DESIGN
OF
SLAB
1
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
A 1.10 m
Ratio m= = = 0.44 < 0.5, therefore ONE - WAY SLAB
B 2.50 m
GIVEN:
Dead loads:
Factored Load:
WUDL = 1.2DL = 1.2(5.163) = 6.20 kPa
2
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
Effective Depth:
l 2.50(1000)
h min= = =89.29 mm;
28 28
say, 90 mm
AT END 1
Wu l 2
Mu= , from Table 406.5.2, NSCP 2015
11
Mu=(9.24)¿ ¿ 5.25 kN-m Where:
Mu 5.25 x 106
Rn= = =¿ 2.0 MPa b= width of slab used every 1m strip
∅ b d 2 0.9∗1000∗54 2
d=¿ effective depth
'
0.85 f c 2 Rn
ρ=
fy ( √
1− 1−
0.85 f ' c )
0.85(28) 2(2)
=
420 ( √
1− 1−
0.85(28)
=¿ 0.00498 )
1.4 1.4 √ f ' c = √ 28 =¿0.0031497;
ρmin = = = 0.00333 or ρmin =
fy 420 4 fy 4 (420)
0.02064
3
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
As = ρbd
Using 12 mm bars:
A ¯¿
Spacing= ¿
As
π∗122
∗1000
4 420.50 mm; say S = 400mm
Spacing= =¿
268.96
Smax = 3h, from 407.7.2.3, NSCP 2015 where: h=90 mm, see page 3
Therefore, S = 270mm
AT MID-SPAN:
4
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
Wu l 2
Mu= , from Table 406.5.3, NSCP 2015
16
Mu=(9.24)¿ ¿
Mu 3.61 x 106
Rn= = =¿ 1.38 MPa
∅ b d 2 0.9∗1000∗54 2
0.85 f ' c 2 Rn
ρ=
fy ( √
1− 1−
0.85 f ' c )
0.85(28) 2(1.38)
=
420 ( √
1− 1−
0.85(28)
=¿ 0.00339)
1.4 1.4 √ f ' c = √ 28 =¿0.0031497
ρmin = = = 0.00333 or ρmin ¿
fy 420 4 fy 4(420)
0.02064
As = ρbd
Using 12 mm bars:
A ¯¿
Spacing= ¿
As
π∗122
∗1000
4 617.82 mm; say S = 600mm
Spacing= =¿
183.06
Smax = 3h, from 407.7.2.3, NSCP 2015 where: h=90mm, see page 3
5
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
Therefore, S = 270 mm
AT END 2:
Wu l 2
Mu= , from Table 406.5.3, NSCP 2015
10
Mu=(9.24)¿ ¿
Mu 5.775 x 106
Rn= = =¿ 2.20 MPa
∅ b d 2 0.9∗1000∗54 2
0.85 f ' c 2 Rn
ρ=
fy ( √
1− 1−
0.85 f ' c )
0.85(28) 2(2.20)
=
420 ( √
1− 1−
0.85(28)
=¿ 0.00551)
1.4 1.4 √ f ' c = √ 28 =¿0.0031497
ρmin = = = 0.00333 or ρmin ¿
fy 420 4 fy 4(420)
0.02064
As = ρbd
As = 0.00551 x 1000 x 54 = 297.54 mm2
Using 12 mm bars:
6
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
A ¯¿
Spacing= ¿
As
π∗122
∗1000
4 380.108 mm; say S = 350mm
Spacing= =¿
297.54
Smax = 3h, from 407.7.2.3, NSCP 2015 where: h=90 mm, see page 3
Therefore, S = 270mm
0.0018∗420
As= bh, from Table 407.6.1.1, NSCP 2015
Fy
A ¯¿
Spacing= ¿*1000
As
π∗122
∗1000
4
Spacing= =1163.55 mm
97.2
7
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
Say, S = 1100mm
Smax = 5h, from 407.7.6.2.1, NSCP 2015
S > SMAX
Therefore, S = 450 mm
8
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
1.10 m
12.mm
270 mm
0.75m
1m
2.50 m
12.mm
450 mm
0.75m
12.mm 12mm
450 mm 270 mm
1.10 m
9
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
GIVEN:
Use 12 mm rebars
A 3.00
Ratio m= = = 0.75 > 0.5, therefore TWO - WAY SLAB.
