Version 1.0
Company assessed and Page 1 of 10
recommended switchgear list
The master version of the this document resides in the E.ON UK Documentum database
CAUTION – any other copy may be out of date
© Central Networks plc
Assessed and Recommended Switchgear list
Purpose This list replaces any and all previous listings of switchgear approved for use in
E ON Central Networks that have been issued by East Midlands Electricity and
Midlands Electricity (and any successor companies).
To provide a guide for switchgear application, selection for Infrastructure
Services , Energy Services , Independent Connections Providers, procurement
and External Service Providers.
Scope This Company assessed and recommended switchgear list covers indoor and
outdoor switchgear with the voltage from 11 kV to 132 kV provides a summary
the main electrical parameters and related assessment information of the ENA
Switchgear Assessment Panel. This also provides a guide for switchgear
application, selection for Infrastructure Services, Energy Services, Independent
Connections Providers, procurement and third party service providers.
The list only includes the switchgear currently in production, available in the
market and assessed and recommended by the company. Switchgear that has
previously been assessed by ENA and approved by CN is not included.
E.ON Central Networks, E.ON UK Business Services, E.ON Energy Services and
their service providers and contractors.
Switchgear Manufacturers.
Restrictions: None
Review Date Annually (or earlier if additional switchgear makes/models are approved by CN
for use on its network) - 2010
The master version of the this document resides in the E.ON UK Documentum database
CAUTION – any other copy may be out of date
© Central Networks plc
Assessed and Recommended Switchgear list
1. SCOPE
This company approved switchgear list has been prepared by E.ON Central Networks. This approved
switchgear list covers the provision of indoor and outdoor, three phase switchgear, for 11 kV, 33kV,
66 kV and 132 kV for continuous service at 50 Hertz, for use on E.ON Central Networks distribution
network. It supersedes all previous approved switchgear lists that have been issued by East
Midlands Electricity and Midlands Electricity (and their successors).
Switchgear covered by this assessed and recommended list shall comply with the relative
International and British Standards (BS) and Energy Networks Association Technical Specifications
(ENATS) listed.
The list only includes the switchgear currently in production, available in the market and approved
by the company.
2. GENERAL REQUIREMENT
The switchgear shall generally, except where varied by the related E ON Central Networks technical
specifications for switchgear is specification, comply with the appropriate requirements of all
relevant sections of the Energy Networks Association Technical Specification 41-36 and 41-37 (ENATS
41-36 & 41-37) and IEC 602271, current at the time of tendering.
In general, the switchgear listed should be reliable and safe to operate, with low life costs,
interchangeability and availability of service. The manufacturer’s manuals should clearly indicate any
special consideration and procedure for installation, commissioning, use, maintenance, disposal in
respect of Health and Safety, Environmental and Statutory obligations. The risk assessment process for
possible/potential hazards and particular areas of difficulty should look at the complete life cycle of the
equipment from installation to removal and disposal, and should be highlighted in the installation and
operation handbooks and manuals.
The master version of the this document resides in the E.ON UK Documentum database
CAUTION – any other copy may be out of date
© Central Networks plc
Manufacturer Designation Rated I (normal) 3s Equipment description Type no iss Date note
Voltage (A) STWC ue
(kV) (kA)
(1) 145 kV GIS (consultant for up date info. re gas zone requirements, three position switch, etc.)
1 ABB ELK-0 Mk.4 145 2500 31.5/40kA Indoor GIS NOC 1003 1 01/01/00
to EATS
41-10
2 Siemens 8DN8 II 145 2500 31.5/40kA Indoor GIS NOC 1037 07/2005
to EATS
41-10
3 Mitsubishi GMKD-GIS 145 2500/3150 40 Indoor GIS NOC 1062 02/2008 has not taken
(2) 145 kV CB
1 ABB LTB145 145 3150 40 Live Tank outdoor open terminal SF6 circuit NOC 1005-2 2 11/2005
D1/B(CSB1) breaker
2 AREVA GL312 145 3150 31.5/40kA Live Tank outdoor open terminal SF6 Circuit NOC 1004-2 2 03/2000
to EATS Breaker
41-10
3 Siemens 3AP1-D/T(145) 145 3150 31.5kA/40 Outdoor Dead Tank open terminal SF6 circuit NOC 1031 1 04/2004
kA to breaker
EATS 41-
10
4 AREVA (Alstom DT1-145 145 3150 40 Dead Tank outdoor SF6 Circuit Breaker NOC 1028-4 4 09/2007
T&D) F1/4031/FK
The master version of the this document resides in the E.ON UK Documentum database
CAUTION – any other copy may be out of date
© Central Networks plc
Assessed and Recommended Switchgear list
(5) 72.5 kV CB
1 Siemens 3AP1-D/T(72.5Kv) 72.5 3150 31.5 outdoor dead tank SF6 circuit breaker NOC 1030 1 04/2004
2 AREVA DT1-72.5 F1/4030 72.5 2500 75ms @ outdoor dead tank SF6 circuit breaker NOC 1052 1 05/2007
FK3-1 40kA
120ms @
31.5kA
(6) 72.5 kV CT VT
ABB IMB-72 72.5 1600 63/40 Current Transformer 2005 model NOC 1038 1 11/2005
2000, 1s/3s
(7) 36 kV CB
1 Areva T&D WSA 2000A 36 2000/2500 25 Indoor SF6 insulated vacuum circuit breaker NOC 1049 1 08/2006
2 ABB ZX1.2 36 1250/2000 25/31.5 Indoor fixed pattern Circuit Breaker Single busbar NOC 1027 1 10/2006
SF6 insulated fixed circuit breaker VD4X 3612-25
with types VG6 (25kA, 1250A, 36kV) vacuum
interrupter, and VD4X 3620-31 with types VG6
(31kA, 2000A, 36kV) vacuum interrupter,
incorporating 3 -
Position disconnector/earthing-switch types
UX2TE 3612-25 (25kA, 1250A, 36kV) and UX2TE
3620-31 (31.5kA, 2000A, 36kV).
