Documente Academic
Documente Profesional
Documente Cultură
Sheet No. 1
I. DESIGN CRITERIA
V. ANALYSIS OF TRANSOM
A. Analysis of Intermediate Transom..................................... V.A Int. Transom 1/7 - 7/7
B. Analysis of Sill Transom......................................................... V.B Sill Transom 1/7 - 7/7
B. Analysis of Head Transom................................................... V.B Head Transom 1/6 - 6/6
Sheet No. 2
IX. APPENDICES
A. ENGINEERING DATA
ADM: Table 2-24
ADM: Table 3.3-1
ASTM E 1300: Table 1 to Table 4
ASTM E 1300: Table 5 to Table 6
ASTM E 1300: APPENDIXES, X2
ASTM E 1300: APPENDIXES, X9
ASTM E 1300: APPENDIXES, X8
AAM TIR A9-91: Table 11 and Table 4
1.0 REFERENCES
2.3 WIND
2.3.1 Zone -------------------------Zone II
2.3.2 Basic Wind Speed -------------V=250kph
2.3.3 Exposure Category ------------Exposure B
II. DESIGN WIND PRESSURE FOR ALLOWABLE STRESS DESIGN (ASD) APPLICATON
Note: 0.6 reduction factor was used for Allowable Stress Design (ASD) application.
II.A Wind Load 1/1
III. ANALYSIS OF GLASS
GLASS
UNDER
ANALYSIS
NOTE: The glass was analyzed using ASTM E-1300 that is subjected to a corner element wind load of -3.41kPa.
I. DESIGN PARAMETERS:
III.A Glass 1/3
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Glass
Date: 18-Feb-20
• FIG.2.1 : ASTM E1300-04 FIG.A1.8 : Non Factored Load Chart (upper chart ) for
6mm Glass with Four Sides Simply Supported.
3.20
III.A Glass 2/3
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Glass
Date: 18-Feb-20
2 3
ASTM X2.2 r0 = 0.553 – 3.83 ( a/b) +1.11 ( a/b ) – 0.0969 (a/b )
= -1.02
2 3
ASTM X2.3 r1 = - 2.29 + 5.83 ( a/b ) - 2. 17 ( a/b ) + 0.2067 (a/b )
= -0.02
2 3
ASTM X2.4 r2 = 1.485 – 1.908 ( a/b) +0.815 ( a/b ) – 0.0822 (a/b )
= 0.76
2 4
ASTM X2.5 x = ln{ln [ q (ab) / E t ]}
= 1.15
ASTM X2.1 δmax = t1 exp ( ro + r1 x + r2 x2 )
= 5.78 mm
Since δmax < δallow Therefore, glass is SAFE on deflection at full design load.
2 3
ASTM X2.2 r0 = 0.553 – 3.83 (a/b) + 1.11 (a/b) – 0.0969 (a/b)
= -1.02
2 3
ASTM X2.3 r1 = - 2.29 + 5.83 (a/b) - 2. 17 (a/b) + 0.2067 (a/b)
= -0.02
2 3
ASTM X2.4 r2 = 1.485 – 1.908 (a/b) + 0.815 (a/b) – 0.0822 (a/b)
= 0.76
2 4
ASTM X2.5 x = ln{ln [ q1 (ab) / E t ]}
= 0.90
ASTM X2.1 δmax/2 = t1 exp (ro + r1 x + r2 x2)
= 3.94 mm
Since δmax/2 < δallow/2 Therefore, glass is SAFE on deflection at half design load.
