Sunteți pe pagina 1din 27

KINGDOM OF SAUDI ARABIA

KING FAISAL UNIVERSITY

KFU GIRLS SCHOOL

FIRE SUPPRESSION CALCULATIONS

ARABIAN AZMEEL
EGYPT BRANCH
Table of Contents

KING FAISAL UNIVERSITY


KFU GIRLS SCHOOL

Serial No. Title Page No.


1 COMBINED SYSTEM CALCULATIONS 2
2 GAS SYSTEM CALCULATIONS 26

1 of 27
Combined System Calculations

2 of 27
(GS)-KFU GIRLS SCHOOL
Fire Sprinkler Reports

for

KING FAISAL UNIVERSITY - AL AHSA CAMPUS

AL AHSA CAMPUS

Prepared By:

Egypt Azmeel Office


Egypt Azmeel Office
EGYPT

ÃÛÓØÓ 04, 2015


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem mohamed (GS)-KFU GIRLS School Page 2

General Project Data Report

General Data
Project Title: (GS)-KFU GIRLS School
Designed By: Egypt Azmeel Office Date: ÃÛÓØÓ 04, 2015
Code Reference: NFPA 13 & NFPA 14 Approving Agency: ÔÑßÉ ÚÈÏÇááå ÇáÓíÝ æÔÑßÇÆå
Client Name: KING FAISAL UNIVERSITY - AL
Phone:
AHSA CAMPUS
Address: AL AHSA CAMPUS City, State Zip Code:
Company Name: Egypt Azmeel Office Representative: Eng.A.Abogresha - Eng.M.Samir
Company Address: EGYPT City And State:
Phone:
Building Name: KING FAISAL UNIVERSITY - AL
(GS)-KFU GIRLS School Building Owner:
AHSA CAMPUS
Contact at Building: Phone at Building:

Project Data
Description Of Hazard: Light Hazard Sprinkler System Type: Wet
Design Area Of Water Application: 1500 ft² Maximum Area Per Sprinkler: 175 ft²
Default Sprinkler K-Factor: 5.60 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 100.00 gpm Outside Hose Stream Allowance: 0.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm

Sprinkler Specifications
Make: Model:
Size: Temperature Rating: 0 F

Water Supply Test Data


Source Of Information:
Test Hydrant ID: Date Of Test:

Hydrant Elevation: 0 ft Static Pressure: 0.00 psi


Test Flow Rate: 0.00 gpm Test Residual Pressure: 0.00 psi
Calculated System Flow Rate: 379.68 gpm Calculated Inflow Residual Pressure: 85.12 psi
Available Inflow Residual Pressure: 0 psi

Calculation Project Data


Calculation Mode: Demand
HMD Minimum Residual Pressure: 15.00 psi Minimum Desired Flow Density: 0.10 gpm/ft²
Maximum Water Velocity: 23.00 ft/s Maximum Frictional Loss / 100 feet: 20.00 psi
Number Of Active Nodes: 42
Number Of Active Pipes: 42 Number Of Inactive Pipes: 0
Number Of Active Sprinklers: 7 Number Of Inactive Sprinklers: 0

Active Version 1000 Pipe Capacity 02 ÓÈÊãÈÑ, 2015


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem mohamed (GS)-KFU GIRLS School Page 3

Fire Sprinkler Input Data

Node Input Data


Node Non-Sprinkler
Sprinkler Pressure
Node No. Node Description Area Group Elevation Discharge
KFactor (K) Estimate (psi)
(feet) (gpm)

