ABSTRACT
This paper proposes the Finite control set function of the proposed FCS-MPC uses the
Model Predictive Control (FCS-MPC) with 27 possible switching states generated by T-
delay compensation for three-phase three- Type NPC, the optimal switching state is
level T-Type NPC inverter (T-Type NPC) of selected in each sampling time that
grid-connected photovoltaic systems (PV). minimizes the cost function. The proposed
The proposed FCS-MPC controls the FCS-MPC has also proposed the delay
objectives: current tracking control, DC-link compensation with two-step prediction
capacitor voltage balance, the reduction of horizon at time k+2 to reduce the total
switching frequency to ensure issues of the harmonic distortion (THD) of the grid current.
power quality and improve the efficiency of The proposed FCS-MPC is verified by using
grid-connected of PV system. The cost Matlab/Simulink.
Keywords: Finite control set Model predictive control, reduction of switching frequency, DC-
link Capacitor voltage balance, T-Type NPC, PV system.
1. INTRODUCTION
In the recent decades, photovoltaic system these disadvantages, the three-phase three-level
(PV system) quickly has been developed about the T-Type Neutral Point Clamp inverter (T-Type
installed power, as well as the penetration into the NPC), shown in Figure 1, is proposed, which has
electrical grid. Photovoltaic is the distributed the advantages about the low THD of output
generation, thus the stability when connecting the current, high efficiency with switching frequency
grid with the photovoltaic is a problem that worth in 4kHz-30kHz, small size, low investment cost
to concern about at this moment. Due to the [1], [2], [3].
restrict of the two-level inverter is the output The structure of a T-Type NPC includes two
current with high THD distortion, the large size DC-link capacitors connected in series, thus the
filters is chosen, however which causes some small voltage vectors and medium voltage vectors
problems: reduction of the efficiency of PV of T-Type NPC produce the voltage oscillations
system, high cost, bulky system [1], [2]. To solve
Trang 5
SCIENCE & TECHNOLOGY DEVELOPMENT, Vol.18, No.K6 - 2015
of the mid-point “O” of dc-link capacitor, making FCS-MPC has presented with the limited
the unbalanced DC-link capacitors [5], [6]. The switching states of the converter for solving the
voltage oscillations of the mid-point of dc-link optimization problem from a discrete model of the
capacitor voltage causes the voltage stress on the system [8], [10], [11], [14], [15]. Many researches
capacitors and the semiconductor devices [4], [5]. with FCS-MPC have been presented for current
Namely the failure in switching and the increase tracking control and DC-link capacitor voltage
of THD of output current, due to the low-order balance [10], [13], [21], [14]; current tracking
harmonics of output voltage [3], [5], [6]. Pulse control and reduce switching frequency [7]. The
width modulation (PWM) is used to balance FCS-MPC with delay compensation (two-step
capacitor voltage with three-level NPC inverter prediction horizon) has presented to reduce the
THD of current [8], [11], [14], [15]. The FCS-
[4]; three-level T-Type NPC [2], [3], [5].
MPC with delay compensation will cause a big
However, the PWM algorithm has the complex
quantity of switching states due to two-step
calculation and is not easy to implement for the
prediction horizon: k+1, k+2, for three-level T-
controlled objects that are nonlinearities and have
Type NPC, number of the switching states can
many constraints [7], [8].
correspond to 272 = 729, the computation amount
to select optimal switching state is massive.
