DIRANA PTM

User Manual
DIRANA PTM User Manual

Manual Version: ENU 1135 05 03


© OMICRON electronics GmbH 2017. All rights reserved.
This manual is a publication of OMICRON electronics GmbH.
All rights including translation reserved. Reproduction of any kind, for example, photocopying,
microfilming, optical character recognition and/or storage in electronic data processing systems,
requires the explicit consent of OMICRON. Reprinting, wholly or in part, is not permitted.
The product information, specifications, and technical data embodied in this manual represent the
technical status at the time of writing and are subject to change without prior notice.
We have done our best to ensure that the information given in this manual is useful, accurate and entirely
reliable. However, OMICRON does not assume responsibility for any inaccuracies which may be
present.
The user is responsible for every application that makes use of an OMICRON product.
OMICRON translates this manual from the source language English into a number of other languages.
Any translation of this manual is done for local requirements, and in the event of a dispute between the
English and a non-English version, the English version of this manual shall govern.

2 OMICRON
Contents

Contents
About this manual 6
Safety symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1 Safety instructions 7
1.1 Operator qualifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2 Safety standards and rules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2.1 Safety standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2.2 Safety rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.3 Safe operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.3.1 Test equipment integrity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.3.2 DIRANA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.3.3 Measurement setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.4 Orderly measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.5 Disclaimer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.6 Compliance statement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.7 Recycling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2 System requirements 11
3 Introduction 12
3.1 Frequency domain spectroscopy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.2 Advanced time domain spectroscopy (PDC+) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.3 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.4 Connections and operating controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.4.1 Front panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.4.2 Rear panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.5 Delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.6 Primary Test Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.7 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4 Installation 18
4.1 Connect DIRANA to the computer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.2 Power up DIRANA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.3 Install Primary Test Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.4 Start Primary Test Manager and connect to DIRANA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5 Home view 20
5.1 Title bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.1.1 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.1.2 Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.1.3 About . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.2 Status bar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.3 Data backup and restoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.4 Data synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5.4.1 Server settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
5.4.2 Managing subscriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.4.3 Database synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6 Create new job 37
6.1 Guided test workflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
6.2 Job overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
6.2.1 Job data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
6.2.2 Approving jobs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
6.2.3 Managing attachments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
6.3 Location view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

OMICRON 3
DIRANA PTM User Manual

6.3.1 Location data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42


6.3.2 Setting the geo coordinates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6.3.3 Managing attachments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6.4 Asset view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
6.4.1 General asset data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
6.4.2 Managing attachments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
6.4.3 Transformer view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
6.4.4 Current transformer view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.4.5 Voltage transformer view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
6.4.6 Rotating machine view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.5 Test view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
6.5.1 Selecting tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.5.2 Importing tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.5.3 Performing tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6.5.4 Processing templates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
7 Execute prepared job 60
8 Manage objects 61
8.1 Search for objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
8.2 Perform operations on objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
8.3 Understanding the master locations and assets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
8.4 Duplicate assets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
8.5 Relocate assets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
8.6 Import and export jobs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
9 Open manual tests 68
10 Generate test reports 69
11 Asset data 71
11.1 Transformer data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
11.1.1 Bushing data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
11.1.2 Tap changer data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
11.1.3 Surge arrester data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
11.2 Spare bushing data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
11.3 Current transformer data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
11.3.1 Common parameters and settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
11.3.2 IEC 60044 protection CTs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
11.3.3 IEC 61869 protection CTs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
11.3.4 IEC 61869 metering CTs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
11.3.5 IEEE C57.13 protection CTs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
11.3.6 IEEE C57.13 metering CTs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
11.4 Voltage transformer data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
11.5 Rotating machine data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
12 Application 84
12.1 DIRANA test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
12.1.1 Test set and software startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
12.1.2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
12.1.3 Settings and conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
12.1.4 Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
12.1.5 Moisture analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
12.1.6 Comparison . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
12.1.7 Disconnection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
12.2 Oil analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
12.3 Insulation Resistance test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
13 Technical data 106

4 OMICRON
Contents

14 TMDRA 100 109


14.1 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
14.2 Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
14.3 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
14.3.1 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
14.3.2 Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
14.3.3 Disconnection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
14.4 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Support 114

OMICRON 5
DIRANA PTM User Manual

About this manual


This User Manual provides information on how to use the DIRANA test system safely, properly and
efficiently. The DIRANA PTM User Manual contains important safety instructions for working with
DIRANA and gets you familiar with operating DIRANA. Following the instructions in this User Manual will
help you to prevent danger, repair costs, and avoid possible down time due to incorrect operation.
The DIRANA PTM User Manual always has to be available on the site where DIRANA is used. The users
of DIRANA must read this manual before operating DIRANA and observe the safety, installation, and
operation instructions therein.
Reading the DIRANA PTM User Manual alone does not release you from the duty to comply with all
national and international safety regulations relevant to working on high-voltage equipment.

Safety symbols used


In this manual, the following symbols indicate safety instructions for avoiding hazards.

DANGER
Death or severe injury will occur if the appropriate safety instructions are not observed.

WARNING
Death or severe injury can occur if the appropriate safety instructions are not observed.

CAUTION
Minor or moderate injury may occur if the appropriate safety instructions are not
observed.

NOTICE
Equipment damage or loss of data possible

6 OMICRON
Safety instructions

1 Safety instructions
1.1 Operator qualifications
Working on high-voltage assets can be extremely dangerous. Consequently, only personnel qualified,
skilled and authorized in electrical engineering and trained by OMICRON are allowed to operate
DIRANA and its accessories. Before starting to work, clearly establish the responsibilities.
Personnel receiving training, instructions, directions, or education on DIRANA must be under constant
supervision of an experienced operator while working with the equipment. The operator is responsible
for the safety requirements during the whole test.
Maintenance and repair of DIRANA and its accessories is only permitted by qualified experts at
OMICRON service centers except for hardware update options delivered with the relevant
Supplementary Sheet.

1.2 Safety standards and rules


1.2.1 Safety standards
Testing with DIRANA must comply with the internal safety instructions and additional safety-relevant
documents.
In addition, observe the following safety standards, if applicable:
• EN 50191 (VDE 0104) "Erection and Operation of Electrical Test Equipment"
• EN 50110-1 (VDE 0105 Part 100) "Operation of Electrical Installations"
• IEEE 510 "IEEE Recommended Practices for Safety in High-Voltage and High-Power Testing"
Moreover, observe all applicable regulations for accident prevention in the country and at the site of
operation.
Before operating DIRANA and its accessories, read the safety instructions in this User Manual carefully.
Do not turn on DIRANA and do not operate DIRANA without understanding the safety information in this
manual. If you do not understand some safety instructions, contact OMICRON before proceeding.
Maintenance and repair of DIRANA and its accessories is only permitted by qualified experts at
OMICRON service centers (see "Support" on page 114).

1.2.2 Safety rules


Always observe the five safety rules:
► Disconnect completely.
► Secure against re-connection.
► Verify that the installation is dead.
► Carry out grounding and short-circuiting.
► Provide protection against adjacent live parts.

OMICRON 7
DIRANA PTM User Manual

1.3 Safe operation


When operating the DIRANA test system and its accessories, observe the following safety instructions.

1.3.1 Test equipment integrity


► Do not open the housing of DIRANA.
► Do not repair, modify, extend, or adapt DIRANA and its accessories.
► Use only the DIRANA original accessories and cables and only use the OMICRON accessories
together with OMICRON devices as described in this manual.
► Operate DIRANA and its accessories only under ambient conditions specified in "Technical data" in
the DIRANA User Manual.

1.3.2 DIRANA
► Use only adequately rated power cords.
► Supply DIRANA only from a power outlet with protective earth (PE).
► Position the measurement setup so that you can easily disconnect DIRANA from mains.
► Do not use extension cables on a cable reel to prevent overheating of the cord. Instead, run out the
extension cord.
► Before handling DIRANA in any way, connect its equipotential ground terminal with a solid connection
of at least 6 mm2 cross-section to the ground terminal of the high-voltage asset under test.
► Do not operate DIRANA and its accessories in the presence of explosives, dangerous gases or
vapors.
► If DIRANA or its accessories do not seem to function properly, stop using them and contact your
regional OMICRON service center.

1.3.3 Measurement setup


► Ensure that the ground terminal of the test object is in good condition, clean, and free of oxidation.
► Do not touch any terminals and do not connect any cables to the test object without a visible
connection to ground.
► Only use test leads and tools which provide full protection against direct contact.
► Always insert connectors completely and use the interlock mechanism.
► Always turn off DIRANA with the power switch before connecting or disconnecting any cable.
► Never remove any cables from DIRANA or the test object during a test.
► Do not insert objects (for example, screwdrivers) into any input/output socket.

8 OMICRON
Safety instructions

1.4 Orderly measures


The DIRANA PTM User Manual or alternatively the e-book has always to be available on the site where
DIRANA is operated.
The users of DIRANA must read this manual before operating DIRANA and observe the safety,
installation, and operation instructions therein.
DIRANA and its accessories may be used only as described in this User Manual. Any other use is not in
accordance with the regulations. The manufacturer and the distributor are not liable for damage resulting
from improper usage. The user alone assumes all responsibility and risk.
Following the instructions provided in this User Manual is also considered part of being in accordance
with the regulations.
Opening DIRANA or its accessories invalidates all warranty claims.

1.5 Disclaimer
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the
equipment may be impaired.

1.6 Compliance statement


Declaration of conformity (EU)
The equipment adheres to the guidelines of the council of the European Community for meeting the
requirements of the member states regarding the electromagnetic compatibility (EMC) directive, the low
voltage directive (LVD) and the RoHS directive.

FCC compliance (USA)


This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in
accordance with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
Changes or modifications not expressly approved by the party responsible for compliance could void the
user's authority to operate the equipment.
Declaration of compliance (Canada)
This Class A digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.

OMICRON 9
DIRANA PTM User Manual

1.7 Recycling
This test set (including all accessories) is not intended for household use. At
the end of its service life, do not dispose of the test set with household waste!
For customers in EU countries (incl. European Economic Area)
OMICRON test sets are subject to the EU Waste Electrical and Electronic
Equipment Directive 2012/19/EU (WEEE directive). As part of our legal obligations
under this legislation, OMICRON offers to take back the test set and ensure that it is
disposed of by authorized recycling agents.
For customers outside the European Economic Area
Please contact the authorities in charge for the relevant environmental regulations in
your country and dispose the OMICRON test set only in accordance with your local
legal requirements.

