Sunteți pe pagina 1din 3

S.No.

Description of Equipment /
Bought-out Quantity
required/ Unit Major Description
ordered

Major Electricals Items


1 11 KV HT Switchgear Existing Modification Panel 2 Nos PANEL NO WILL BE 4UA PANEL NO:4 AND 6UA PANEL NO: 21.

2 11 KV HT Switchgear Panel (4UA) 6 Nos 01 NO 1250A INCOMER PANEL & 04 NOS 1250A O/G
TRABSFORMER FEEDER PANEL & 01 NO 1250A O/G CUSTOMER
USE FEEDER. FAULT LEVEL WILL BE 40KA FOR 1SEC.

3 11 KV HT Switchgear Panel (6UB) 6 Nos 01 NO 1250A INCOMER PANEL & 04 NOS 1250A O/G
TRABSFORMER FEEDER PANEL & 01 NO 1250A O/G CUSTOMER
USE FEEDER. FAULT LEVEL WILL BE 40KA FOR 1SEC.
TRANSFORMER WILL BE 1600KVA 11/0.433 KV,50Hz, VECTOR
4 11KV/0.433 KV Transformer (1600 KVA) 4 NO GROUP WILL BE DYN11. PERCENTAGE IMPEDANCE WILL BE 6.25%
AS PER IS-1180

5 11KV/0.433 KV Transformer (1000 KVA) 4 NO TRANSFORMER WILL BE 1000KVA 11/0.433 KV,50Hz, VECTOR
GROUP WILL BE DYN11. PERCENTAGE IMPEDANCE WILL BE 5% AS
PER IS-1180
PANEL NO WILL BE 34 BUS SECTION-A, 17 FOR BUS SECTION-B &
6 3.3 KV HT SWITCHGEAR Existing Modification Panel 3 Nos
PANEL NO 19 FOR BUS SECTION-C

3 NOS 1250A INCOMER PANELS, 02 NOS 1250A BUSCOUPLER


PANEL, 03 NOS 3.3/ROOT3 / 110/ROOT3 100 VA BUS-PT PANEL,
7 New 3.3KV HT Switchgear 32 Nos 15 NOS 630A COMPRESSOR MOTOR FEEDER, 3 NOS 630A SPARE
MOTOR FEEDER, 06 NOS 1250A CUSTOMER USE FEEDERS.
FAULT LEVEL WILL BE 40KA FOR 1SEC.

8 415V MCC STAGE-I Compressor House 1 No 2 X 2500A Incomer ,1 X 2500A Buscoupler with necessary O/G
Feeder. Fault Level will be 50KA For 1 sec

2 X 2500A Incomer ,1 X 2500A Buscoupler with necessary O/G


9 415V MCC STAGE-II Compressor House 1 No
Feeder. Fault Level will be 50KA For 1 sec

2 X 800A Incomer ,1 X 800A Buscoupler with necessary O/G


10 415V MCC STAGE-I Compressor For Unit-4
1 No
(Located at Stage-I Compressor House) Feeder. Fault Level will be 50KA For 1 sec

11 1 No 2 X 1600A Incomer ,1 X 1600A Buscoupler with necessary O/G


415V MCC STAGE-I Silo Area Feeder. Fault Level will be 50KA For 1 sec

2 X 1600A Incomer ,1 X 1600A Buscoupler with necessary O/G


12 415V MCC STAGE-II Silo Area 1 No
Feeder. Fault Level will be 50KA For 1 sec

13 360 KW Transport Air Compressor Motor 6 Nos MOTOR WILL BE 3.3 KV GRADE. MOTOR FULL LOAD CURRENT
WILL BE 78.5 A & NO LOAD CURRENT WILL BE APPROX 26A

MOTOR WILL BE 3.3 KV GRADE. MOTOR FULL LOAD CURRENT


14 300 KW Transport Air Compressor Motor 9 Nos
WILL BE 65.5 A & NO LOAD CURRENT WILL BE APPROX 24A

MOTOR WILL BE 415 V GRADE. MOTOR FULL LOAD CURRENT WILL


19 145 KW Instrument Air Compressor Motor 7 Nos
BE 232 A & NO LOAD CURRENT WILL BE APPROX 100A

20 Transport Air Driyer 15 Nos It WILL BE 415 V GRADE. Approx Lod Requirement will be 23 KW

21 Instrument Air Driyer 7 Nos It WILL BE 415 V GRADE. Approx Lod Requirement will be 26 KW

MAJOR 415V GRADE LT MOTOR LIST


MOTOR WILL BE 415 V GRADE. MOTOR FULL LOAD CURRENT WILL
22 90 KW Cooling Water Pump Motor For Stage-I 2 Nos
BE 153 A

MOTOR WILL BE 415 V GRADE. MOTOR FULL LOAD CURRENT WILL


23 75 KW Cooling Water Pump Motor For Stage-II 2 Nos
BE 128 A

24 11 KW Buffer Hopper Fluidisng Blower For Both Stage-I & II 10 Nos MOTOR WILL BE 415 V GRADE. MOTOR FULL LOAD CURRENT WILL
BE 20.4A

25 37 KW Transfer Water Pump for Stage-I Silo Area 2 Nos MOTOR WILL BE 415 V GRADE. MOTOR FULL LOAD CURRENT WILL
BE 66A

26 30 KW Transfer Water Pump for Stage-II Silo Area 2 Nos MOTOR WILL BE 415 V GRADE. MOTOR FULL LOAD CURRENT WILL
BE 51.3A

27 22 KW Silo Blower For Both Stage-I & II 12 Nos MOTOR WILL BE 415 V GRADE. MOTOR FULL LOAD CURRENT WILL
BE 37.8A

MOTOR WILL BE 415 V GRADE. MOTOR FULL LOAD CURRENT WILL


28 22 KW DE Fan For Both Stage-I & II 10 Nos
BE 37.8A
MOTOR WILL BE 415 V GRADE. MOTOR FULL LOAD CURRENT WILL
29 15 KW Ash Conditioner Water Pump Motor 6 Nos
BE 27.3

30 15 KW Floor Wash Water Pump Motor 4 Nos MOTOR WILL BE 415 V GRADE. MOTOR FULL LOAD CURRENT WILL
BE 27.3