DESIGN OF GROUND SUPPORTED FIBER REINFORCED SLAB

BASED ON ACI

PROJECT NAME: Stock Letty

DESIGN MADE FOR: TECINCI SRL

DESIGNER: domaniczky.nicolas@py.sika.com

DATE: 06/29/2020

Sika Corp • 4019 Industry Drive • Chattanooga, TN 37416 • www.fibermesh.com


1-833-236-1255

Fibermesh®, Fibercast®, Enduro®, Novomesh®, Novocon are registered trademarks of Propex Operating Company, LLC.
Detailed Calculation Analysis
Project: Stock Letty
Date: 06/29/2020

User Input

Concrete Information
Slab Name Piso interior
Concrete Compressive Strength f'c = 25 N/mm²
Concrete Flexural Strength fr = 3.735 N/mm²
Modulus of Elasticity E = 23,665 N/mm²
Slab Thickness h = 100.00 mm
Joint Spacing JS = 4.00 m
Poisson's Ratio v = 0.20

Modulus of Elasticity is the measurement of the relationship between concrete stress versus strain. This value
can vary depending on concrete strength, concrete age and characteristics of the concrete matrix.
Joint spacing – appropriate joint design, layout and construction should be adopted for the selected joint
spacing. The slab panel shall have a maximum aspect ratio of 1:1.5.
Jointless Slab: Please contact the Fibermesh representative for the Jointless slab typical notes.
Poisson's Ratio is the ratio of lateral expansion to the longitudinal shortening of the concrete subject to
compressive loads

Subgrade Information
The subgrade is assumed to be a uniform medium whose elasticity is characterized by the resulting deflection of
a given force over a distributed unit area. Westergaard termed this 'modulus of subgrade reaction', k as the load
per unit area causing a deflection with units lbs/in³ or N/mm³.

Modulus of Subgrade k = 0.030 N/mm³

Fiber Information
Fiber Type Sika Fibermesh 650
Sika Corp • 4019 Industry Drive • Chattanooga, TN 37416
p 1-833-236-1255 - www.fibermesh.com

2
Fiber Quantity 2.00 kg/m³

Equivalent Flexural Ratio


Re,3 is the measure of the fiber reinforced concrete in sustaining a load after the first crack. The value is
determined by testing as indicated in ASTM C1609, EN14651 or JSCE SF-4.

Re,3 = 18.4%

Vehicle Load Information

Single wheels on axle are spaced at a distance (S) greater than L


Load Name Automóvil 3 Tn por eje
Axle Load P = 30.300 kN
Contact Pressure Cp = 0.69 N/mm²
Overall Tire Spacing S = 1,828.00 mm

Analysis
The equations and mythology of the fiber reinforced concrete is based Meyerhof. This theory allows for the
development of formulae to determine the slab stresses for interior and edge load cases.

Material & Load Factors


Material Reduction Factor, ϒm ϒm = 1.5
Partial Load Factor, ϒf ϒf = 1.6

Radius of Relative Stiffness


Radius of Relative Stiffness is the stiffness measurement of the combined concrete elasticity and subgrade
capacity, as defined by Westergaard;
0.25
L = [(Eh³)/(12(1-ν²)k)] = 511.54 mm

Sika Corp • 4019 Industry Drive • Chattanooga, TN 37416


p 1-833-236-1255 - www.fibermesh.com

3
Load Contact Area
Single Axle loads
Contact area, Ca = P/Cp = 21,986 mm²
aw = √(Ca/π) = 83.66 mm
a / L Ratio = 0.16
Moment Calculation
Mp=(fr(Re,3/100)h²) / (ϒm 6) = 764.43 N-mm/mm
Mn=(frh²)/(ϒm 6) = 4,150.00 N-mm/mm
Mallow = Mn + Mp = 4,914.43 N-mm/mm

Allowable Load Calculation for Single wheel - Single Axle


Interior Load

Where a/L = 0 PI1 = 2 π Mallow


Where a/L > 0.2 PI2 = (4 π Mallow ) / (1 – (a/3L))
Where 0 < a/L < 0.2 PI3 = PI1 + [( PI2 – PI1 ) ( a / L )] / 0.2

Edge Load

Where a/L = 0 PE1 = π / 2 Mallow + 2 Mn


Where a/L > 0.2 PE2 = ( π Mallow + 4 Mn ) / [ 1 – ( 2 a / 3 L )]
Where 0 < a/L < 0.2 PE3 = PE1 + [( PE2 – PE1 ) ( a / L )] / 0.2

