Sunteți pe pagina 1din 4

Datasheet

Surge Arrester Monitoring system


SAM 3.0

Technical Data

The surge arrester monitoring system, SAM 3.0 is used


to measure operating current of the surge arrester and
to r­ egister discharge events. The system classifies ­o ccurring
surge current pulses in three classes and saves the over-
voltage events with time and date information (time stamp).
It consists of a current sensor with selectable cable lengths
and a display device which can be mounted sepa­r ately from
the arrester.
The SAM 3.0 is used for monitoring of surge arresters in
medium and high voltage networks, and in gas-insulated
switchgear.

Surge event counter

-
Classification of overvoltage Class 1 0.1–1 kA
Measurement of current amplitudes Class 2 1–10 kA
Operating current at alternating voltage Class 3 10–100 kA

-
Threshold (50 Hz sinus) 100 A
Record and classification of Overlap between current classes < 20 %
Electrical surge events Time format of saved events YYYY:MM:DD hh:mm

-
storage capacity, non-volatile 2000 events
Application
Outdoor and Indoor Operating current at alternating voltage
measurement range (peak value) 0–20 mA
accuracy of measurement < ±5 % of measured value
and ±0.1 mA below 40°C
< ±10 % of measured value
and ±0.1 mA above 40°C
frequency range 16.7 bis 60 Hz

General Data
Weight of display unit ca. 680 g
ca. 950 g with support
Weight of sensor ca. 250 g (without cable)
Ambient temperature –40 °C to +55 °C (no visual display
at temperatures below –20 °C)
Altitude < 1800 m
Energy supply 1 High energy Lithiumbattery 3.6 V
Replacement of battery 2 years at normal operation
Technical Data

Selection
There are mounting kits for the sensors available for outdoor
Tests arresters, gas insulated surge arresters and POLIM-D..PI-2
Degree of protection as well as POLIM-D..PI-3.
according to IEC 90529 IP65 Existing sensor cable lengths are 1, 7, 10 and 20 meters.
EMV Tests IEC 60664-1:07 cl. 6.1.2.2.1 For outdoor applications and in gas-insulated switchgear,
IEC 61000-3-2:05 (ed.3) a support is available. The distance of 230 mm between the
IEC 61000-3-3:94+A1:01 +A2:05  11.5 mm holes of the support corresponds to distance
(Cons. ed.1.2) ­d imension of the surge-counters type SCE, SCF and SCM.
IEC 61000-6-2:05 (ed.2) For an optimal monitoring of surge arresters and for recor-
IEC 61000-6-3:06 (ed.2) Class B ding of events, a setup according to Figure 1 is recommend.
IEC 61326-1:05 (ed.1)
Figure 1: Setup with one sensor per surge arrester

2  SAM 3.0  |  Surge Arrester Monitoring system


Dimensions

Figure 2: Display unit

Figure 3: Display unit with support

Figure 4: Sensor

Surge Arrester Monitoring system | SAM 3.0 3


For further information please contact: Note

1HC0076312 E01 AB
We reserve the right to make technical changes or modify the contents of
ABB Switzerland Ltd this document without prior notice. With regard to purchase orders, the
High Voltage Products ­a greed particulars shall prevail. ABB AG does not accept any responsibility
whatsoever for potential errors or possible lack of information in this docu-
Surge Arresters
ment. We reserve all rights in this document and in the subject matter and
Jurastrasse 45 ­illustrations contained therein. Any reproduction, disclosure to third parties
CH-5430 Wettingen/Switzerland or utilization of its contents – in whole or in parts – is forbidden without prior
Tel. +41 58 585 29 11 written consent of ABB AG.

Fax +41 58 585 55 70 Copyright © 2012 ABB


E-mail: sales.sa@ch.abb.com All rights reserved

www.abb.com/arrestersonline

Our products are certified according to ISO 9001, 14001, 18001, IRIS
For detailed information for dimensioning of our products
see following ABB documents:
– Application guidelines Overvoltage protection Metal oxide
surge arresters in medium voltage systems
– Application guidelines Overvoltage protection Metal oxide
surge arresters in railway facilities

For pdf or print version please send E-mail to:


sales.sa@ch.abb.com