Documente Academic
Documente Profesional
Documente Cultură
Branch Circuits
EEE 3 Lecture 12
Trivia
• Defibrillators: output is measured in power
• Current actually delivered is dependent on the resistance
between device and person’s skin
• Recommended 2-4 J/kg
• Electric chair: ranging from 500 – 2000 V
• For 30 sec, repeated until person is dead
• Again, dependent on person’s resistance
3
Sources:
https://www.sciencedirect.com/topics/medicine-and-dentistry/defibrillation
https://deathpenaltyinfo.org/descriptions-execution-methods?scid=8&did=479
Design Process
2 4
• Loads • Branch • Feeders
• Outlets Circuits • Panel
• Switches Boards
1 3 5
7
• Service • Grounding
• Conduits
• Other Devices
6 8
4
BRANCH CIRCUIT REQUIREMENTS
5
Overcurrent Protection
VI. Branch Circuit Overcurrent Protection
1. General Rule
–The rating or setting of an overcurrent device in any
branch circuit must not exceed the current-carrying
capacity of the circuit conductors.
BC rating ≤ conductors
• If the device rating is greater than the capacity of the
conductors, the conductors will burn before the device
can actuate. 6
Allowable BC
Type of BC Permissible Loads
Rating (A)
Individual Any Any
(serving one
outlet)
–General-purpose lighting load
15 or 20 –Rating of any one Cord-and-plug attached
equipment ≤ 0.8 (BC Rating)
–If supplying other loads, total rating of
equipment fastened in place (not including
luminaires) ≤ 0.5 (BC Rating)
Multi-outlet
- Serving –Luminaires with heavy-duty lamp holders not
multiple 30 in dwelling units
outlets –Cord-and-plug attached equipment ≤ 0.8 (BC
Rating)
40 or 50 –Cooking appliances fastened in place.
–Luminaires with heavy-duty lamp holders not7
in dwelling units, infrared heating units, etc.
>50 Non-lighting outlets
Selecting overcurrent protection
• When the maximum rating is not a standard
rating, the next higher standard rating may be
selected.
9
Continuous load – maximum current (RMS) is expected
to continue for 3 hrs.
Maximum Rating of Individual BC
10
NCL + 1.25CL ≤ BC rating ≤ conductors
14
Conductors - Table 3.10.1.16 Raceway
ALUMINUM OR COPPER-CLAD
COPPER
ALUMINUM
2.0(1.6) 15 15 25 25 …. …. …. …. ….
3.5(2.0) 20 20 30 30 15 15 25 25 3.5(2.0)
5.5(2.6) 30 30 40 40 25 25 30 30 5.5(2.6)
8.0(3.2) 40 45 50 50 30 40 40 40 8.0(3.2)
14 55 65 70 70 40 50 55 55 14
22 70 85 90 90 55 65 70 70 22
30 90 110 115 115 70 85 90 90 30
38 100 125 130 130 80 95 100 100 38
50 120 145 150 150 95 115 120 120 50
60 135 160 170 170 105 125 135 135 60
80 160 195 205 205 125 150 160 160 80
100 185 220 225 225 145 170 180 180 100
125 210 255 265 265 170 200 210 210 125
150 240 280 295 295 190 230 240 240 150
200 280 330 355 355 225 270 290 290 200
250 315 375 400 400 260 305 330 330 250
325 370 435 470 470 295 355 380 380 325
400 405 485 515 515 330 395 420 420 400
500 445 540 580 580 370 440 475 475 500
15
Conductors - Table 3.10.1.16
Size Temperature Rating of Conductor. See Table 3.10.1.13
Raceway
Size
60º C 75º C 85º C 90º C 60º C 75º C 85º C 90º C
Types Types Types Types Types Types Types Types
RUW, FEPW, V, TA, RUW, RH, V, TA,
T, RH, MI TBS, T, RHW, MI TBS,
TW, RHW, SA, TW, RUH, SA,
mm2 UF RUH, AVB, UF THW, AVB, mm2
(mm. dia.) THW, SIS, THWN, SIS, (mm. dia.)
THWN, †FEP, XHHW, †RHH,
XHHW, †FEPB, USE †THHN,
USE, †RHH, †XHHW*
ZW †THHN,
†XHHW*
COPPER ALUMINUM OR COPPER-CLAD
ALUMINUM
CORRECTION FACTORS
Ambient For ambient temperature over 30º C, multiply the ampacities Ambient
Temp. ºC shown above by the appropriate correction factor to determine Temp. ºC
31-40 0.82 0.88 0.90 0.91 0.82 0.88 0.90 0.91 31-40
41-50 0.58 0.75 0.80 0.82 0.58 0.75 0.80 0.82 41-50
51-60 …. 0.58 0.67 0.71 …. 0.58 0.67 0.71 51-60
61-70 …. 0.35 0.52 0.58 …. 0.35 0.52 0.58 61-70
71-80 …. …. 0.30 0.41 …. …. 0.30 0.41 71-80
† The load current rating and the overcurrent protection for these conductors shall not exceed 15 amperes 16
for 2 mm2 (1.6 mm. dia.) 20 amperes for 3.5 mm2 (2.0 mm. dia.), and 30 amperes for 5.5 mm2 (2.6 mm. dia.)
copper; or 15 amperes for 3.5 mm2 (2.0 mm. dia.) and 25 amperes for 5.5 mm2 (2.6 mm. dia.) aluminum and
copper-clad aluminum.