Allowable Load
Interior Edge
P1 (kN) 30.88 16.02
P2 (kN) 65.32 35.96
P3 (kN) 59.04 32.32

a/L 0.16 0.16


Controlling Load Case, P (kN) 59.04 32.32
Pu =Pϒf (kN) 24.27 24.27

Factor of Safety, P/ Pu 2.43 1.33

Because a/L (=0, ≥0.2, or >0 and <0.2)

Sika Corp • 4019 Industry Drive • Chattanooga, TN 37416


p 1-833-236-1255 - www.fibermesh.com

4
All solution factors of safety should be greater than 1. Where solution factors of safety are less than 1, a further
review should be undertaken to determine whether the solution is appropriate for the load and location. For
further advice contact your company's representative.

Sika Corp • 4019 Industry Drive • Chattanooga, TN 37416


p 1-833-236-1255 - www.fibermesh.com

5
User Input

Concrete Information
Slab Name Piso exterior
Concrete Compressive Strength f'c = 25 N/mm²
Concrete Flexural Strength fr = 3.735 N/mm²
Modulus of Elasticity E = 23,665 N/mm²
Slab Thickness h = 100.00 mm
Joint Spacing JS = 4.00 m
Poisson's Ratio v = 0.20

Modulus of Elasticity is the measurement of the relationship between concrete stress versus strain. This value can
vary depending on concrete strength, concrete age and characteristics of the concrete matrix.
Joint spacing – appropriate joint design, layout and construction should be adopted for the selected joint
spacing. The slab panel shall have a maximum aspect ratio of 1:1.5.
Jointless Slab: Please contact the Fibermesh representative for the Jointless slab typical notes.
Poisson's Ratio is the ratio of lateral expansion to the longitudinal shortening of the concrete subject to
compressive loads

Subgrade Information
The subgrade is assumed to be a uniform medium whose elasticity is characterized by the resulting deflection of a
given force over a distributed unit area. Westergaard termed this 'modulus of subgrade reaction', k as the load
per unit area causing a deflection with units lbs/in³ or N/mm³.

Modulus of Subgrade k = 0.030 N/mm³

Fiber Information
Fiber Type Sika Fibermesh 650
Fiber Quantity 2.00 kg/m³

Equivalent Flexural Ratio


Re,3 is the measure of the fiber reinforced concrete in sustaining a load after the first crack. The value is
determined by testing as indicated in ASTM C1609, EN14651 or JSCE SF-4.

Sika Corp • 4019 Industry Drive • Chattanooga, TN 37416


p 1-833-236-1255 - www.fibermesh.com

6
Re,3 = 18.4%

Vehicle Load Information

Single wheels on axle are spaced at a distance (S) greater than L


Load Name Automóvil 3 Tn por eje
Axle Load P = 30.300 kN
Contact Pressure Cp = 0.69 N/mm²
Overall Tire Spacing S = 1,828.00 mm

Analysis
The equations and mythology of the fiber reinforced concrete is based Meyerhof. This theory allows for the
development of formulae to determine the slab stresses for interior and edge load cases.

Material & Load Factors


Material Reduction Factor, ϒm ϒm = 1.5
Partial Load Factor, ϒf ϒf = 1.6

Radius of Relative Stiffness


Radius of Relative Stiffness is the stiffness measurement of the combined concrete elasticity and subgrade
capacity, as defined by Westergaard;
0.25
L = [(Eh³)/(12(1-ν²)k)] = 511.54 mm

Load Contact Area


Single Axle loads
Contact area, Ca = P/Cp = 21,986 mm²
aw = √(Ca/π) = 83.66 mm
a / L Ratio = 0.16

Sika Corp • 4019 Industry Drive • Chattanooga, TN 37416


p 1-833-236-1255 - www.fibermesh.com

7
Moment Calculation
Mp=(fr(Re,3/100)h²) / (ϒm 6) = 764.43 N-mm/mm
Mn=(frh²)/(ϒm 6) = 4,150.00 N-mm/mm
Mallow = Mn + Mp = 4,914.43 N-mm/mm

Allowable Load Calculation for Single wheel - Single Axle


Interior Load

Where a/L = 0 PI1 = 2 π Mallow


Where a/L > 0.2 PI2 = (4 π Mallow ) / (1 – (a/3L))
Where 0 < a/L < 0.2 PI3 = PI1 + [( PI2 – PI1 ) ( a / L )] / 0.2