III.A Glass 3/3
IV. ANALYSIS OF MULLION
Tributary Area
I. DESIGN PARAMETERS:
IV.A Int. Mullion 1/10
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Mullion @ Corner Wall Element
Date: 18-Feb-20
IV.A Int. Mullion 2/10
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Mullion @ Corner Wall Element
Date: 18-Feb-20
TABLE 2.4 : Torsional Constant for Open Parts ( Refer Figure 2.1 )
no. length of thickness of length over Torsional Constant
item of items element element thickness b/t < 10 b/t > 10
3
n b t b/t n(1/3-0.2t/b)bt nbt3/3
TABLE 2.5 : Torsional Constant for Open Parts ( Refer Figure 2.2 )
no. length of thickness of length over Torsional Constant
item of items element element thickness b/t < 10 b/t > 10
n b t b/t n(1/3-0.2t/b)bt3 nbt3/3
Jf = 2298.10 mm4
IV.A Int. Mullion 3/10
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Mullion @ Corner Wall Element
Date: 18-Feb-20
2.8 Member : Mullion (23mm thick x 28mm & 6mm thick x 25mm Flat bar Steel Insert)
• FIGURE 2.3 :
IV.A Int. Mullion 4/10
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Mullion @ Corner Wall Element
Date: 18-Feb-20
4
Actual Deflection dmax = 5 WwL Lu
384 Ea Ix-tot
= 16.024 mm
ADM Table 2-24 Sec. 3.4.2 Tension in Beam "Ft" ( Extreme Fiber , Net Section )
Slenderness, S = Lb
ry-m
= 29.143
Lower Slenderness Limit, S1 = 22.00
Upper Slenderness Limit, S2 = 94.00
S1 < S < S2
IV.A Int. Mullion 5/10
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Mullion @ Corner Wall Element
Date: 18-Feb-20
= Mmax Ix-m
Max. Moment carried by Male Mullion, Mmax-m
Ix-tot
= 1347345.40 N-mm
fb < Fb SAFE
ADM Table 2-24 Sec. 3.4.2 Tension in Beam "Ft" ( Extreme Fiber , Net Section )
IV.A Int. Mullion 6/10
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Mullion @ Corner Wall Element
Date: 18-Feb-20
Slenderness, S = Lb
ry-f
= 37.825
Lower Slenderness Limit, S1 = 22.00
Upper Slenderness Limit, S2 = 94.00
S1 < S < S2
fb < Fb SAFE
IV.A Int. Mullion 7/10
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Mullion @ Corner Wall Element
Date: 18-Feb-20
Total Axial Dead load, RDL = 1.1 (Wglass + Wmullion + Wtransom + Wms)
= 1075.48 N
ADM Table 2-24 Sec. 3.4.7 Compression in column " Fa1" ( Axial Gross Section )
(compression in column, axial : all column)
Slenderness, S = k Lb
r
= 29.14
Lower Slenderness Limit, S1 = 0.00
Upper Slenderness limit, S2 = 78.00
S1 < S < S2
ADM Table 2-24 Sec. 3.4.9 Compression in Column Elements " Fa2" ( Gross Section )
(compression in column elemets, gross section : flat elements supported on both edge)
fa < Fa SAFE
IV.A Int. Mullion 8/10
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Mullion @ Corner Wall Element
Date: 18-Feb-20
ADM Table 2-24 Sec. 3.4.7 Compression in column " Fa1" ( Axial Gross Section )
(compression in column, axial : all column)
Slenderness, S = k Lb
r
= 37.83
Lower Slenderness Limit, S1 = 0.00
Upper Slenderness limit, S2 = 78.00
S1 < S < S2
ADM Table 2-24 Sec. 3.4.9 Compression in Column Elements " Fa2" ( Gross Section )
(compression in column elemets, gross section : flat elements supported on both edge)
fa < Fa SAFE
IV.A Int. Mullion 9/10
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Mullion @ Corner Wall Element
Date: 18-Feb-20
fa fb
+ = 0.70 < 1.00 SAFE
Fa Fb
fa fb
+ = 0.68 < 1.00 SAFE
Fa Fb
IV.A Int. Mullion 10/10
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Mullion @ Typical Wall Element
Date: 18-Feb-20
Tributary Area
I. DESIGN PARAMETERS:
IV.B Int. Mullion 1/10
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Mullion @ Typical Wall Element
Date: 18-Feb-20
IV.B Int. Mullion 2/10
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Mullion @ Typical Wall Element
Date: 18-Feb-20
TABLE 2.4 : Torsional Constant for Open Parts ( Refer Figure 2.1 )
no. length of thickness of length over Torsional Constant
item of items element element thickness b/t < 10 b/t > 10
n b t b/t n(1/3-0.2t/b)bt3 nbt3/3
TABLE 2.5 : Torsional Constant for Open Parts ( Refer Figure 2.2 )
no. length of thickness of length over Torsional Constant