10 Sprinkler 5.60 15.00 44.00 0.00

20 No Discharge N/A 14.74 46.00 0.00

30 No Discharge N/A 16.49 46.00 0.00

40 Sprinkler 14.00 16.13 46.00 0.00

45 No Discharge N/A 18.15 46.00 0.00

50 No Discharge N/A 19.19 46.00 0.00

60 Sprinkler 5.60 19.86 44.00 0.00

70 No Discharge N/A 24.08 46.00 0.00

80 Sprinkler 14.00 23.21 46.00 0.00

90 No Discharge N/A 27.50 46.00 0.00

100 No Discharge N/A 23.53 46.00 0.00

110 Sprinkler 5.60 23.93 44.00 0.00

120 No Discharge N/A 20.52 46.00 0.00

130 No Discharge N/A 18.70 46.00 0.00

140 No Discharge N/A 17.25 46.00 0.00

150 Sprinkler 5.60 17.76 44.00 0.00

160 Sprinkler 14.00 17.38 46.00 0.00

170 No Discharge N/A 29.44 46.00 0.00

180 No Discharge N/A 33.11 45.30 0.00

190 No Discharge N/A 34.24 45.30 0.00

200 No Discharge N/A 36.75 45.30 0.00

210 No Discharge N/A 39.27 45.30 0.00

220 No Discharge N/A 41.86 45.30 0.00

230 No Discharge N/A 44.02 45.30 0.00

240 No Discharge N/A 42.85 45.30 0.00

245 No Discharge N/A 40.32 45.30 0.00

250 No Discharge N/A 37.86 45.30 0.00

255 No Discharge N/A 35.42 45.30 0.00

260 No Discharge N/A 53.09 45.30 0.00

270 No Discharge N/A 50.94 45.30 0.00

Active Version 1000 Pipe Capacity 02 ÓÈÊãÈÑ, 2015


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem mohamed (GS)-KFU GIRLS School Page 4

Fire Sprinkler Input Data

Node Input Data (cont'd)


Node Non-Sprinkler
Sprinkler Pressure
Node No. Node Description Area Group Elevation Discharge
KFactor (K) Estimate (psi)
(feet) (gpm)

280 Non-Sprinkler N/A 53.79 35.50 100.00

290 No Discharge N/A 57.02 45.30 0.00

300 No Discharge N/A 64.45 31.20 0.00

310 No Discharge N/A 67.28 31.20 0.00

320 No Discharge N/A 83.00 0.00 0.00

330 No Discharge N/A 83.23 0.00 0.00

340 No Discharge N/A 83.36 0.00 0.00

350 No Discharge N/A 84.01 0.00 0.00

360 No Discharge N/A 84.60 0.00 0.00

370 No Discharge N/A 84.84 0.00 0.00

380 No Discharge N/A 85.07 0.00 0.00

390 No Discharge N/A 85.12 0.00 0.00

Active Version 1000 Pipe Capacity 02 ÓÈÊãÈÑ, 2015


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem mohamed (GS)-KFU GIRLS School Page 5

Fire Sprinkler Input Data

Pipe Input Data


Nominal Nominal Fitting Total CFactor
Beg. End. Type Fitting
Pipe Description Diameter Length Length Length (gpm/inch-
Node Node Group Data
(inch) (feet) (feet) (feet) psi)

