Republic of the Philippines

BATANGAS STATE UNIVERSITY


Gov. Pablo Borbon Campus II, Alangilan Batangas City, Philippines 4200
College of Engineering, Architecture & Fine Arts
www.batstate-u.edu.ph Tel. No. (043) 425-0139 loc. 118
Civil & Sanitary Engineering Department

REINFORCED CONRETE DESIGN OF


A TWO-STOREY RESIDENTIAL BUILDING

Submitted by:
ALVAREZ, Ladylyn P.
MACATANGAY, Lorielyn C.

Submitted to:
Engr. Victor A. Semira

CE 413 – Reinforced Concrete Design


CE – 4101
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

DESIGN
OF
SLAB

DESIGN OF CRITICAL ONE WAY SLAB

1
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

A 1.10 m
Ratio m= = = 0.44 < 0.5, therefore ONE - WAY SLAB
B 2.50 m

GIVEN:

Short side, A: 1.10 m


Long Side, B: 2.50 m
f’c= 28 MPa
fy= 420 MPa
Φ: 0.9, From Table 421.2.1, NSCP 2015
β: 0.85 ; f’c<30 MPa
Concrete Unit weight: 23.5 kN/m3
Cover: 30 mm
Use 12 mm rebars

Dead loads:

Self-weight= 23.5 kN/m3(0.11 m) ---------------------------- 2.585 kPa


Floor Fill ( lightweight concrete per mm) ---------------- 0.015 kPa
Floor Finish (ceramic or quarry tile 20 mm on 25 mm
mortar bed) ----------------------------------------------------- 1.10 kPa
Ceiling Load (plaster on tile or concrete) ------------- 0.24 kPa
Miscellaneous Load ----------------------------------------- 1 kPa
Mechanical duct allowance ------------------- 0.20 kPa
Electrical Load --------------------------------------------- 0.023kPa

DL= 5.163 kPa

Live load for basic floor areas ------------1.9 kPa

(from Table 405.1, NSCP 2015)

Factored Load:
WUDL = 1.2DL = 1.2(5.163) = 6.20 kPa

2
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

WULL = 1.6LL = 1.6(1.9) = 3.04 kPa


WU = WUDL + WULL = 6.20 kPa + 3.04 kPa = 9.24 kPa

Effective Depth:

From Table 407.3.1.1, NSCP 2015:

l 2.50(1000)
h min= = =89.29 mm;
28 28
say, 90 mm

Eff. depth = h – cover – radius of bar


D =90 – 30 - 6 = 54 mm

AT END 1

Wu l 2
Mu= , from Table 406.5.2, NSCP 2015
11
Mu=(9.24)¿ ¿ 5.25 kN-m Where:

Mu 5.25 x 106
Rn= = =¿ 2.0 MPa b= width of slab used every 1m strip
∅ b d 2 0.9∗1000∗54 2
d=¿ effective depth
'
0.85 f c 2 Rn
ρ=
fy ( √
1− 1−
0.85 f ' c )
0.85(28) 2(2)
=
420 ( √
1− 1−
0.85(28)
=¿ 0.00498 )
1.4 1.4 √ f ' c = √ 28 =¿0.0031497;
ρmin = = = 0.00333 or ρmin =
fy 420 4 fy 4 (420)

therefore, use 0.00333

0.02064

When ρmin < ρ < ρmax

3
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

Therefore, use ρ = 0.00498 for As

As = ρbd

As = 0.00498 x 1000 x 54 = 268.96 mm2

Using 12 mm bars:

A ¯¿
Spacing= ¿
As
π∗122
∗1000
4 420.50 mm; say S = 400mm
Spacing= =¿
268.96

Smax = 3h, from 407.7.2.3, NSCP 2015 where: h=90 mm, see page 3

Smax = 3*90 = 270 mm

Smax < S required

Therefore, S = 270mm

Use 12mmØ reinforcing bars


@270mm spacing

AT MID-SPAN:

4
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

Wu l 2
Mu= , from Table 406.5.3, NSCP 2015
16

Mu=(9.24)¿ ¿

Mu 3.61 x 106
Rn= = =¿ 1.38 MPa
∅ b d 2 0.9∗1000∗54 2

0.85 f ' c 2 Rn
ρ=
fy ( √
1− 1−
0.85 f ' c )
0.85(28) 2(1.38)
=
420 ( √
1− 1−
0.85(28)
=¿ 0.00339)
1.4 1.4 √ f ' c = √ 28 =¿0.0031497
ρmin = = = 0.00333 or ρmin ¿
fy 420 4 fy 4(420)

