 Ohms

CT CALC, 11KV - 39
Selected stabilizing resistor = 0 – 2700 Ohms (variable)

1.5) Requirement of Metrosil :-

The maximum voltage in the absence of CT saturation is

Vf = IF T1 (RCT+2RL+RSR+Rrelay)

CT CALC, 11KV - 40
= 13.12 [14 + (2 x 0.675) + 2080 + 20]

= 27753.4 Volts

Peak voltage developed across relay

Vp = 2  2Vk (Vf – Vk)

CT CALC, 11KV - 41
Doc.No.JAP006-D73/COM/D21/2162

CT CALC, 11KV - 42
Vk = 550V (Actual knee pt. voltage of CT)

= 2  2 x 550 (27753.4 - 550)

= 10940.5 Volts

CT CALC, 11KV - 43
Since peak voltage developed across relay is more than 3 kV, metrosil is
provided.

Type : 600A / S1 / S1088

C : 900

 : 0.25

CT Provided by the Manufacturer :-

CT CALC, 11KV - 44
CT Ratio : 3200/1 A

Class of accuracy : CL X

CT Secondary resistance at 75ºC, Rct  14 Ohms

Knee point voltage Vk  550 Volts

Magnetising current, Imag  3 mA at Vk/2

CT CALC, 11KV - 45
Rated continuous thermal current : 120%

CT CALC, 11KV - 46
CT CALC, 11KV - 47
Doc.No.JAP006-D73/COM/D21/2162

2) CT : - T3L1

Application : 3 Pole O/C Protection & Energy meter + BCU +


Summation CT For Power Factor Control
Relay type/Make : DCD314B,M/s. VA Tech Reyrolle, U.K /
Energy meter (Prometer 3222),CEWE, Sweden

CT CALC, 11KV - 48
CT Ratio : 3200 – 1600/1 A

2.1) Calculation of Burden at Rated Current :-

1) DCD 314B = 0.05 VA

2) BCU = 0.1 VA

3) Cabling loop = 0.09 VA

CT CALC, 11KV - 49
4) Summation CT = 5.0 VA

5) ICT = 2.00 VA

6) Energy meter(Prometer 3222)= 0.2 VA


------------
Total = 7.44 VA
------------
Total burden required = 7.44 VA

CT CALC, 11KV - 50
2.2) Verification of Accuracy limit factor

The CT VA rating considering rated resistance burden shall be  the total actual burden
considering actual resistance burden
i.e., VACT  (ALF) x (VADEVICE + VACTR) - VACTR
N
Maximum fault current on the 11kV System is 25 kA.

CT CALC, 11KV - 51
Required ALF = 25,000 = 7.813 For 3200 A tap………(i)
3,200

= 25,000 = 15.625 For 1600 A tap……(ii)


1,600

N = Rated accuracy limit factor

= 15

CT CALC, 11KV - 52
VACT = CT Rated burden

= 15 – 15 VA

Doc.No.JAP006-D73/COM/D21/2162

VADEVICE = Actual connected burden

CT CALC, 11KV - 53
= 7.44 VA

VACTR = CT Secondary resistance


19.5 Ohms for 3200 A tap
9.5 Ohms for 1600 A tap

VACT  7.813 [7.44 + 19.5] – 19.5


15

CT CALC, 11KV - 54
 - 5.47 For 3200 A Tap

VACT  15.625 [7.44 + 9.5] – 9.5


15

 8.15 For 1600 A Tap

Hence, accuracy limit factor of 15 and burden 15 VA are adequate for both the CT taps.

CT CALC, 11KV - 55
CT Provided by the Manufacturer :-

Current transformer ratio : 3200 - 1600 /1 A

Class of accuracy : CL 5P15

Burden : 15 VA - 15 VA

Rated continuous thermal current : 120% - 120%

CT CALC, 11KV - 56
CT CALC, 11KV - 57
Doc.No.JAP006-D73/COM/D21/2162

CT CALC, 11KV - 58
4) T2L & T2L/1 : -

Application : High Impedance Busbar Protection


Relay type/Make : MCAG 34, M/s.Alstom, U.K
CT Ratio : 3200/1 A

4.1) Calculation of VK :-

4.1.1) Voltage Setting Vs :-

CT CALC, 11KV - 59
As per ESI 48 – 3, clause 7.12, fig 18

(i) Consider an external phase to earth short circuit and assume complete saturation
of a line CT, then Vs shall not be less than

