Cerberus PRO
Tabular Annunciators
Models FT2008-U1/R1, FT2009-U1/R1
ARCHITECT AND ENGINEER SPECIFICATIONS
• Tabular annunciators come in either 16 zones or 32 zones,
and are available in either black or red
 16-zone annunciators: Models FT2008-U1/R1
 32-zone annunciators: Models FT2009-U1/R1

• Each module requires external power (24 Volts, DC) for operation
 System power is obtained from either a Cerberus PRO addressable
panel or from a separate 24VDC power supply
• Each tabular annunciator provides control of Acknowledge, Reset,
Silence/Unsilence and Lamp Test system functions remotely FT2008-R1
16-zone Tabular Annunciator
• Operated and supervised via a RS–485 communication bus
 Maximum eight (8) modules allowed on each RS–485 interface
• All user-control buttons are key-switch (T-45 key) protected
• Annunciator backboxes contain six (6) holes, allowing single-gang,
double-gang or 4-inch-square (10.2 cm.) mounting
• Set address and baud rate via programmable DIP switches
• Two (2) cable ties and one (1) end-of-line (EOL) jumper are included
FT2009-U1
• UL 864 9th Edition Listed, ULC-S527 3rd Edition Listed 32-zone Tabular Annunciator

Product Overview Specifications


The Tabular Annunciators from Siemens – Fire The Tabular Annunciators provide 16 zones (Model FT2008-
Safety allow system events sent from Cerberus U1/R1), or 32 zones (via Model FT2009-U1/R1) on Cerberus
PRO addressable panels to be displayed remotely PRO addressable panels. Each annunciator requires 24VDC
in real-time. The Model FT2008 series of tabular external power directly from either the panel, or from a
annunciators has 16 zones, and the Model FT2009 separate UL Listed 24VDC power-supply source.
series uses 32 zones. Up to two (2) light-emitting
Tabular annunciators easily and promptly display user-
diodes (LEDs) can be used per zone.
defined system commands: Reset; Silence/Unsilence;
Tabular Annunciators provide outputs for system Acknowledge, and Lamp Test. The system commands are
and zone status, are available in black or red. For operated and supervised by a RS–485 interface.
Cerberus PRO 50-point addressable panels (Model
FC901), a built-in RS−485 interface controls the Model FT200x-series tabular annunciator backboxes have
operation and supervision of the 16-zone and 32- six (6) mounting holes, allowing for single-gang, double-
zone Tabular Annunciators. gang or 4-inch-square (10.2 cm.) mounting. Two (2) cable
ties and one (1) EOL jumper are included per order.
For Cerberus PRO 252 / 504-point panels, a
RS−485 interface module (Model FCA2016-U1) All annunciator control features on all tabular annunciators
must be ordered, so the tabular annunciators can are key-switch protected (T-45 key), and its front-end
have the capability to receive communication from design is comparable to the modern, sleek appearance of
the panel. the Cerberus PRO addressable control panels.

Cerberus PRO 9825


Fire Safety Products Tabular Annunciators

Answers for infrastructure


Technical Data Temperature and Humidity Range
Unit The Cerberus PRO Tabular Annunciators are UL
Operating Voltage: 16 ─ 30 VDC Listed for indoor dry locations within a temperature
(at 24VDC, nominal)
range of 120 +/- 3°F (49 +/- 2°C) to 32+/- 3°F (0 +/- 2°C)
Activation Current: for and a relative humidity of 93 +/- 2% at a temperature
Supply FT2008-U1/R1
65mA
Inputs of 90 +/- 3°F (32 +/- 2°C).
Activation Current: for
105mA
FT2009-U1/R1 – Special Note for Applications in Canada –
Operating Current: The 16-zone and 32-zone Tabular Annunciators are
25mA
(quiescent)
used optionally in the provinces, and can be utilized
 Design for display only.
RS-485
interface:  Admissible 14 ─ 18, 28 AWG In order to comply with ULC regulations, each
Connections cross-section [American Wire Gauge] tabular annunciator must be housed in a lockable
cable ULC-S527 Listed enclosure.
Operating
Indoor / dry
Location:
Operating
General Temperature:
0° – 120°F
(0° – 49°C)
Details for Ordering
Properties Storage 0° – 140°F Part
Model Description
Temperature: (0° – 60°C) Number
Humidity: ≤95 %, relative 16-zone Tabular
FT2008-U1 S54400-A143-A1
Annunciator, Black
Dimensions: 8.1” -x- 7.4” -x- 2.0”
{ W-x-H-x-D } for 16-zone Tabular
(20.6 cm. -x- 18.7 cm. -x- 5.1 cm.) FT2008-R1 S54400-A144-A1
FT2008-U1/R1 Annunciator, Red
Dimensions: 11.4” -x- 7.4” -x- 2.0”
{ W-x-H-x-D } for 32-zone Tabular
Physical FT2009-U1 S54400-A145-A1
FT2009-U1/R1 (29.0 cm. -x- 18.7 cm. -x- 5.1 cm.) Annunciator, Black
Properties Weight: 2.6 Lbs. (1.2 kg), unit 32-zone Tabular
FT2009-R1 S54400-A146-A1
{FT2008-U1/R1} Approximately 4 Lbs. (1.8 kg), packaged Annunciator, Red

Weight: 3.8 Lbs. (1.7 kg), unit 1HU Enclosure Kit, Black
{FT2009-U1/R1} Approximately 5 Lbs. (2.3 kg), packaged FHB2001-U1 (1 Qty.)
FHK2001-U3 S54400-C54-A1 FHD2001-U3 (1 Qty.)
Includes: FHD2004-U1 (1 Qty.)
FHD2006-U1 (1 Qty.)

1HU Enclosure Kit, Red


Related Documentation FHB2001-R1 (1 Qty.)
FHK2001-R3 S54400-C54-A2 FHD2001-R3 (1 Qty.)
Data Sheet Number Includes: FHD2004-U1 (1 Qty.)
Cerberus PRO System Enclosures ( UL | ULC) 9807 FHD2006-U1 (1 Qty.)

Cerberus PRO 50-point addressable FACP 9813


Cerberus PRO 252 /504-point
9815
addressable (fire-only) FACP
Cerberus PRO Intelligent Voice (IVC)
9821
Communication panels

NOTICE ─ The information contained in this data-sheet document is intended only as a summary, and is
s Cerberus PRO subject to change without notice. The devices described here have specific instruction sheets that cover
various technical, limitation and liability information.
Siemens Industry, Inc. ─ Building Technologies Div. Copies of these instruction sheets and the General Product Warning and Limitations document,
8 Fernwood Road • Florham Park, NJ 07932 which also contains important information, are provided with the product and, are available from
the Manufacturer.
Tel: (973) 593-2600 • Fax: (908) 547-6877
Information contained in these documents should be consulted before specifying or using the product.