Therefore, use 0.00333

0.02064

When ρmin < ρ < ρmax


Therefore, use ρ = 0.00339 for As

As = ρbd

As = 0.00339 x 1000 x 54 = 183.06 mm2

Using 12 mm bars:

A ¯¿
Spacing= ¿
As

π∗122
∗1000
4 617.82 mm; say S = 600mm
Spacing= =¿
183.06

Smax = 3h, from 407.7.2.3, NSCP 2015 where: h=90mm, see page 3

Smax = 3*90 = 270 mm

5
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

Smax > S required

Therefore, S = 270 mm

Use 12mmØ reinforcing bars


@270mm spacing

AT END 2:

Wu l 2
Mu= , from Table 406.5.3, NSCP 2015
10

Mu=(9.24)¿ ¿

Mu 5.775 x 106
Rn= = =¿ 2.20 MPa
∅ b d 2 0.9∗1000∗54 2

0.85 f ' c 2 Rn
ρ=
fy ( √
1− 1−
0.85 f ' c )
0.85(28) 2(2.20)
=
420 ( √
1− 1−
0.85(28)
=¿ 0.00551)
1.4 1.4 √ f ' c = √ 28 =¿0.0031497
ρmin = = = 0.00333 or ρmin ¿
fy 420 4 fy 4(420)

Therefore, use 0.00333

0.02064

When ρmin < ρ < ρmax


Therefore, use ρ = 0.00551 for As

As = ρbd
As = 0.00551 x 1000 x 54 = 297.54 mm2
Using 12 mm bars:

6
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

A ¯¿
Spacing= ¿
As

π∗122
∗1000
4 380.108 mm; say S = 350mm
Spacing= =¿
297.54

Smax = 3h, from 407.7.2.3, NSCP 2015 where: h=90 mm, see page 3

Smax = 3*90 = 270 mm


Smax > S required

Therefore, S = 270mm

Use 12mmØ reinforcing bars


@270 mm spacing

For Temperature Bars:

0.0018∗420
As= bh, from Table 407.6.1.1, NSCP 2015
Fy

Where: ρ= ratio of tension reinforcement


b= width of slab used for every 1m strip; 1m=1000m
d= effective depth; d= 54 mm

As=0.0018*1000*54= 97.2 mm2

Using 12 mm dia. bars.

A ¯¿
Spacing= ¿*1000
As

π∗122
∗1000
4
Spacing= =1163.55 mm
97.2

7
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

Say, S = 1100mm
Smax = 5h, from 407.7.6.2.1, NSCP 2015

Smax = 5*90 = 450 mm

S > SMAX

Therefore, S = 450 mm

Use 12mmØ reinforcing bars


@450mm spacing

8
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

1.10 m
12.mm
270 mm
0.75m

1m
2.50 m
12.mm
450 mm

0.75m

12.mm 12mm
450 mm 270 mm

1.10 m

9
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

DESIGN OF CRITICAL TWO-WAY SLAB

GIVEN:

Short side, A: 3.00 m


Long Side, B: 4.00 m
f’c= 28 MPa
fy= 420 MPa
Φ: 0.9, From Table 421.2.1, NSCP 2015
β: 0.85 ; f’c<30 MPa
Concrete Unit weight: 23.5 kN/m3
Cover: 30 mm

Use 12 mm rebars

A 3.00
Ratio m= = = 0.75 > 0.5, therefore TWO - WAY SLAB.
B 4.00

Minimum thickness,

ln
Minimum thickness, h= , from Table 408.3.1.1, NSCP 2015
33

4000 mm
= = 121.21 mm
33

Therefore, minimum thickness = 125 mm

EFFECTIVE DEPTH, dA and dB

dA = effective depth for Short Span;


where: short span is A=3 m
dA = h – (cover) – (half of rebar ɸ)
= 125 mm – 30mm – 6mm
dA = 89 mm

10
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

dB = effective depth for Long Span;


where: long span is B=4 m
dB = h – cover – rebar – half of rebar

dB = 115 – 30–12– 6

dB = 77 mm

From Table 205-1, NSCP 2015

Live Load =1.9 kPa (basic floor area)

From Table 204-2, NSCP 2015

Dead load:
Floor finish (ceramic or quarry tile on 25mm mortar bed) = 1.1 kPa
Floor fill (lightweight concrete per mm) = 0.15kPa
Ceiling finish (plaster on tile or concrete) = 0.24 kPa
Mechanical Duct Allowance = 0.20 kPa
Miscellaneous Load = 1 kPa
Electrical Load = 0.023kPa

