9315 200-500kVA

Installation and Initial Startup


Parallel Cabinets
3.40 INSTALLATION VERIFICATION
Customer Name:       Date:      
Site Contact:       Phone #:      
UPS Model      
# of Modules:      kVA per Module:      
Total System      
Serial Number(s):      

CTO(s)      

3.41 MECHANICAL INSPECTION

THE BATTERY CABINETS WILL HAVE LETHAL VOLTAGES PRESENT AT


ALL TIMES. IF THE BATTERY CABINETS HAVE BEEN CONNECTED, THE
BATTERY INPUT OF EACH UPS MAY HAVE OPEN CIRCUIT BATTERY
VOLTAGE AT TERMINALS E4 AND E5 (F21 & F22).

MANY SYSTEMS WILL HAVE MULTIPLE AC AND DC POWER SOURCES.


NEVER ASSUME THAT POWER SOURCES TO ANY OF THE UPS
MODULES IS OFF. ALWAYS VERIFY ALL VOLTAGES WITH A
VOLTMETER. ENSURE POWER SOURCES ARE LOCKED OUT AND
TAGGED OUT WHEN WORKING AROUND INPUT TERMINALS OF A UPS
MODULE AND INPUT TERMINALS OF OPTIONAL EQUIPMENT TO THE
UPS.

Start-Up Information
1. Verify that each module in the system has suffered no shipping damage. OK
2. Verify power wiring to and from the UPS system has been properly OK
installed.

Page 1 of 3
3. Verify that the system is properly grounded. OK
4. Verify that the battery system installation. OK
5. Verify that all field service bulletins have been installed. OK

3.42 ELECTRICAL VERIFICATION

IF THE LOAD BUS IS NOT TO BE HOT AT THIS TIME, THE CUSTOMERS


DOWN STREAM LOAD BREAKER MUST BE OPENED.

TO BEGIN TESTING, ENSURE THAT RECTIFIER INPUT BREAKERS (CB1)


ARE OPEN, POWER OFF RESETS ARE PUSHED IN, MODE SWITCH (S3)
IS ON BYPASS, BATTERY SWITCH (S4) IS DISABLED, AND MOB
BREAKERS (MOB1 AND MOB2) ARE OPEN.

Ensure the area around the UPS system is not cluttered. Verify that each
UPS and auxiliary cabinet air inlets and exhaust passages are not
blocked. Verify the debris covers are removed from the top of each
cabinet.

System and Module Control Status Battery Breaker


UPS #1 CB1: Open Mode Switch: Bypass Battery Switch: Disabled Open MOB1: Open
UPS #2 CB1: Open Mode Switch: Bypass Battery Switch: Disabled Open MOB2: Open
1. Apply AC input power to each module. OK
2. Check all monitors, lamps and indicators for proper operation. OK

3.43 UPS MODULE VERIFICATION

Energize the load connections on the output of each UPS module.


1. Verify alarms, notices and status in the Alarm Queue. OK
System and Module Control Status Battery Breaker

Page 2 of 3
UPS #1 CB1: Closed Mode Switch: Normal UPS #1 CB1: Closed Mode Switch: Normal
UPS #2 CB1: Closed Mode Switch: Normal UPS #2 CB1: Closed Mode Switch: Normal

3.44 Optional Equipment


NOTE:
If problems are encountered with optional equipment, refer to appropriate
Troubleshooting Section of the manual.

Location Measured with DVM UPS Metering Screen


UPS Module #1 UPS Module #2 UPS Module #1 UPS Module #2
Rectifier Input AB       VAC AB       VAC AB       VAC AB       VAC
Voltage BC       VAC BC       VAC BC       VAC BC       VAC
CA       VAC CA       VAC CA       VAC CA       VAC

Rectifier Input AB       AAC AB       AAC       AAC       AAC
Current BC       AAC BC       AAC       AAC       AAC
CA       AAC CA       AAC       AAC       AAC

Inverter Output AB       VAC AB       VAC       VAC       VAC
Voltage BC       VAC BC       VAC       VAC       VAC
CA       VAC CA       VAC       VAC       VAC

Inverter Output AB       AAC AB       AAC       AAC       AAC
Current BC       AAC BC       AAC       AAC       AAC
CA       AAC CA       AAC       AAC       AAC

Input Power       kVA       kVA       kVA       kVA
      kW       kW       kW       kW
      Pf       Pf       Pf       Pf

DC Link Voltage       VDC       VDC       VDC       VDC

DC Link Voltage       ADC       ADC       ADC       ADC

Installation Completed By:

Date:      
Authorized customer acceptance signature:

Date:      
Comments:
     

Page 3 of 3