Breaker Size , Cable Size and Voltage Drop Calculation

From Substation to MLTP

Circuit Length = 350 meters

Connected Load = 131.11 kW

Demand Factor = 0.80

Maximum Demand = 104.89 kW

Load Current = 188.80 Amps

Proposed Circuit Breaker Rating = 400 Amps(Adj)

Installation Method = Laid directly in ground Reference Method D in BS 7671

Soil Temperature = 30 Degree Celcius

Soil Thermal Resistivity = 1.5 km/W


Conversion Factor f1 for Temperature = 0.89 Refer Table 4B2 in BS 7671
Conversion Factor f2 for Grouping = 1

2 Nos 3-1/2 Core 150 sq. mm


Proposed Cable = PVC/SWA/PVC

C.C.C = 217 Amps Refer Table 4D4A in BS 7671

Derated C.C.C = 193.13 Amps

No. of Conductors Per Phase = 2

Total C.C.C = 386.26 Amps

Volt Drop per Unit Length = 0.29 mV/A/m Refer Table 4D4B in BS 7671

Total Volt drop = mV/A/m x Load Current x Length

1000

= 9.58 Volt

Percentage Voltage Drop = 2.31 %

07/02/2020
FAUJI MEAT LIMITED
LTOD-1
Voltage Drop Calculation for Street Lighting (1R1,1Y1,1B1)
4 Core 10 sq.mm PVC/SWA/PC Cu. Conductor
(Considering 1B1)
Lamp Current Number of Load Current Distance mV/A/m Voltage Drop Voltage Drop
(A) Lights (meters) 3 Phase Single Phase
MLTP 105.03 350 0.29 10.661 6.162
DB-LT 3.6 10 3.8 0.137 0.079
Pole 1 0.00 0 3.8 0.000
Pole 2 0.00 0 3.8 0.000
Pole 3 2.5 2 5.00 65 3.8 1.235
Pole 4 0.00 0 3.8 0.000
Pole 5 0.00 0 3.8 0.000
Pole 6 2.5 1 2.50 142 3.8 1.349

Total Voltage Drop 8.825


Percentage Voltage Drop 3.8