PCONT t Is 2 x Rstab
PCONT t 0.065 2 x 1800
PCONT t 7.6W
VFint 2
P1SEC t Where: V Fint t 4
(V K 3 x R stab x I Fint ) x 1.3
Rstab
8400
IFint 14A
600
VFint t 4 (VK 3 x Rstab x IFint) x 1.3
VFint t 4 450 3 x 1800 x 14 u 1.3 1600V
2
1600
P1SEC t 1422 W
1800
Settings Requirements
Rated current = VA / (¥3 x VL)
6
Rated current = 10 x 10 / (¥3 x 33000) = 175A
Assigned through fault current (rated stability limit) = 16 x rated current = 2.8kA. See section 2.2.1
Required Primary Operate Current
Typically 10 – 25% of protected winding rated current (Irated), or as specified by the user.
POCprov (10 – 25% of Irated) = 17.5 – 43.8A. Say 20A. (0.1A secondary). See section 2.2.2
The required for the value of operate current to flow through the shunt setting resistor (Rstab) can be calculated
from:
POC = ( 3(IMAGLCT) + Is + Ishunt) / T
Ishunt = POC x T – (3(IMAGLCT) + Is )
= 0.1 – (3(IMAGLCT) + 0.02)
Metrosil Specification
For values < 8kW/s the integral 75mm Metrosil is suitably rated.
VFint 2
P1SEC t Where: VFint t 4 (VK 3 x Rshunt x IFint) x 1.3
Rstab
2800
IFint 14A
200
VFint t 4 (VK 3 u Rshunt u IFint) x 1.3
VFint t 4 (120 3 x 820 x 14 u 1.3 488 V
2
488
P1SEC t 290 W
820
Vs = 50V
4.2 7PG23 Relay: Restricted Earth Fault Protection - 3 Wire + Earth System
Settings Requirements
Rated current = VA / (¥3 x VL)
Rated current = 10 x 106 / (¥3 x 11000) = 525A
Assigned through fault current (rated stability limit) = 16 x rated current = 8.4kA. See section 2.2.1
Required Primary Operate Current (Fault Setting)
10 – 25% of protected winding rated current, or as specified by the user.
POCprov (10 – 25% of Irated) = 52.5 - 131A. Say 60A. (0.1A secondary). See section 2.2.2
VS t IF (RCT RL ) u T
8400
VS t u 7.5 0.15 107.1V
600
8400
VS t u 6 0.2 86.8V
600
V 300
VS d KMIN 150V
2 2
? 107.1 Vs 150
The required for the value of operate current to flow through the shunt setting resistor (Rstab) can be calculated
from:
POC = (3(IMAGLCT) + IMAGECT + Is + Ishunt ) / T
Ishunt = POC x T – (3(IMAGLCT) + IMAGECT + Is)
= 0.1 – (3(IMAGLCT) + IMAGECT + 0.02)
Metrosil Specification
For values < 8kW/s the integral 75mm Metrosil is suitably rated.
VFint 2
P1SEC t Where: VFint t 4 (VK 3 x Rshunt x IFint) x 1.3
Rstab
2800
IFint 14A
200
VFint t 4 (VK 3 u Rshunt u IFint) x 1.3
VFint t 4 (360 3 x 2400 x 14 u 1.3 1455 V
2
1455
P1SEC t 882 W
2400
Vs = 120V