Vs  IF [A+D+2G] T

Where

CT CALC, 11KV - 60
IF = Fault current corresponding to rated stability limit.
(100 percentage of switchgear short circuit rating as per
clause 5.6 of ESI 48 – 3)

= 25 kA

A = Resistance of wiring plus CT secondary winding

= RCT + RL

CT CALC, 11KV - 61
= 10 + 0.675

= 10.675 Ohms

D = Lead burden

= 0.675 Ohms

G = Lead burden (Already included in A & D)

CT CALC, 11KV - 62
= 0 Ohms

T = Turns ratio

= 1__
3200

CT CALC, 11KV - 63
Doc.No.JAP006-D73/COM/D21/2162

Therefore, Vs  25000 (10.675 + 0.675)


3200

 88.67 ~ 89 Volts

(ii) Also consider phase to phase or 3 phase external short circuit and assume
complete saturation of a line CT, then Vs shall not be less than

CT CALC, 11KV - 64
Vs = IF (A+G) T

 25000 (10.675 + 0)
3200

 83.39 Volts ~ 84 Volts

CT CALC, 11KV - 65
From (i) & (ii) above, consider voltage setting of Vs = 95 Volts

4.1.2) Knee Point Voltage Calculation :-

As per ESI 48 – 3, the knee point voltage of CT’s shall be at least twice the value of
setting voltage Vs.

Knee point voltage Vk  2 x Vs

 2 x 95

CT CALC, 11KV - 66
 190 Volts

4.2) Magnetising Current Imag :-

As per ESI 48 – 3, the fault setting shall be between 10% and 30% of a minimum fault
current available

Minimum fault current at 11kV bus = 2000 Amps

CT CALC, 11KV - 67
The fault setting shall be between 200 and 600 Amps

Effective primary fault setting, Ifs is given by

Ifs = [Is + nI1 + Isr + Ims] / T Amps

Where,
Is = Selected Relay Setting Current = 0.05 Amps

n = No. of CT’s in parallel for = 57

CT CALC, 11KV - 68
CHECK Zone.

Doc.No.JAP006-D73/COM/D21/2162

= No. of CT’s in parallel for = 20 (for zone-1& zone-3)


DISC. Zone (minimum)

CT CALC, 11KV - 69
I1 = Magnetising current at Vs = 0.002 Amps

Isr = Current drawn by the supervision = (95/90,000)


Relay at Vk/2

Ims = Metrosil current at selected voltage = 0.005 A (Assumed)


Setting

Ifs (For check zone) = [0.05 + (57x0.002) + (95/90,000) + 0.005] x 3200

CT CALC, 11KV - 70
= 544 Amps

= 27.2% of minimum fault current

Ifs (For disc.zone) = [0.05 + (20x0.002) + (95/90,000) + 0.005] x 3200

= 307.4 Amps

= 15.4% of minimum fault current

CT CALC, 11KV - 71
Relay current setting will be provided with 5% to 20%

4.3) Stabilising Resistor :-

Approximate value of series = Vs VA


Is - Is2
= 95.00 - 1
0.05 (0.05)2
= 1500 Ohms

CT CALC, 11KV - 72
Hence, selected value of Rsr = 0-1800 Ohms (variable)

4.4) Metrosil :-

The maximum voltage in the absence of CT saturation

Vf = IF T (Rct + 2RL + Rsr + Rrelay)

CT CALC, 11KV - 73
= 25,000 x [10+(2x0.675)+1500+400]
3200

= 14932 Volts

Doc.No.JAP006-D73/COM/D21/2162

CT CALC, 11KV - 74
Peak voltage developed across the relay,

Vp = 2 2 Vk (Vf – Vk)

= 2 2 x 200 (14932 - 200)

= 4855 Volts

CT CALC, 11KV - 75
Since the peak voltage developed across the relay is more than 3kV, metrosils are
provided.