10 OMICRON
System requirements

2 System requirements
Table 2-1: Primary Test Manager system requirements

Characteristic Requirement (*recommended)


Operating system Windows 10 64-bit*
Windows 8.1 64-bit*,
Windows 8 64-bit*,
Windows 7 SP1 64-bit* and 32-bit
CPU Multicore system with 2 GHz or faster*,
single-core system with 2 GHz or faster
RAM min. 2 GB (4 GB*)
Hard disk min. 4 GB of available space
Storage device DVD-ROM drive
Graphics adapter Super VGA (1280×768) or higher-resolution video adapter and monitor1
Interface Ethernet NIC2,
USB 2.03
Installed software Microsoft Office 2016*, Office 2013, Office 2010, Office 2007
required for the optional
Microsoft Office
interface functions
1. We recommend graphics adapter supporting Microsoft DirectX 9.0 or later.
2. For testing with TESTRANO 600, CPC 100 and CIBANO 500. NIC = Network Interface Card.TESTRANO 600, CPC 100 and
CIBANO 500 can be connected with RJ-45 connectors either directly to the computer or to the local network, for example, by
using an Ethernet hub.
3. For testing with FRANEO 800

OMICRON 11
DIRANA PTM User Manual

3 Introduction
Water in oil-paper insulated assets such as power transformers or instrument transformers is
accelerating the aging of the paper insulation and thus reducing the life expectance of the asset.
Knowing the water content therefore allows to assess the aging status of assets. By measuring the
dielectric response of the equipment in a wide frequency range, DIRANA determines the moisture
content. To save time, DIRANA combines frequency domain spectroscopy (FDS) and advanced time
domain spectroscopy (PDC+).
DIRANA can also be used as an universal dielectric analyzer für all kind of asset insulations, for
example, for bushings and rotating machines.

3.1 Frequency domain spectroscopy


By using the frequency domain spectroscopy (FDS), the dissipation factor of the insulation system under
test is measured by frequency sweep. The FDS allows fast measurements at high frequencies but
requires long measurement times at lower frequencies.

3.2 Advanced time domain spectroscopy (PDC+)


The advanced time domain spectroscopy (PDC+) uses the principles of the PDC measurement which
applies a DC voltage to the insulation and measures the response current. The result (current over time)
is mathematically transferred to the frequency domain so that the result can be presented, for example,
as power factor/dissipation factor over frequency. PDC+ is applicable for frequencies lower than 0.1 Hz
and is significantly faster than frequency domain measurements.

12 OMICRON
Introduction

3.3 Designated use


DIRANA is a dielectric response analyzer for the insulation diagnosis. The underlying concept –
combined FDS and PDC+ methods – makes DIRANA an intelligent, fast, and powerful solution for the
insulation diagnosis of high-voltage assets in the power industry such as power transformers, rotating
machines, and cables.
DIRANA combines the FDS and PDC+ measurements to get the advantages of both methods. At high
frequencies, the dielectric response is measured with the FDS while at low frequencies, the results
obtained by measuring the polarization current are transformed into the frequency domain and the
dielectric response is calculated. This unique concept facilitates the dielectric response measurements
within a wide frequency range. By comparing the dielectric response with model curves, DIRANA
provides an indication of the insulation condition such as:
• Moisture content in the oil/paper insulation
• Condition of OIP, RBP, and RIP high-voltage bushings
• Condition of the generator, motor, and cable insulation
DIRANA is controlled by Primary Test Manager running on a computer connected to DIRANA by USB
interface. Primary Test Manager combines seamlessly the FDS and PDC+ methods and merges the
results, allowing you to work only in the frequency domain. DIRANA provides two measurement
channels for faster measurements. Primary Test Manager provides an automatic procedure for the
moisture content analysis of the power transformer insulation based on fitting the measurement results
with a collection of model curves which are adapted to fit the measured asset.

OMICRON 13
DIRANA PTM User Manual

3.4 Connections and operating controls


This section describes the connections and operating controls of DIRANA.

3.4.1 Front panel

WARNING
Death or severe injury caused by high voltage or current possible
► Do not touch the OUTPUT connector or any parts of the test setup when the red LED
lights continuously or flashes.
► Always ensure that the device is safely switched off and the sample is discharged
before touching any parts of the test setup.
► Before connecting DIRANA to the test object, observe the five safety rules (see
1.2.2 "Safety rules" on page 7) and all additional relevant laws and internal safety
standards.

OUTPUT connector I/0 switch CH 1 connector CH 2 connector

GUARD connector
Red LED Green LED Yellow LED Yellow LED

Figure 3-1: Front view of DIRANA

Table 3-1: Front-panel operating controls

Operating control State Description


OUTPUT connector n/a Signal source output
I/0 switch n/a Starts and to stops measurements in the
disconnected mode.
CH 1 connector n/a Channel 1 input
CH 2 connector n/a Channel 2 input
GUARD connector n/a Connector for connecting an additional guard
cable
LED is flashing Signals that a measurement is running.
Red LED On for approx. 10 s Signals that you the test object is depolarized
after a measurement has been stopped.

14 OMICRON
Introduction

Table 3-1: Front-panel operating controls (continued)

Operating control State Description


Green LED On Indicates that the power switch is on.
The LED next to the Signals that measurement results are available in
active channel is DIRANA for one-channel measurements.
flashing
LEDs are flashing Signal that measurement results are available in
concurrently DIRANA for two-channel measurements.
Yellow LEDs
LEDs are flashing Signal an error during a measurement.
alternately In the disconnected mode, after a computer has
been connected to DIRANA, the error information
is sent to the computer and the LEDs switch over
to continuous lighting.

3.4.2 Rear panel


DC power input 5 V DC output

Power switch Equipotential ground terminal USB connector

Figure 3-2: Rear view of DIRANA

OMICRON 15
DIRANA PTM User Manual

3.5 Delivery
The DIRANA delivery includes:

DIRANA Power supply Power cable Grounding cable


(GR/YE) 6 m/20 ft,
6 mm2 with clamp

Braid wire USB 2.0 A/B cable 50 Ω triaxial cable 50 Ω triaxial cable
2 m/6.6 ft 18 m/60 ft (red) 18 m/60 ft (blue)

50 Ω triaxial cable 3 × triaxial cable 3 × laboratory cable Terminal adapters with


18 m/60 ft (yellow) adapter with banana 6 m/20 ft, 2.5 mm2 with banana socket
plugs banana plugs

Screw clamp 3 × measuring clamp 3 × connection clamp Crocodile clamps with


with triaxial and guard with banana plugs banana socket
connections

16 OMICRON
Introduction

TMDRA 100 Soft bag Transport case DIRANA Getting Started

Primary Test Manager


DVD

3.6 Primary Test Manager


Primary Test Manager is a control software for testing high-voltage assets with OMICRON test systems.
Primary Test Manager provides a computer interface to the test set and assists you with the hardware
configuration and performing tests.
With Primary Test Manager, you can create new jobs, execute prepared jobs, manage objects, create
new manual tests, open existing manual tests, and perform tests. After you have performed a test, you
can generate test reports. Primary Test Manager runs on a computer and communicates with DIRANA
through USB interface.
For detailed information about Primary Test Manager, see the relevant chapters in the DIRANA PTM
User Manual.

3.7 Cleaning

WARNING
Death or severe injury caused by high voltage or current possible
► Do not clean the DIRANA test set when connected to the test object.
► Before cleaning DIRANA and its accessories, always disconnect the test object,
accessories and connection cables.

To clean DIRANA and its accessories, use a cloth dampened with isopropanol alcohol.

OMICRON 17
DIRANA PTM User Manual

4 Installation
This section describes how to put the DIRANA test system into operation. The DIRANA operation is
controlled by the Primary Test Manager software. Consequently, before operating DIRANA, you must
install Primary Test Manager and connect DIRANA to a computer.

4.1 Connect DIRANA to the computer


DIRANA communicates with the computer through USB interface. To connect DIRANA to the computer:
1. Connect the USB 2.0 A/B cable to the USB connector on the DIRANA rear panel (see
Figure 3-2: "Rear view of DIRANA" on page 15).

NOTICE
Equipment damage possible
► Do not crush the cables when closing the transport case.
► Always place the cables deliberately before closing the transport case.
2. Connect the USB cable on the front of the transport case to the USB connector of your computer by
using the USB 2.0 A/B cable.

4.2 Power up DIRANA

WARNING
Death or severe injury caused by high voltage or current possible
► Do not power up DIRANA without grounding connection.
► Before powering DIRANA up, connect its equipotential ground terminal with a solid
connection of at least 6 mm2 cross-section to the ground terminal of the asset under
test.

To power DIRANA by using the delivered AC power supply:


1. Plug the DC output connector of the AC power supply into the DC power input on the DIRANA rear
panel (see Figure 3-2: "Rear view of DIRANA" on page 15).
2. Connect the power cable to the AC power supply.

DANGER
Death or severe injury caused by high voltage or current
► Do not use power outlets without protective ground (PE).
► Only use the delivered AC power supply to power DIRANA.
► Connect the DIRANA power supply only to a power outlet that is equipped with
protective ground (PE).
► For safe operation always make sure that protective ground and equipotential ground
are connected properly.

18 OMICRON
Installation

3. Plug the mains plug of the power cable into the power outlet.
4. Toggle the power switch on the DIRANA rear panel.

4.3 Install Primary Test Manager


For the minimum requirements your computer needs to run Primary Test Manager, see 2 "System
requirements" on page 13.
► To install Primary Test Manager, put the delivered Primary Test Manager DVD in the DVD drive of
your computer and follow the instructions on the screen.

4.4 Start Primary Test Manager and connect to DIRANA


► To start Primary Test Manager, click Start on the task bar, and then click
OMICRON Primary Test Manager, or double-click the OMICRON Primary Test Manager icon
on the desktop.
► To connect to DIRANA, select the device from the list, and then click Connect.

Figure 4-1: Connecting to DIRANA

If you could not connect to your DIRANA device, do one of the following:
► Ensure that DIRANA is switched on and connected to the computer.
► Click More beneath the Connect button, and then click Refresh.
► Press F5.
Note: The Update device software, Open device web interface and Add device manually options
are not available for DIRANA.
Alternatively, you can manage the connection to DIRANA in the Primary Test Manager status bar (see
"Status bar" in the DIRANA PTM User Manual).
During the connection process, Primary Test Manager checks the DIRANA firmware version and
updates it, if necessary.

NOTICE
Equipment damage or loss of data possible
► Do not disconnect DIRANA from the computer during the firmware update process.
► Always wait until the firmware update has finished before disconnecting DIRANA.

OMICRON 19
DIRANA PTM User Manual

5 Home view
After starting Primary Test Manager, the home view opens. In the home view, you can select different
user tasks designed to support you during diagnostic testing and management of test objects and test
data.

Figure 5-1: Primary Test Manager home view

Primary Test Manager processes data of different workflow importance. This is indicated by balloons of
different categories as described in the following table.

Table 5-1: Data importance categories

Balloon Category Description


Mandatory Indicates data required for performing tests.

Recommended Indicates data supporting the Primary Test Manager workflow.

Information Contains descriptive information.

20 OMICRON
Home view

Primary Test Manager supports the following user tasks.

Table 5-2: Selecting the user tasks

Button Description Action


Create new job Click the Create new job button to start the guided test
workflow (see 6 "Create new job" on page 37).