This paper focuses on the control for the
objectives of grid-connected of PV system:
current tracking control, balancing dc-link
capacitor voltage, the reduction of switching
frequency by using the proposed FCS-MPC with
delay compensation. In order to reduce the
computation amount, this paper proposes that the
values of current and dc-link capacitor voltages at
Figure 1. Three-level T-Type NPC inverter for three-
time k+1, will be estimated based on the optimal
phase grid-connected of PV system
switching state at time k-1, then use these
Model predictive control (MPC) bases on the estimated values to predict the values at time k+2.
good mathematical model of system to support the Therefore, the proposed FCS-MPC only chooses
exact and complete the prediction about the future 27 switching states of T-Type NPC for two-step
behaviors of system in control. In addition, the prediction horizon for the reduction of the
development of the microprocessor’s speed computation amount in comparison [8], [15]. The
allows calculating quickly the MPC [9], [10]. This optimal switching state is selected that minimizes
makes MPC more and more popular in many the cost function of the proposed FCS-MPC. The
fields of the power electronics. MPC have distinct change of weighting factor in the interrelationship
advantages: simple, easy to implement, well between the objectives of cost function, will prove
control with the systems that are non-linear and the flexibility of the proposed FCS-MPC for
have many constraints, fast responds with solving the problems of power quality and
changing of the system, sustainable when enhancing efficiency of grid-connected for PV
compared to the classic control uses the system via the reduction of switching frequency.
proportional - integral controller (PI) and the 2. MODEL OF T-TYPE NPC FOR GRID-
PWM modulators [8], [9], [11], [12]. CONNECTED OF PV SYSTEM
2.1 Model of the system
Trang 6
TAÏP CHÍ PHAÙT TRIEÅN KH&CN, TAÄP 18, SOÁ K6- 2015
T-Type NPC for grid-connected of PV Grid current and grid voltage vector are
system using L-filter is illustrated in Figure 1, the defined [14], [17]:
dc-link voltage is assumed constant, we have the 2
i (ia aib a 2ic ) (5)
relation between voltage and current of grid- 3
connected of PV system in (1) [11], [14], [17]: 2
e (ea aeb a 2 ec ) (6)
di 3
vao L a Ria ea v No With,
dt
2 2
dib (1) (vNo avNo a 2 vNo ) vNo (1 a a 2 ) 0(7)
vbo L Rib eb vNo 3 3
dt From (4) (5) (6) (7), mathematical model of
di the grid-connected for PV system is re-written:
vco L c Ric ec v No
dt di
v L Ri e (8)
ia, ib, ic : grid current dt
ea, eb, ec : grid voltage Equation (8) demonstrates the mathematical
model of the grid-connected for PV system with
L,R : filter inductance and filter resistance of
T-Type NPC inverter. With the voltage vector is
L-filter
defined by (2), there are totally 19 separate
vao, vbo, vco : output voltage of T-Type NPC voltage vectors for corresponding to 27 switching
The voltage vector of T-Type NPC is defined: combinations of T-Type NPC as Figure 2.
2
v (Vao aVbo a 2Vco ) (2) 2.2 Grid-connected control for PV system
3j2π/3
Where, a = e Voltage oriented control (VOC) method is
Considering a constant dc-link voltage, and proposed to control grid-connected for PV
balanced capacitor voltages, the voltages system. According to [16], the instantaneous
generated by the T-Type NPC at the inverter active and reactive powers in the rotating dq frame
terminals are obtained in (3) and Table 1 [14]. injected into the grid by PV system are given in
V (3) (9):
Vxo S x dc
2
Table 1. Switching state of T-Type NPC,
with x = a, b, c [1]
1 1 1 0 0 Vdc/2
0 0 1 1 0 0
ed, eq: grid voltage in the rotating dq frame The proposed FCS-MPC for T-Type NPC of
id, iq : grid current in the rotating dq frame the grid-connected of PV system is illustrated in
Figure 4. The proposed FCS-MPC for T-Type
Assuming that the d axis is perfectly aligned
NPC of the grid-connected of PV system uses 27
with the grid voltage, thus eq = 0. The active
switching states corresponding to 19 separate
power and reactive power are rewritten:
voltage vectors as Figure 2. The optimal switching
3
P ed id state is selected that minimizes the cost function.