Edge Load

Where a/L = 0 PE1 = π / 2 Mallow + 2 Mn


Where a/L > 0.2 PE2 = ( π Mallow + 4 Mn ) / [ 1 – ( 2 a / 3 L )]
Where 0 < a/L < 0.2 PE3 = PE1 + [( PE2 – PE1 ) ( a / L )] / 0.2

Allowable Load
Interior Edge
P1 (kN) 30.88 16.02
P2 (kN) 65.32 35.96
P3 (kN) 59.04 32.32

a/L 0.16 0.16


Controlling Load Case, P (kN) 59.04 32.32
Pu =Pϒf (kN) 24.27 24.27

Factor of Safety, P/ Pu 2.43 1.33

Because a/L (=0, ≥0.2, or >0 and <0.2)


All solution factors of safety should be greater than 1. Where solution factors of safety are less than 1, a further
review should be undertaken to determine whether the solution is appropriate for the load and location. For
further advice contact your company's representative.

Sika Corp • 4019 Industry Drive • Chattanooga, TN 37416


p 1-833-236-1255 - www.fibermesh.com

8
User Input

Concrete Information
Slab Name Piso interior Alto Tránsito
Concrete Compressive Strength f'c = 25 N/mm²
Concrete Flexural Strength fr = 3.735 N/mm²
Modulus of Elasticity E = 23,665 N/mm²
Slab Thickness h = 120.00 mm
Joint Spacing JS = 4.00 m
Poisson's Ratio v = 0.20

Modulus of Elasticity is the measurement of the relationship between concrete stress versus strain. This value can
vary depending on concrete strength, concrete age and characteristics of the concrete matrix.
Joint spacing – appropriate joint design, layout and construction should be adopted for the selected joint
spacing. The slab panel shall have a maximum aspect ratio of 1:1.5.
Jointless Slab: Please contact the Fibermesh representative for the Jointless slab typical notes.
Poisson's Ratio is the ratio of lateral expansion to the longitudinal shortening of the concrete subject to
compressive loads

Subgrade Information
The subgrade is assumed to be a uniform medium whose elasticity is characterized by the resulting deflection of a
given force over a distributed unit area. Westergaard termed this 'modulus of subgrade reaction', k as the load
per unit area causing a deflection with units lbs/in³ or N/mm³.

Modulus of Subgrade k = 0.030 N/mm³

Fiber Information
Fiber Type Sika Fibermesh 650
Fiber Quantity 2.00 kg/m³

Equivalent Flexural Ratio


Re,3 is the measure of the fiber reinforced concrete in sustaining a load after the first crack. The value is
determined by testing as indicated in ASTM C1609, EN14651 or JSCE SF-4.

Sika Corp • 4019 Industry Drive • Chattanooga, TN 37416


p 1-833-236-1255 - www.fibermesh.com

9
Re,3 = 18.4%

Vehicle Load Information

Sd is greater than 2h
Load Name Camión 10Tn eje
Axle Load P = 100.400 kN
Contact Pressure Cp = 0.69 N/mm²
Overall Tire Spacing S = 1,828.00 mm
Dual Wheel Spacing Sd = 305.00 mm

Analysis
The equations and mythology of the fiber reinforced concrete is based Meyerhof. This theory allows for the
development of formulae to determine the slab stresses for interior and edge load cases.
Material & Load Factors
Material Reduction Factor, ϒm ϒm = 1.5
Partial Load Factor, ϒf ϒf = 1.6

Radius of Relative Stiffness


Radius of Relative Stiffness is the stiffness measurement of the combined concrete elasticity and subgrade
capacity, as defined by Westergaard;
0.25
L = [(Eh³)/(12(1-ν²)k)] = 586.50 mm

Load Contact Area


Dual Wheel - Single Axle loads where Sd is greater than 2h
Contact area, Ca = P/Cp = 36,377 mm²
a = √(Ca/π) = 107.61 mm
a / L Ratio = 0.18

Sika Corp • 4019 Industry Drive • Chattanooga, TN 37416


p 1-833-236-1255 - www.fibermesh.com

10
Moment Calculation
Mp=(fr(Re,3/100)h²) / (ϒm 6) = 1,100.78 N-mm/mm
Mn=(frh²)/(ϒm 6) = 5,976.00 N-mm/mm
Mallow = Mn + Mp = 7,076.78 N-mm/mm

