Project no.: D108337 Substation: SWH38A1
Location: Plot P18, Zayed Military City
DANGER!
High Voltage! Danger! If the panel feeders are included in the rated short-duration power-frequency
withstand voltage test, the panel connections are live during the test. Keep a minimum distance of 1.5
mtr to the panel connections.
ATTENTION!
Rack-out the Voltage Transformer in Incoming Feeder.
Earth and short-circuit all test sockets of the voltage detecting system when the test voltage
goes above rated voltage.
Short & Earth all CT Circuit.
For the rated short-duration power-frequency withstand voltage test, Rack-in the Circuit Breaker to
service position & switch Circuit-breaker in the First to Last panel to CLOSED Position.
Check Capdis by injecting a small amount of voltage i.e. between 10% to 45% of Rated
Line voltage (short capdis with earth).
Check Capdis Voltage detector is shorted with respect phase to earth when High voltage is injected
above nominal voltage
Apply the power-frequency test voltage as per test format
SIGNATURE
DATE 08.06.2020
CONDITION: All the feeders (from K01 to K09) CB CLOSED AND IN SERVICE POSITION.
APPLIED LEAKAGE
TEST POINT DURATION REMARKS
VOLTAGE CURRENT (mA)
R – (Y+B+E) 22.4 kV 1 min 20 WITHSTOOD
Y – (R+B+E) 22.4 kV 1 min 20 WITHSTOOD
B – (Y+R+E) 22.4 kV 1 min 20 WITHSTOOD
3. REMARKS:
SIGNATURE
DATE 08.06.2020