Dead loads:

Self-weight= 23.5 kN/m3(0.125 m) --------------------------- 2.94 kPa


Floor Fill (Lightweight concrete per mm) ------------------- 0.15 kPa
Floor Finish (ceramic or quarry tile 20 mm on 25 mm
mortar bed) -------------------------------------------------------- 1.10 kPa
Ceiling Load (plaster on tile or concrete)---------------------- 0.24 kPa
Miscellaneous Load ------------------------------------- 1 kPa
Mechanical duct allowance ------------------------ 0.20 kPa
Electrical Load 0.023kPa
--------------------------

DL= 5.651 kPa

11
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

Factored Load:

W U = 1.2DL = 1.2(5.651) = 6.781 kPa


DL

W U = 1.6LL = 1.6(1.9) = 3.04 kPa


¿

WU = W U + W U = 6.781 kPa + 3.04 kPa = 9.8212 kPa


DL ¿

Solving Moments using Coefficient Method based on 1963 ACI Code

Using CASE 9 (3 edges continuous, 1 edge discontinuous) Moment Coefficients (by


interpolation):

CA=0.078
CB=0.014
C A =0.031
DL

C B =0.007
DL

C A =0.046
¿

C B =0.013
¿

SOLVING FOR MOMENTS:

A. Short Span, Middle Strip

At continuous edge:
A 3
Ratio= = = = 0.75
B 4
MOMENT COEFFICIENT, C A : SEE TABLE 1.a,page 43

MA=(Wu) (CA) (A2)= 9.8212 (0.078)(4.0)2

MA = 12.26 kN.m

At mid-span:
MOMENT COEFFICIENT, C A : SEE TABLE 1.b,page 43
DL

M A = (W U ) (C A ) (A2) = 9.8212 (0.031)(4.0)2


DL DL DL

12
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

M A = 4.87 kN.m
DL

MOMENT COEFFICIENT, C A : SEE TABLE 1.c,page 44 ¿

M A = (W U ) (C A ) (A2) = 9.8212 (0.046)(4.0)2


¿ ¿ ¿

M A = 7.23 kN.m
¿

MA= M A + M A = 4.87 + 7.23 = 12.1 kN.m


DL ¿

B. Long Span, Middle Strip


MOMENT COEFFICIENT, CB : SEE TABLE 2.a,page 44

MB= (Wu) (CB) (B2) = 9.8212 (0.014)(4.0)2


MB= 2.20 kN.m

At mid-span:

MOMENT COEFFICIENT, C B : SEE TABLE 2.b,page 45 DL

M B = (W U ) (C B ) (B2) =9.8212 (0.007)(4.0)2


DL DL DL

M B = 1.10 kN.m
DL

MOMENT COEFFICIENT, C B : SEE TABLE 2.c,page 45 ¿

M B =(W U ) (C B ) (B2) =9.8212 (0.013)(4.0)2


¿ ¿ ¿

M B = 2.04 kN.m
¿

13
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

MB= M B + M B = 1.10 + 2.04 = 3.14 kN.m


DL ¿

SOLVING :

A. Short Span, Middle Strip

At continuous edge:
where:
MA 12.26 x 106
Rn= 2
= = 1.72 MPa MA = 12.26 KN.m, see page 12
∅ bd 0.9∗1000∗892
b= width of slab used every 1m strip
d=effective depth,89 mm, see page 10
0.85 f ' c 2 Rn
ρact =
fy
[1− 1−

0.85 f ' c
]

0.85∗28 2∗1.72
ρact =
420
1− 1− ( √
0.85∗28 )
ρact =0.00425

1.4 1.4
ρmin = = = 0.00333
fy 420

f 'c 28
ρmin = √ = √ =¿ 0.0031497
4 fy 4∗420

Therefore, use 0.00333

3 0.85 βf ' c 3 20.23


ρmax = = =¿ 0.02064
7 fy 7 420

When ρmin < ρact ¿ ρmax

Therefore use ρact = 0.00425 for As

14
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

Where:
A s=ρbd ρ=¿ratio of tension reinforcement
A s=0.00425∗1000 mm∗89 d=¿effective depth, 89mm,see page 10
A s=378.25 mm2 b= width of slab used every 1m strip

Using 12 mm bars:

A ¯¿
Spacing= ¿
As
π∗122
∗1000
4 say 300 mm
Spacing= =299 mm
378.25

Smax= 2h Where: h=125mm, see page 10


Smax=2*125=250 mm

Smax < S required

Use 12mmØ reinforcing bars


@250mm spacing

At Mid-span:
Where:
MA 12.1 x 106
Rn= = = 1.70 MPa MA= 12.1 KN.m, see page 13
∅ b d 2 0.9∗1000∗892
b= width of slab used every 1m strip
d= effective depth, 89mm, see page
10
0.85 f ' c 2 Rn
ρact =
fy √
[1− 1−
0.85 f ' c
]

0.85∗28 2∗1.70
ρact =
420 ( √
1− 1−
0.85∗28 )
15
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

ρact =0.0042

1.4 1.4
ρmin = = = 0.00333
fy 420

f 'c 28
ρmin = √ = √ =¿ 0.00314
4 fy 4∗420

Therefore, use 0.00333

3 0.85 βf ' c 3 20.2


ρmax = = =¿ 0.02064
7 fy 7 420

ρmin > ρact ¿ ρmax

Therefore, use ρact = 0.0042 for As

Where:
A s=ρbd ρ=¿ratio of tension reinforcement
A s=0.0042∗1000∗89=373.8 mm2 b= width of slab used every 1m strip
d=¿effective depth,89mm, see page
10
Using 12 mm bars:

A ¯¿
Spacing= ¿
As
π∗122
∗1000
4 say 300 mm
Spacing= =302.56 mm
373.8

Smax=2h Where: h=125mm, see page 10


Smax=2*125 = 250 mm

Smax < S required

16
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

Use 12mmØ reinforcing bars


@250mm spacing

B. Long Span, Middle Strip

At continuous edge: Where:


MB= 2.20 KN.m, see page 13
MB 2.20 x 106
Rn= 2
= = 0.41 MPa b= width of slab used every 1m strip
∅ bd 0.9∗1000∗77 2
d= effective depth, 77mm, see page
11
0.85 f ' c 2 Rn
ρact =
fy √
[1− 1−
0.85 f ' c
]

0.85∗28 2∗0.41
ρact =
420 ( √
1− 1−
0.85∗28 )
ρact =0.00098

1.4 1.4
ρmin = = = 0.00333
fy 420

f 'c 28
ρmin = √ = √ =¿ 0.0031497
4 fy 4∗420

Therefore, use 0.00333

3 0.85 βf ' c 3 20.2


ρmax = = =¿ 0.02064
7 fy 7 420

ρact < ρmin ¿ ρmax

Therefore, use ρmin = 0.00333 for As

Where:

17
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

A s=ρbd ρ=¿ratio of tension reinforcement


A s=0.00333∗1000∗77=256.41 mm2 b= width of slab used every 1m strip
d=¿ effective depth,77mm,see page
11

Using 12 mm bars:

A ¯¿
Spacing= ¿
As
π∗122
∗1000
4 say 400mm
Spacing= =441.08 mm
256.41

Smax=2h
Smax=2*125= 250 mm

Smax < S required

Use 12mmØ reinforcing bars


@250mm spacing

At Mid-span:

Where:
MB 3.14 x 106
Rn= 2
= = 0.58 MPa MB= 3.14 KN.m, see page 13
∅ bd 0.9∗1000∗77 2
b= width of slab used every 1m strip
d= effective depth, 77mm, see page 11
0.85 f ' c 2 Rn
ρact =
fy √
[1− 1−
0.85 f ' c
]

0.85∗28 2∗0.58
ρact =
420 ( √
1− 1−
0.85∗28 )
ρact =0.00140

18
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

1.4 1.4
ρmin = = = 0.00333
fy 420

f 'c 28
ρmin = √ = √ =¿ 0.0031497
4 fy 4∗420
Therefore, use 0.00333

3 0.85 βf ' c 3 20.2


ρmax = = =¿ 0.02064
7 fy 7 420

When ρact < ρmin ¿ ρmax

Therefore, use ρmin = 0.00333 for As

Where:
A s=ρbd ρ=¿ratio of tension reinforcement
A s=0.00333∗1000∗77=256.41 mm2 b= width of slab used every 1m strip
d=¿ effective depth,77mm,see page
11

Using 12 mm bars:

A ¯¿
Spacing= ¿
As
π∗122
∗1000
4 say 400mm
Spacing= =441.08 mm
256.41

Smax=2h
Smax=2*125=250 mm

Smax < S required

Use 12mmØ reinforcing bars


@250mm spacing

19
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

3.0m
0.75m 1.5m 0.75m

1m
250 mm

4.0m2m
250 mm

1m

250m

3.0 m

20
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

DESIGN OF
BEAM
(B-1)