Allowable Load Calculation for Dual wheel - Single Axle


Interior Load

Where a/L = 0 PI1 = 2 π Mallow


Where a/L > 0.2 PI2 = (4 π Mallow ) / (1 – (a/3L))
Where 0 < a/L < 0.2 PI3 = PI1 + [( PI2 – PI1 ) ( a / L )] / 0.2

Edge Load

Where a/L = 0 PE1 = π / 2 Mallow + 2 Mn


Where a/L > 0.2 PE2 = ( π Mallow + 4 Mn ) / [ 1 – ( 2 a / 3 L )]
Where 0 < a/L < 0.2 PE3 = PE1 + [( PE2 – PE1 ) ( a / L )] / 0.2

Allowable Load
Interior Edge
P1 (kN) 44.46 23.07
P2 (kN) 94.72 52.57
P3 (kN) 90.57 50.13

a/L 0.18 0.18


Controlling Load Case, P (kN) 90.57 50.13
Pu =Pϒf (kN) 40.16 40.16

Factor of Safety, P/ Pu 2.26 1.25

Because a/L (=0, ≥0.2, or >0 and <0.2)


All solution factors of safety should be greater than 1. Where solution factors of safety are less than 1, a further
review should be undertaken to determine whether the solution is appropriate for the load and location. For
further advice contact your company's representative.

Sika Corp • 4019 Industry Drive • Chattanooga, TN 37416


p 1-833-236-1255 - www.fibermesh.com

11
Shrinkage and Curling
Shrinkage and curling stresses are always critical components of the design of the slab on ground and should be
evaluated on a project basis depending on several factors, including, but not limited to:
Concrete Mix Design - Shrinkage and curling stresses can vary greatly depending upon aggregate size, type and
quality, water content, paste content, admixture usage, and concrete temperature.
Placement Conditions - Subgrade moisture and preparation, subgrade restraint, use of a vapor retarder,
protection from environmental conditions (temperature variations, wind, and humidity).
Contraction Joints – Maximum joints spacing should be 24 to 36 times the slab thickness. All slab panels should
be square as possible. The panel length to width ratio should not exceed 1:1.5. Saw cut must be 1/3 depth if
using wet cut saw or 1/4 depth if using an early entry dry cut concrete saw with a minimum depth of 1 in.
Consult your company's representative to discuss the possibility for extended joint spacing or Jointless slab
design.
Curing - Is vital to all concrete construction. Wet burlap, plastic sheeting and sprayed applied curing agents may
be considered as the conditions warrant. Sika Corp recommends good practices and relevant industry standards
be followed.

Construction Loads
The evaluation of construction loads is often overlooked in the design process, yet they can often affect the
performance and long-term durability of the slab on ground. Care should be taken by the engineer/designer to
account for construction loads that may have an effect on the slab.

Liability Statement:
Use of this software application and/or any resulting report in no way represents an actual or implied agreement
or warranty, including, but not limited to, the implied warranties of merchantability, fitness for a particular
purpose, or infringement, between the user and Sika Corporation. This application is provided as is, and at the
user’s own risk, and solely as an accommodation for purchasers of Sika Corporation products. The calculations
reported are solely based on information entered by the user of this application. Sika Corporation does not verify
the accuracy or the completeness of any of the data submitted by the user, and it reserves its right to revise,
adjust or otherwise refute any information provided. Furthermore, all information and data points contained
within this application are subject to change without notice. Sika Corporation disclaims all liability for all damages,
including without limitation direct, indirect, special, consequential or incidental damages, arising out of or in
connection with the use of any information contained herein or the use or performance of this application. By
using this application, the user hereby agrees to these limitations to Sika Corporation’s liability, and further
agrees to indemnify and hold Sika Corporation and its affiliates harmless from any and all damages, losses, costs
and expenses of any kind or nature (including, but not limited to, attorneys’ fees and all costs of investigation,
defense and settlement) relating to this application and/or any resulting report. The methodology and
performance reported by this application is related solely to Sika Corporation products.

Sika Corp • 4019 Industry Drive • Chattanooga, TN 37416


p 1-833-236-1255 - www.fibermesh.com

12
Sika Corp • 4019 Industry Drive • Chattanooga, TN 37416
p 1-833-236-1255 - www.fibermesh.com

13