10 20 SCHED 40 WET STEEL 1.000 0 E 2.00 2.00 4.00 120

20 30 SCHED 40 WET STEEL 1.000 0 T 6.60 5.00 11.60 120

30 40 SCHED 40 WET STEEL 1.500 0 3.30 0.00 3.30 120

30 45 SCHED 40 WET STEEL 1.500 0 E 4.30 4.00 8.30 120

45 50 SCHED 40 WET STEEL 1.500 0 5.20 0.00 5.20 120

50 60 SCHED 40 WET STEEL 1.000 0 1.00 0.00 1.00 120

50 70 SCHED 40 WET STEEL 1.500 0 T 6.60 8.00 14.60 120

70 80 SCHED 40 WET STEEL 1.500 0 5.70 0.00 5.70 120

70 90 SCHED 40 WET STEEL 2.000 0 T 3.60 10.00 13.60 120

90 170 SCHED 40 WET STEEL 2.500 0 E 1.30 6.00 7.30 120

100 90 SCHED 40 WET STEEL 1.500 0 T 2.60 8.00 10.60 120

120 100 SCHED 40 WET STEEL 1.500 0 T 5.70 8.00 13.70 120

100 110 SCHED 40 WET STEEL 1.000 0 2.00 0.00 2.00 120

130 120 SCHED 40 WET STEEL 1.500 0 E 4.30 4.00 8.30 120

160 130 SCHED 40 WET STEEL 1.500 0 T 3.30 8.00 11.30 120

130 140 SCHED 40 WET STEEL 1.000 0 E 6.20 2.00 8.20 120

140 150 SCHED 40 WET STEEL 1.000 0 2.00 0.00 2.00 120

170 180 SCHED 40 WET STEEL 2.500 0 T 0.70 12.00 12.70 120

180 190 SCHED 40 WET STEEL 2.500 0 F 12.10 3.00 15.10 120

255 180 SCHED 40 WET STEEL 2.500 0 T 19.70 12.00 31.70 120

190 200 SCHED 40 WET STEEL 2.500 0 F 30.80 3.00 33.80 120

200 210 SCHED 40 WET STEEL 2.500 0 F 30.80 3.00 33.80 120

210 220 SCHED 40 WET STEEL 2.500 0 F 31.80 3.00 34.80 120

220 230 SCHED 40 WET STEEL 2.500 0 T 17.10 12.00 29.10 120

230 240 SCHED 40 WET STEEL 2.500 0 F 13.10 3.00 16.10 120

230 260 SCHED 40 WET STEEL 2.500 0 TGC 7.20 27.00 34.20 120

240 245 SCHED 40 WET STEEL 2.500 0 F 31.80 3.00 34.80 120

245 250 SCHED 40 WET STEEL 2.500 0 F 30.80 3.00 33.80 120

250 255 SCHED 40 WET STEEL 2.500 0 F 30.50 3.00 33.50 120

260 270 SCHED 40 WET STEEL 2.000 0 E 17.90 5.00 22.90 120

Active Version 1000 Pipe Capacity 02 ÓÈÊãÈÑ, 2015


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem mohamed (GS)-KFU GIRLS School Page 6

Fire Sprinkler Input Data

Pipe Input Data (cont'd)


Nominal Nominal Fitting Total CFactor
Beg. End. Type Fitting
Pipe Description Diameter Length Length Length (gpm/inch-
Node Node Group Data
(inch) (feet) (feet) (feet) psi)

260 290 SCHED 40 WET STEEL 3.000 0 T 9.20 15.00 24.20 120

270 280 SCHED 40 WET STEEL 2.000 0 E 9.80 5.00 14.80 120

290 300 SCHED 40 WET STEEL 4.000 0 E 20.70 10.00 30.70 120

300 310 SCHED 40 WET STEEL 4.000 0 E 55.50 10.00 65.50 120

310 320 SCHED 40 WET STEEL 4.000 0 T 31.20 20.00 51.20 120

320 330 SCHED 40 WET STEEL 6.000 0 E 26.20 14.00 40.20 120

330 340 SCHED 40 WET STEEL 6.000 0 E 8.50 14.00 22.50 120

340 350 SCHED 40 WET STEEL 6.000 0 E 95.40 14.00 109.40 120

350 360 SCHED 40 WET STEEL 6.000 0 E 87.30 14.00 101.30 120

360 370 SCHED 40 WET STEEL 6.000 0 E 26.20 14.00 40.20 120

370 380 SCHED 40 WET STEEL 6.000 0 E 26.60 14.00 40.60 120

390 380 SCHED 40 WET STEEL 6.000 0 7.00 0.00 7.00 120

Active Version 1000 Pipe Capacity 02 ÓÈÊãÈÑ, 2015


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem mohamed (GS)-KFU GIRLS School Page 7

Fire Sprinkler Output Data

Overall Node Groupings Output Data


Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

10 20 0 -21.69 21.69 0.00 0.00 15.00 -0.00001

20 10 0 21.69 0.00 0.00 0.00 14.74 0.00005


20 30 0 -21.69

30 20 0 21.69 0.00 0.00 0.00 16.49 -0.00004


30 40 0 56.23
30 45 0 -77.92

40 30 0 -56.23 56.23 0.00 0.00 16.13 0.00021

45 30 0 77.92 0.00 0.00 0.00 18.15 0.00000


45 50 0 -77.92

50 45 0 77.92 0.00 0.00 0.00 19.19 0.00000


50 60 0 24.96
50 70 0 -102.88

60 50 0 -24.96 24.96 0.00 0.00 19.86 0.00020

70 50 0 102.88 0.00 0.00 0.00 24.08 -0.00003


70 80 0 67.44
70 90 0 -170.32

80 70 0 -67.44 67.44 0.00 0.00 23.21 0.00091

90 70 0 170.32 0.00 0.00 0.00 27.50 -0.00004


90 170 0 -279.67
90 100 0 109.36

100 90 0 -109.36 0.00 0.00 0.00 23.53 0.00000


100 120 0 81.96
100 110 0 27.40

110 100 0 -27.40 27.40 0.00 0.00 23.93 0.00039

120 100 0 -81.96 0.00 0.00 0.00 20.52 0.00000


120 130 0 81.96

130 120 0 -81.96 0.00 0.00 0.00 18.70 0.00001


130 160 0 58.36
130 140 0 23.60

140 130 0 -23.60 0.00 0.00 0.00 17.25 -0.00002


140 150 0 23.60

150 140 0 -23.60 23.60 0.00 0.00 17.76 0.00010

160 130 0 -58.36 58.36 0.00 0.00 17.38 0.00026

170 90 0 279.67 0.00 0.00 0.00 29.44 0.00001


170 180 0 -279.67

180 170 0 279.67 0.00 0.00 0.00 33.11 -0.00001


180 190 0 -140.68
180 255 0 -139.00

190 180 0 140.68 0.00 0.00 0.00 34.24 0.00001


190 200 0 -140.68

Active Version 1000 Pipe Capacity 02 ÓÈÊãÈÑ, 2015


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem mohamed (GS)-KFU GIRLS School Page 8