Type = 600A / S3 / I / S802

C = 450

 = 0.25

CT Provided by Manufacturer

CT CALC, 11KV - 76
CT Ratio : 3200/1 A

Class of accuracy : CL X

CT Secondary Resistance at 75 C, Rct  10 Ohms

Knee point voltage, Vk  200 Volts

Magnetising Current, Imag  2 mA at Vk/2

CT CALC, 11KV - 77
Rated continuous thermal current : 120%

CT CALC, 11KV - 78
CT CALC, 11KV - 79
Doc.No.JAP006-D73/COM/D21/2162

5) T3LN Core 1 :-

Application : Standby Earth fault protection


Relay type/Make : DCD114A,VA Tech Reyrolle,U.K
CT Ratio : 3200 – 1600/1 A

CT CALC, 11KV - 80
5.1) Calculation of Burden at Rated Current :-

1) DCD114A = 0.05 VA

2) Cabling loop = 1.8 VA


------------
Total = 1.85 VA
------------
Total burden required = 1.85 VA

CT CALC, 11KV - 81
5.2) Verification of Accuracy limit factor
The CT VA rating considering rated resistance burden shall be  the total actual burden
considering actual resistance burden
i.e., VACT  (ALF) x (VADEVICE + VACTR) – VACTR
N

Maximum fault current on the 11kV System is 25 kA.

CT CALC, 11KV - 82
Required ALF = 25,000 = 7.81 For 3200 A tap
3200

= 25,000 = 15.625 For 1600 A tap


1600

N = Rated accuracy limit factor

= 20

CT CALC, 11KV - 83
VACT = CT Rated burden

= 15 VA

VADEVICE = 1.85 VA

VACTR = CT Secondary resistance


23.3 Ohms for 3200 A tap
11.4 Ohms for 1600 A tap

CT CALC, 11KV - 84
Doc.No.JAP006-D73/COM/D21/2162

VACT  7.81 [1.85 + 23.3] - 23.3

CT CALC, 11KV - 85
20

 - 13.48 For 3200 A tap

VACT  15.625 [1.85 + 11.4] - 11.4


20

 -1.05 for 1600 A tap

Hence, accuracy limit factor of 20 and burden 15 VA are adequate for both the CT taps.

CT CALC, 11KV - 86
CT Provided by the Manufacturer :-

Current transformer ratio : 3200 - 1600 / 1A

Class of accuracy : CL 5P20 - CL 5P20

Burden : 15 VA - 15 VA

CT CALC, 11KV - 87
Rated continuous thermal current : 120% - 120%

CT CALC, 11KV - 88
CT CALC, 11KV - 89
Doc.No.JAP006-D73/COM/D21/2162

6) T3LN Core 2 :-

ET - HV Neutral CT : -

CT CALC, 11KV - 90
Application : REF protection
Relay type / Make : DCD124A , M/s.VA Tech Reyrolle, U.K
CT Ratio : 3200 / 1 A

For knee point voltage calculation, magnetizing current requirement, please refer the
calculation of for item 1.2.

CT Provided by the Manufacturer :-

Current transformer ratio : 3200/1 A

CT CALC, 11KV - 91
Class of accuracy : CL X

CT Secondary resistance 75 deg. C, Rct  14 Ohms

Knee point voltage, Vk  550 Volts

Magnetising current, Imag  3 mA at Vk/2

CT CALC, 11KV - 92
Rated continuous thermal current : 120%

CT CALC, 11KV - 93
CT CALC, 11KV - 94
CT CALC, 11KV - 95
Doc.No.JAP006-D73/COM/D21/2162

II) OUTGOING FEEDER CIRCUITS (WITH METERING)

1) CT Core T7L :-

Application : 3 O/C & E/F Protection + BCU


Relay Type / Make : DCD314B/DCD114A, M/s.VA Tech. Reyrolle, U.K

CT CALC, 11KV - 96
CT Ratio : 400 / 1A

1.1) Calculation of Burden at Rated Current :-

1) DCD314B = 0.05 VA

2) DCD114A = 0.05 VA

3) BCU = 0.1 VA

CT CALC, 11KV - 97
4) Cabling loop = 0.09 VA
------------
Total = 0.29 VA
------------
Total burden required = 0.29 VA

1.2) Verification of Accuracy limit factor

CT CALC, 11KV - 98
The CT VA rating considering rated resistance burden shall be  the total actual burden
considering actual resistance burden
i.e., VACT  (ALF) x (VADEVICE + VACTR) – VACTR
N

Maximum fault current on the 11kV System is 25 kA.

