transformer will feed the two nos of 12KV 3600A Station Switchgear SA and
SB. The Station Transformer is located in transformer yard area outside A Row
There is a provision for charging of station boards (1SA and 1SB) from
Construction power with power cable. Further, a Tie is also provided for
forming station grid i.e to import/ export of power from one unit to other unit
(1SA-2SA) and (1SB-2SB). One Tie panel is envisaged for charging of Unit
bus duct.
The following Motors/ Transformers / Switch boards fed from 1SB Board:
DC Feeder 1: AC Feeder 1:
DC Feeder 2: AC Feeder 2:
Switchgear Details:
Breaker: Vacuum
ITEM
TESTING OBJECTIVES
2.0
2.1 To ensure that HT switchgear panels and bus ducts are correctly
assembled, erected and tested in accordance with good engineering
practices.
2.2 To ensure that equipments and all its components conform to the
specifications agreed in the terms and conditions of the contract.
2.3 To prove the equipments are capable of operation under service conditions.
2.6 To ensure the equipment is charged and is ready for energizing the
3.1 Testing will be carried out for all the individual 12 KV Vacuum breakers
contained in 11 KV switch gear room as per their standard check list and
test procedures.
3.2 All relays and protection/control circuit will be tested according to their
standard check lists and testing procedures. Different inter locks as per the
3.3 It will be the duty of the testing team leader to carry out detail possible
inspection while all the equipments are in service to ensure that they are
schedule.
4.1 220 V D.C supplies from DC Distribution board for protection and control
ckts.
4.3 All test sets and equipments required for testing of individual equipments
ITEM SAFETY
5.0
NTPC TESTING SCHEDULE TELANGANA
5.1 The Engineer in charge of the testing team will inform to each member
of his team as to the exact nature and extent of his contribution and
5.2 Only the nominated persons will take part in the tests. All others will keep them
5.3 All persons must acquaint themselves with use and location of fire
5.5 Each test will be carried out under the control of the team leader.
5.6 A strict and safe method of using test leads shall be practiced. Bare wires shall
5.7 A record note of alteration made during the test such as shorting and
5.8 Each test will be carefully planned and carried out so that there is no danger
will be safe and easy access to all equipment under test. Test area will be
5.9 During HIGH VOLTAGE test the area will be cordoned off. Danger/Warning
testing.
5.12 Safety clearance certificate and safety clearance notifications should be in force
5.15 First aid charts for treatment of electrical shock should be displayed at the test
6.1 First aid chart for acid injury and electric shock will be displayed.
6.2 In case of any accident involving acid burn neutralizing solution must be
applied.
6.3 All the persons working on battery shall wear acid proof aprons.
6.4 All the members of Testing team and persons associated with this Testing
6.5 Schedule should be familiar with the testing procedures and the equipments
involved in testing.
6.6 There should be safe access to, and escape routes from confined areas.
6.8 Access to the area under test should be restricted. Proper caution boards should
6.9 Permanent and adequate lighting facilities should be available at all times.
6.10 All handrails, stairs, guards and trech/ manhole covers should be properly fitted/
in place.
6.14 It will be the responsibility of the testing team leader to instruct all members of
the testing team what actions are to be taken in the event of fire, accident or
6.15 Telephone numbers of First Aid/ Ambulance Fire Station and Hospitals should
6.16 In the event of any sign of abnormality, the source of supply for the particular
ITEM
STATE OF THE PLANT
7.0
7.3 For carrying out SCL’s and testing procedures which from a part of this
Testing Schedule, all the equipments covered by this schedule shall be dead
7.4 TRF I/C and TIE Bkrs are in withdrawn position and castle keys are kept
away in a secured place.
7.5 All circuit breakers of the switch gear concerned are in withdrawn
position.
7.6 Clearances are accorded from erection for carrying out testing.
ITEM
TEST METHOD
8.0
Checks and Tests To be Carried out:
1. Ensure that switchgear factory test reports are submitted and Vacuum
NTPC TESTING SCHEDULE TELANGANA
personnel.
38. Ensure that AC/DC higt pot test (high voltage test) is carried out
and following format is filled up.
39. Checking general cleanliness by opening inspection covers of bus
duct.
40. Check end termination tightness and clearance. Also ensure that
bi-metallic strips are provided if material of bus duct and same of
bus bar are different.
41. Ensure that breathers are provided and silica gel color is blue.
42. Check IR value of heater circuit.
43. Water tightness test for outdoor portion of bus duct by fire hose.
44. Air tightness to be carried out bus duct.
45. Check with Multi-meter phase to earth openness of bus before
charging.
46. Ensure that no part of bus duct is open and supports are
permanent.
47. Ensure that bus duct earthing is done.
R-E R-E
Y-E Y-E
B-E B-E
R-Y R-Y
R-B R-B
B-Y B-Y
Milli volt Drop test of Bus bar Joints :
ITEM
PROGRAM
9.0
NTPC TESTING SCHEDULE TELANGANA
9.1 When STATE OF THE PLANT is as per checks of item no. 6 and
program and as per the directive of the team leader. All the concerned
9.2
Date of commencement of the test shall be decided in the working group
meeting.
ITEM
RESULTS
10.0
NTPC TESTING SCHEDULE TELANGANA
10.1 On completion, the check lists and test procedures used for 11KV
enclosure of it.
ITEM
REINSTATEMENT & PRESERVATION.
11.0
NTPC TESTING SCHEDULE TELANGANA
11.1 When breakers are not required for service, they shall be kept in
withdrawn position.
11.2
Whenever any cable termination is to be done, it shall be with a
valid permit to work which will ensure that breaker is out of service.
ITEM
STAFFING, RESPONSIBILITIES AND COMMUNICATIONS
12.0
NTPC TESTING SCHEDULE TELANGANA
12.1 The Testing Team which has been approved by the station commissioning
panel shall consist of the following persons:
Name Department
a)
b)
c)
d)
Name Department
a)
b)
c)
d)