Fire Sprinkler Output Data

Overall Node Groupings Output Data (cont'd)


Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

200 190 0 140.68 0.00 0.00 0.00 36.75 0.00000


200 210 0 -140.68

210 200 0 140.68 0.00 0.00 0.00 39.27 0.00000


210 220 0 -140.68

220 210 0 140.68 0.00 0.00 0.00 41.86 0.00000


220 230 0 -140.68

230 220 0 140.68 0.00 0.00 0.00 44.02 0.00003


230 240 0 139.00
230 260 0 -279.67

240 230 0 -139.00 0.00 0.00 0.00 42.85 -0.00001


240 245 0 139.00

245 240 0 -139.00 0.00 0.00 0.00 40.32 0.00000


245 250 0 139.00

250 245 0 -139.00 0.00 0.00 0.00 37.86 0.00000


250 255 0 139.00

255 180 0 139.00 0.00 0.00 0.00 35.42 0.00000


255 250 0 -139.00

260 230 0 279.67 0.00 0.00 0.00 53.09 -0.00008


260 270 0 100.00
260 290 0 -379.67

270 260 0 -100.00 0.00 0.00 0.00 50.94 0.00000


270 280 0 100.00

280 270 0 -100.00 0.00 100.00 0.00 53.79 0.00012

290 260 0 379.67 0.00 0.00 0.00 57.02 -0.00002


290 300 0 -379.67

300 290 0 379.67 0.00 0.00 0.00 64.45 0.00002


300 310 0 -379.67

310 300 0 379.67 0.00 0.00 0.00 67.28 -0.00001


310 320 0 -379.67

320 310 0 379.67 0.00 0.00 0.00 83.00 -0.00005


320 330 0 -379.67

330 320 0 379.67 0.00 0.00 0.00 83.23 -0.00001


330 340 0 -379.68

340 330 0 379.68 0.00 0.00 0.00 83.36 0.00004


340 350 0 -379.67

350 340 0 379.67 0.00 0.00 0.00 84.01 0.00000


350 360 0 -379.67

360 350 0 379.67 0.00 0.00 0.00 84.60 -0.00002


360 370 0 -379.67

Active Version 1000 Pipe Capacity 02 ÓÈÊãÈÑ, 2015


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem mohamed (GS)-KFU GIRLS School Page 9

Fire Sprinkler Output Data

Overall Node Groupings Output Data (cont'd)


Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

370 360 0 379.67 0.00 0.00 0.00 84.84 0.00000


370 380 0 -379.67

380 370 0 379.67 0.00 0.00 0.00 85.07 -0.00004


380 390 0 -379.68

390 380 0 379.68 0.00 0.00 0.00 85.12

Active Version 1000 Pipe Capacity 02 ÓÈÊãÈÑ, 2015


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem mohamed (GS)-KFU GIRLS School Page 10

Fire Sprinkler Output Data

Overall Pipe Output Data


Nom. Dia. F. L./ft Pipe-Len.
Beg. Nodal Spk/Hose Residual Q (gpm) PF-(psi)
Elevation Inside Dia. (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Velocity PE-(psi)
(feet) C-Value Fittings Tot-Len.
Node (K) (gpm) (psi) (fps) PV-(psi)
Type-Grp (ft)

10 5.60 44.00 21.69 15.00 1.00 21.69 0.15125 2.00 0.605


20 0.00 46.00 0.00 14.74 1.049 8.05 E 2.00 -0.866
SCHED 40 WET STEEL 120 0 4.00 0.020

20 0.00 46.00 0.00 14.74 1.00 21.69 0.15125 6.60 1.754


30 0.00 46.00 0.00 16.49 1.049 8.05 T 5.00 0.000
SCHED 40 WET STEEL 120 0 11.60 0.020

30 0.00 46.00 0.00 16.49 1.50 56.23 0.10942 3.30 0.361


40 14.00 46.00 56.23 16.13 1.610 8.86 ----- 0.00 0.000
SCHED 40 WET STEEL 120 0 3.30 0.009

30 0.00 46.00 0.00 16.49 1.50 77.92 0.20009 4.30 1.661


45 0.00 46.00 0.00 18.15 1.610 12.28 E 4.00 0.000
SCHED 40 WET STEEL 120 0 8.30 0.013
WARNING: Maximum friction loss exceeded for this pipe

45 0.00 46.00 0.00 18.15 1.50 77.92 0.20009 5.20 1.040


50 0.00 46.00 0.00 19.19 1.610 12.28 ----- 0.00 0.000
SCHED 40 WET STEEL 120 0 5.20 0.013
WARNING: Maximum friction loss exceeded for this pipe