21
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

A-E ALONG GRIDLINE 3


From Table 204-2, NSCP 2015

Dead Load:
Floor Finish (ceramic or quarry tile on 25mm mortar bed) = 1.1kPa
Ceiling Finish (plaster on tile or concrete) = 0.24kPa
Mechanical Duct Allowance = 0.20kPa
Electrical Load = 0.023kPa
Miscellaneous = 1kPa

FOR DEAD LOAD: (DL)


kN
Slab weight (two way)=23. 5 ( 0.125 m )=2.94 kPa
m3
Floor finish=1.1 kPa
Ceiling Load=0.24 kPa
Mechanical Duct Allowance=0. 20 kPa
Electrical Load=0. 023 kPa
Miscellaneous=1 kPa
w DL =5.503 kPa

Assume beam size (0.3 m x 0.25m)


W Wall = Area x Unit weight of concrete

22
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

kN kN
(
W Wall =( 0.20 m ) ( 3.2m ) 23.5
m )
3
=15.04
m

W beam =Area of beam x Unit weight of concrete

kN kN
(
W beam =( 0.3 m )( 0.25 m ) 23.5
m 3)=1.763
m

FOR DEAD LOADS (DL)

wDL ( S ) w DL ( S )
Wu DL ( AB)=1.2 ( 3
+
3 )
+ wbeam +w wall

5.503 ( 2.5 ) 5.503 ( 2.5 ) kN


¿ 1.2 ( + +1.763+15.04 ) =31.17
3 3 m

w ( S ) w ( S)
=1.2 ( +w +w )
DL DL
Wu DL ( BC ) + beam wall
3 3

5.503 ( 2.5 ) 5.503 ( 2.5 ) kN


¿ 1.2 ( + +1.763+15.04 ) =31.17
3 3 m

w ( S) w ( S )
=1.2 ( +w +w )
DL DL
Wu DL ( CD ) + beam wall
3 3

5.503 ( 2 ) 5.503 ( 2 ) kN
¿ 1.2 ( + +1.763+15.04 )=28.97
3 3 m

w ( S) w ( S )
Wu =1.2 (
DL ( DE )
DL
+ DL
+w +w ) beam wall
3 3

5.503 ( 3 ) 5.503 ( 3 ) kN
¿ 1.2 ( + +1.763+15.04 ) =33.37
3 3 m

FOR LIVE LOAD (LL)

W ¿ =2.9 kPa (Exterior Balconies)(from Table 205-1, NSCP 2015)


W ¿ =1.9 kPa (Basic floor area)(from Table 205-1, NSCP 2015)

W ¿ ( S) W ¿ (S ) 1,9 ( 2.5 ) 1.9 ( 2.5 ) kN


Wu ¿(AB )=1.6(
3
+
3
)=1.6
3 ( +
3 ) =5.07
m

23
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

W ¿ (S ) W ¿ ( S) 1.9 ( 2.5 ) 1.9 ( 2.5 ) kN


Wu ¿(BC)=1.6(
3
+
3 (
)=1.6
3
+
3 )=5.07
m

W ( S) W ( S ) 1.9 ( 2 ) 2.9 ( 2 )
Wu ¿(CD) =1.6 (
3
¿
+
3 )
¿
=1.6 ( 3 + 3 )=5.12 kNm
W (S ) W (S ) 1.9 ( 3 ) 2.9 ( 3 ) kN
Wu ¿(DE) =1.6( ¿
+ ¿
)=1.6 ( + ) =7.68
3 3 3 3 m

TOTAL UNIFORM LOAD


WuTOTAL = WuDL + WuLL
kN
Wu AB = Wu BA = 31.17 + 5.07 = 36.24
m
kN
Wu BC = Wu CB= 31.17 + 5.07 = 36.24
m
kN
Wu CD = Wu DC = 28.97 + 5.12 = 34.09
m
kN
Wu DE = Wu ED = 33.37 + 7.68 = 41.05
m

FOR FIXED END MOMENTS:

(L¿¿ 2) ( 36.24 ) ( 2.5 )2


FEM AB =Wu AB = =18.88 kNm ¿
12 12

(L¿¿ 2) −( 36.24 )( 2.5 )2


FEM BA=−Wu BA = =−18.88 kNm ¿
12 12

( L¿¿ 2) ( 36.24 )( 2.5 )2


FEM BC =Wu AB = =18.88 kNm ¿
12 12

(L¿¿ 2) −( 36.24 )( 2.5 )2


FEM CB =−Wu CB = =−18.88 kNm ¿
12 12

( L¿¿ 2) ( 34.09 ) ( 2 )2
FEM C D=Wu CD = =11.36 kNm ¿
12 12

(L¿¿ 2) −( 34.09 ) ( 2 )2
FEM DC =−Wu DC = =−11.36 kNm ¿
12 12
( L¿¿ 2) ( 41.05 )( 3 )2
FEM DE=Wu DE = =30.79 kNm ¿
12 12

24
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

(L¿¿ 2) − ( 41.05 ) ( 3 )2
FEM ED=−Wu ED = =−30.79 kNm ¿
12 12

SOLUTION:

COMPUTATION OF STIFFNESS FACTOR (K)

where: Length of Column = 3.2m

Length of BeamA-B, B-C = 2.5m

Length of BeamC-D = 2.0m

Length of BeamD-E = 3.0m

LCM: 3.2 x 2.5 x 2.0 x 3.0 = 48

Solving for Beam Stiffness (k):


LCM 48
KAB= KBA = KBC = KCB = = =19.2
L 2.5
LCM 48
KCD = KDC = = =24
L 2
LCM 48
KDE = KED = = =16
L 3

Solving for Column Stiffness (k):


LCM 48
KAA”= KBB” = KCC” = KDD” = KEE”= =¿ = 15
L 3.2
LCM 48
KAA’= KBB’ = KCC’ = KDD’ = KEE’= =¿ = 15
L 3.2

KA’A = KB’B = KC’C = KD’D= KE’E =0


KA”A = KB”B = KC”C = KD”D =K E”E =0

25
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

Solving for Distribution Factor (DF):


K
@ Joint A DF=
K total @ Joint A
K 15
DFAA’=DFAA”= = =0.305
K total @ Joint A 19.2+15+15
K 19.2
DFAB= = =¿ 0.390
K total @ Joint A 19.2+15+15

K
@ Joint B DF=
K total @ Joint B
K 19.2
DFBA=DFBC= = =0.281
K total @ Joint B 19.2+ 15+15+19.2
K 15
DFBB’= DFBB’’= = =0.219
K total @ Joint B 19.2+ 15+15+19.2

K
@ Joint C DF=
K total @ Joint C
K 19.2
DFCB = = =0.262
K total @ Joint C 24+19.2+15+15
K 15
DFCC’= DFCC”= = =0.204
K total @ Joint C 24+19.2+15+15
K 24
DFCD = = =0.328
K total @ Joint C 24+19.2+15+15

K
@ Joint D DF=
K total @ Joint C

26
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

MDM FOR GRIDLINES A-E ALONG GRIDLINE 3 DFDC =

K 24
= =0.343
K total @ Joint D 24+ 16+15+15
K 15
DFDD’= DFDD”= = =0.214
K total @ Joint D 24+ 16+15+15
K 16
DFDE = = =0.229
K total @ Joint D 24+ 16+15+15

K
@ Joint E DF=
K total @ Joint E
K 16
DFED = = =0.348
K total @ Joint E 16+15+ 15
K 15
DFEE’= DFEE”= = =0.326
K total @ Joint E 16+15+ 15

CONTINUATION…

27
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

LOAD DIAGRAM

SHEAR DIAGRAM

MOMENT DIAGRAM

28
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

MOST STRESSED MEMBER ALONG GRIDLINE 3

Ultimate Moments
(from MDM see page 27)

Maximum moment from moment diagram = 30.452 kN m


GIVEN:
f’c = 28 MPa
fy = 420 MPa
Φ: 0.9, from Table 421.2.1, NSCP 2015
β: 0.85 ; f’c<30 MPa
Concrete Unit weight: 23.5 kN/m3
Concrete cover = 40 mm
Tie bar diameter = 10 mm
Rebar diameter = 20 mm
Es = 200000 MPa

Mu = 30.452 kN.m

Nominal Moment Capacity,

Mu =Φ Mn

Mu 30.452
Mn = = = 33.84 kN.m
Φ 0.9

EFFECTIVE DEPTH, de
1
d e=h+cov er+2( d bar )
2
1
d e=300 mm+40 mm+2( (20 mm ))
2
d e=360 mm

29
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

ASSUMING SINGLE REINFORCEMENT

0.85 f ' cβ 600


ρmax =0.75 [ ( )]
fy 600+ fy

0.75∗0.85∗28∗0.85 600
ρmax = ( )¿
420 600+420

ρmax =0 .02125

Wherein,

Compressive force = Tensile Force

0.85 f ' c a b d= Asfy d

Asfy d
a= '
0.85 f c bd

As
ρmax =
bd

ρmax fy d
a=
0.85 f ' c

0.02125(420)(360)
a= =135 mm
0.85(28)
a
Mn=0.85 f ' c a b x (d− )
2

0.135
Mn=0.85 ( 28 x 103 ) ( 0.135 ) (0.250)(0.36− )
2

Mn=234.95 kNm

234.95 kN.m > 33.84 kN.m

Therefore, the beam is singly reinforced!