Execute prepared job Click the Execute prepared job button to execute a
prepared job (see 7 "Execute prepared job" on page 60).

Manage Click the Manage button to manage locations, assets, jobs,


and reports (see 8 "Manage objects" on page 61).

Create new manual Click the Create new manual tests button to create a new
tests manual test (not available for DIRANA).

Open manual tests Click the Open manual tests button to open a manual test
(see 9 "Open manual tests" on page 68)

OMICRON 21
DIRANA PTM User Manual

5.1 Title bar


Note: The title bar is displayed in any Primary Test Manager view.
The following table describes the title bar commands.

Table 5-3: Title bar commands

Command Action
Home Click Home to move from any view to the home view.
Synchronize1 Click Synchronize to synchronize your local database with the Primary
Test Manager server database
(see 5.4 "Data synchronization" on page 34).
Settings Click Settings to open the Settings dialog box
(see 5.1.1 "Settings" later in this chapter).
Help Click Help to open the DIRANA technical documentation and send data to
OMICRON Technical Support
(see 5.1.2 "Help" on page 30).
About Click About to open the About Primary Test Manager dialog box
(see 5.1.3 "About" on page 31).
1. Only enabled with the appropriate license.

5.1.1 Settings
In the Settings dialog box, you can make a number of Primary Test Manager settings to match your
regional conventions, manage the job templates, and set the Primary Test Manager server settings for
data synchronization (see 5.4 "Data synchronization" on page 34). To open the Settings dialog box,
click Settings in the title bar.

NOTICE
Equipment damage or loss of data possible
Changing the settings in the Settings dialog box affects all data in Primary Test Manager.
► Only change settings if you are qualified to do so.
► Review your changes before clicking OK.

Note: After changing a setting, you must restart Primary Test Manager for the setting to take effect.

Profiles
On the Profiles tab, you can set your profile, the default rated frequency, the loss index, the units of your
own profiles, and make the test system settings.

22 OMICRON
Home view

Note: The dissipation factor and the tangent delta are identical characteristics of the primary asset under
test. For your convenience, with Primary Test Manager you can use your preferred naming.

Figure 5-2: Profiles tab: Global settings

With Primary Test Manager, you can use predefined profiles and create your own profiles for naming
conventions.
Note: Primary Test Manager sets the default profile according to the regional settings of your computer.
► To set a profile, select the profile you want to use from the Profiles list.
To create your own profile:
1. Click Create custom profile.
2. In the Create custom profile dialog box, type the profile name, and then click Create.
3. Under Global settings, set the default rated frequency, the loss index, and your preferred units.

OMICRON 23
DIRANA PTM User Manual

4. Under Transformer, Current transformer, or Voltage transformer, make your preferred settings
for the asset under test.

Figure 5-3: Profiles tab: Transformer

24 OMICRON
Home view

Figure 5-4: Profiles tab: Current transformer

OMICRON 25
DIRANA PTM User Manual

Figure 5-5: Profiles tab: Voltage transformer

5. If applicable, select the terminal names scheme you want to use from the Terminal names scheme
list or create your own terminal names scheme (see "Create your own terminal names scheme" on
page 26.)
6. Click OK to close the Settings dialog box.
► To delete your own profile, select the profile from the Profiles list, and then click
Delete current profile.

Create your own terminal names scheme


With Primary Test Manager, you can use predefined terminal names schemes according to the
established standards and create your own terminal names schemes.
To create your own terminal names scheme:
1. Click Create custom scheme.
2. In the Enter scheme name dialog box, type the scheme name.
3. Set the terminal names, scheme options, and preferences depending on the asset.
► To delete your own terminal name scheme, select the scheme from the Terminal names scheme
list, and then click Delete current scheme.

26 OMICRON
Home view

Figure 5-6: Profiles tab: DIRANA moisture analysis

Under DIRANA moisture analysis, you can set the moisture and oil conductivity categories. You can
rename the default category names and the thresholds according to your needs. To restore the default
names and thresholds, click Restore default names and Restore default values respectively.

OMICRON 27
DIRANA PTM User Manual

Templates
On the Templates tab, you can edit, import and export job templates. For information on how to process
the templates, see 6.5.4 "Processing templates" on page 58.

Figure 5-7: Templates tab

To manage the job templates, select Transformer from the Display templates for list, and then do one
of the following:
► To import a template, click the Import button , and then browse to the template you want to import.
► To edit the template properties, select the template, and then click the Edit button .
► To delete a template, select the template, and then click the Delete button .
► To export a template, select the template, and then click the Export button .
The right pane of the template workspace displays the template preview.

28 OMICRON
Home view

General
On the General tab, you can make general settings of Primary Test Manager.

Figure 5-8: General tab

► To set the Primary Test Manager language, select your preferred language from the Language list.
► To set the logging level, select your preferred level from the Logging PTM and Logging Device lists.
The logging function provides information to help find the cause for an error in cooperation with an
OMICRON support engineer. Logging PTM collects information on PTM while Logging Device
focuses on your device.
Note: Log files do not contain any information about users or devices.

Table 5-4: Logging levels

Logging level Description


Disabled Logging is disabled.
Errors only Only errors are logged.
Recommended setting
Info Errors and some additional information are logged.
Full All software-related activities are logged.
Note: Full logging will slow down software performance.

OMICRON 29
DIRANA PTM User Manual

► To set the types of available devices, select the respective check boxes.
Note: Select the Automatic connection if only one device detected check box if only one device is
available. Then Primary Test Manager connects to the available device automatically.
Under Default test device configuration, Primary Test Manager displays the default devices for
testing different assets. If several devices are available for an asset, you can set your preferred test
system as default device for that asset.
Under Customer Experience Improvement Program, Primary Test Manager displays information
about the Customer Experience Improvement Program. The program collects information about how you
use Primary Test Manager without interrupting you. This helps OMICRON identify which features to
improve. No information collected is used to identify or contact you. We encourage you to join the
program to help improve Primary Test Manager.
Under Server settings, you can set server settings for DataSync. For more information, see
5.4.1 "Server settings" on page 34.

5.1.2 Help
In the Help dialog box, you can get the relevant information about DIRANA and data synchronization,
and send data to OMICRON Technical Support. To open the Help dialog box, click Help in the title bar.

Figure 5-9: Help dialog box

30 OMICRON
Home view

5.1.3 About
In the About Primary Test Manager dialog box, you can enter a license key to upgrade your Primary
Test Manager and enhance its functionality by installing additional features. To open the
About Primary Test Manager dialog box, click About in the title bar.

Figure 5-10: About Primary Test Manager dialog box

To activate a license, enter the license key in the About Primary Test Manager dialog box, and then
click Add license key. For detailed information about the Primary Test Manager licensing, contact your
OMICRON local sales representative or distributor.

5.2 Status bar


Note: The status bar is displayed in any Primary Test Manager view.
The status bar displays information about the status of the test system and provides access to the zoom
function. The following table describes the statuses of the test system.

Table 5-5: Test system statuses

Symbol Status
DIRANA is connected and idle.
DIRANA is connected and a measurement is running.
DIRANA is not connected.

In the status bar, you can connect to and disconnect from a test system, and show and refresh the test
set information.

OMICRON 31
DIRANA PTM User Manual

To connect to a test system:


1. Right-click the DIRANA symbol in the status bar, and then click Connect.

Figure 5-11: Connect to device dialog box

2. In the Connect to device dialog box, select the test system from the list, and then click Connect.
Note: Select the Automatic connection if only one device detected check box if only one device is
available. Then Primary Test Manager connects to the available device automatically.
After you have connected to the test system, the following dialog box appears.

Figure 5-12: Connected to device dialog box

After you have connected to a test system, right-click the DIRANA symbol in the status bar, and then do
one of the following:
► To disconnect from a test system, click Disconnect.
► To display information about the connected test system, click Show test set information.
► To update the test set information, click Refresh test set information.

32 OMICRON
Home view

Note: You can open the Connect to device and the Connected to device dialog boxes also by double-
clicking the DIRANA symbol.

5.3 Data backup and restoring


We strongly recommend backing up your data in the Primary Test Manager database on a regular basis.
Primary Test Manager reminds you to back up the data periodically by prompting you to save the data
in your preferred location. The Primary Test Manager data is backed up in DBPTM format.
To back up the data without the Primary Test Manager prompt:
1. In the home view, click Back up your data.

Figure 5-13: Primary Test Manager home view

2. Save the data in your preferred location.


To restore the data:
1. In the home view, click Restore data from a backup.
2. Browse to the file you want to restore.

OMICRON 33
DIRANA PTM User Manual

5.4 Data synchronization


Primary Test Manager comes with the client/server architecture. With this feature, you can synchronize
your local database with the Primary Test Manager server database.
Note: To synchronize your data, you need a license. To get the license, contact your regional OMICRON
Service Center or sales partner. You can find our Service Center or sales partner closest to you at
www.omicronenergy.com.
The data synchronization is a partial data replication based on subscriptions. All local data is uploaded
to the server database and only selected data on the server is downloaded to the local database.

5.4.1 Server settings


Before synchronizing the Primary Test Manager databases for the first time, you need to set the server
settings. To set the server settings:
1. In the title bar, click Settings, and then select the General tab in the Settings dialog box.
The next step depends on the data synchronization method (DataSync via web server or DataSync
on premises) you use.

DataSync via web server


► For the DataSync service address and the authentication certificate, contact your regional
OMICRON Service Center.

DataSync on premises
► For the DataSync service address and the authentication certificate, contact your system
administrator.

34 OMICRON
Home view

2. Under Server settings, type the service address and the authentication certificate.

Figure 5-14: Server settings for DataSync

3. To test the connection to the server, click Test connection.


Server settings profiles
You can create server settings profiles in order to use different data bases for testing and switch between
them.
► Use the corresponding buttons next to the Profile drop-down box to create, edit or delete a profile.
► To switch to a different profile, select one from the drop-down list and click Set as active.

OMICRON 35
DIRANA PTM User Manual

5.4.2 Managing subscriptions


You can select data on the server database which you want to synchronize with your local database by
managing subscriptions. To manage subscriptions:
1. In the home view (see Figure 5-1: "Primary Test Manager home view" on page 20), click the Manage
button .

Figure 5-15: Manage view

2. In the manage view, click Manage subscriptions on the top of the workspace.
3. In the Manage Subscriptions dialog box, select the data on the server database you want to
synchronize with your local database, and then click OK.

5.4.3 Database synchronization


► To synchronize the local Primary Test Manager database with the server database, click
Synchronize in the title bar of the Manage view.
Primary Test Manager then displays the synchronization progress.
Note: You can synchronize databases at any time, as long as a connection to the server database is
available.
When the database synchronization is complete, the locations, assets, and jobs (objects) newly added
to the local database are marked with blue dots in the manage view. You can sort the objects by this
column. As soon as you open an object, its blue dot is removed. All blue dots are removed when you
perform another database synchronization.