50 0.00 46.00 0.00 19.19 1.00 24.96 0.19613 1.00 0.196


60 5.60 44.00 24.96 19.86 1.049 9.27 ----- 0.00 -0.866
SCHED 40 WET STEEL 120 0 1.00 0.023

50 0.00 46.00 0.00 19.19 1.50 102.88 0.33457 6.60 4.885


70 0.00 46.00 0.00 24.08 1.610 16.21 T 8.00 0.000
SCHED 40 WET STEEL 120 0 14.60 0.017
WARNING: Maximum friction loss exceeded for this pipe

70 0.00 46.00 0.00 24.08 1.50 67.44 0.15317 5.70 0.873


80 14.00 46.00 67.44 23.21 1.610 10.63 ----- 0.00 0.000
SCHED 40 WET STEEL 120 0 5.70 0.011

70 0.00 46.00 0.00 24.08 2.00 170.32 0.25182 3.60 3.425


90 0.00 46.00 0.00 27.50 2.067 16.28 T 10.00 0.000
SCHED 40 WET STEEL 120 0 13.60 0.010
WARNING: Maximum friction loss exceeded for this pipe

100 0.00 46.00 0.00 23.53 1.50 109.36 0.37458 2.60 3.971
90 0.00 46.00 0.00 27.50 1.610 17.23 T 8.00 0.000
SCHED 40 WET STEEL 120 0 10.60 0.018
WARNING: Maximum friction loss exceeded for this pipe

120 0.00 46.00 0.00 20.52 1.50 81.96 0.21970 5.70 3.010
100 0.00 46.00 0.00 23.53 1.610 12.92 T 8.00 0.000
SCHED 40 WET STEEL 120 0 13.70 0.014
WARNING: Maximum friction loss exceeded for this pipe

100 0.00 46.00 0.00 23.53 1.00 27.40 0.23302 2.00 0.466
110 5.60 44.00 27.40 23.93 1.049 10.17 ----- 0.00 -0.866
SCHED 40 WET STEEL 120 0 2.00 0.025
WARNING: Maximum friction loss exceeded for this pipe

130 0.00 46.00 0.00 18.70 1.50 81.96 0.21970 4.30 1.824
120 0.00 46.00 0.00 20.52 1.610 12.92 E 4.00 0.000
SCHED 40 WET STEEL 120 0 8.30 0.014

Active Version 1000 Pipe Capacity 02 ÓÈÊãÈÑ, 2015


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem mohamed (GS)-KFU GIRLS School Page 11

Fire Sprinkler Output Data

Overall Pipe Output Data (cont'd)


Nom. Dia. F. L./ft Pipe-Len.
Beg. Nodal Residual Q (gpm) PF-(psi)
Elevation Discharge Inside Dia. (psi/ft) Fit-Len.
End. KFactor Pressure Velocity PE-(psi)
(feet) (gpm) C-Value Fittings Tot-Len.
Node (K) (psi) (fps) PV-(psi)
Type-Grp (ft)

WARNING: Maximum friction loss exceeded for this pipe

160 14.00 46.00 58.36 17.38 1.50 58.36 0.11720 3.30 1.324
130 0.00 46.00 0.00 18.70 1.610 9.20 T 8.00 0.000
SCHED 40 WET STEEL 120 0 11.30 0.010

130 0.00 46.00 0.00 18.70 1.00 23.60 0.17685 6.20 1.450
140 0.00 46.00 0.00 17.25 1.049 8.76 E 2.00 0.000
SCHED 40 WET STEEL 120 0 8.20 0.022

140 0.00 46.00 0.00 17.25 1.00 23.60 0.17685 2.00 0.354
150 5.60 44.00 23.60 17.76 1.049 8.76 ----- 0.00 -0.866
SCHED 40 WET STEEL 120 0 2.00 0.022

90 0.00 46.00 0.00 27.50 2.50 279.67 0.26529 1.30 1.937


170 0.00 46.00 0.00 29.44 2.469 18.74 E 6.00 0.000
SCHED 40 WET STEEL 120 0 7.30 0.008
WARNING: Maximum friction loss exceeded for this pipe

170 0.00 46.00 0.00 29.44 2.50 279.67 0.26529 0.70 3.369
180 0.00 45.30 0.00 33.11 2.469 18.74 T 12.00 0.303
SCHED 40 WET STEEL 120 0 12.70 0.008
WARNING: Maximum friction loss exceeded for this pipe