Mu= ϕRnbd2
30.452 = 0.9Rn(250)(300)2
Rn= 1.504 MPa

30
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

ρ=
0.85 f ' c
fy [ √
1− 1−
2 Rn
0.85 f ' c ]
=
0.85(28)
420 [ √
1− 1−
2(1.504 )
0.85 (28) ]
ρ = 0.003702

1.4 √ fc ' = 1.4 ∨ √ 28


ρ min = or
fy 4 fy 420 4 (420)
ρ min = 0.00333 or 0.0031497
Therefore, use 0.00333

0.85 f ' cβ 600


ρmax =0.75 [ ( )]
fy 600+ fy
0.75∗0.85∗28∗0.85 600
ρmax = ( )¿
420 600+420

ρmax =0 .02125

When ρ min < ρ < ρmax


Therefore, use ρ = 0.003702

As = ρ bd1
= (0.003702)(250)(300)
= 277.64 mm2

For tension reinforcement:


Using 20 mm diameter bars

As 277.64
No. of bars = =
Ad π ¿ ¿ ¿

Use 2-20mm reinforcing bars

STIRRUPS or WEB REINFORCEMENTS


31
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

Bar diameter = 10 mm

For bar Spacing, S: whichever is smaller of the following:

A v fs
S1=
Vsb
Vd
V s =V n −V cV n=
b de

64.35 kN
V n= =715 2
( 0.250 ) ( 0.360 ) m

V c =0.09 √ f ' c
kN
V c =0.09 √ 28 x 103 =15.06
m2

kN
V s =715−15.06=699.94
m2

A v =2¿

(0.000157)(420 x 10 6)
S1 = =0.142m∨use 150 mm
( 1.08986 x 106 ) (0.250)

de 0.36
S2 = = =0.180 m
2 2

Therefore, S= 150 mm

Length to be provided with web reinforcement/ stirrups of spacing (whichever length


is longest)
Given that allowable bond stress = 2420 kPa

32
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

LV s 4(0.69994 MPa)
l 1= = =1.96 m
2Vn 2(0.715 MPa)

l 2=de +a+ de

Wherein,

L V
a=[ −d e ] s
2 Vn

4 0.70
a= [ 2
−0.360]0.72
=1.59 m

l 2=0.36+ 1.59+ 0.36=2.31m

Therefore L=2.0 m or 2000 mm


L 2310
¿ of spaces= = =16 spaces
S 15 0
L 231 0
¿ of stirrups= +1= +1=17 pcs
S 15 0

33
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

DESIGN OF
COLUMN
(C-1)

34
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

DESIGN OF SQUARE TIED COLUMN

COMPUTATION OF Pu

Pu2nd floor = 102.53 kN see load diagram, page 21

Pumax= Pu2ndFloor + 1.2WCOLUMN


Pumax= 102.53 + 1.2(0.4m x 0.4m x 23.5kN/m3 x 6.4m)
Pumax= 131.41 kN

Φ = 0.80 (2015 NSCP: Φ=0.80 for tied and 0.85 for spiral)

Initial ρ =0.02
fy= 420 MPa
f’c= 28 MPa
50 mm concrete cover
Assumed Section=(400 mm) (400 mm)
Assumed Ag = 160,000 mm2

Using 20 mm Φ rebar

10 mm Φ bar stirrups

b=400 mm, h= 400 mm

d = 400 – concrete cover – stirrup Φ – 1/2 Φ rebar

d = 400 – 50 – 10 - ½ (20) =330 mm

35
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

MAXIMUM AXIAL LOAD


Pumax = 131.41 kN

Pu=0.80 ϕ [0.85 f ' c ( Ag− As ) + fy ( As )]

Pu
Ag= '
ϕ ( 0.80 ) [0.85 ( f c ) ( 1−ρ ) + ( 420 ) ρ]

131.41 ×103
Ag=
0.80 ( 0.80 ) [0.85 ( 28 ) (1−0.02 ) + ( 420 ) (0.02)]