item of items element element thickness b/t < 10 b/t > 10
n b t b/t n(1/3-0.2t/b)bt3 nbt3/3
Jf = 2298.10 mm4
IV.B Int. Mullion 3/10
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Mullion @ Typical Wall Element
Date: 18-Feb-20
2
Maximum Design Moment, Mmax = WwL Lu
8
= 1492566.08 N-mm
IV.B Int. Mullion 4/10
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Mullion @ Typical Wall Element
Date: 18-Feb-20
ADM Table 2-24 Sec. 3.4.2 Tension in Beam "Ft" ( Extreme Fiber , Net Section )
Slenderness, S = Lb
ry-m
= 29.143
Lower Slenderness Limit, S1 = 22.00
Upper Slenderness Limit, S2 = 94.00
S1 < S < S2
IV.B Int. Mullion 5/10
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Mullion @ Typical Wall Element
Date: 18-Feb-20
= Mmax Ix-m
Max. Moment carried by Male Mullion, Mmax-m
Ix-tot
= 790626.55 N-mm
fb < Fb SAFE
ADM Table 2-24 Sec. 3.4.2 Tension in Beam "Ft" ( Extreme Fiber , Net Section )
Slenderness, S = Lb
ry-f
= 37.825
Lower Slenderness Limit, S1 = 22.00
Upper Slenderness Limit, S2 = 94.00
S1 < S < S2
IV.B Int. Mullion 6/10
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Mullion @ Typical Wall Element
Date: 18-Feb-20
fb < Fb SAFE
Total Axial Dead load, RDL = 1.1 (Wglass + Wmullion + Wtransom + Wms)
= 885.89 N
IV.B Int. Mullion 7/10
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Mullion @ Typical Wall Element
Date: 18-Feb-20
ADM Table 2-24 Sec. 3.4.7 Compression in column " Fa1" ( Axial Gross Section )
(compression in column, axial : all column)
Slenderness, S = k Lb
r
= 29.14
Lower Slenderness Limit, S1 = 0.00
Upper Slenderness limit, S2 = 78.00
S1 < S < S2
ADM Table 2-24 Sec. 3.4.9 Compression in Column Elements " Fa2" ( Gross Section )
(compression in column elemets, gross section : flat elements supported on both edge)
fa < Fa SAFE
IV.B Int. Mullion 8/10
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Mullion @ Typical Wall Element
Date: 18-Feb-20
ADM Table 2-24 Sec. 3.4.7 Compression in column " Fa1" ( Axial Gross Section )
(compression in column, axial : all column)
Slenderness, S = k Lb
r
= 37.83
Lower Slenderness Limit, S1 = 0.00
Upper Slenderness limit, S2 = 78.00
S1 < S < S2
ADM Table 2-24 Sec. 3.4.9 Compression in Column Elements " Fa2" ( Gross Section )
(compression in column elemets, gross section : flat elements supported on both edge)
fa < Fa SAFE
IV.B Int. Mullion 9/10
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Mullion @ Typical Wall Element
Date: 18-Feb-20
fa fb
+ = 0.41 < 1.00 SAFE
Fa Fb
fa fb
+ = 0.40 < 1.00 SAFE
Fa Fb
IV.B Int. Mullion 10/10
V. ANALYSIS OF TRANSOM
th1
th2
I. DESIGN PARAMETERS:
V.A Int. Transom 1/7
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Transom
Date: 18-Feb-20
• FIGURE 2.1 :
t1 = 3.00 mm
t2 = 3.00 mm
a = 90.00 mm
b = 82.00 mm
2 2
Jt = 2 t1 t2 ( a - t1 ) ( b - t2 )
( a t1 + b t2 - t12 -t22
)
4
Jt = 1707402.253 mm
V.A Int. Transom 2/7
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Transom
Date: 18-Feb-20
ADM Table 2-24 Sec. 3.4.2 Tension in Beam "Ft" ( Extreme Fiber , Net Section )
Slenderness, S = 2 Lb Sc
√Iy J
= 25.25
Lower Slenderness Limit, S1 = 130.00
Upper Slenderness Limit, S2 = 2400.00
S1 > S < S2
V.A Int. Transom 3/7
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Transom
Date: 18-Feb-20
V.A Int. Transom 4/7
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Transom
Date: 18-Feb-20
4 2 2
Maximum Deflection, dmax = 5 WDL Lb Pg a ( 3L – 4a )
+
384 Itx Ea 24 Ea Itx
= 0.02 mm
V.A Int. Transom 5/7
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Transom
Date: 18-Feb-20
11.1 Shear Normal to Glass as per Specs. 2-24.20 Shear in Elements, Gross Section
11.2 Shear Parallel to Glass as per Specs. 2-24.20 Shear in Elements , Gross Section
V.A Int. Transom 6/7
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Intermediate Transom
Date: 18-Feb-20
XII. CHECK UNDER COMBINED SHEAR AND BENDING STRESS RATIO ( CSR ):
2 2
fbtx fbty fvty fvty
CSR = + + 2 + 2 = 0.06
Fbtx Fbty Fvty Fvty
V.A Int. Transom 7/7
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Sill Transom