Required ALF = 25,000 = 62.5 For 400A tap


400

CT CALC, 11KV - 99
N = Rated accuracy limit factor
= 15

VACT = CT Rated burden

= 15 VA

VADEVICE = 0.29 VA

VACTR = CT Secondary resistance

CT CALC, 11KV - 100


3 Ohms for 400 A tap

Doc.No.JAP006-D73/COM/D21/2162

CT CALC, 11KV - 101


VACT  62.5 [0.29 + 3] - 3
15

 10.7 For 400A tap

Hence, accuracy limit factor of 15 and burden 15 VA are adequate for the CT ratio
400/1A.

CT Provided by the Manufacturer :-

CT CALC, 11KV - 102


Current transformer ratio : 400/1 A

Burden : 15 VA

Class of accuracy : CL 5P15

Rated continuous thermal current : 120 %

CT CALC, 11KV - 103


CT CALC, 11KV - 104
CT CALC, 11KV - 105
Doc.No.JAP006-D73/COM/D21/2162

CT CALC, 11KV - 106


2) CT Core T7L1 :-

Application : Metering
Type / Make : Energymeter (Prometer 3222), M/s.CEWE,Sweden
MDI – BIQC96, M/s.Celsa
CT Ratio : 400/1 A

2.1) Calculation of Burden at Rated Current :-

CT CALC, 11KV - 107


1) Energy meter (Prometer 3222) = 0.2 VA (For R & B phases)

2) MDI – BIQC96 = 2.5 VA (For Y phase only)

3) Cabling loop = 0.09 VA

Total burden = 0.29 VA (For R & B phases)

= 2.59 VA (For Y phase)

CT CALC, 11KV - 108


2.2) Verification of Instrument Security Factor :-

Connected burden VA device = 0.29 VA (For R&B phases)

= 2.59 VA (For Y phase)

Rated burden VACT = 10 VA

Rated Fs (N) = 5

CT CALC, 11KV - 109


In order to maintain the rated instrument security factor 5,the rated burden shall be
equal to the connected burden. In this case, the connected burden is 0.29VA for R&B
phases and 2.59VA for Y phase. However, the higher VA rating is possible since the
ISF of energy meter is 40xIn for 1 sec. & for MDI 20xFL for 1sec. Hence the CT
shall be supplied with more rated burden.

VACT < (ALF) x (VADEVICE + VACTR) – VACTR


N

CT CALC, 11KV - 110


Where,

N = Rated accuracy limit factor (Fs)

= 5

CT CALC, 11KV - 111


Doc.No.JAP006-D73/COM/D21/2162

VACT = CT Rated burden

= 10 VA

CT CALC, 11KV - 112


VADEVICE = 0.29 VA (For R & B phases)

= 2.59 VA (For Y phase)

VACTR = CT Secondary resistance


2.1 Ohms for 400 A tap

Therefore, N x (VACT+VACTR) < ALF x (VADEV+VACTR)

CT CALC, 11KV - 113


5 x (VACT+2.1) < 40 x (0.29+2.1) -For R & B phases

5 x (VACT+2.1) < 20 x (2.59+2.1) -For Y phase

VACT < 17.02 (For R & B phases – Energy meter)

VACT < 16.66 (For Y phase – MDI)

The CT with 10 VA burden will be supplied which is adequate.

CT CALC, 11KV - 114


CT Provided by the Manufacturer :-

Current transformer ratio : 400/1 A

Class of accuracy : CL 0.5 Fs5

Burden : 10 VA

CT CALC, 11KV - 115


Rated short time thermal current : 120%

CT CALC, 11KV - 116


Doc.No.JAP006-D73/COM/D21/2162

CT CALC, 11KV - 117


3) CT Core T8L & T8L1 :-

Application : High Impedance Busbar Protection


Relay type / Make : MCAG 34, M/s.Alstom, U.K
CT Ratio : 3200/1 A

For CT requirement calculation refer item no. 4 of IDT feeder CT calculation.