B 4.00
Minimum thickness,
ln
Minimum thickness, h= , from Table 408.3.1.1, NSCP 2015
33
4000 mm
= = 121.21 mm
33
10
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
dB = 115 – 30–12– 6
dB = 77 mm
Dead load:
Floor finish (ceramic or quarry tile on 25mm mortar bed) = 1.1 kPa
Floor fill (lightweight concrete per mm) = 0.15kPa
Ceiling finish (plaster on tile or concrete) = 0.24 kPa
Mechanical Duct Allowance = 0.20 kPa
Miscellaneous Load = 1 kPa
Electrical Load = 0.023kPa
Dead loads:
11
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
Factored Load:
CA=0.078
CB=0.014
C A =0.031
DL
C B =0.007
DL
C A =0.046
¿
C B =0.013
¿
At continuous edge:
A 3
Ratio= = = = 0.75
B 4
MOMENT COEFFICIENT, C A : SEE TABLE 1.a,page 43
❑
MA = 12.26 kN.m
At mid-span:
MOMENT COEFFICIENT, C A : SEE TABLE 1.b,page 43
DL
12
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
M A = 4.87 kN.m
DL
M A = 7.23 kN.m
¿
At mid-span:
M B = 1.10 kN.m
DL
M B = 2.04 kN.m
¿
13
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
SOLVING :
At continuous edge:
where:
MA 12.26 x 106
Rn= 2
= = 1.72 MPa MA = 12.26 KN.m, see page 12
∅ bd 0.9∗1000∗892
b= width of slab used every 1m strip
d=effective depth,89 mm, see page 10
0.85 f ' c 2 Rn
ρact =
fy
[1− 1−
√
0.85 f ' c
]
0.85∗28 2∗1.72
ρact =
420
1− 1− ( √
0.85∗28 )
ρact =0.00425
1.4 1.4
ρmin = = = 0.00333
fy 420
f 'c 28
ρmin = √ = √ =¿ 0.0031497
4 fy 4∗420
14
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
Where:
A s=ρbd ρ=¿ratio of tension reinforcement
A s=0.00425∗1000 mm∗89 d=¿effective depth, 89mm,see page 10
A s=378.25 mm2 b= width of slab used every 1m strip
Using 12 mm bars:
A ¯¿
Spacing= ¿
As
π∗122
∗1000
4 say 300 mm
Spacing= =299 mm
378.25
At Mid-span:
Where:
MA 12.1 x 106
Rn= = = 1.70 MPa MA= 12.1 KN.m, see page 13
∅ b d 2 0.9∗1000∗892
b= width of slab used every 1m strip
d= effective depth, 89mm, see page
10
0.85 f ' c 2 Rn
ρact =
fy √
[1− 1−
0.85 f ' c
]
0.85∗28 2∗1.70
ρact =
420 ( √
1− 1−
0.85∗28 )
15
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
ρact =0.0042
1.4 1.4
ρmin = = = 0.00333
fy 420
f 'c 28
ρmin = √ = √ =¿ 0.00314
4 fy 4∗420
Where:
A s=ρbd ρ=¿ratio of tension reinforcement
A s=0.0042∗1000∗89=373.8 mm2 b= width of slab used every 1m strip
d=¿effective depth,89mm, see page
10
Using 12 mm bars:
A ¯¿
Spacing= ¿
As
π∗122
∗1000
4 say 300 mm
Spacing= =302.56 mm
373.8
16
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
0.85∗28 2∗0.41
ρact =
420 ( √
1− 1−
0.85∗28 )
ρact =0.00098
1.4 1.4
ρmin = = = 0.00333
fy 420
f 'c 28
ρmin = √ = √ =¿ 0.0031497
4 fy 4∗420
Where:
17
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
Using 12 mm bars:
A ¯¿
Spacing= ¿
As
π∗122
∗1000
4 say 400mm
Spacing= =441.08 mm
256.41
Smax=2h
Smax=2*125= 250 mm
At Mid-span:
Where:
MB 3.14 x 106
Rn= 2
= = 0.58 MPa MB= 3.14 KN.m, see page 13
∅ bd 0.9∗1000∗77 2
b= width of slab used every 1m strip
d= effective depth, 77mm, see page 11
0.85 f ' c 2 Rn
ρact =
fy √
[1− 1−
0.85 f ' c
]
0.85∗28 2∗0.58
ρact =
420 ( √
1− 1−
0.85∗28 )
ρact =0.00140
18
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
1.4 1.4
ρmin = = = 0.00333
fy 420
f 'c 28
ρmin = √ = √ =¿ 0.0031497
4 fy 4∗420