36 OMICRON
Create new job

6 Create new job


When creating a new job, Primary Test Manager leads you through the guided test workflow. To open
the create new job view, click the Create new job button in the home view.

Figure 6-1: Create new job view

In the create new job view, you can configure and execute jobs. A job contains all relevant information
about the location, the asset under test, and the tests. With Primary Test Manager, you can process jobs
as separate entities. During the guided test workflow, the job status displayed in the left pane of the
create new job view changes. The following table describes the job statuses.

Table 6-1: Job statuses

Status Description
New Location has been defined.
Prepared Asset has been defined.
Partially executed At least one measurement has been executed.
Executed All tests of the job have been executed.
Approved Job has been approved.

OMICRON 37
DIRANA PTM User Manual

6.1 Guided test workflow


The guided test workflow leads you through the following steps:
1. Enter the job data (see 6.2 "Job overview" on page 39).
2. Specify the location (see 6.3 "Location view" on page 41).
3. Specify the asset (see 6.4 "Asset view" on page 45).
4. Specify and perform the tests (see 6.5 "Test view" on page 56).
5. Generate the test reports (see 10 "Generate test reports" on page 69).
To navigate through the test workflow, click the navigation buttons in the left pane of the create new job
view.

Figure 6-2: Navigation buttons

Note: You can anytime interrupt the test workflow and return to any view by clicking the corresponding
navigation button.
By using the commands on the menu bar, you can process jobs. The following table describes the
available operations.

Table 6-2: Operations on the jobs

Command Action
Close Closes a job displayed in the create new job view and leads you back to
home or manage view respectively.
Save job Saves the job displayed in the create new job view.
Copy test1 Adds another test of the same kind and with the same settings to the test
list. Results are not copied.
Take screenshot1 Takes screenshot of the selected area of the Primary Test Manager
workspace. The screenshot appears as attachment in the General area and
can be attached to the test report (see 10 "Generate test reports" on
page 69).
1 Only available if a test is open

For more information about operations on the jobs, see 8 "Manage objects" on page 61.

38 OMICRON
Create new job

6.2 Job overview


In the job overview of the create new job view, you can enter the job data (see Table 6-3: "Job data" on
page 39). In the course of the guided test workflow, Primary Test Manager sets also some basic location,
asset, and test data. To open the job overview, click the Create new job button in the home view.

Figure 6-3: Job overview

6.2.1 Job data


The following table describes the job data.

Table 6-3: Job data

Data Description
Name/WO1 Name of the job or work order
(by default generated by Primary Test Manager)
Creation date Date the job was created
Execution date Date the job was executed
Tested by Person who performed the test

OMICRON 39
DIRANA PTM User Manual

Table 6-3: Job data (continued)

Data Description
Approved by Person who approved the test
Approval date Date the job was approved (see 6.2.2 "Approving jobs" later in this section)
Summary Text field to summarize the job data in own words
Attachments Attachments to the job (see 6.2.3 "Managing attachments" on page 40)
1 Mandatory data

6.2.2 Approving jobs


If the job displayed in the job overview has been approved, you can set the approval date of the job. To
set the job approval date, click Approve.
Note: After approving a job, some settings cannot be edited anymore. The job approval cannot be
undone.

6.2.3 Managing attachments


Under Attachments, you can manage attachments to jobs.
To add an attachment to a job:
1. Click the Add button .
2. In the Select Files dialog box, browse to the file you want to attach to the job.
To open an attachment, do one of the following:
► Select the attachment, and then click the Open button .
► Double click the attachment.
To delete an attachment from a job:
1. Select the attachment you want to delete.
2. Click the Remove button .

40 OMICRON
Create new job

6.3 Location view


In the location view of the create new job view, you can specify locations. To open the location view, click
the Location navigation button .

Figure 6-4: Location view

To specify a location, do one of the following:


► Enter the location data (see Table 6-4: "Location data" later in this section).
Note: If you enter location data different from the master location, a notification bar at the top of the
Primary Test Manager workspace prompts you to import the master location or update the master
location. For more information, see 8.3 "Understanding the master locations and assets" on page 64.

OMICRON 41
DIRANA PTM User Manual

► To load the location data available in Primary Test Manager, click Load existing location, and then
select the location you want to load in the Select location dialog box.

Figure 6-5: Select location dialog box

In the Select location dialog box, you can search for locations (see 8.1 "Search for objects" on
page 62).

6.3.1 Location data


The following table describes the location data.

Table 6-4: Location data

Data Description
Name1 Name of the location where the asset is located
Region Region where the asset is located
Division Division where the asset is located
Area Area where the asset is located
Plant Plant where the asset is located
Address Address of the location where the asset is located
City City where the asset is located
State/Province State or province where the asset is located
Postal code Postal code of the location where the asset is located
Country Country where the asset is located
Geo coordinates Geo coordinates of the location where the asset is located
(see 6.3.2 "Setting the geo coordinates" later in this section)
Location system code Location code used by maintenance planning systems

42 OMICRON
Create new job

Table 6-4: Location data (continued)

Data Description
Contact person
Name Name of the contact person
Phone no. 1 Phone number of the contact person
Phone no. 2 Alternative phone number of the contact person
Fax no. Fax number of the contact person
E-mail E-mail address of the contact person
Comment Comment on the location
Attachments Attachments to the location (see 6.3.3 "Managing attachments" on page 44)
Company
Company Company the asset belongs to
Department Department of the company
Address Address of the company
City City where the company is located
State/Province State or province where the company is located
Postal code Postal code of the company
Country Country where the company is located
Phone no. Phone number of the contact person
Fax no. Fax number of the contact person
E-mail E-mail address of the contact person
1 Mandatory data

In the location view, you can enter additional addresses of, for example, a client, owner or utility. To enter
additional addresses, click Add address under Additional addresses. For the additional address data,
see Table 6-4: "Location data" on page 42.

OMICRON 43
DIRANA PTM User Manual

6.3.2 Setting the geo coordinates


To set the geo coordinates of a location:
1. In the location view, click Edit coordinates.

Figure 6-6: Edit Coordinates dialog box

2. In the Edit Coordinates dialog box, enter the latitude and longitude of the location.

6.3.3 Managing attachments


Under Attachments, you can manage attachments to locations.
To add an attachment to a location:
1. Click the Add button .
2. In the Select Files dialog box, browse to the file you want to attach to the location.
To open an attachment, do one of the following:
► Select the attachment, and then click the Open button .
► Double click the attachment.
To delete an attachment from a location:
1. Select the attachment you want to delete.
2. Click the Remove button .

44 OMICRON
Create new job

6.4 Asset view


In the asset view of the create new job view, you can specify assets. To open the asset view, click the
Asset navigation button .

Figure 6-7: Asset view

The asset view depends on the asset you want to specify with Primary Test Manager. To specify an
asset, do one of the following:
► Enter the asset data.The asset data includes the general asset data common to all assets (see
Table 6-5: "General asset data" on page 46) and the asset-specific data described in 11 "Asset data"
on page 71.
Note: If you enter asset data different from the master asset, a notification bar at the top of the
Primary Test Manager workspace prompts you to import the master asset or update the master
asset. For more information, see 8.3 "Understanding the master locations and assets" on page 64.
► To load the asset data available in Primary Test Manager, click Load existing asset, and then select
the asset you want to load in the Select asset dialog box.

OMICRON 45
DIRANA PTM User Manual

Figure 6-8: Select asset dialog box

In the Select asset dialog box, you can search for assets (see 8.1 "Search for objects" on page 62) and
sort them alphabetically or in the chronological order.

6.4.1 General asset data


The following table describes the general asset data.

Table 6-5: General asset data

Data Description
Asset1 Asset under test
Asset type Type of the asset
Serial no.1 Serial number of the asset
Manufacturer Manufacturer of the asset
Manufacturer type Type of the asset according to the manufacturer
Manufacturing year Year of the asset’s manufacturing
Asset system code Code of the asset used by the maintenance planning systems
Apparatus ID2 Identifier of the asset
Feeder Feeder the asset is connected to
Comment Comment on the asset
Attachments Attachments to the asset (see 6.4.2 "Managing attachments" on page 47)
1 Mandatory data
2 Visible after you have selected an asset

46 OMICRON
Create new job

6.4.2 Managing attachments


Under Attachments, you can manage attachments to assets.
To add an attachment to an asset:
1. Click the Add button .
2. In the Select Files dialog box, browse to the file you want to attach to the asset.
To open an attachment, do one of the following:
► Select the attachment, and then click the Open button .
► Double click the attachment.
To delete an attachment from an asset:
1. Select the attachment you want to delete.
2. Click the Remove button .

6.4.3 Transformer view


In the transformer view, you can specify transformers and assets associated with the transformers such
as bushings, tap changers, and surge arresters.
To specify a transformer:
1. From the Asset list, select Transformer.
2. From the Asset type list, select the type of the transformer.

Figure 6-9: Transformer view

OMICRON 47
DIRANA PTM User Manual

3. In the transformer view, enter the general asset data (see Table 6-5: "General asset data" on
page 46).
4. In the Winding configuration area, set the transformer’s vector group (see "Setting the vector
group" later in this section).
5. In the Ratings area, the Impedances area and the Others area, enter the transformer data (see
11.1 "Transformer data" on page 71).
6. Optionally, specify the bushings mounted on the transformer (see "Bushings tab" on page 49).
7. Optionally, specify the tap changers of the transformer (see "Tap changers tab" on page 50).
8. Optionally, specify the surge arresters mounted on the transformer (see "Surge arresters tab" on
page 52).

Setting the vector group


To set the vector group of a transformer:
1. In the Winding configuration area, select the number of transformer’s phases.
2. Click Select winding configuration and in the Edit Vector Group dialog box, set the transformer’s
vector group.

Figure 6-10: Edit Vector Group dialog box

Note: Primary Test Manager sets the vector group of an autotransformer without tertiary winding
automatically.

48 OMICRON
Create new job

Bushings tab
On the Bushings tab, you can specify bushings mounted on the transformer.

Figure 6-11: Transformer view: Bushings tab

To specify a bushing:
1. From the Asset type list, select the type of the bushing for all transformer’s terminals.
2. Enter the bushing data (see 11.2 "Spare bushing data" on page 74).
Under Copy bushing data, you can copy data of a bushing to other bushings. To copy the bushing data,
select the respective bushings from the From and To lists, and then click Copy.

OMICRON 49
DIRANA PTM User Manual

Tap changers tab


On the Tap changers tab, you can specify the transformer’s tap changers.

Figure 6-12: Transformer view: Tap changers tab

To specify an on-load tap changer (OLTC):


1. Select the OLTC check box.
2. Enter the OLTC data (see 11.1.2 "Tap changer data" on page 73).
3. Under Tap changer configuration, set the tap changer’s winding, the tap scheme, and the number
of taps.

50 OMICRON
Create new job

4. Under Voltage table, do one of the following:


► Type the voltage of all taps.
► Click Calculate to calculate the tap voltage automatically.