Date: 18-Feb-20
th1
I. DESIGN PARAMETERS:
V.B Sill Transom 1/7
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Sill Transom
Date: 18-Feb-20
• FIGURE 2.1 :
t1 = 3.00 mm
t2 = 3.00 mm
a = 91.00 mm
b = 39.00 mm
J1 = 2 t1 t2 ( a - t1 )2 ( b - t2 )2
( a t1 + b t2 - t12 - t22 )
4
J1 = 485623.742 mm
V.B Sill Transom 2/7
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Sill Transom
Date: 18-Feb-20
TABLE 2.2 : Torsional Constant for Open Parts ( Refer Figure 2.1 )
no. length of thickness of length over Torsional Constant
item of items element element thickness b/t < 10 b/t > 10
3 3
n b t b/t n(1/3-0.2t/b)bt nbt /3
Jt = J1 + J2
= 485915.34 mm4
ADM Table 2-24 Sec. 3.4.2 Tension in Beam "Ft" ( Extreme Fiber , Net Section )
V.B Sill Transom 3/7
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Sill Transom
Date: 18-Feb-20
V.B Sill Transom 4/7
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Sill Transom
Date: 18-Feb-20
4
Maximum Deflection, dmax = 5 WDL Lb Pg a ( 3L2 – 4a2 )
+
384 Itx Ea 24 Ea Itx
= 0.07 mm
V.B Sill Transom 5/7
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Sill Transom
Date: 18-Feb-20
11.1 Shear Normal to Glass as per Specs. 2-24.20 Shear in Elements, Gross Section
11.2 Shear Parallel to Glass as per Specs. 2-24.20 Shear in Elements , Gross Section
V.B Sill Transom 6/7
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Sill Transom
Date: 18-Feb-20
XII. CHECK UNDER COMBINED SHEAR AND BENDING STRESS RATIO ( CSR ):
2 2
fbx fby fvy fvy
CSR = + + 2 + 2 = 0.04
Fbx Fby Fvy Fvy
V.B Sill Transom 7/7
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Head Transom
Date: 18-Feb-20
th
I. DESIGN PARAMETERS:
V.C Head Transom 1/6
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Head Transom
Date: 18-Feb-20
• FIGURE 2.1 :
t1 = 3.00 mm
t2 = 3.00 mm
a = 82.10 mm
b = 54.50 mm
J1 = 2 t1 t2 ( a - t1 )2 ( b - t2 )2
( a t1 + b t2 - t12 - t22 )
4
J1 = 762387.029 mm
V.C Head Transom 2/6
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Head Transom
Date: 18-Feb-20
TABLE 2.2 : Torsional Constant for Open Parts ( Refer Figure 2.1 )
no. length of thickness of length over Torsional Constant
item of items element element thickness b/t < 10 b/t > 10
3 3
n b t b/t n(1/3-0.2t/b)bt nbt /3
Jt = J1 + J2
= 762907.23 mm4
ADM Table 2-24 Sec. 3.4.2 Tension in Beam "Ft" ( Extreme Fiber , Net Section )
V.C Head Transom 3/6
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Head Transom
Date: 18-Feb-20
2
Maximum Design Moment, Mmax ( x - x ) = WDL Lb
( for Uniform Load ) 8
= 2603.27 N-mm
V.C Head Transom 4/6
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Head Transom
Date: 18-Feb-20
4
Maximum Deflection, dmax = 5 WDL Lb
384 Itx Ea
= 0.002 mm
V.C Head Transom 5/6
Project Name: Arbor Lanes - Phase 3
Location: Mango Road, Taguig City, Philippines
Item: Analysis of Head Transom
Date: 18-Feb-20
11.1 Shear Normal to Glass as per Specs. 2-24.20 Shear in Elements, Gross Section
11.2 Shear Parallel to Glass as per Specs. 2-24.20 Shear in Elements, Gross Section
XII. CHECK UNDER COMBINED SHEAR AND BENDING STRESS RATIO ( CSR ):
V.C Head Transom 6/6
VI. ANALYSIS OF TRANSOM TO MULLION CONNECTION
Pg
T1
T2
I. DESIGN PARAMETERS:
2
Total Area of Screws, ATOTAL = 4.00 mm
VI.A Screw 1/5
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Intermediate Transom Connection
Date: 19-Feb-20
IV. CHECK ALLOWABLE SHEAR & BEARING AS PER ALUMINUM DESIGN MANUAL:
2 2 2
Sum. of x & y Dist. of Screws, Σ(x + y ) = 6393.123 mm
4.2 Clause 5.4.3.1 Allowable Shear for member in contact with the screw head
4.3 Clause 5.4.3.2 Allowable Shear for member not in contact with the screw head
VI.A Screw 2/5
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Intermediate Transom Connection
Date: 19-Feb-20
4.5 ADM Table 2-24 Sec 3.4.6 : Bearing on flat surfaces, 6063 – T6
nPU
No. 12 X 50.8L PHSTS
T1 + T2 + Pg + RDL
VI.A Screw 3/5
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Intermediate Transom Connection
Date: 19-Feb-20