2
(10) The proposed FCS-MPC for grid-connected of PV
3 system produces the optimized switching state
Q ed iq
2 directly to the T-Type NPC, without using the
From (10), we can independently control
between active and reactive powers with id and iq modulation techniques such as CB-PWM or
currents. We assume that: the dc-link voltage is Space Vector Modulation (SVM).
constant, delivering symmetrical and balanced ac The proposed FCS-MPC for grid-connected
currents to the grid, so we can skip the calculation of PV system has two main assumptions: keeping
of the reference grid current (i*dq) [13]. In this the stable DC-link voltage, symmetrical and
paper, we only choose i*dq as an external reference balanced grid voltages, so we treat only i*dq(k) for
for implementing the proposed FCS-MPC, as controlling the grid-connected of PV system, not
shown in Figure 4. operating in islanded case with grid systems.
3. THE PROPOSED FCS-MPC From Figure 4, grid voltage and grid current are
measured at time k, which are used for predicting
3.1 Finite control set model predictive
the grid current at time k+2 and the predicted grid
control (FCS-MPC) with delay
current shows in stationary αβ frame. The
compensation
reference grid current in the dq frame have to
FCS-MPC for the current tracking control show in stationary αβ frame for implementing the
presented in [11], [14]. x*(k) represents the proposed FCS-MPC, so we use Phase-Locked-
reference values of the desired control object, x(k) Loop block (PLL) to synchronize the phase angle
is the measured value at time k, x(k+2) is the (θ) between the grid system and the PV systems
predicted value for possible switching states of T- [16]. We use Park and Clark transformations for
Type NPC inverter at time k+2 (two-step the conversion between the abc, αβ, dq frames
prediction horizon). The error between x(k+2) and with phase angle (θ) calculated by PLL blocks.
x*(k) is obtained to minimize the cost function The cost-function of the proposed FCS-MPC
and the switching state that minimizes the cost produces the optimal switching state based on the
function will be chosen. FCS-MPC block diagram reference grid current and the predicted grid
is illustrated in Figure 3 [9]. current, or other controlled objectives. In this
paper, x(k) presents for the desired control
objectives: grid current, DC-link voltage,
switching frequency.
Trang 8
TAÏP CHÍ PHAÙT TRIEÅN KH&CN, TAÄP 18, SOÁ K6- 2015
Figure 4. The proposed FCS-MPC applies for T-Type NPC of grid-connected of PV System
Trang 9
SCIENCE & TECHNOLOGY DEVELOPMENT, Vol.18, No.K6 - 2015
For a small enough Ts, we can approximate time k-1 to thereby calculate switching instants for
e(k+1) ≈ e(k), equation (13) is rewritten: each switching state. The cost function for
RTs T reducing the switching frequency is defined:
i p (k 2) (1 )i(k 1) s (v(k 1) e(k)) (15)
L L g 2 sw . N k 2
From equation (15) shows that the different (22)
switching states of T-Type NPC inverter will λsw : weighting factor of the reduction of
produce the different values of predicted grid switching frequency
current at time k+2. The cost function for current Nk+2 : the total switching instants is calculated
tracking control is defined with the predicted grid by the change between of each expected switching
current and the reference grid current at time k+2, state of the 27 possible switching states generated
gives in (16): by T-Type NPC with optimal switching state was
g1 (i* (k 2) ip (k 2))2 (i* (k 2) ip (k 2))2 (16) chosen at time k-1.