CT Provided by the Manufacturer :-

CT CALC, 11KV - 118


CT Ratio : 3200/1 A

Class of accuracy : CL X

CT Secondary resistance at 75ºC, Rct  10 Ohms

Knee point voltage Vk  200 Volts

Magnetising current, Imag  2 mA at Vk/2

CT CALC, 11KV - 119


Rated continuous thermal current : 120%

CT CALC, 11KV - 120


CT CALC, 11KV - 121
Doc.No.JAP006-D73/COM/D21/2162

CT CALC, 11KV - 122


III) OUTGOING FEEDER CIRCUITS (WITHOUT METERING)

1) CT Core T7L :-

Application : 3 O/C & E/F Protection + BCU


Relay type / Make : DCD314B/DCD114A, M/s.VA Tech. Reyrolle, U.K
CT Ratio : 400/1 A

CT CALC, 11KV - 123


1.1) Calculation of Burden at Rated Current :-

1) DCD314B = 0.05 VA

2) DCD114A = 0.05 VA

3) BCU = 0.1 VA

4) Cabling loop = 0.09 VA

CT CALC, 11KV - 124


------------
Total = 0.29 VA
------------
Total burden required = 0.29 VA

1.2) Verification of Accuracy limit factor

CT CALC, 11KV - 125


The CT VA rating considering rated resistance burden shall be  the total actual burden
considering actual resistance burden
i.e., VACT  (ALF) x (VADEVICE + VACTR) – VACTR
N

Maximum fault current on the 11kV system is 25 kA.

Required ALF = 25,000 = 62.5 For 400A tap


400

CT CALC, 11KV - 126


N = Rated accuracy limit factor
= 15

VACT = CT Rated burden

= 15 VA

VADEVICE = 0.29 VA

VACTR = CT Secondary resistance

CT CALC, 11KV - 127


3 Ohms for 400 A tap

Doc.No.JAP006-D73/COM/D21/2162

VACT  62.5 [0.29 + 3] - 3


15

CT CALC, 11KV - 128


 10.7 For 400A tap

Hence, accuracy limit factor of 15 and burden 15 VA is applicable for the CT ratio,
400/1A.

CT Provided by the Manufacturer :-

CT CALC, 11KV - 129


Current transformer ratio : 400/1 A

Burden : 15 VA

Class of accuracy : CL 5P15

Rated continuous thermal current : 120 %

CT CALC, 11KV - 130


CT CALC, 11KV - 131
CT CALC, 11KV - 132
Doc.No.JAP006-D73/COM/D21/2162

CT CALC, 11KV - 133


2) CT Core T7L1 :-

Application : Metering
Type / Make : MDI – BIQC96, M/s.Celsa
CT Ratio : 400/1 A

2.1) Calculation of Burden at Rated Current :-

1) MDI – BIQC96 = 2.5 VA (Y phase only)

CT CALC, 11KV - 134


2) Cabling loop = 0.09 VA
------------
Total = 2.59 VA
------------
Total burden required = 2.59 VA

2.2) Verification of Instrument Security Factor :-

CT CALC, 11KV - 135


Connected burden VA device = 2.59 VA

Rated burden VACT = 10 VA

Rated Fs (N) = 5

In order to maintain the rated instrument security factor 5,the rated burden shall be
equal to the connected burden. In this case, the connected burden is 2.59VA.
However, the higher VA rating is possible since the ISF of MDI is 20xFL for 1sec.
Hence the CT shall be supplied with more rated burden.

CT CALC, 11KV - 136


VACT < (ALF) x (VADEVICE + VACTR) – VACTR
N

Where,

N = Rated accuracy limit factor (Fs)

CT CALC, 11KV - 137


= 5

VACT = CT Rated burden

= 10 VA

VADEVICE = 2.59 VA

CT CALC, 11KV - 138


Doc.No.JAP006-D73/COM/D21/2162

VACTR = CT Secondary resistance


2.1 Ohms for 400 A tap

Therefore, N x (VACT+VACTR) < ALF x (VADEV+VACTR)

5 x (VACT+2.1) < 20 x (2.59+2.1)

CT CALC, 11KV - 139


5VACT < 83.3

VACT < 83.3 < 16.66 VA


5

Therefore the VA burden is < 16.66 VA.

The CT with 10 VA burden will be supplied which is adequate.