Ag = 6472.33 mm2

b=√ Ag=80.45 mm
Therefore, use 400 mm x 400 mm column

SELECTING LONGITUDINAL (MAIN) BARS:

For As: As= ρAg

Where : ρ=0.02 , Ag=( 400 ) ( 400 )=160 000 mm 2

As=( 0.02 )(160 000 mm 2)

As=3200 mm 2

Number of Main Bars


Using 25mm bars

As=3200 mm 2
As
Number of main bars=
π d2
4
3200
Number of main bars=
π (20)2
4
Number of main ¯¿ 10.1859

Say, 10 bars

Therefore, use 10- 20 mm longitudinal dia. bars


36
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

MAXIMUM SPACING TIES

a. 16 db = 16(20) = 320mm

b. 48 dt = 48(10) = 480mm

c. Least dimension of column = 400mm

Therefore, use S = 400mm

SUMMARY:
Column size: 400 mm x 400 mm
Main bars: 10 – 20 mm diameter rebars
Ties: 10 mm diameter bars
Spacing: 400 mm

37
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

DESIGN OF
COLUMN-
FOOTING
(C1-F1)
38
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

DESIGN OF COLUMN- FOOTING

Column Load: Pumax= 131.41 kN


Soil Bearing pressure = 200 kPA

Reinforcement = 16mm dia. Deformed bar


Concrete covering = 40mm
Column size = 400 mm x 400 mm
Allowable Punching Shear, Vp = 1500 kPa
Allowable Bond Stress, µ = 2420 kPa
f’c = 28 MPa
fy = 420 MPa
a = column dimension = 300 mm

DESIGN COMPUTATION

load
Required Footing Area, A =
s oil pressure

131.41kN
=
200

= 0.66 m2

Try: 1.2 m x 1.2 m x 300 mm thick concrete footing with 16 mm Φ reinforcements

Provided area= 1.2 m x 1.2 m = 1.44 m2

1.44 m2 > 0.71 m2

Provided area > Required area OK SAFE!

1
Moment Capacity, Mc= Net Upward Pressure NUP (B) ( ) (B – a) 2
2

Where; a = column dimension = 300mm

B = footing dimension = 1200mm

39
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

load 131.41
NUP= = = 91.26 kPa
provided area 1.44

200 kPA > 91.26 kPa

NUP < Soil Bearing Pressure OK SAFE!

Mc= (91.26 kPa) (1.2 m) (1/2) (1.2 m - 0.300 m) 2 = 44.35 kN.m

Reinforcements, As:

Mc
As = ; where j = 0.89
fsjde

Effective depth, de:

de = d – concrete cover - bar diameter

= 400 mm - 40mm – 16 mm

= 344 mm

Mc 44.35
As = = = 344.902 mm2
fsjde ( 420 x 1 0 ) ( 0.89 ) (0.344)
3

As 344.902
No .of bars= =
π d2 π¿¿¿
4

Say, 2 bars

Therefore use, 2 pcs – 16 mm diameter deformed bars bothways

40
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

Checking for Punching Shear, Vp:

vp
V p=
4 d e (a+d e )

v p =¿ NUP {(B1B2 – [a1 +de][a2+de]}

v p =¿ 91.26 {(1.44) – [0.4 + 0.344][0.4+ 0.344]} = 80.90 kN

80.90
V p= = 79.02 kPa
4(0.344 )( 0.4+0.344 )

1500 kPa >79.02 kPa


Allowable Punching Shear > Punching Shear OK SAFE!

Checking for Bond Stress, u:

V
μ=
ε 0 jde

V= NUP (B) (de)

V= 91.26 (1.2)(0.344) = 37.67 kN

Where, ε 0 = total perimeter of the reinforcing bars = 6(π)(0.016) = 0.302 m

37.67
μ= = 407.42 kPa
( 0.3 02 ) ( 0.89 ) (0.344)

2420 kPa>407.42 kPa

Allowable Bond Stress > Bond Stress OK SAFE!

Summary:

Footing Dimension 1.2 m x 1.2 m x 0.400 m


Reinforcement 2 – 16 mm Φ deformed bars bothways

41
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

APPENDIX

42
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

Based on 1963 ACI Code


TABLE 1.a

43
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

TABLE 1.b

TABLE 1.c

44
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

TABLE 2.a

45
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

TABLE 2.b

46
RCD of Proposed Two-Storey Reinforced Concrete Residential Building CE 413

TABLE 2.c