i p ( k 2) ip ( k 2) jip (k 2) (17) 3.4 Balancing DC-link capacitor voltages
i* (k 2) i* (k 2) ji* (k 2) (18) Assuming the DC-link capacitor voltage is
ipα(k+2), ipβ(k+2) of the predicted grid current constant. From Figure 1, the prediction for the
and i*α(k+2), i*β(k+2) of the reference grid current voltage of each capacitor at the time k+1 is [14]:
show in αβ frame at time k+2. T T
vC1(k 1) vC1(k) s iC1(k) vC1 (k) s io (k)
C 2C
The i*(k+2) at time k+2 can be determined by (23)
Ts T
Lagrange extrapolation formula as follows [14]: vC2 (k 1) vC2 (k) iC 2 (k) vC2 (k) s io (k)
C 2C
i* (k 2) 6i* (k ) 8i* (k 1) 3i * (k 2) (19) vC1, vC2 : DC-link capacitor voltage
For a small enough Ts, we can approximate C : capacitance of each DC-link capacitor
i*(k+2) ≈ i*(k) [14], [17]. The cost function for
io : current at the mid-point of dc-link
current tracking control is rewritten:
capacitor “O”
g1 (i* (k ) ip (k 2))2 (i* (k ) ip ( k 2)) 2 (20)
The current at the mid-point of dc-link
3.3 Reduction of switching frequency capacitor “O” can be defined from currents ia, ib,
The switching frequency for MPC is limited ic on each phase at the current time and switching
to half the sampling frequency (fs) [14], [17]. The state depended function Sxo , with switching state
switching frequency is the average switching Sx in Table 1 [14]:
frequency value of power semiconductors of io (k ) Sao (k )ia (k ) Sbo (k )ib (k ) Sco (k )ic (k ) (24)
inverter. Switching frequency for FCS-MPC for
Sxo = 1 if Sx=0; Sxo = 0 if Sx = 1 or -1; (25)
T-Type NPC with 12 power semiconductors
(IGBTs) is calculated [11], [17]: with x = a,b,c
N (21) The proposed FCS-MPC will delay 01
f sw
12* t sampling period (Ts), thus we will predict the
N : the total switching instants of 12 IGBTs
future value k+2 based on the estimated value at
during period of t
the time k+1. DC-link capacitor voltage is
t : time of simulation or experiment predicted at time k+2 [14]:
The total switching instants N should be
T T
decreased to reduce the switching frequency. vC1(k 2) vC1(k 1) s iC1(k 1) vC1(k 1) s io (k 1)
C 2C (26)
Comparing the 27 switching states of T-Type Ts Ts
vC2 (k 2) vC2 (k 1) iC2 (k 1) vC2(k 1) io (k 1)
NPC inverter with optimum switching state at C 2C
Trang 10
TAÏP CHÍ PHAÙT TRIEÅN KH&CN, TAÄP 18, SOÁ K6- 2015
Trang 11
SCIENCE & TECHNOLOGY DEVELOPMENT, Vol.18, No.K6 - 2015
frequency [7], [14]. We can see that the switching the THD of grid current is higher than
frequency depends on the weighting factors λsw in implemented by λDC = 8, λsw = 0.1, shown in
the cost function. With the same capacitor balance Figure 5(a) and Figure 5(b).
weighting factor λDC = 8, and λsw = 1.5 produces
Grid current - iabc (A)
ia
ib
ic
(a)
Figure 5. Waveform and THD of grid current in abc frame: (a) λDC = 8, λsw = 1.5; (b) λDC = 8, λsw = 0.1
Trang 12
TAÏP CHÍ PHAÙT TRIEÅN KH&CN, TAÄP 18, SOÁ K6- 2015
Trang 13
SCIENCE & TECHNOLOGY DEVELOPMENT, Vol.18, No.K6 - 2015
Trang 14
TAÏP CHÍ PHAÙT TRIEÅN KH&CN, TAÄP 18, SOÁ K6- 2015
TÓM TẮT:
Bài báo này đề xuất giải thuật điều khiển Control (FCS-MPC) có bù trễ cho nghịch lưu
dự báo Finite control set Model Predictive 3 pha 3 bậc T-Type NPC (T-Type NPC) của
Trang 15
SCIENCE & TECHNOLOGY DEVELOPMENT, Vol.18, No.K6 - 2015
hệ thống năng lượng mặt trời kết nối lưới. cắt tối ưu được chọn trong mỗi thời gian lấy
FCS-MPC được đề xuất cho điều khiển nhiều mẫu là trạng thái mà ở đó hàm mục tiêu có
đối tượng: điều khiển bám dòng điện, cân giá trị bé nhất. Giải thuật FCS-MPC được đề
bằng điện áp tụ DC-link, giảm tần số đóng cắt xuất là có bù trễ với hai thời khoảng dự báo
để qua đó đảm bảo các vấn đề chất lượng tại thời điểm k+2 để qua đó giúp giảm méo
điện năng và hiệu suất của hệ thống năng dạng sóng hài của dòng điện lên lưới. FCS-
lượng mặt trời kết nối lưới. Hàm mục tiêu của MPC được đề xuất sử dụng phần mềm
FCS-MPC sử dụng 27 trạng thái đóng cắt Matlab/Simulink để kiểm chứng.