3 Siemens NX PLUS 36 with 36 1250/2000 31.5 Single busbar SF6 insulated fixed circuit breaker NOC 1033 1 06/2004 We should be using the motor to
Vacuum 1900A bus 3AH15 with type VSG36031 vacuum interrupters operate the disconnector as this
Circuit-Breakers section (1250A and 2000A) and 3 position disconnector prevents damage to the 3ps by over
eager manual operation by those
(N.B. Manual operation only – Motor fitted as
who are too strong for light work.
standard but disconnected)
Version: 1.0 Date of Issue: March 2009 Page 5 of 10
The master version of the this document resides in the E.ON UK Documentum database
CAUTION – any other copy may be out of date
© Central Networks plc
Assessed and Recommended Switchgear list
4 Schneider CBGS-0 36 1250 25 Circuit Breaker (Fixed Pattern) NOC 1047 RECERVED NOC no.
On trial
5 Schneider CBGS-0 36 630/1250 25 Switch Disconnector NOC 1048 On trial
6 Ormazabal CML 36 630 20kA SF6 Switch Disconnector NOC 1022 10/2002
Combined busbar and switch-disconnector/
50kA earthing switch; cable
(10xC) Feeder (incoming or outgoing) unit with CTs in
cable compartment; busbar cable connector
7 Ormazabal CMP-V 36 630 20kA Circuit Breaker (Fixed Pattern) NOC 1023 10/2002
45ms
D.C. Single busbar SF6 insulated fixed circuit
compone breaker type IV-3 with Cutler Hammer type
nt 29% WL-35747A vacuum interrupters incorporating
3 position disconnector type SDG
- compartments combined busbar and circuit
breaker; cable
- variants assessed Feeder (incoming or outgoing)
unit with CTs in
or below cable compartment; VT panel
(with/without protection or metering CTs); bus
section
(with/without metering VT/CTs)
The master version of the this document resides in the E.ON UK Documentum database
CAUTION – any other copy may be out of date
© Central Networks plc
Assessed and Recommended Switchgear list
2 Morris Line Equip. RDB 72kV up to 2000 25 or Rotating Double Break Disconnector CN approved 08/2007
31.5kA/3s
(9) 12 kV CB
1 Areva T&D Visax S 12 800 & 1250 25kA D.C Single busbar air insulated switchgear with NOC 1021 2 06/2008
VISAX S 1225 compone rotating vacuum circuit breaker and AVI type VG2 NOC 1035 1 11/2004
nt vacuum interrupter (BLV23 and AVI type VG3
/ 36% vacuum interrupter for 2000A)
The master version of the this document resides in the E.ON UK Documentum database
CAUTION – any other copy may be out of date
© Central Networks plc
Assessed and Recommended Switchgear list
3 Schneider Genie Evo 12 630/1250 25KA Circuit Breaker (Fixed Pattern) NOC 1032 06/2004 For dis.
630A feeder; 1250A incomer Not primary gear
45ms with fixed VT (removable primary fuses) & top and
D.C. bottom entry cable compartment;
compone 630A & 1250A Bus-section & ‘riser’
nt –27%
2 Schneider RN6c 13.8 630 (630) 21 Outdoor RMU 630A SF6 CB (95 kV BIL) NOC 1018 - 04/2004 Provision for
automation
required as CN
spec.
