33/11 kV 5 MVA Transformer Test

Report (1CF.B710.32.16)
Client 33/11 kV 5 MVA Tr
Execution date 6/23/2020 Reason of the job Commission
Tested by JRCTESTING-PC\JRC TESTING Location RRP Agro
Approved by Asset Transformer
Report ID 1 Asset type Two-winding
Report issue date 25/6/2020 7:17:44 PM Asset serial number 1CF.B710.32.16
Work order RRP Transformer testing Manufacturer FATO

Summary

Performed tests Assessment


Winding DF & CAP Pass
Turns Ratio Prim-Sec Pass
DC Winding Resistance Prim Pass
DC Winding Resistance Sec Pass

Overall Assessment Not assessed

Tested by: Approved by:

1
Location & company information
Location Company
Name RRP Agro Company
Region NARSHINDI Department
Division DHaka Address
Area City
Plant State/Province
Address Postal code
City Country
State/Province Phone No.
Postal code Fax No.
Country E-mail

Geo coordinates

Contact person Comment


Name
Phone No. 1
Phone No. 2
Fax No.
E-mail

Transformer nameplate data


Serial number 1CF.B710.32.16 Apparatus ID
Manufacturer FATO Feeder 33kV
Manufacturing year No. phases 3
Manufacturer type Vector group Dyn11

Comment

Voltage ratings
Winding Voltage L-L Voltage L-N Insul. level L-L
Prim 33.000 kV kV 75 kV
Sec 11.000 kV 6.351 kV kV

Current ratings at rated power

Winding
Prim Sec Rated power
87.500 A 262.400 A 5.000 MVA

22
Short-circuit impedance Prim - Sec
uk[%] Base power Base voltage Load losses Pk OLTC position DETC position

6.780 % MVA kV W

Others
Category Distribution

Status In operation

Tank type Free breathing

Insulation medium Mineral oil

Fluid insulation volume l

Fluid insulation weight 2370 kg

Total weight 10810 kg

Global test conditions


Weather Clear Humidity 30 %

Unit location Outside Ambient temperature 32 °C

3
Global test conditions
Weather Clear Humidity 30 %
Unit location Outside Ambient temperature 32 °C

4
Winding DF & CAP
Ambient temperature 30 °C Weather Cloudy
Top oil temperature 32 °C Humidity 71 %

Comments

Standard test

Injection at Prim
Corr. temperature 40 °C
Corr. factor 0.64

No. Meas. Test mode Freq. V out I out Watt losses DF meas DF corr Cap. meas Assessment

1 ICH+ICHL GST 50.00 Hz 10.00 kV 16.12 mA 1433.16 mW 0.8886 % 0.5687 % 5126.8 pF Pass
2a ICH (V) GSTg-A 50.00 Hz 10.01 kV 5.50 mA 1323.10 mW 0.8406 % 0.5401 % 1744.9 pF Pass
3a ICHL (V) UST-A 50.00 Hz 10.00 kV 10.63 mA 280.76 mW 0.2640 % 0.1690 % 3383.7 pF Pass

Graphs for frequency sweep

4
Turns Ratio Prim-Sec
Test voltage 150 V Use CP SB1 No

IEC 61378-1 No

Comments

Standard test

Phase A Phase B Phase C


Nom. ratio TTR Ratio dev TTR Ratio dev TTR Ratio dev Assessment
5.7158 5.7133 -0.04 % 5.7112 -0.08 % 5.7112 -0.08 % Pass
5.5859 5.5868 0.02 % 5.5849 -0.02 % 5.5846 -0.02 % Pass

5.1962 5.196 0.00 % 5.1941 -0.04 % 5.1941 -0.04 % Pass

4.8064 4.8013 -0.11 % 4.7994 -0.15 % 4.7996 -0.14 % Pass

4.6765 4.675 -0.03 % 4.6732 -0.07 % 4.6733 -0.07 % Pass

5
7
DC Winding Resistance Prim
Test current 3.0 A Use CP SB1 No
Winding temperature 40 °C Mode Manual
Temperature corr. factor (K) 1.128

Comments

Standard test

Phase A Phase B Phase C


Tap R meas R dev R corr R meas R dev R corr R meas R dev R corr Assessment
Nom. 1.394 Ω 0.088 % 1.572 Ω 1.394 Ω 0.069 % 1.572 Ω 1.395 Ω 0.084 % 1.574 Ω Pass

6
DC Winding Resistance Sec
Test current 3.0 A Use CP SB1 No
Winding temperature 40 °C Mode Manual
Temperature corr. factor (K) 1.128

Comments

Standard test

Phase A Phase B Phase C


Tap R meas R dev R corr R meas R dev R corr R meas R dev R corr Assessment
Nom. 65.314 mΩ 0.092 % 73.675 mΩ 65.180 mΩ 0.089 % 73.523 mΩ 65.263 mΩ 0.066 % 73.617 mΩ Pass