Figure 6-13: Calculate dialog box

To calculate the tap voltage automatically:


1. Do one of the following:
► In the Calculate dialog box, select Based on first two entries, and then type the voltage of the
first two taps.
► Select Based on middle position, and then type the voltage of the middle-position tap and the
deviation.
2. Click Calculate.
To specify a de-energized tap changer (DETC):
1. Select the DETC check box.
2. Enter the DETC data (see 11.1.2 "Tap changer data" on page 73).
3. Under Tap changer configuration, set the tap changer’s winding, the tap scheme, the number of
taps, and the current tap position.
4. Type the voltage of all taps.
To add a tap, select the tap below which you want to add a tap, and then click Add.
Note: The added taps match no tap scheme.
To delete a tap, select the tap you want to delete, and then click Delete.
To delete all taps, click Remove all.

OMICRON 51
DIRANA PTM User Manual

Surge arresters tab


On the Surge arresters tab, you can specify surge arresters mounted on the transformer.

Figure 6-14: Transformer view: Surge arresters tab

To specify a surge arrester:


1. Select the respective Surge arrestor check box.
2. Enter the surge arrester data (see 11.1.3 "Surge arrester data" on page 73).
Under Copy surge arrester data, you can copy data of a surge arrester to other surge arresters. To
copy the surge arrester data, select the respective surge arrestors from the From and To lists, and then
click Copy.

DGA Trending
DGA Trending is a licensed feature that visualizes a transformer’s historic Oil analysis data in various
charts and offers a comparison of data recorded at different points in time.
Refer to 12.2 "Oil analysis" on page 99 for more detailed information on the Oil analysis.

52 OMICRON
Create new job

6.4.4 Current transformer view


In the current transformer view, you can specify current transformers.
To specify a current transformer:
1. From the Asset list, select Current transformer.

Figure 6-15: Current transformer view

2. In the current transformer view, enter the general asset data (see Table 6-5: "General asset data"
on page 46).
3. In the Ratings area and the CT configuration area, enter the current transformer data (see
11.3 "Current transformer data" on page 76).

OMICRON 53
DIRANA PTM User Manual

6.4.5 Voltage transformer view


In the voltage transformer view, you can specify voltage transformers.
To specify a voltage transformer:
1. From the Asset list, select Voltage transformer.
2. From the Asset type list, select the type of the voltage transformer.

Figure 6-16: Voltage transformer view

3. In the voltage transformer view, enter the general asset data (see Table 6-5: "General asset data"
on page 46).
4. In the Ratings area and the VT configuration area, enter the voltage transformer data (see
11.4 "Voltage transformer data" on page 82).

54 OMICRON
Create new job

6.4.6 Rotating machine view


In the rotating machine view, you can specify rotating machines.
To specify a rotating machine:
1. From the Asset list, select Rotating machine.
2. From the Asset type list, select the type of the rotating machine.

Figure 6-17: Rotating machine view

3. In the rotating machine view, enter the general asset data (see Table 6-5: "General asset data" on
page 46).
4. In the Configuration area and the Ratings area, enter the rotating machine data (see 11.5 "Rotating
machine data" on page 83).

OMICRON 55
DIRANA PTM User Manual

6.5 Test view


In the test view, you can select, import and perform tests. To open the test view, click the Tests
navigation button .

Figure 6-18: Test view

The test view is divided into the Available tests area, the Selected tests area, and the
General test settings area.
On the top of the Available tests area, click the button labeled with the test system with which you want
to perform the test. Then Primary Test Manager displays the available guided tests and optional manual
tests supported for the selected test system and the asset under test. To display the guided tests
grouped in categories, click the Show test categories button . .
You can select tests for different test systems supported by Primary Test Manager within the same job.
Then the symbol indicates the tests not available for the connected test system to signal to you that
you need to connect another test system before proceeding to execute the job.
The optional manual tests are asset-independent. You can perform manual tests for any asset described
in this User Manual, but Primary Test Manager does not guide you through the tests and provides no
test settings data. The manual tests offer a large amount of flexibility to define the test procedures and
specify test settings according to your specific needs.
The Selected tests area displays the tests you want to perform. By default, Primary Test Manager
displays the tests recommended by OMICRON.

56 OMICRON
Create new job

6.5.1 Selecting tests


► To add a test into the Selected tests area, click the symbol next to the test name or double-click
the test in the Available tests area.
► To add all tests of a category into the Selected tests area, click the symbol.
Note: The tests added to the Selected tests area are displayed under Tests in the left pane of the test
view.
► To rename a test, click the test name, and then type the name you want to use.
The Selected tests area displays the test in the recommended execution order. You can change the
order of the tests by dragging them or by using the and symbols.
► To remove a test from the Selected tests area and from the left pane, click the symbol next to the
test name.
► To open a test, click the test name in the left pane of the test view.
After you have opened a test, the workspace is split into the following areas:
• General
Displays the wiring diagram and test instructions. Optionally, you can type a comment on the test and
add an attachment.
• Settings and conditions
Displays the test settings. For the test settings description, see 12 "Application" on page 84.
• Measurements
Displays the measurement results.
The General test settings area displays the reason for the job, the global test conditions, and some
asset-specific data.

6.5.2 Importing tests


In the test view, you can import test data (measurement results without any information about the job,
the asset or the location) in the following formats.

Table 6-6: Supported file import formats

Format name File name extension Description


DIRANA test file .drax DIRANA 1.x native exchange format
DIRANA CSV file .csv Comma-separated values format
IDAX test file .idax Format for import of test data from the IDAX-300
insulation diagnostic analyzer

To import test data:


1. In the Selected tests area, click Add from file.
2. In the Open dialog box, browse to the file you want the import.
Note: The tests contained in the imported .drax file are appended to the test list.
For information about importing and exporting jobs, see 8.6 "Import and export jobs" on page 67.

OMICRON 57
DIRANA PTM User Manual

6.5.3 Performing tests


To perform the tests, you must know and understand the test settings and the measurement data. For
detailed information, see 12 "Application" on page 84.

6.5.4 Processing templates


In the guided test workflow, you can save jobs as templates and open the saved templates. By using the
templates, you can configure jobs according to your needs (for example, for repeated routines), and then
repeatedly perform the (once defined) tests. When you create a new job, the favorite template for the
corresponding manufacturer and manufacturer type is loaded automatically, if available.
To save a job as template:
1. In the guided test workflow, configure a job.
2. In the Selected tests area of the test view, click Save as template.

Figure 6-19: Save Tests as New Template dialog box

3. In the Save Tests as New Template dialog box:


► Select the asset type from the Asset type list.
► Select the number of transformer’s phases.
► In the Name box, enter the template name.
► Optionally, type a comment on the template.

58 OMICRON
Create new job

To open a template:
1. In the Selected tests area of the test view, click Open template.

Figure 6-20: Choose Template dialog box

2. In the Choose Template dialog box, select the template you want to open.
► To replace the tests in the currently opened job with the selected template, click
Replace existing testplan.
► To add the selected template to the currently opened job, click Append to existing testplan.

OMICRON 59
DIRANA PTM User Manual

7 Execute prepared job


In a typical application scenario, Primary Test Manager tests primary assets in the field. To facilitate the
field tests, you or your colleague can configure a job in the office, save it in Primary Test Manager, and
execute it later in the field.
To execute a prepared job saved in a file:
1. In the home view, click the Execute prepared job button .

Figure 7-1: Execute prepared job view

2. In the execute prepared job view, click Open job from file.
3. In the Open dialog box, browse to the .ptm file you want to import.
4. Import the job, and then go through the guided test workflow (see 6 "Create new job" on page 37).
To execute a prepared job available in Primary Test Manager:
1. In the home view, click the Execute prepared job button .
2. In the execute prepared job view, search for the job you want to execute (see 8.1 "Search for objects"
on page 62).
3. Open the job, and then go through the guided test workflow (see 6 "Create new job" on page 37).

60 OMICRON
Manage objects

8 Manage objects
In the manage view, you can manage locations, assets, jobs, and test reports. To open the manage view,
click the Manage button in the home view.
Note: In this chapter, the locations, assets, jobs, and test reports are collectively called objects.

Figure 8-1: Manage view

Note: The mounted assets are displayed in italics. To hide them, expand the Search area under Asset,
and then select the Hide mounted assets check box.
The manage view displays the objects in a hierarchical structure as follows:
• If you select a location, the manage view displays the assets, jobs, and reports associated with the
selected location.
• If you select an asset, the manage view displays the jobs and reports associated with the selected
asset.
• If you select a job, the manage view displays the reports associated with the selected job.
You can sort the objects alphabetically or in the chronological order.
► Drag and drop the column headers to rearrange the columns.

OMICRON 61
DIRANA PTM User Manual

In the manage view, you can:


• Search for objects (see 8.1 "Search for objects" on page 62)
• Perform operations on objects (see 8.2 "Perform operations on objects" on page 63)
• Relocate assets (see 8.5 "Relocate assets" on page 66)
• Import and export jobs (see 8.6 "Import and export jobs" on page 67)

8.1 Search for objects


In the manage view, you can search for the objects available in Primary Test Manager:
• By searching for keywords in all object data
• By searching for keywords in particular object data
► To search for keywords in all object data, type the keyword you search for in the respective Search
box.
To search for keywords in particular object data:
1. Expand the Search area by clicking the arrow next to Search.
2. Type the keyword(s) you search for in the respective object data box(es).
The following table describes the location search data.

Table 8-1: Location search data

Data Description
Name Name of the location
Address Address of the location
City City where the asset is located
State/Province State or province where the asset is located
Postal code Postal code of the location
Country Country where the asset is located
Company Company the asset belongs to

62 OMICRON
Manage objects

The following table describes the asset search data.

Table 8-2: Asset search data

Data Description
Asset kind Asset under test
Asset type Type of the asset
Serial no. Serial number of the asset
Manufacturer Manufacturer of the asset
Manufacturer type Type of the asset according to the manufacturer
Asset system code Code of the asset used by the maintenance planning systems
Apparatus ID Identifier of the asset
Feeder Feeder the asset is connected to

The following table describes the job search data.

Table 8-3: Job search data

Data Description
Name/WO Name of the job or work order
Tested by Person who performed the test
Executed between Time period between the job was executed
Status Status of the job

The following table describes the report search data.

Table 8-4: Report search data

Data Description
Name Name of the report
Client Customer for which the report is designated
Created between Time period between the report was created

8.2 Perform operations on objects


To perform operations on objects, select an object from the respective list, and then do one of the
following:
► Click the Create new object button to add a new object of the same category.
► Click the Open selected object button to display the data of the selected object.
► Click the Delete selected object button to delete the selected object.

OMICRON 63
DIRANA PTM User Manual

Additionally, you can copy jobs with the associated location, asset and test data. The test results and
reports are not copied. To copy a job:
1. Select the job you want to copy.
2. Click the Copy selected job button .