Nominal Pull-Out Strength of Screw, Pnot = 1.2DFty2 (0.25 – tc) + 1.16AsnFtu2 (tc – 0.125)
ADM 2005: Eq. 5.4.2.1-2 = 6.409 kips
VI.A Screw 4/5
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Intermediate Transom Connection
Date: 19-Feb-20
Vmax2 Pu
2
+ = 0.03
Vallow2 Pallow2
VI.A Screw 5/5
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Sill Transom Connection
Date: 19-Feb-20
Pg
T
I. DESIGN PARAMETERS:
2
Total Area of Screws, ATOTAL = 4.00 mm
VI.B Screw 1/4
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Sill Transom Connection
Date: 19-Feb-20
IV. CHECK ALLOWABLE SHEAR & BEARING AS PER ALUMINUM DESIGN MANUAL:
2 2 2
Sum. of x & y Dist. of Screws, Σ(x + y ) = 1950.250 mm
4.2 Clause 5.4.3.1 Allowable Shear for member in contact with the screw head
4.3 Clause 5.4.3.2 Allowable Shear for member not in contact with the screw head
VI.B Screw 2/4
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Sill Transom Connection
Date: 19-Feb-20
4.5 ADM Table 2-24 Sec 3.4.6 : Bearing on flat surfaces, 6063 – T6
nPU
T + Pg + RDL
VI.B Screw 3/4
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Sill Transom Connection
Date: 19-Feb-20
Nominal Pull-Out Strength of Screw, Pnot = 1.2DFty2 (0.25 – tc) + 1.16AsnFtu2 (tc – 0.125)
ADM 2005: Eq. 5.4.2.1-2 = 6.409 kips
Vmax2
2
Pu
+ = 0.05
Vallow2 Pallow2
VI.B Screw 4/4
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Head Transom Connection
Date: 19-Feb-20
I. DESIGN PARAMETERS:
2
Total Area of Screws, ATOTAL = 4.00 mm
VI.C Screw 1/4
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Head Transom Connection
Date: 19-Feb-20
IV. CHECK ALLOWABLE SHEAR & BEARING AS PER ALUMINUM DESIGN MANUAL:
2 2 2
Sum. of x & y Dist. of Screws, Σ(x + y ) = 3914.090 mm
4.2 Clause 5.4.3.1 Allowable Shear for member in contact with the screw head
4.3 Clause 5.4.3.2 Allowable Shear for member not in contact with the screw head
VI.C Screw 2/4
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Head Transom Connection
Date: 19-Feb-20
4.5 ADM Table 2-24 Sec 3.4.6 : Bearing on flat surfaces, 6063 – T6
nPU
No. 12 X 50.8L
PHSTS
T + RDL
VI.C Screw 3/4
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Head Transom Connection
Date: 19-Feb-20
Nominal Pull-Out Strength of Screw, Pnot = 1.2DFty2 (0.25 – tc) + 1.16AsnFtu2 (tc – 0.125)
ADM 2005: Eq. 5.4.2.1-2 = 6.409 kips
Vmax2
2
Pu
+ = 0.01
Vallow2 Pallow2
VI.C Screw 4/4
VII. ANALYSIS OF ANCHORS
I. Design Criteria
VII.A Reaction 1/1
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Sill Inter. Anchor @ Negative Load
Date: 19-Feb-20
I. LOAD REACTIONS:
RWL
Mb
VII.B1 Sill Anchor 1/1
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 1
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Specifier's comments:
1 Input data
Anchor type and size: HIT-HY 200 + HIT-V (5.8) M10
Effective embedment depth: hef,act = 120 mm (hef,limit = - mm)
Material: 5.8
Approval No.: ETA 11/0493
Issued I Valid: 2/3/2017 | -
Proof: Design method ETAG BOND (EOTA TR 029)
Stand-off installation: eb = 0 mm (no stand-off); t = 12 mm
Baseplate: lx x ly x t = 300 mm x 75 mm x 12 mm; (Recommended plate thickness: not calculated
Profile: no profile
Base material: cracked concrete, C35/45, fc,cube = 45.00 N/mm2; h = 300 mm, Temp. short/long: 40/24 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: No reinforcement or Reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 2
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 3
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the baseplate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 4
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
7 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid base plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• Drilled hole cleaning must be performed according to instructions for use (blow twice with oil-free compressed air (min. 6 bar), brush twice,
blow twice with oil-free compressed air (min. 6 bar)).
• Characteristic bond resistances depend on short- and long-term temperatures.
• Please contact Hilti to check feasibility of HIT-V rod supply.