Therefore, use 0.00333
Where:
A s=ρbd ρ=¿ratio of tension reinforcement
A s=0.00333∗1000∗77=256.41 mm2 b= width of slab used every 1m strip
d=¿ effective depth,77mm,see page
11
Using 12 mm bars:
A ¯¿
Spacing= ¿
As
π∗122
∗1000
4 say 400mm
Spacing= =441.08 mm
256.41
Smax=2h
Smax=2*125=250 mm
19
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
3.0m
0.75m 1.5m 0.75m
1m
250 mm
4.0m2m
250 mm
1m
250m
3.0 m
20
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
DESIGN OF
BEAM
(B-1)
21
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
Dead Load:
Floor Finish (ceramic or quarry tile on 25mm mortar bed) = 1.1kPa
Ceiling Finish (plaster on tile or concrete) = 0.24kPa
Mechanical Duct Allowance = 0.20kPa
Electrical Load = 0.023kPa
Miscellaneous = 1kPa
22
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
kN kN
(
W Wall =( 0.20 m ) ( 3.2m ) 23.5
m )
3
=15.04
m
kN kN
(
W beam =( 0.3 m )( 0.25 m ) 23.5
m 3)=1.763
m
wDL ( S ) w DL ( S )
Wu DL ( AB)=1.2 ( 3
+
3 )
+ wbeam +w wall
w ( S ) w ( S)
=1.2 ( +w +w )
DL DL
Wu DL ( BC ) + beam wall
3 3
w ( S) w ( S )
=1.2 ( +w +w )
DL DL
Wu DL ( CD ) + beam wall
3 3
5.503 ( 2 ) 5.503 ( 2 ) kN
¿ 1.2 ( + +1.763+15.04 )=28.97
3 3 m
w ( S) w ( S )
Wu =1.2 (
DL ( DE )
DL
+ DL
+w +w ) beam wall
3 3
5.503 ( 3 ) 5.503 ( 3 ) kN
¿ 1.2 ( + +1.763+15.04 ) =33.37
3 3 m
23
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
W ( S) W ( S ) 1.9 ( 2 ) 2.9 ( 2 )
Wu ¿(CD) =1.6 (
3
¿
+
3 )
¿
=1.6 ( 3 + 3 )=5.12 kNm
W (S ) W (S ) 1.9 ( 3 ) 2.9 ( 3 ) kN
Wu ¿(DE) =1.6( ¿
+ ¿
)=1.6 ( + ) =7.68
3 3 3 3 m
( L¿¿ 2) ( 34.09 ) ( 2 )2
FEM C D=Wu CD = =11.36 kNm ¿
12 12
(L¿¿ 2) −( 34.09 ) ( 2 )2
FEM DC =−Wu DC = =−11.36 kNm ¿
12 12
( L¿¿ 2) ( 41.05 )( 3 )2
FEM DE=Wu DE = =30.79 kNm ¿
12 12
24
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
(L¿¿ 2) − ( 41.05 ) ( 3 )2
FEM ED=−Wu ED = =−30.79 kNm ¿
12 12
SOLUTION:
25
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
K
@ Joint B DF=
K total @ Joint B
K 19.2
DFBA=DFBC= = =0.281
K total @ Joint B 19.2+ 15+15+19.2
K 15
DFBB’= DFBB’’= = =0.219
K total @ Joint B 19.2+ 15+15+19.2
K
@ Joint C DF=
K total @ Joint C
K 19.2
DFCB = = =0.262
K total @ Joint C 24+19.2+15+15
K 15
DFCC’= DFCC”= = =0.204
K total @ Joint C 24+19.2+15+15
K 24
DFCD = = =0.328
K total @ Joint C 24+19.2+15+15
K
@ Joint D DF=
K total @ Joint C
26
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
K 24
= =0.343
K total @ Joint D 24+ 16+15+15
K 15
DFDD’= DFDD”= = =0.214
K total @ Joint D 24+ 16+15+15
K 16
DFDE = = =0.229
K total @ Joint D 24+ 16+15+15
K
@ Joint E DF=
K total @ Joint E
K 16
DFED = = =0.348
K total @ Joint E 16+15+ 15
K 15
DFEE’= DFEE”= = =0.326
K total @ Joint E 16+15+ 15
CONTINUATION…
27
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
LOAD DIAGRAM
SHEAR DIAGRAM
MOMENT DIAGRAM
28
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
Ultimate Moments
(from MDM see page 27)
Mu = 30.452 kN.m
Mu =Φ Mn
Mu 30.452
Mn = = = 33.84 kN.m
Φ 0.9
EFFECTIVE DEPTH, de
1
d e=h+cov er+2( d bar )
2
1
d e=300 mm+40 mm+2( (20 mm ))
2
d e=360 mm
29
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
0.75∗0.85∗28∗0.85 600
ρmax = ( )¿
420 600+420
ρmax =0 .02125
Wherein,
Asfy d
a= '