180 0.00 45.30 0.00 33.11 2.50 140.68 0.07440 12.10 1.124
190 0.00 45.30 0.00 34.24 2.469 9.43 F 3.00 0.000
SCHED 40 WET STEEL 120 0 15.10 0.004

190 0.00 45.30 0.00 34.24 2.50 140.68 0.07440 30.80 2.515
200 0.00 45.30 0.00 36.75 2.469 9.43 F 3.00 0.000
SCHED 40 WET STEEL 120 0 33.80 0.004

200 0.00 45.30 0.00 36.75 2.50 140.68 0.07440 30.80 2.515
210 0.00 45.30 0.00 39.27 2.469 9.43 F 3.00 0.000
SCHED 40 WET STEEL 120 0 33.80 0.004

210 0.00 45.30 0.00 39.27 2.50 140.68 0.07440 31.80 2.589
220 0.00 45.30 0.00 41.86 2.469 9.43 F 3.00 0.000
SCHED 40 WET STEEL 120 0 34.80 0.004

220 0.00 45.30 0.00 41.86 2.50 140.68 0.07440 17.10 2.165
230 0.00 45.30 0.00 44.02 2.469 9.43 T 12.00 0.000
SCHED 40 WET STEEL 120 0 29.10 0.004

230 0.00 45.30 0.00 44.02 2.50 139.00 0.07277 13.10 1.172
240 0.00 45.30 0.00 42.85 2.469 9.31 F 3.00 0.000
SCHED 40 WET STEEL 120 0 16.10 0.004

240 0.00 45.30 0.00 42.85 2.50 139.00 0.07277 31.80 2.532
245 0.00 45.30 0.00 40.32 2.469 9.31 F 3.00 0.000
SCHED 40 WET STEEL 120 0 34.80 0.004

245 0.00 45.30 0.00 40.32 2.50 139.00 0.07277 30.80 2.459
250 0.00 45.30 0.00 37.86 2.469 9.31 F 3.00 0.000
SCHED 40 WET STEEL 120 0 33.80 0.004

250 0.00 45.30 0.00 37.86 2.50 139.00 0.07277 30.50 2.438
255 0.00 45.30 0.00 35.42 2.469 9.31 F 3.00 0.000

Active Version 1000 Pipe Capacity 02 ÓÈÊãÈÑ, 2015


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem mohamed (GS)-KFU GIRLS School Page 12

Fire Sprinkler Output Data

Overall Pipe Output Data (cont'd)


Nom. Dia. F. L./ft Pipe-Len.
Beg. Nodal Residual Q (gpm) PF-(psi)
Elevation Discharge Inside Dia. (psi/ft) Fit-Len.
End. KFactor Pressure Velocity PE-(psi)
(feet) (gpm) C-Value Fittings Tot-Len.
Node (K) (psi) (fps) PV-(psi)
Type-Grp (ft)

SCHED 40 WET STEEL 120 0 33.50 0.004

255 0.00 45.30 0.00 35.42 2.50 139.00 0.07277 19.70 2.307
180 0.00 45.30 0.00 33.11 2.469 9.31 T 12.00 0.000
SCHED 40 WET STEEL 120 0 31.70 0.004

230 0.00 45.30 0.00 44.02 2.50 279.67 0.26529 7.20 9.073
260 0.00 45.30 0.00 53.09 2.469 18.74 TGC 27.00 0.000
SCHED 40 WET STEEL 120 0 34.20 0.008
WARNING: Maximum friction loss exceeded for this pipe

260 0.00 45.30 0.00 53.09 2.00 100.00 0.09402 17.90 2.153
270 0.00 45.30 0.00 50.94 2.067 9.56 E 5.00 0.000
SCHED 40 WET STEEL 120 0 22.90 0.006

270 0.00 45.30 0.00 50.94 2.00 100.00 0.09402 9.80 1.392
280 0.00 35.50 100.00 53.79 2.067 9.56 E 5.00 -4.243
SCHED 40 WET STEEL 120 0 14.80 0.006

260 0.00 45.30 0.00 53.09 3.00 379.67 0.16216 9.20 3.924
290 0.00 45.30 0.00 57.02 3.068 16.48 T 15.00 0.000
SCHED 40 WET STEEL 120 0 24.20 0.005

290 0.00 45.30 0.00 57.02 4.00 379.67 0.04317 20.70 1.325
300 0.00 31.20 0.00 64.45 4.026 9.57 E 10.00 6.105
SCHED 40 WET STEEL 120 0 30.70 0.002

300 0.00 31.20 0.00 64.45 4.00 379.67 0.04317 55.50 2.828
310 0.00 31.20 0.00 67.28 4.026 9.57 E 10.00 0.000
SCHED 40 WET STEEL 120 0 65.50 0.002