• Edge reinforcement is not required to avoid splitting failure
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 5
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
8 Installation data
Baseplate, steel: - Anchor type and size: HIT-HY 200 + HIT-V (5.8) M10
Profile: no profile Installation torque: 0.020 kNm
Hole diameter in the fixture: df = 12 mm Hole diameter in the base material: 12 mm
Plate thickness (input): 12 mm Hole depth in the base material: 120 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 150 mm
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to instructions for use is required
150 150
38
38
1 2 x
38
38
63 175 63
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 6
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Head Inter. Anchor @ Negative Load
Date: 19-Feb-20
I. LOAD REACTIONS:
Mb
RWL
VII.B2 Head Anchor 1/1
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 1
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Specifier's comments:
1 Input data
Anchor type and size: HIT-HY 200 + HIT-V (5.8) M10
Effective embedment depth: hef,act = 120 mm (hef,limit = - mm)
Material: 5.8
Approval No.: ETA 11/0493
Issued I Valid: 2/3/2017 | -
Proof: Design method ETAG BOND (EOTA TR 029)
Stand-off installation: eb = 0 mm (no stand-off); t = 12 mm
Baseplate: lx x ly x t = 300 mm x 75 mm x 12 mm; (Recommended plate thickness: not calculated
Profile: no profile
Base material: cracked concrete, C35/45, fc,cube = 45.00 N/mm2; h = 300 mm, Temp. short/long: 40/24 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: No reinforcement or Reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 2
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 3
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the baseplate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 4
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
7 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid base plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• Drilled hole cleaning must be performed according to instructions for use (blow twice with oil-free compressed air (min. 6 bar), brush twice,
blow twice with oil-free compressed air (min. 6 bar)).
• Characteristic bond resistances depend on short- and long-term temperatures.
• Please contact Hilti to check feasibility of HIT-V rod supply.
• Edge reinforcement is not required to avoid splitting failure
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 5
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
8 Installation data
Baseplate, steel: - Anchor type and size: HIT-HY 200 + HIT-V (5.8) M10
Profile: no profile Installation torque: 0.020 kNm
Hole diameter in the fixture: df = 12 mm Hole diameter in the base material: 12 mm
Plate thickness (input): 12 mm Hole depth in the base material: 120 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 150 mm
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to instructions for use is required
150 150
38
38
1 2 x
38
38
63 175 63
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 6
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Sill Inter. Anchor @ Positive Load
Date: 19-Feb-20
I. LOAD REACTIONS:
RWL
Mb
VII.B3 Sill Anchor 1/1
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 1
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Specifier's comments:
1 Input data
Anchor type and size: HIT-HY 200 + HIT-V (5.8) M10
Effective embedment depth: hef,act = 120 mm (hef,limit = - mm)
Material: 5.8
Approval No.: ETA 11/0493
Issued I Valid: 2/3/2017 | -
Proof: Design method ETAG BOND (EOTA TR 029)
Stand-off installation: eb = 0 mm (no stand-off); t = 12 mm
Baseplate: lx x ly x t = 300 mm x 75 mm x 12 mm; (Recommended plate thickness: not calculated
Profile: no profile
Base material: cracked concrete, C35/45, fc,cube = 45.00 N/mm2; h = 300 mm, Temp. short/long: 40/24 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: No reinforcement or Reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 2
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 3
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the baseplate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 4
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
7 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid base plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• Drilled hole cleaning must be performed according to instructions for use (blow twice with oil-free compressed air (min. 6 bar), brush twice,
blow twice with oil-free compressed air (min. 6 bar)).
• Characteristic bond resistances depend on short- and long-term temperatures.
• Please contact Hilti to check feasibility of HIT-V rod supply.
• Edge reinforcement is not required to avoid splitting failure
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 5
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
8 Installation data
Baseplate, steel: - Anchor type and size: HIT-HY 200 + HIT-V (5.8) M10
Profile: no profile Installation torque: 0.020 kNm
Hole diameter in the fixture: df = 12 mm Hole diameter in the base material: 12 mm
Plate thickness (input): 12 mm Hole depth in the base material: 120 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 150 mm
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to instructions for use is required
150 150
38
38
1 2 x
38
38
63 175 63
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 6
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Head Inter. Anchor @ Positive Load
Date: 19-Feb-20
I. LOAD REACTIONS:
Mb
RWL
VII.B4 Head Anchor 1/1
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 1
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Specifier's comments:
1 Input data
Anchor type and size: HIT-HY 200 + HIT-V (5.8) M10
Effective embedment depth: hef,act = 120 mm (hef,limit = - mm)
Material: 5.8
Approval No.: ETA 11/0493
Issued I Valid: 2/3/2017 | -
Proof: Design method ETAG BOND (EOTA TR 029)
Stand-off installation: eb = 0 mm (no stand-off); t = 12 mm
Baseplate: lx x ly x t = 300 mm x 75 mm x 12 mm; (Recommended plate thickness: not calculated
Profile: no profile
Base material: cracked concrete, C35/45, fc,cube = 45.00 N/mm2; h = 300 mm, Temp. short/long: 40/24 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: No reinforcement or Reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 2
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 3
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the baseplate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 4
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
7 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid base plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• Drilled hole cleaning must be performed according to instructions for use (blow twice with oil-free compressed air (min. 6 bar), brush twice,
blow twice with oil-free compressed air (min. 6 bar)).
• Characteristic bond resistances depend on short- and long-term temperatures.
• Please contact Hilti to check feasibility of HIT-V rod supply.