khác nhau của T-Type NPC, trạng thái đóng
Từ khóa: Finite control set Model predictive control, giảm tần số đóng cắt, cân bằng điện áp
tụ DC-link, nghịch lưu T-Type NPC, hệ thống năng lượng mặt trời.
REFERENCES
[1]. Schweizer, M.; Kolar, J.W., Design and connected Three-Level Inverters using a
Implementation of a Highly Effiient Three- Discontinuous Pulse Width Modulation,
Level T-Type Converter for Low-Voltage Vehicle Power and Propulsion Conference
Applications, Power Electronics, IEEE (VPPC), IEEE Transactions on, pp. 638 -
Transactions on, pp. 899 - 907, June 2012. 642, Oct. 2012.
[2]. June-Seok Lee; Kyo-Beum Lee, New [6]. Bin Wu, High-power converters and AC
Modulation Techniques for a Leakage drivers, IEEE press and John Wiley & Sons
Current Reduction and a Neutral-Point Ltd, 2006.
Voltage Balance in Transformerless [7]. Cortes, P.; Vattuone, L.; Rodriguez, J., A
Photovoltaic Systems Using a Three-Level comparative study of Predictive Current
Inverter, Power Electronics, IEEE Control for Three-Phase Voltage Source
Transactions on, pp. 1720 - 1732, June 2013. Inverters based on switching frequency and
[3]. Ui-Min Choi; Blaabjerg, F.; Kyo-Beum Lee, current error, Power Electronics and
Method to Minimize the Low-Frequency Applications, IEEE Transactions on, pp. 1 -
Neutral-Point Voltage Oscillations with 8, Aug. 30 2011-Sept. 1 2011.
Time-Offset Injection for Neutral-Point- [8]. Yaramasu,V; Wu, B.; Rivera,M.;
Clamped Inverters, Industry Applications, Rodriguez,J.; Wilson,A., Cost-Function
IEEE Transactions on, pp. 1678 - 1691, based Predictive Voltage Control of Two-
August 2014. Level Four-Leg Inverters using Two Step
[4]. June-Seok Lee; Kyo-Beum Lee, A Carrier- Prediction Horizon for Standalone Power
Based PWM Method for Neutral-Point Systems, Applied Power Electronics
Ripple Reduction of a 3-Level Inverter, Conference and Exposition (APEC), 2012
Energy Conversion Congress and Exposition Twenty-Seventh Annual IEEE, IEEE
(ECCE), IEEE Transactions on, pp. 2095 - Transactions on, pp. 128 - 135, Feb. 2012.
2100, Sept. 2014. [9]. Vazquez,S.; Leon,J.I.; Franquelo,L.G. ;
[5]. Hyun-Hee Lee, Ui-Min Choi, Kyo-Beum Rodriguez,J.; Young,H.A.; Marquez,A.;
Lee, Neutral-Point Voltage Control for Grid Zanchetta,P., Model Predictive Control A
Trang 16
TAÏP CHÍ PHAÙT TRIEÅN KH&CN, TAÄP 18, SOÁ K6- 2015
Trang 17