8.3 Understanding the master locations and assets


Primary Test Manager supports master locations and assets to help you keep your data consistent.
When you create a job, the location and asset associated with the job – called master location and
master asset respectively – are copied to the job.
Consequently, whenever you try to change the location or the asset of an existing job, a notification bar
at the top of the Primary Test Manager workspace prompts you to do one of the following:
► Click Import from master location or Import from master asset to import the location or asset
originally associated with the job (master location/asset) to the current job.
► Click Update master location or Update master asset to update the location or asset originally
associated with the job (master location/asset) with the data of the current job.

64 OMICRON
Manage objects

8.4 Duplicate assets


In the manage view, you can duplicate assets available in Primary Test Manager. To duplicate an asset:
1. From the asset list, select the asset you want to duplicate.
2. Click the Duplicate button .
3. In the asset view, type the serial number(s) of the new asset.

Figure 8-2: Asset view

4. In the asset view, click Save asset.


Note: By default, the duplicated asset are linked to location of the original asset. For relocating the asset
to a different location, see 8.5 "Relocate assets" later in this chapter.

OMICRON 65
DIRANA PTM User Manual

8.5 Relocate assets


In the manage view, you can relocate assets available in Primary Test Manager. To relocate an asset:
1. From the asset list, select the asset you want to relocate.
2. Click the Relocate button .

Figure 8-3: Relocate Asset dialog box

3. In the Relocate Asset dialog box, select the location you want to move the asset to.
4. If the asset you want to relocate is mountable, select an asset where the moved asset is to be
mounted.
Note: You can filter the locations and assets by searching for keywords (see 8.1 "Search for objects" on
page 62).

66 OMICRON
Manage objects

8.6 Import and export jobs


Primary Test Manager supports data exchange between different test systems.
You can export Primary Test Manager jobs in the following formats.

Table 8-5: Supported job export formats

Format name File name extension Description


PTM files .ptm Primary Test Manager native exchange format
DIRANA CSV file .csv Comma-separated values format
DIRANA 1.7 CSV file .csv Comma-separated values format compatible with
the DIRANA software version 1.7

To export a job:
1. From the job list, select the job you want to export.
2. Click the Export button , and then click Export to file.
3. In the Save as dialog box, browse to the folder where you want to save the file.
You can import Primary Test Manager jobs in the following formats.

Table 8-6: Supported job import formats

Format name File name extension Description


PTM files .ptm Primary Test Manager native exchange format
DIRANA test file .drax DIRANA 1.x native exchange format
DIRANA CSV file .csv Comma-separated values format
IDAX test file .idax Format for import of test data from the IDAX-300
insulation diagnostic analyzer

To import a job:
1. In the Job area, click the Import button , and then click Import from file.
2. In the Open dialog box, select the data format of the file you want to import.
3. Browse to the file you want to import.

OMICRON 67
DIRANA PTM User Manual

9 Open manual tests


With Primary Test Manager, you can open existing manual tests. To open a manual test:
1. Click the Open manual tests button in the home view (see Figure 5-1: "Primary Test Manager
home view" on page 20).
2. In the Open dialog box, browse to the file you want to open.

Figure 9-1: Open manual tests view

The open manual tests view displays the tests in the left pane. To view the test results, click the
corresponding test button.

68 OMICRON
Generate test reports

10 Generate test reports


In the report view, you can configure and generate test reports. To open the report view, click the Report
button in the left pane.

Figure 10-1: Report view

The report view is divided into the New report area, the Settings area and the Existing reports area.
In the New report area, you can set the report data. The following table describes the report data.

Table 10-1: Report data

Data Description
Title Title of the report. Appears as the report header.
Report language Language the report is created in
Report ID1 Identifier of the report
Client Customer for which the report is designated
Logo Logo to appear in the report
(see "Setting the logo" later in this chapter)
Summary Text field to summarize the content of the test report in own words
1. By default generated by Primary Test Manager.

OMICRON 69
DIRANA PTM User Manual

Setting the logo


To insert your own logo:
1. In the New report area, click Select image.
2. In the Open Image File dialog box, browse to the file you want to insert.
To set your own logo as default, click Set as default.
In the Settings area, you can configure the test report by selecting the respective check boxes. You can
generate test reports as Microsoft Word and Microsoft Excel documents or in PDF format. To generate
a test report in your preferred format, click Report to Word, Export to Excel or Report as PDF. You
can also add custom reports to jobs. To add a report to a job:
1. In the Settings area, click Add report from file.
2. In the Add dialog box, browse to the report you want to add.
The Existing reports area displays the reports available for the job.

70 OMICRON
Asset data

11 Asset data
This section describes the asset specific data.

11.1 Transformer data


The following tables describe the transformer data.

Table 11-1: Winding configuration

Data Description
Phases Number of the transformer’s phases
Vector group Vector group of the transformer
(see "Setting the vector group" on page 48)
Unsupported vector group Vector group not supported by Primary Test Manager as text for
(for documentation) documentation

Table 11-2: Ratings

Data Description
Rated frequency Rated frequency of the transformer
Voltage ratings
Winding Transformer’s winding
Voltage L-L L-L voltage of the transformer’s winding
Voltage L-N L-N voltage of the transformer’s winding
Insul. level L-L (BIL) L-L basic impulse level rating of the transformer’s winding
Power ratings
Rated power Power rating of the transformer
Cooling class Cooling class of the transformer
Temp. rise wind. Temperature rise of the transformer’s winding
Current ratings at rated power
H/X/Y1 Maximum power frequency current of the transformer at rated power
Short-circuit rating
Max. short-circuit current Maximum short-circuit current of the transformer in kA during a given time
in seconds
1. Set by the regional conventions (see 5.1.1 "Settings" on page 22).

OMICRON 71
DIRANA PTM User Manual

Table 11-3: Impedances

Data Description
Ref. temp. Reference temperature
Short-circuit impedances H - X1, H - Y1, X - Y1
Short-circuit impedance Short-circuit impedance of the transformer
Z (%)1
Base power Base power used for calculating the percent values of impedances
Base voltage Base voltage used for calculating the percent values of impedances
Load losses Pk Load loss at the transformer’s rated load
OLTC position Tap position of the OLTC
DETC position Tap position of the DETC
Zero sequence impedance
Base power Base power used for calculating the percent values of impedances
Base voltage Base voltage used for calculating the percent values of impedances
Winding Transformer’s winding
Zero sequence Zero sequence impedance of the transformer
impedance Z0 (%)
1. Set by the regional conventions (see 5.1.1 "Settings" on page 22).

Table 11-4: Others

Data Description
Category Application category of the transformer
Status Usage status of the transformer
Tank type Type of the transformer’s tank
Insulation medium Insulation medium of the transformer
Weight Weight of the transformer’s insulation
Insulation
Volume Volume of the transformer’s insulation
Total weight Total weight of the transformer
Winding Transformer’s winding
Conductor material Conductor material of the transformer’s winding

11.1.1 Bushing data


For the data of the transformer’s bushings, see 11.2 "Spare bushing data" on page 74.

72 OMICRON
Asset data

11.1.2 Tap changer data


The following table describes the on-load tap changer (OLTC) and the de-energized tap changer (DETC)
data.

Table 11-5: Tap changer data

Data Description
OLTC/DETC Select the OLTC check box to set the OLTC data.
Select the DETC check box to set the DETC data.
Tap changer configuration
Winding Transformer’s winding to which the tap changer is connected
Tap scheme Notation scheme for tap identification
No. of taps Number of the tap changer’s taps
Current tap position1 Current position of the tap
Voltage table
Tap Number of the tap
Voltage Voltage on the tap
1. Only available for the DETC

11.1.3 Surge arrester data


The following table describes the surge arrester data.

Table 11-6: Surge arrester data

Data Description
General
Overall ID Identifier of the surge arrester stack
Ratings
Units in stack Number of the surge arrester’s units
Numerical positions Select the Numerical positions check box to set numerical positions of
the surge arrester.
Literal positions Select the Literal positions check box to set alphabetical positions of the
surge arrester.
Position Position of the surge arrester
Serial no. Serial number of the surge arrester
MCOV rating Maximum continuous operating voltage between the terminals of the
surge arrester
Rated voltage Rated voltage of the surge arrester
Max. system voltage Maximum voltage between phases during normal service
Test voltage Test voltage of the surge arrester
Unit ID Identifier of the surge arrester’s unit

OMICRON 73
DIRANA PTM User Manual

11.2 Spare bushing data


The following table describes the spare bushing data.

Table 11-7: Spare bushing data

Data Description
Pos.1 Terminal of the transformer’s winding to which the spare bushing is
connected
Ratings
Rated frequency Rated frequency of the spare bushing
Insul. level LL (BIL) L-L basic impulse level rating of the spare bushing
Voltage L-ground Rated line-to-ground voltage
Max. system voltage Maximum voltage between phases during normal service
Rated current Rating current of the spare bushing
Manufacturer info
Catalog no. Catalog number of the spare bushing
Drawing no. Drawing number of the spare bushing
Style no. Style number of the spare bushing
Nominal values
PF (C1)/ Power factor, dissipation factor, or tangent delta of the capacitance C1
DF (C1)/ between the top of the spare bushing and the voltage/test tap
Tanδ (C1)2
Cap. (C1) Capacitance C1 between the top of the spare bushing and the voltage/test
tap
PF (C2)/ Power factor, dissipation factor, or tangent delta of the capacitance C2
DF (C2)/ between the voltage/test tap of the spare bushing and ground
Tanδ (C2)2
Cap. (C2) Capacitance C2 between the voltage/test tap of the spare bushing and
ground

74 OMICRON
Asset data

Table 11-7: Spare bushing data (continued)

Data Description
Other
Insulation type Insulation type of the spare bushing
Outer insulation type Outer insulation type of the spare bushing
1. Only available for spare bushings mounted on another assets
2. Set by the regional conventions (see 5.1.1 "Settings" on page 22).

OMICRON 75
DIRANA PTM User Manual

11.3 Current transformer data


11.3.1 Common parameters and settings
The table below lists all parameters and settings that are displayed for all standards, CT types and
classes.
In addition to these common parameters, specific additional parameters are displayed, depending on the
selected standard, CT type (protection or metering CT) and class. For these specific parameters, please
refer to the tables on pages 76 to 81.