• Edge reinforcement is not required to avoid splitting failure
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 5
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
8 Installation data
Baseplate, steel: - Anchor type and size: HIT-HY 200 + HIT-V (5.8) M10
Profile: no profile Installation torque: 0.020 kNm
Hole diameter in the fixture: df = 12 mm Hole diameter in the base material: 12 mm
Plate thickness (input): 12 mm Hole depth in the base material: 120 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 150 mm
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to instructions for use is required
150 150
38
38
1 2 x
38
38
63 175 63
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 6
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Sill Jamb Anchor @ Negative Load
Date: 19-Feb-20
I. LOAD REACTIONS:
RWL
Mb
VII.C1 Sill Anchor 1/1
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 1
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Specifier's comments:
1 Input data
Anchor type and size: HIT-HY 200 + HIT-V (5.8) M10
Effective embedment depth: hef,act = 120 mm (hef,limit = - mm)
Material: 5.8
Approval No.: ETA 11/0493
Issued I Valid: 2/3/2017 | -
Proof: Design method ETAG BOND (EOTA TR 029)
Stand-off installation: eb = 0 mm (no stand-off); t = 12 mm
Baseplate: lx x ly x t = 200 mm x 75 mm x 12 mm; (Recommended plate thickness: not calculated
Profile: no profile
Base material: cracked concrete, C35/45, fc,cube = 45.00 N/mm2; h = 300 mm, Temp. short/long: 40/24 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: No reinforcement or Reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 2
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 3
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the baseplate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 4
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
7 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid base plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• Drilled hole cleaning must be performed according to instructions for use (blow twice with oil-free compressed air (min. 6 bar), brush twice,
blow twice with oil-free compressed air (min. 6 bar)).
• Characteristic bond resistances depend on short- and long-term temperatures.
• Please contact Hilti to check feasibility of HIT-V rod supply.
• Edge reinforcement is not required to avoid splitting failure
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 5
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
8 Installation data
Baseplate, steel: - Anchor type and size: HIT-HY 200 + HIT-V (5.8) M10
Profile: no profile Installation torque: 0.020 kNm
Hole diameter in the fixture: df = 12 mm Hole diameter in the base material: 12 mm
Plate thickness (input): 12 mm Hole depth in the base material: 120 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 150 mm
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to instructions for use is required
100 100
38
38
1 2 x
38
38
38 125 38
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 6
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Head Jamb Anchor @ Negative Load
Date: 19-Feb-20
I. LOAD REACTIONS:
Mb
RWL
VII.C2 Head Anchor 1/1
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 1
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Specifier's comments:
1 Input data
Anchor type and size: HIT-HY 200 + HIT-V (5.8) M10
Effective embedment depth: hef,act = 120 mm (hef,limit = - mm)
Material: 5.8
Approval No.: ETA 11/0493
Issued I Valid: 2/3/2017 | -
Proof: Design method ETAG BOND (EOTA TR 029)
Stand-off installation: eb = 0 mm (no stand-off); t = 12 mm
Baseplate: lx x ly x t = 200 mm x 75 mm x 12 mm; (Recommended plate thickness: not calculated
Profile: no profile
Base material: cracked concrete, C35/45, fc,cube = 45.00 N/mm2; h = 300 mm, Temp. short/long: 40/24 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: No reinforcement or Reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 2
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 3
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the baseplate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 4
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
7 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid base plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• Drilled hole cleaning must be performed according to instructions for use (blow twice with oil-free compressed air (min. 6 bar), brush twice,
blow twice with oil-free compressed air (min. 6 bar)).
• Characteristic bond resistances depend on short- and long-term temperatures.
• Please contact Hilti to check feasibility of HIT-V rod supply.
• Edge reinforcement is not required to avoid splitting failure
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 5
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
8 Installation data
Baseplate, steel: - Anchor type and size: HIT-HY 200 + HIT-V (5.8) M10
Profile: no profile Installation torque: 0.020 kNm
Hole diameter in the fixture: df = 12 mm Hole diameter in the base material: 12 mm
Plate thickness (input): 12 mm Hole depth in the base material: 120 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 150 mm
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to instructions for use is required
100 100
38
38
1 2 x
38
38
38 125 38
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 6
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Sill Jamb Anchor @ Positive Load
Date: 19-Feb-20
I. LOAD REACTIONS:
RWL
Mb
VII.C3 Sill Anchor 1/1
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 1
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Specifier's comments:
1 Input data
Anchor type and size: HIT-HY 200 + HIT-V (5.8) M10
Effective embedment depth: hef,act = 120 mm (hef,limit = - mm)
Material: 5.8
Approval No.: ETA 11/0493
Issued I Valid: 2/3/2017 | -
Proof: Design method ETAG BOND (EOTA TR 029)
Stand-off installation: eb = 0 mm (no stand-off); t = 12 mm
Baseplate: lx x ly x t = 200 mm x 75 mm x 12 mm; (Recommended plate thickness: not calculated
Profile: no profile
Base material: cracked concrete, C35/45, fc,cube = 45.00 N/mm2; h = 300 mm, Temp. short/long: 40/24 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: No reinforcement or Reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 2
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 3
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the baseplate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 4
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
7 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid base plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• Drilled hole cleaning must be performed according to instructions for use (blow twice with oil-free compressed air (min. 6 bar), brush twice,
blow twice with oil-free compressed air (min. 6 bar)).