CT CALC, 11KV - 140


CT Provided by the Manufacturer :-

Current transformer ratio : 400/1 A

Class of accuracy : CL 0.5 Fs5

Burden : 10 VA

CT CALC, 11KV - 141


Rated short time thermal current : 120%

Note : -

CT CALC, 11KV - 142


For R & B phase CTs (Class 0.5 Fs<5), secondary will be shorted at 11kV Swgr. LV
compartment.

CT CALC, 11KV - 143


Doc.No.JAP006-D73/COM/D21/2162

CT CALC, 11KV - 144


3) CT Core T8L & T8L1 :-

Application : High Impedance Busbar Protection


Relay type / Make : MCAG 34, M/s.Alstom, U.K
CT Ratio : 3200/1 A

For CT requirement calculation refer item no. 4 of IDT feeder CT Calculation

CT Provided by the Manufacturer :-

CT CALC, 11KV - 145


CT Ratio : 3200/1 A

Class of accuracy : CL X

CT Secondary resistance at 75ºC, Rct  10 Ohms

Knee point voltage Vk  200 Volts

Magnetising current, Imag  2 mA at Vk/2

CT CALC, 11KV - 146


Rated short time thermal current Ith : 25 kA for 3 sec.

Rated continuous thermal current : 120%

CT CALC, 11KV - 147


CT CALC, 11KV - 148
Doc.No.JAP006-D73/COM/D21/2162

CT CALC, 11KV - 149


IV) BUS SECTION CIRCUIT :-

1) CT Core T6L :-

Application : 3 O/C & E/F Protection + BCU


Relay type / Make : DCD314B/DCD114A, M/s.VA Tech Reyrolle.U.K
CT Ratio : 3200 / 1 A

CT CALC, 11KV - 150


1.1) Calculation of Burden at Rated Current :-

1) DCD314B = 0.05 VA

2) DCD114A = 0.05 VA

3) BCU = 0.1 VA

4) Cabling loop = 0.09 VA


------------

CT CALC, 11KV - 151


Total = 0.29 VA
------------
Total burden required = 0.29 VA

1.2) Verification of Accuracy limit factor

The CT VA rating considering rated resistance burden shall be  the total actual burden
considering actual resistance burden
i.e., VACT  (ALF) x (VADEVICE + VACTR) – VACTR

CT CALC, 11KV - 152


N

Maximum fault current on the 11kV System is 25 kA.

Required ALF = 25,000 = 7.8125 For 3200A tap


3200

N = Rated accuracy limit factor


= 15

CT CALC, 11KV - 153


VACT = CT Rated burden

= 15 VA

VADEVICE = 0.29 VA

VACTR = CT Secondary resistance


17 Ohms for 3200 A

CT CALC, 11KV - 154


Doc.No.JAP006-D73/COM/D21/2162

VACT  7.8125 [ 0.29 + 17 ] - 17


15

 - 7.99

CT CALC, 11KV - 155


Hence, accuracy limit factor of 15 and burden 15 VA are adequate for the CT ratio
3200 / 1A .

CT Provided by the Manufacturer :-

CT Ratio : 3200/1 A

Burden : 15 VA

CT CALC, 11KV - 156


Class of accuracy : CL5P15

Rated continuous thermal current : 120%

CT CALC, 11KV - 157


CT CALC, 11KV - 158
CT CALC, 11KV - 159
Doc.No.JAP006-D73/COM/D21/2162

CT CALC, 11KV - 160


2) CT Core T4L & T5L :-

Application : High Impedance Busbar Protection


Relay type / Make : MCAG 34, M/s.Alstom, U.K
CT Ratio : 3200/1 A

For CT requirement calculation refer item no. 4 of IDT feeder CT Calculation.