310 0.00 31.20 0.00 67.28 4.00 379.67 0.04317 31.20 2.210
320 0.00 0.00 0.00 83.00 4.026 9.57 T 20.00 13.510
SCHED 40 WET STEEL 120 0 51.20 0.002

320 0.00 0.00 0.00 83.00 6.00 379.67 0.00587 26.20 0.236
330 0.00 0.00 0.00 83.23 6.065 4.22 E 14.00 0.000
SCHED 40 WET STEEL 120 0 40.20 0.000

330 0.00 0.00 0.00 83.23 6.00 379.68 0.00587 8.50 0.132
340 0.00 0.00 0.00 83.36 6.065 4.22 E 14.00 0.000
SCHED 40 WET STEEL 120 0 22.50 0.000

340 0.00 0.00 0.00 83.36 6.00 379.67 0.00587 95.40 0.642
350 0.00 0.00 0.00 84.01 6.065 4.22 E 14.00 0.000
SCHED 40 WET STEEL 120 0 109.40 0.000

350 0.00 0.00 0.00 84.01 6.00 379.67 0.00587 87.30 0.594
360 0.00 0.00 0.00 84.60 6.065 4.22 E 14.00 0.000
SCHED 40 WET STEEL 120 0 101.30 0.000

360 0.00 0.00 0.00 84.60 6.00 379.67 0.00587 26.20 0.236
370 0.00 0.00 0.00 84.84 6.065 4.22 E 14.00 0.000
SCHED 40 WET STEEL 120 0 40.20 0.000

370 0.00 0.00 0.00 84.84 6.00 379.67 0.00587 26.60 0.238
380 0.00 0.00 0.00 85.07 6.065 4.22 E 14.00 0.000
SCHED 40 WET STEEL 120 0 40.60 0.000

Active Version 1000 Pipe Capacity 02 ÓÈÊãÈÑ, 2015


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem mohamed (GS)-KFU GIRLS School Page 13

Fire Sprinkler Output Data

Overall Pipe Output Data (cont'd)


Nom. Dia. F. L./ft Pipe-Len.
Beg. Nodal Residual Q (gpm) PF-(psi)
Elevation Discharge Inside Dia. (psi/ft) Fit-Len.
End. KFactor Pressure Velocity PE-(psi)
(feet) (gpm) C-Value Fittings Tot-Len.
Node (K) (psi) (fps) PV-(psi)
Type-Grp (ft)

390 0.00 0.00 0.00 85.12 6.00 379.68 0.00587 7.00 0.041
380 0.00 0.00 0.00 85.07 6.065 4.22 ----- 0.00 0.000
SCHED 40 WET STEEL 120 0 7.00 0.000

Active Version 1000 Pipe Capacity 02 ÓÈÊãÈÑ, 2015


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem mohamed (GS)-KFU GIRLS School Page 14

Fire Sprinkler Output Data

Overall Sprinkler Output Data


Flowing Sprinkler Residual Flowing Sprinkler
Area Group Sprinkler Flowing Area
Sprinkler Elevation Pressure Density Discharge
Code KFactor (K) (ft²)
Node No. (feet) (psi) (gpm/ft²) (gpm)

10 5.60 44.00 15.00 175.00 0.124 21.69


Sub Totals For Non-Group 175.00 0.124 21.69

40 14.00 46.00 16.13 175.00 0.321 56.23


Sub Totals For Non-Group 175.00 0.321 56.23

60 5.60 44.00 19.86 175.00 0.143 24.96


Sub Totals For Non-Group 175.00 0.143 24.96

80 14.00 46.00 23.21 175.00 0.385 67.44


Sub Totals For Non-Group 175.00 0.385 67.44

110 5.60 44.00 23.93 175.00 0.157 27.40


Sub Totals For Non-Group 175.00 0.157 27.40

150 5.60 44.00 17.76 175.00 0.135 23.60


Sub Totals For Non-Group 175.00 0.135 23.60

160 14.00 46.00 17.38 175.00 0.333 58.36


Sub Totals For Non-Group 175.00 0.333 58.36

Totals For All Groups 1225.00 0.333 279.68

Active Version 1000 Pipe Capacity 02 ÓÈÊãÈÑ, 2015


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem mohamed (GS)-KFU GIRLS School Page 15

Fire Sprinkler Output Summary

Hydraulically Most Demanding Sprinkler Node


HMD Sprinkler Node Number: 10
HMD Actual Residual Pressure: 15.00 psi
HMD Actual GPM: 21.69 gpm