• Characteristic bond resistances depend on short- and long-term temperatures.
• Please contact Hilti to check feasibility of HIT-V rod supply.
• Edge reinforcement is not required to avoid splitting failure
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 5
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
8 Installation data
Baseplate, steel: - Anchor type and size: HIT-HY 200 + HIT-V (5.8) M10
Profile: no profile Installation torque: 0.020 kNm
Hole diameter in the fixture: df = 12 mm Hole diameter in the base material: 12 mm
Plate thickness (input): 12 mm Hole depth in the base material: 120 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 150 mm
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to instructions for use is required
100 100
38
38
1 2 x
38
38
38 125 38
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 6
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Head Jamb Anchor @ Positive Load
Date: 19-Feb-20
I. LOAD REACTIONS:
Mb
RWL
VII.C4 Head Anchor 1/1
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 1
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Specifier's comments:
1 Input data
Anchor type and size: HIT-HY 200 + HIT-V (5.8) M10
Effective embedment depth: hef,act = 120 mm (hef,limit = - mm)
Material: 5.8
Approval No.: ETA 11/0493
Issued I Valid: 2/3/2017 | -
Proof: Design method ETAG BOND (EOTA TR 029)
Stand-off installation: eb = 0 mm (no stand-off); t = 12 mm
Baseplate: lx x ly x t = 200 mm x 75 mm x 12 mm; (Recommended plate thickness: not calculated
Profile: no profile
Base material: cracked concrete, C35/45, fc,cube = 45.00 N/mm2; h = 300 mm, Temp. short/long: 40/24 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: No reinforcement or Reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 2
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 3
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the baseplate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 4
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
7 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid base plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• Drilled hole cleaning must be performed according to instructions for use (blow twice with oil-free compressed air (min. 6 bar), brush twice,
blow twice with oil-free compressed air (min. 6 bar)).
• Characteristic bond resistances depend on short- and long-term temperatures.
• Please contact Hilti to check feasibility of HIT-V rod supply.
• Edge reinforcement is not required to avoid splitting failure
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 5
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
8 Installation data
Baseplate, steel: - Anchor type and size: HIT-HY 200 + HIT-V (5.8) M10
Profile: no profile Installation torque: 0.020 kNm
Hole diameter in the fixture: df = 12 mm Hole diameter in the base material: 12 mm
Plate thickness (input): 12 mm Hole depth in the base material: 120 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 150 mm
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to instructions for use is required
100 100
38
38
1 2 x
38
38
38 125 38
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.com.ph Profis Anchor 2.7.3
Company: Page: 6
Specifier: Project:
Address: Fastening Point:
Phone I Fax: | Date: 2/19/2020
E-Mail:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
VIII. ANALYSIS OF OPERABLE COMPONENTS &
ACCESSORIES
I. DESIGN PARAMETERS:
Total Weight of Glass & Accessories, Wg = 332.700 N IV.A Int. Transom 4/7
• FIG.2.0 : Friction Bar Hinge Connections at Mullion and Vertical Sash Frame
Reference Drawing Details
SUB-SASH FRAME
BAR HINGE
#10 SCREW
II. CHECK ALLOWABLE SHEAR & BEARING AS PER ALUMINUM DESIGN MANUAL
2.2 Clause 5.4.3.1 Allowable Shear for member in contact with the screw head
VIII.A Hinge 1/4
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Operable Components (Hinge Connections)
Date: 19-Feb-20
2.3 Clause 5.4.3.2 Allowable Shear for member not in contact with the screw head
2.5 ADM Table 2-24 Sec 3.4.6 : Bearing on flat surfaces, 6063 – T6
Fp > fp SAFE
VIII.A Hinge 2/4
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Operable Components (Hinge Connections)
Date: 19-Feb-20
Vmax2 Pu
+ = 0.08 < 1
Vallow2 Pallow
VIII.A Hinge 3/4
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Operable Components (Hinge Connections)
Date: 19-Feb-20
VIII.A Hinge 4/4
Project Name: The Gentry Residential Tower
Location: Makati City
Item: Analysis of Operable Components (Lock Points)
Date: 19-Feb-20
I. DESIGN PARAMETERS:
VIII.B Lock Points 1/1
IX. APPENDICES