Table 11-8: Ratings

Data Description
Standard Standard used for testing the current transformer
Rated frequency Rated frequency of the current transformer
Rated Ipn : Isn1 Rated primary- to-secondary current ratio of the current transformer
Rated Ipr : Isr 2
Primary windings Number of primary windings on the current transformer (for primary
reconnection)
IEEE C57.13
System voltage System voltage of the current transformer
Rated insulation level Basic impulse level rating of the current transformer
(BIL)
Rating factor (RF) Continuous thermal current rating factor of the current transformer
IEC 60044/IEC 61869
Um (r.m.s.) Highest voltage for equipment
U withstand (r.m.s.) Rated power-frequency withstand voltage
U lightning (peak) Rated lightning impulse withstand voltage
Icth Rated continuous thermal current
Idyn (peak) Rated dynamic current
Ith (r.m.s.) Rated short time thermal current
Duration Duration of rated short time thermal current
1. According to IEC 60444
2. According to IEC 61869 and IEEE C57.13

76 OMICRON
Asset data

Table 11-9: CT configuration

Data Description
Cores Number of the current transformer’s cores
Name Inter-tap identification
Ipn1/Ipr2 Inter-tap rated primary current

Isn1/Isr2 Inter-tap rated secondary current


In use Tap on which the CT is operated
Ratings
Application Application category of the current transformer
Class Rated accuracy class of the current transformer
Rated burden Rated burden of the current transformer
Burden Secondary burden of the current transformer
Operating burden Burden (VA value) connected to the current transformer
cos φ Phase angle of the secondary burden
1. According to IEC 60444
2. According to IEC 61869 and IEEE C57.13

11.3.2 IEC 60044 protection CTs


The following parameters are only displayed if the standard IEC 60044 is selected with the type
"Protection CT".

Table 11-10: Specific parameters and settings displayed for IEC 60044 protection CTs
Available for
IEC 60044 Available for
Parameter Description protection CTs, IEC 60044, class
class
xP xPR PX TPS TPX TPY TPZ
ALF Accuracy limiting factor. x x
Win-ding resistance Specified secondary winding resistance. x x x x x x
Ts Specified secondary time constant. x x x
Kx Dimensioning factor. x
Ek Rated knee point e.m.f. x
Ie Accuracy limiting current x
E1 User-defined e.m.f. to verify the excitation
x
current at this specific e.m.f.
Ie1 Maximum allowed excitation current at E1. x
Kssc Rated symmetrical short-circuit current
x x x x
factor.
Tp Primary time constant. x x x x
K Dimensioning factor. x

OMICRON 77
DIRANA PTM User Manual

Table 11-10: Specific parameters and settings displayed for IEC 60044 protection CTs (continued)
Available for
IEC 60044 Available for
Parameter Description protection CTs, IEC 60044, class
class
xP xPR PX TPS TPX TPY TPZ
V-al Rated equivalent excitation limiting
x
secondary voltage.
I-al Accuracy limiting secondary excitation
x
current.
Ktd Rated transient dimensioning factor. x x x
Duty Specified duty cycle. x x
t1 Duration of first current flow. The specified
accuracy limit must not be reached within x x
time tal1.

t-al1 Permissible time to accuracy limit for first


x x
energizing period of the duty cycle.
t2 Duration of second current flow. The
specified accuracy limit must not be x x
reached within time tal2.

t-al2 Permissible time to accuracy limit for


x x
second energizing period of the duty cycle.
tfr Dead time between first opening and
x x
reclosure.

The following parameters are only displayed if the standard IEC 60044 is selected with the type
"Metering CT".

Table 11-11: Specific parameters and settings displayed for IEC 60044 metering CTs
Available for
IEC 60044 metering
Parameter Description CTs, class
0.1, 0.2, 0.2s, 0.5,
0.5s, 1, 3, 5
FS Instrument security factor. x
ext. Ipn Extended current rating. x

78 OMICRON
Asset data

11.3.3 IEC 61869 protection CTs


The following parameters are only displayed if the standard IEC 61869 is selected with the type
"Protection CT".

Table 11-12: Specific parameters and settings displayed for IEC 61869 protection CTs
Available for IEC 61869
protection CTs, class
Parameter Description
protection transient protection
xP xPR PX PXR TPX TPY TPZ
ALF Accuracy limiting factor. x x
Winding resistance Specified secondary winding resistance. x x x x x x
Ts Specified secondary time constant. x x x x
Kx Dimensioning factor. x x
Ek Rated knee point e.m.f. x x
E1 User-defined e.m.f. to verify the excitation
x x
current at this specific e.m.f.
Ie Accuracy limiting current. x x
Ie1 Maximum allowed excitation current at E1. x x
Kssc Rated symmetrical short-circuit current
x x x
factor.
Duty cycle spec. The accuracy class assessment has to be
performed for the specific protection
requirements the CT is built for. According
to the standard, these requirements are
normally stated by the duty cycle and the
time constants.
However, in some cases the choice of one
x x x
specific duty cycle/time constant cannot
describe all protection requirements.
Therefore, Primary Test Manager offers the
possibility to specify "more general
requirements" (which cover the
requirements of different duty cycles and
time constants) by entering the Ktd instead.

Ktd Rated transient dimensioning factor


according to the name plate.
x x x
Note: Only displayed if parameter "Duty
cycle spec." is "by Ktd".
Tp Primary time constant.
Note: Only displayed if parameter "Duty x x x
cycle spec." is "by Duty".
Duty Specified duty cycle.
Note: Only displayed if parameter "Duty x x x
cycle spec." is "by Duty".

OMICRON 79
DIRANA PTM User Manual

Table 11-12: Specific parameters and settings displayed for IEC 61869 protection CTs (continued)
Available for IEC 61869
protection CTs, class
Parameter Description
protection transient protection
xP xPR PX PXR TPX TPY TPZ
t-al1 Permissible time to accuracy limit for first
energizing period of the duty cycle.
x x x
Note: Only displayed if parameter "Duty
cycle spec." is "by Duty".
t1 Duration of first current flow. The specified
accuracy limit must not be reached within
time tal1.
x x x
Note: Only displayed if parameter "Duty
cycle spec." is "by Duty" and "Duty" is "CO-
CO".
tfr Dead time between first opening and
reclosure.
Note: Only displayed if parameter "Duty x x x
cycle spec." is "by Duty" and "Duty" is "CO-
CO".
t-al2 Permissible time to accuracy limit for
second energizing period of the duty cycle.
Note: Only displayed if parameter "Duty x x x
cycle spec." is "by Duty" and "Duty" is "CO-
CO".

11.3.4 IEC 61869 metering CTs


The following parameters are only displayed if the standard IEC 61869 is selected with the type
"Metering CT".

Table 11-13: Specific parameters and settings displayed for IEC 61869 metering CTs
Available for
IEC 61869 metering
Parameter Description CTs, class
0.1, 0.2, 0.2s, 0.5,
0.5s, 1, 3, 5
FS Instrument security factor. x
ext. Ipn Extended current rating. x
ext. VA Extended burden range. x

80 OMICRON
Asset data

11.3.5 IEEE C57.13 protection CTs


The following parameter is only displayed if the IEEE C57.13 standard is selected with the type
"Prot. CT".

Table 11-14: Specific parameters and settings displayed for IEEE C57.13 protection CTs
Available for IEEE C57.13,
Parameter Description class
C T X K
Vb Rated secondary terminal voltage.
If the IEEE C57.13 standard is selected with the type "protection
CT" (class C, K or T), the VA and Cos ϕ parameters are not x x x
accessible to the user. In this case, the user has to enter the
terminal voltage Vb instead.
Vk User-defined measuring point.
x x
Vk1 User-defined measuring point 1.
Ik User-defined measuring point.
x x
Ik1 User-defined measuring point 1.
RE(20*Isn) Ratio error at 20 * Isn. x
Winding resistance Specified secondary winding resistance. x

11.3.6 IEEE C57.13 metering CTs


The following parameter is only displayed if the IEEE C57.13 standard is selected with the type
"Metering CT".

Table 11-15: Specific parameters and settings displayed for IEEE C57.13 metering CTs
Available for
IEEE C57.13
metering CTs,
Parameter Description class
0.15, 0.15s, 0.3, 0.6,
1.2
RF Continuous current rating factor. x

OMICRON 81
DIRANA PTM User Manual

11.4 Voltage transformer data


The table below lists all parameters and settings that are displayed for all standards, VT types and
classes.

Table 11-16: Ratings

Data Description
Standard Standard used for testing the voltage transformer
Rated frequency Rated frequency of the voltage transformer
Upr Rated primary voltage

Table 11-17: VT configuration

Data Description
Windings Number of windings on the voltage transformer
Usr Rated secondary voltage
Rated burden Rated burden of the voltage transformer
cos φ Phase angle of the secondary burden

82 OMICRON
Asset data

11.5 Rotating machine data


The following tables describe the rotating machine data.

Table 11-18: Configuration

Data Description
Star point1 Star point connection of the rotating machine during test
Overall capacitance Overall capacitance of the rotating machine
Capacitance per phase1 Capacitance per phase of the rotating machine

1. Only available for three-phase rotating machines

Table 11-19: Ratings

Data Description
Rated frequency Rated frequency of the rotating machine
Rated voltage L-L L-L voltage of the rotating machine
Rated current Rated current of the rotating machine
Rated speed (rpm) Rated speed of the rotating machine in revolutions per minute
Rated power Rated power of the rotating machine
Rated thermal class Rated thermal class of the rotating machine
Rated excitation current Rated excitation current of the rotor
(rotor)
Rated excitation voltage Rated excitation voltage of the rotor
(rotor)
cos(φ) Rated power factor of the rotating machine

OMICRON 83
DIRANA PTM User Manual

12 Application
This section describes testing of high-voltage assets with DIRANA. Primary Test Manager in
combination with DIRANA supports the following guided tests:
• DIRANA test
• Oil analysis
and the Insulation Resistance manual test.
Note: You can configure the tests in different ways as described earlier in this User Manual. For
conciseness, the wording open the test in the application procedures means clicking the test in the
Primary Test Manager workspace independently of how the test has been configured.

12.1 DIRANA test


The DIRANA test is used for the insulation diagnosis of high-voltage assets. With the DIRANA test, you
can measure the dielectric response of the insulation system, analyze the moisture content of the power
transformer insulation, and compare the measurement results.

12.1.1 Test set and software startup


To put DIRANA into operation and start Primary Test Manager:
1. Connect the DIRANA equipotential grounding terminal to the substation ground properly.
2. Start Primary Test Manager.
After you have started Primary Test Manager, proceed as described earlier in this User Manual. You can:
• Create new jobs (see 6 "Create new job" on page 37)
• Execute prepared jobs (see 7 "Execute prepared job" on page 60)
• Manage locations, assets, jobs and test reports (see 8 "Manage objects" on page 61)
• Open existing manual tests (see 9 "Open manual tests" on page 68)
• Generate test reports (see 10 "Generate test reports" on page 69)

12.1.2 Connection
To connect DIRANA to the test object:
1. In Primary Test Manager, open the DIRANA test.

WARNING
Death or severe injury caused by high voltage or current possible
► Before connecting DIRANA to the test object, observe the five safety rules (see
1.2.2 "Safety rules" on page 7) and all additional relevant laws and internal safety
standards.
► Do not touch the OUTPUT connector or any parts of the test setup when the red LED
on the DIRANA front panel lights continuously or blinks.
► Always ensure that the device is safely switched off and the sample is discharged
before touching any parts of the test setup.

84 OMICRON
Application

2. Connect DIRANA to the test object’s terminals by using the delivered cables and clamps according
to the wiring diagram displayed in the General area of the Primary Test Manager workspace.
Note: We recommend using the default settings for the measurement profile and selecting the
Configure all parameters automatically check box for optimum results of moisture analysis.