CT Provided by the Manufacturer :-

CT CALC, 11KV - 161


CT Ratio : 3200/1 A

Class of accuracy : CL X

CT Secondary resistance at 75ºC, Rct  10 Ohms

Knee point voltage Vk  200 Volts

Magnetising current, Imag  2 mA at Vk/2

CT CALC, 11KV - 162


Rated continuous thermal current : 120%

CT CALC, 11KV - 163


CT CALC, 11KV - 164
CT CALC, 11KV - 165
Doc.No.JAP006-D73/COM/D21/2162

V) CAPACITOR BANK FEEDERS :

1) CT Core T7L :-

CT CALC, 11KV - 166


Application : 3 O/C & E/F Protection + BCU
Relay type / Make : DCD314B/DCD114A, M/s.VA Tech Reyrolle, U.K
CT Ratio : 400/1 A

1.1) Calculation of Burden at Rated Current :-

1) DCD314B = 0.05 VA

2) DCD114A = 0.05 VA

CT CALC, 11KV - 167


3) BCU = 0.1 VA

4) Cabling loop = 0.09 VA


------------
Total = 0.29 VA
------------
Total burden required = 0.29 VA

1.2) Verification of Accuracy limit factor

CT CALC, 11KV - 168


The CT VA rating considering rated resistance burden shall be  the total actual burden
considering actual resistance burden
i.e., VACT  (ALF) x (VADEVICE + VACTR) – VACTR
N
Maximum fault current on the 11kV System is 25 kA.

Required ALF = 25,000 = 62.5 For 400A tap


400

CT CALC, 11KV - 169


N = Rated accuracy limit factor
= 15

VACT = CT Rated burden


= 15 VA

VADEVICE = 0.29 VA

VACTR = CT Secondary resistance


3 Ohms for 400 A tap

CT CALC, 11KV - 170


Doc.No.JAP006-D73/COM/D21/2162

CT CALC, 11KV - 171


VACT  62.5 [0.29 + 3] - 3
15

 10.7 For 400A tap

Hence, accuracy limit factor of 15 and burden 15 VA are adequate for the CT ratio 400/1 A.

CT Provided by the Manufacturer :-

CT CALC, 11KV - 172


Current transformer ratio : 400/1 A

Burden : 15 VA

Class of accuracy : CL 5P15

Rated continuous thermal current : 120%

CT CALC, 11KV - 173


CT CALC, 11KV - 174
CT CALC, 11KV - 175
CT CALC, 11KV - 176
Doc.No.JAP006-D73/COM/D21/2162

2) CT Core T7L1 :-

Application : Spare
CT Ratio : 400/1 A

CT CALC, 11KV - 177


CT Provided by the Manufacturer :-

Current transformer ratio : 400/1 A

Burden : 10 VA

Class of accuracy : CL 0.5 Fs5

Rated short time thermal current : 120%

CT CALC, 11KV - 178


Note : -

Class 0.5 CT Secondary will be shorted at 11kV Swgr. LV Compartment.

CT CALC, 11KV - 179


CT CALC, 11KV - 180
CT CALC, 11KV - 181
Doc.No.JAP006-D73/COM/D21/2162

3) CT Core T8L & T8L1 :-

CT CALC, 11KV - 182


Application : High Impedance Busbar Protection
Relay type / Make : MCAG 34, M/s.Alstom, U.K
CT Ratio : 3200/1A

For CT requirement calculation refer item no. 4 of IDT feeder CT Calculation.

CT Provided by the Manufacturer :-

CT Ratio : 3200/1 A

CT CALC, 11KV - 183


Class of accuracy : CL X

CT Secondary resistance at 75ºC, Rct  10 Ohms

Knee point voltage Vk  200 Volts

Magnetising current, Imag  2 mA at Vk/2

Rated continuous thermal current : 120%

CT CALC, 11KV - 184


CT CALC, 11KV - 185
CT CALC, 11KV - 186
Doc.No.JAP006-D73/COM/D21/2162

4) Out of balance CT :-

CT CALC, 11KV - 187


Application : Out of balance protection
Relay type / Make : SPAJ160C, M/s.ABB
CT Ratio : 20-10/5 A

1.1) Calculation of Burden at Rated Current :-

1) SPAJ160C = 0.1 VA

2) Cabling loop = 0.09 VA

CT CALC, 11KV - 188


------------
Total = 0.19 VA
------------
Total burden required = 0.19 VA

CT Provided by the Manufacturer :-

CT CALC, 11KV - 189


Current transformer ratio : 20-10/5 A

Burden : 15 VA

Class of accuracy : CL 1

Note:-

CT CALC, 11KV - 190


Out of Balance Neutral CT will be supplied as a loose item.

CT CALC, 11KV - 191


CT CALC, 11KV - 192
CT CALC, 11KV - 193