0.85 f c bd
As
ρmax =
bd
ρmax fy d
a=
0.85 f ' c
0.02125(420)(360)
a= =135 mm
0.85(28)
a
Mn=0.85 f ' c a b x (d− )
2
0.135
Mn=0.85 ( 28 x 103 ) ( 0.135 ) (0.250)(0.36− )
2
Mn=234.95 kNm
Mu= ϕRnbd2
30.452 = 0.9Rn(250)(300)2
Rn= 1.504 MPa
30
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
ρ=
0.85 f ' c
fy [ √
1− 1−
2 Rn
0.85 f ' c ]
=
0.85(28)
420 [ √
1− 1−
2(1.504 )
0.85 (28) ]
ρ = 0.003702
ρmax =0 .02125
As = ρ bd1
= (0.003702)(250)(300)
= 277.64 mm2
As 277.64
No. of bars = =
Ad π ¿ ¿ ¿
Bar diameter = 10 mm
A v fs
S1=
Vsb
Vd
V s =V n −V cV n=
b de
64.35 kN
V n= =715 2
( 0.250 ) ( 0.360 ) m
V c =0.09 √ f ' c
kN
V c =0.09 √ 28 x 103 =15.06
m2
kN
V s =715−15.06=699.94
m2
A v =2¿
(0.000157)(420 x 10 6)
S1 = =0.142m∨use 150 mm
( 1.08986 x 106 ) (0.250)
de 0.36
S2 = = =0.180 m
2 2
Therefore, S= 150 mm
32
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
LV s 4(0.69994 MPa)
l 1= = =1.96 m
2Vn 2(0.715 MPa)
l 2=de +a+ de
Wherein,
L V
a=[ −d e ] s
2 Vn
4 0.70
a= [ 2
−0.360]0.72
=1.59 m
33
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
DESIGN OF
COLUMN
(C-1)
34
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
COMPUTATION OF Pu
Φ = 0.80 (2015 NSCP: Φ=0.80 for tied and 0.85 for spiral)
Initial ρ =0.02
fy= 420 MPa
f’c= 28 MPa
50 mm concrete cover
Assumed Section=(400 mm) (400 mm)
Assumed Ag = 160,000 mm2
Using 20 mm Φ rebar
10 mm Φ bar stirrups
35
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
Pu
Ag= '
ϕ ( 0.80 ) [0.85 ( f c ) ( 1−ρ ) + ( 420 ) ρ]
131.41 ×103
Ag=
0.80 ( 0.80 ) [0.85 ( 28 ) (1−0.02 ) + ( 420 ) (0.02)]
Ag = 6472.33 mm2
b=√ Ag=80.45 mm
Therefore, use 400 mm x 400 mm column
As=3200 mm 2
As=3200 mm 2
As
Number of main bars=
π d2
4
3200
Number of main bars=
π (20)2
4
Number of main ¯¿ 10.1859
Say, 10 bars
a. 16 db = 16(20) = 320mm
b. 48 dt = 48(10) = 480mm
SUMMARY:
Column size: 400 mm x 400 mm
Main bars: 10 – 20 mm diameter rebars
Ties: 10 mm diameter bars
Spacing: 400 mm
37
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
DESIGN OF
COLUMN-
FOOTING
(C1-F1)
38
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
DESIGN COMPUTATION
load
Required Footing Area, A =
s oil pressure
131.41kN
=
200
= 0.66 m2
1
Moment Capacity, Mc= Net Upward Pressure NUP (B) ( ) (B – a) 2
2
39
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
load 131.41
NUP= = = 91.26 kPa
provided area 1.44
Reinforcements, As:
Mc
As = ; where j = 0.89
fsjde
= 400 mm - 40mm – 16 mm
= 344 mm
Mc 44.35
As = = = 344.902 mm2
fsjde ( 420 x 1 0 ) ( 0.89 ) (0.344)
3
As 344.902
No .of bars= =
π d2 π¿¿¿
4
Say, 2 bars
40
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
vp
V p=
4 d e (a+d e )
80.90
V p= = 79.02 kPa
4(0.344 )( 0.4+0.344 )
V
μ=
ε 0 jde
37.67
μ= = 407.42 kPa
( 0.3 02 ) ( 0.89 ) (0.344)
Summary:
41
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
APPENDIX
42
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
43
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
TABLE 1.b
TABLE 1.c
44
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
TABLE 2.a
45
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
TABLE 2.b
46
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413
TABLE 2.c
47