3 Lucy SABRE VRN2A 12 250A CB 20kA 3 Outdoor RMU NOC 1041 2 05/2007
(630 A sec. 95Kv
switches)
4 Schneider SE6 13.8 630 21kA Outdoor extensible SF6 switch disconnector AN 157A 1 03/1994
(95kV BIL)
5 Schneider CE2 13.8 200 21kA Outdoor extensible SF6 switch disconnector AN 160A 1 03/1994
(95kV BIL)
6 Schneider CE6 13.8 630 21kA Outdoor extensible SF6 switch disconnector AN 159 1 03/1994
(95kV BIL)
7 Schneider SE6-E1 13.8 630 21kA Outdoor extensible SF6 busbar earth switch (95kV
BIL)
8 Schneider CN2 12 200 16kA Outdoor non-extensible SF6 circuit breaker AN 158 1 03/1994
(75kVBIL)
9 Schneider SE6-B1 13.8 630 21kA Outdoor extensible SF6 bus-section switch AN
disconnector
10 Schneider CE6-B5 13.8 630 21kA Outdoor extensible SF6 bus-section circuit AN 200 1
breaker
11 Schneider MU2 12 16kA Air Insulated Metering Unit (75kV BIL)
12 Lucy AIMU 12 400 16kA Air Insulated Metering Unit 75 Kv BIL NOC 1013 1 11/2001
The master version of the this document resides in the E.ON UK Documentum database
CAUTION – any other copy may be out of date
© Central Networks plc
Assessed and Recommended Switchgear list
1 Morris Line Equip. MLS 12 630 25 Outdoor pole mounted Air Break Switch CN Approved 08/2007
Disconnector
Rated short-circuit making current 25kA pk.
Manula independant spring assisted high level rod
operated mechanism. Fitted with 400 amp
interrupter heads
2 Cooper Power Type L Cut-out 27kV Up to 300 10kA Pole mounted Dropout Expulsion Fuse to NEMA CN Approved 10/2002
Systems L9COP1A standard. Including:
100 amp fuse holder LDCA00A
300 amp link LDC300A.
3 Cooper Bussmann 27ASL50CR5-2 27kV Up to 50 10kA Automatic Sectionalising Link for use in NEMA CN Approved 10/2002
standard 27kV cut-out
(12) LV cabinet
1 Schneider Fuse Cabinet EC 415V 800 18 outdoor, substation cable distribution board, 4 NOC 1054 1 05/2007
N0 2R4 outgoing fuse ways,
2 Schneider Fuse Cabinet EC 415V 1600 35.5 outdoor, substation cable distribution board, 4, NOC 1056 1 05/2007
N0 3R4 outgoing fuse ways,
3 Schneider Fuse Cabinet 415V 1600 35.5 outdoor, substation cable distribution board, 5 NOC 1058 1 05/2007
EC N0 4R4 outgoing fuse ways,
4 Schneider Fuse Cabinet 415V 800 18.0 Outgoing Breaker type Masterpact NT08, CN Approved 04/2005
EC N0 6R4 Micrologic 5.0A 800A ACB Cab 1 way with
metering CT’s 800/5A, 10VA,Class 0.5
5 Schneider Fuse Cabinet 415V 1600 35.5 Outgoing Breaker type Masterpact NT12, CN Approved 04/2005
EC N0 7R4 Micrologic 5.0A 1250A ACB Cab 1 way with
metering CT’s 1200/5A, 10VA,Class 0.5
6 Schneider Fuse Cabinet 415V 1600 35.5 Outgoing Breaker type Masterpact NT16, CN Approved 04/2005
EC N0 8R4 Micrologic 5.0A 1600A ACB Cab 1 way with
metering CT’s 1600/5A, 10VA,Class 0.5
7 Lucy Fuse Cabinet 415V 800 18 Outdoor, substation cable distribution board. 2 AN 155 01/1993
Trifca outgoing fuse ways,
The master version of the this document resides in the E.ON UK Documentum database
CAUTION – any other copy may be out of date
© Central Networks plc
Assessed and Recommended Switchgear list
8 Lucy Fuse Cabinet 415V 1600 35.5 outdoor, substation cable distribution board, 4 AN 156 01/1993
Trifca outgoing fuse ways,
9 Lucy LV ACB 415V 800 35.0 Terasaki ACB type of AR208S fitted with CN Approved 04/2005
AGR21BL OCR
10 Lucy LV ACB 415V 1250 35.0 Terasaki ACB type of AR212S fitted with CN Approved 04/2005
AGR21BL OCR
11 Lucy LV ACB 415V 1600 35.0 Terasaki ACB type of AR216S fitted with CN Approved 04/2005
AGR21BL OCR
(13) 36kV & 72kV Fault Throwing Switch
1 FKI horizon Fault 38 kV 25 kA Single phase to earth fault making switch CN approved 08/2006
thrower
2 Morris Line Equip. FTS 36kV 40kA/1s Fault Throwing Switch CN approved 10/1995
3 Morris Line Equip. FTS 72kV 40kA/1s Fault Throwing Switch CN approved 10/1995
The master version of the this document resides in the E.ON UK Documentum database
CAUTION – any other copy may be out of date
© Central Networks plc