* For dry locations only. See 75º C column for wet locations.
Conductors - Table 3.10.1.17
Table 3.10.1.17 Allowable Ampacities of Insulated Conductors
Rated 0 - 2000 Volts, 60º to 90º C
† The load current rating and the overcurrent protection for these conductors shall
not exceed 20 amperes for 2 mm2 (1.6 mm. dia.), 25 amperes for 3.5 mm2 (2.0 mm. 19
dia.), and 40 amperes for 5.5 mm2 (2.6 mm. dia.) copper; or 20 amperes for 3.5 mm2
(2.0 mm. dia.) and 30 amperes for 5.5 mm2 (2.6 mm. dia.) aluminum and copper-
clad aluminum.
Notes to tables 3.10.1.6 through 3.10.1.13
More than 3 Conductors in a raceway or cable. Where the number
of conductors in a raceway or cable exceeds 3, the maximum
allowable load current of each conductor shall be reduced as shown
in the following table
Percent of Values in
Number of
Tables 5.3.2.4 and
Conductors
5.3.2.6
Raceway
4 thru 6 80
7 thru 24 70
25 thru 42 60
43 and above 50
• In dwelling units:
• 20-A Small-appliance BC (at least 2)
• 20-A Bathroom BC (for equipment in bathroom)
• 20-A Laundry BC
23
Required Branch Circuits
▪ For a dwelling unit with floor area not more
than 50sqm., it shall be permitted to have only
one 20-A BC provided that the total load shall
not exceed 3680 VA.
Assuming BC rating is 20 A (derated)
→ Actual total load = (BC rating)/1.25
= 20A/1.25 = 16A
o Default voltage to be used is 230V
General Receptacles
- 180 volt-amperes per receptacle (sec2.20.1.3(b))
Branch Circuit Rating: 15 or 20 A
32
Calculation of branch circuit loads
Laundry Loads for Dwelling Unit
Branch Circuit Rating: 20 A
Motor Loads
-Motor VA: 1.25 * Motor FLC*230V
Branch Circuit Rating: Any
33
Calculation of branch circuit loads
No. of BCs = Total computed load (in VA) per B.C. group
(B.C. Rating, Amperes) x (230V)
34
Example 1:
Determine the minimum number of branch circuits
required for an office building with the following lighting
and receptacle loads:
a. General Illumination
Larger of:
–Using table of VA/sqm.:
30m x 60m x 28 VA/sq.m. x 1.25 = 63,000 VA
OR
–Using actual load data:
400 units x 150 VA/unit x 1.25 = 75,000 VA
37
c. General Receptacles
38
Overcurrent Protection
Specific Rules
1. An overcurrent device must be placed at the supply end of
each ungrounded conductor of the circuit to be protected.
2. An overcurrent device must NOT be placed in a
permanently-grounded conductor, except where the device
simultaneously opens all conductors of the circuit.
3. Where the device protecting a conductor has a rating or
setting that also provides protection for smaller conductors,
there is no need to provide protection at the point where the
smaller conductors are tapped from the larger conductor.
4. Non-motor-operated appliance branch circuit protective
devices shall not exceed 150% of the appliance rating.
5. Overcurrent devices must be located such that they are 39
readily accessible.
Allowable BC
Type of BC Permissible Loads
Rating (A)
Individual Any Any
(serving one
outlet)
–General-purpose lighting load
15 or 20 –Rating of any one Cord-and-plug attached
equipment ≤ 0.8 (BC Rating)
–If supplying other loads, total rating of
equipment fastened in place (not including
luminaires) ≤ 0.5 (BC Rating)
Multi-outlet
- Serving –Luminaires with heavy-duty lamp holders not
multiple 30 in dwelling units
outlets –Cord-and-plug attached equipment ≤ 0.8 (BC
Rating)
40 or 50 –Cooking appliances fastened in place.
–Luminaires with heavy-duty lamp holders not 40
in dwelling units, infrared heating units, etc.
>50 Non-lighting outlets
Motor Branch Circuits
• Identify the different elements of a motor branch circuit.
• Explain the function of each element.
• Calculate the minimum size of branch circuit conductors.
• Calculate the maximum rating of the overcurrent
protection.
• Calculate the minimum rating of the disconnecting
means.
41
Why are there
two protective
devices?
42
Why are there two protective
devices?
• Overcurrent protection: for short circuit
• Short circuit = unintentional connection of two points that are
normally at different voltage levels
• Overload protection: for overload (duh)
• Overload = overload operation due to mechanical load / loss of
lubrication / improper application of brakes
43
Disconnecting Means
44
Overcurrent Protection
45
Conductors: (Ungrounded
and/or grounded)
Minimum ampacity
• May be specified by the
manufacturer
• If not specified, equal to
125% of the full-load
current (from label or from
PEC – the larger one).
• If serving multiple loads,
equal to 125% of the full-
load current of the largest
motor plus the full-load 46
current of the other loads.
Full-load currents from PEC
47
Full-load currents from PEC
48
For motor branch circuits
• Still the same
49
Selecting overcurrent protection
• When the maximum rating is not a standard
rating, the next higher standard rating may be
selected.
53