Sprinkler Summary
Sprinkler System Type: Wet
Specified Area Of Application: 1500.00 ft²
Minimum Desired Density: 0.100 gpm/ft²
Application Average Density: 0.186 gpm/ft²
Application Average Area Per Sprinkler: 214.29 ft²
Sprinkler Flow: 279.68 gpm
Average Sprinkler Flow: 39.95 gpm

Flow Velocity And Imbalance Summary


Maximum Flow Velocity ( In Pipe 90 - 170 ) 18.74 ft/sec
Maximum Velocity Pressure ( In Pipe 100 - 110 ) 0.03 psi

Allowable Maximum Nodal Pressure Imbalance: 0.0010 psi


Actual Maximum Nodal Pressure Imbalance: 0.0006 psi
Actual Average Nodal Pressure Imbalance: 0.0002 psi
Actual Maximum Nodal Flow Imbalance: 0.0009 gpm
Actual Average Nodal Flow Imbalance: 0.0001 gpm

Overall Network Summary


Number Of Unique Pipe Sections: 42
Number Of Flowing Sprinklers: 7

Pipe System Water Volume: 179.96 gal

Sprinkler Flow: 279.68 gpm


Non-Sprinkler Flow: 100.00 gpm
Total System Demand Flow: 379.68 gpm

Minimum Required Residual Pressure At System Inflow


85.12 psi
Node:
Demand Flow At System Inflow Node: 379.68 gpm

Active Version 1000 Pipe Capacity 02 ÓÈÊãÈÑ, 2015


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem mohamed (GS)-KFU GIRLS School Page 16

Fire Sprinkler Output Data

Hydraulic Supply/Demand Graph

100 98

90 87
84

80

70
Pressure psi

60

50

40

30

20

10

0
1 2 3 4 5 6 7 8 9 10
Flowrate(x100) gpm

Adjusted Hydrant Data


Static Pressure: 0 psi
Test Residual Pressure: 0 psi
Test Flow Rate: 0 gpm

Demand Point Data


Calculated Residual Pressure: 85.12 psi
Calculated Flow Rate: 379.68 gpm
Excess Available Inflow Residual Pressure: -85.12 psi

Active Version 1000 Pipe Capacity 02 ÓÈÊãÈÑ, 2015


Gas System Calculations

26 of 27
MEDIUM VOLTAGE ROOM (G-04)

W=agent weight in Kg
V=Hazard Volume m3
C=FM200 volumetric concentration in air
S= specific volume of super heated FM200 vapor in m3/kg

T=25 Room temperature


Area = 20.8 m
Height = 3.8 m
Volume = 79.04 m
Room Temp = 25
Specific volum0.1394
c= 7
W= 42.68 Kg
W= 43 Kg
TRANSFORMER ROOM (G-128)

W=agent weight in Kg
V=Hazard Volume m3
C=FM200 volumetric concentration in air
S= specific volume of super heated FM200 vapor in m3/kg

T=25 Room temperature


Area = 64.4 m
Height = 3.8 m
Volume = 244.72 m
Room Temp = 25
Specific volum0.1394
c= 7
W= 132.14 Kg
W= 133 Kg
ELECTRICAL ROOM (G-129)

W=agent weight in Kg
V=Hazard Volume m3
C=FM200 volumetric concentration in air
S= specific volume of super heated FM200 vapor in m3/kg

T=25 Room temperature


Area = 78.8 m
Height = 3.8 m
Volume = 299.44 m
Room Temp = 25
Specific volum0.1394
c= 7
W= 161.68 Kg
W= 163 Kg
GENERATOR ROOM (G-127)

CO2 required=Flooding factor x Volume

Area = 25.4 m
Height = 3.8 m
Volume = 96.52 m³ ˃ 56.6 m³

Flooding factor = 1.33

No of Cylinder = Flooding factor x Volume/45

No of Cylinder= 2.85
No of Cylinder= 3
ELECTRICAL ROOM (G-31)

CO2 required=Flooding factor x Volume

Area = 23.6 m
Height = 3.8 m
Volume = 89.68 m³ ˃ 56.6 m³

Flooding factor = 1.33

No of Cylinder = Flooding factor x Volume/45

No of Cylinder= 2.65
No of Cylinder= 3
ELECTRICAL ROOM (G-07)

CO2 required=Flooding factor x Volume

Area = 15.9 m
Height = 3.8 m
Volume = 60.42 m³ ˃ 56.6 m³

Flooding factor = 1.33

No of Cylinder = Flooding factor x Volume/45

No of Cylinder= 1.79
No of Cylinder= 2

S-ar putea să vă placă și