Figure 12-1: Example of the wiring diagram for a two-winding transformer

3. Connect DIRANA to the computer with the delivered USB cable and switch the computer on.
4. Connect DIRANA to the mains power supply by using the delivered power cord.
5. Switch DIRANA on by toggling the power switch on the rear panel.
6. Connect Primary Test Manager to DIRANA as described in 4.4 "Start Primary Test Manager and
connect to DIRANA" on page 19.

OMICRON 85
DIRANA PTM User Manual

12.1.3 Settings and conditions


The following table describes the DIRANA test settings and conditions.

Table 12-1: DIRANA test settings and conditions

Setting Description
Measurement settings
Asset with screen electrode Select the Asset with screen electrode check box if you test
an asset with the screen electrode.
Measurement profile Measured insulation of the asset under test
We highly recommend using the default setting for moisture
analysis. Other settings can lead to inaccurate results.
Measurement sequence Measurement method
(see "Measurement sequence" later in this section)
Configure all parameters Select the Configure all parameters automatically check
automatically box to set the recommended values of the test parameters.
We highly recommend using this setting for moisture analysis.
A manual change of settings can lead to inaccurate results.
Check for noise and connectivity Select the Check for noise and connectivity problems
problems check box to check automatically the measurement
environment before starting the measurement.
We recommend checking for noise and connectivity problems
as the time is justifiable compared with the total measurement
time.
Start frequency Highest test frequency
Stop frequency Lowest test frequency
FDS voltage FDS output peak voltage
PDC voltage PDC output voltage
Test conditions
Oil temperature Temperature of the transformer’s oil
Overwrite global test conditions Select the Overwrite global test conditions check box to set
test conditions different from the global test conditions.
Ambient temperature Ambient temperature
Humidity Relative ambient humidity
Weather Weather during the test
Estimated meas. time (h:m) The estimated measurement time applies for a full sweep of
the frequency range. As it is very likely that only a part of the
full frequency range has to be measured, the real
measurement time is most probably shorter than this time.
During the measurement, the required time is updated once all
relevant information for the calculation has been measured.

86 OMICRON
Application

Measurement sequence
The following table describes the measurement methods available for the DIRANA test.

Table 12-2: Measurement methods


Measurement sequence Description
FDS and PDC+ Combined FDS and PDC methods with optimization of the
measurement time
FDS only FDS method
PDC only PDC method1
PDC with depolarization PDC method with the measurement of the depolarization
measurement current1
FDS and PDC with depolarization Combined FDS and PDC methods with the measurement of
measurement the depolarization current
1. Only applicable for frequencies < 100 mHz

The following table describes the advanced settings of the DIRANA test.
Note: We strongly recommend using the default advanced settings. Change the advanced settings in
well-founded cases only if you are an experienced user.

Table 12-3: Advanced DIRANA test settings

Setting Description
FDS sampling points Measurement frequencies of the FDS method
(see "FDS sampling points" later in this section)
Polarization time Time interval during which the test object is polarized (charged)
by the applied PDC voltage.
Depolarization time Time interval during which the test object is depolarized
(discharged).
Noise suppression (PDC) Noise suppression level of the PDC method:
• Default (hardware only): no software-based noise
suppression
• Moderate (software enhanced)
• Strong (software enhanced)
• Extreme (software enhanced)
The software enhanced options (moderate, strong, extreme)
smooth the measurement curve before transformation into the
frequency domain. The software enhanced options enable
using the combined FDS and PDC methods in the presence of
severe noise but can result in reduced measurement accuracy.

OMICRON 87
DIRANA PTM User Manual

Table 12-3: Advanced DIRANA test settings (continued)

Setting Description
Noise suppression (FDS) Level of noise suppression of the FDS method: Default or
Improved
The Improved option suppresses the noise better than the
Default option but results in longer measurement times.
Pre-measurement delay1
Minimum time Minimum pre-measurement delay
Depol. current below Threshold level of the depolarization current
1. Only available if the Check for noise and connectivity problems check box is cleared.

FDS sampling points


Under FDS sampling points, you can manage the measurement frequencies of the FDS method.
When you set the start and stop sweep frequencies, Primary Test Manager generates a default list of
the FDS measurement frequencies. You can edit the list as follows.
To add a measurement frequency to the list:
1. In the FDS sampling points list, select the frequency above which you want to add the new
measurement frequency.
2. Click .
► To change a measurement frequency in the list, click the frequency, and then edit the frequency
value.
► To remove a measurement frequency from the list, select the frequency, and then click .
► To remove all measurement frequencies from the list, click Clear all.
► To restore the default list, click Restore.

12.1.4 Measurement
To perform a measurement:
1. In the Settings and conditions area, enter the settings and conditions of the DIRANA test (see
12.1.3 "Settings and conditions" on page 86).
Note: We recommend configuring all parameters automatically by selecting the
Configure all parameters automatically check box if you do not have a particular reason to set
some special parameter values.
2. Enter the oil temperature of the asset. If more than one temperature sensor is available, use the top
oil temperature.

WARNING
Death or severe injury caused by high voltage or current possible
► Do not touch the OUTPUT connector or any parts of the test setup when the red LED
on the DIRANA front panel lights continuously or blinks.
► Always ensure that the device is safely switched off and the sample is discharged
before touching any parts of the test setup.

88 OMICRON
Application

3. On the Measurements tab in the Measurements area, click Start to start the measurement.
Note: You can start a measurement only if Primary Test Manager is connected to DIRANA.

Figure 12-2: Starting a measurement

OMICRON 89
DIRANA PTM User Manual

After the measurement has finished, Primary Test Manager displays the measurement results.

Figure 12-3: Typical dielectric response of power transformer insulation

90 OMICRON
Application

The measurement data depends on the display mode selected on the Display settings tab
(see "Display settings" later in this section) in the Measurements area. The following tables describe
the DIRANA test measurement data for different display modes.

Table 12-4: DIRANA test measurement data for the Power factor/Dissipation factor/Tanδ1, Capacitance
and Impedance display mode

Data Description
Measurement Editable measurement name
Channel DIRANA measurement channel
Moisture Moisture content of the insulation in weight percent
Category Moisture content category
Oil conduct. Oil conductivity
Cursor frequency Measurement frequency set by the cursor
Power factor/ Power factor or dissipation factor of the insulation
Dissipation factor
Capacitance Capacitance of the insulation
Impedance (Z) Impedance of the insulation
Resistance (R) Parallel resistance of the equivalent circuit
C(10 mHz) / C(50 Hz) Ratio of the capacitance at 10 mHz to the capacitance at 50 Hz
1. Set on the Profiles tab of the Settings dialog box

Table 12-5: DIRANA test measurement data for the Current display mode

Data Description
Measurement Editable measurement name
Channel DIRANA measurement channel
Moisture Moisture content of the insulation in weight percent
Category Moisture content category
Cursor time Measurement time set by the cursor
Polarization current Polarization current of the PDC+ method
Resistance (R) Resistance of the insulation determined by the test voltage
divided by the measured current at this time
Depol. current Depolarization current of the PDC+ method
Polarization index Ratio of the current after 60 s to the current after 600 s
DAR Dielectric absorption ratio
Ratio of the current after 60 s to the current after 30 s

OMICRON 91
DIRANA PTM User Manual

Display settings
To access the display settings of the DIRANA test, click the Display settings tab on the right of the
Measurements area.

Figure 12-4: Display settings of the DIRANA test

The following table describes the display settings of the DIRANA test.

Table 12-6: Display settings

Setting Description
Display mode Measured quantity displayed in the chart:
Power factor/Dissipation factor/Tanδ1, Current,
Capacitance or Impedance
X-axis scale Scale of the X-axis
Y-axis scale Scale of the Y-axis
Show point markers Select the Show point markers check box to display the
measurement points with markers.
Default zoom Default zoom setting
Zoom to fit Zoom setting for the best fit of the measurement results
Fit X-axis Zoom setting for the best fit of the measurement data on the
X-axis
Fit Y-axis Zoom setting for the best fit of the measurement data on the
Y-axis
Legend Under Legend, you can select information to be displayed in
the chart and set the chart colors.
1. Set on the Profiles tab of the Settings dialog box

Note: Alternatively, you can access the display settings quickly on the left bottom of the chart.

92 OMICRON
Application

12.1.5 Moisture analysis


Primary Test Manager provides an automated procedure for the moisture content analysis of the
cellulose (pressboard and paper) of the power transformer insulation. A manual adjustment of single
parameters is usually not required and should only be performed by experienced users. The moisture
analysis is based on fitting the measured dielectric response by model curves of the transformer
insulation system available in Primary Test Manager. For the insulation diagnosis of other high-voltage
assets, see 12.1.6 "Comparison" on page 95. The moisture analysis requires only the insulation
temperature to be known. Primary Test Manager calculates all values for the best fit. Consequently, the
automated fitting procedure finds out any of the insulation parameters, even if none is known.
To enter the moisture analysis:
1. In the Measurements area, click the Moisture analysis tab.
2. From the Selected measurement list, select the measurement for which you want to perform the
moisture analysis.

Figure 12-5: Setting the moisture analysis parameters

OMICRON 93
DIRANA PTM User Manual

Table 12-7: Moisture analysis parameters

Parameter Description
Geometry
Barriers (X) Insulation barriers (axial) in percent of the volume between the
windings (stray channel)
The values are determined automatically and do not have to be
set manually.
Spacers (Y) Insulation spacers (radial) in percent of the volume between
the windings (stray channel)
The values are determined automatically and do not have to be
set manually.
Use asset specific limits in moisture Select the Use asset specific limits in moisture analysis
analysis check box to constrain the values of barriers and spacers
within a typical range for the asset under test.
Insulation material Select the insulation material of the asset under test from the
Insulation material list.
3. On the top of the workspace, set the chart options.

Table 12-8: Chart options

Option Description
Model curve color Color of the model curve
Visible frequency range of the model Frequency range of the model curve displayed in the chart
curve
4. On the Display settings tab on the right of the Measurements area, set your preferred display
settings (see "Display settings" on page 92).
5. Click Start moisture analysis to perform an automated moisture analysis. All parameters for which
you selected the check boxes are determined automatically.
After the moisture analysis has finished, Primary Test Manager displays the numerical analysis results
and the model curve fitting the measured dielectric response (see Figure 12-5: "Setting the moisture
analysis parameters" on page 93).

Table 12-9: Moisture analysis results

Data Description
Oil
Conductivity Oil conductivity
Conductivity @ 20 ºC Oil conductivity at 20 ºC
Category Moisture content category
εr Relative permittivity of the oil
Compensation of aging byproducts If this option is selected, Primary Test Manager automatically
compensates the result for aging byproducts which otherwise
could lead to an overestimation of the water content.

94 OMICRON
Application

Table 12-9: Moisture analysis results (continued)

Data Description
Cellulose
Moisture Moisture content of the cellulose in weight percent
Category Moisture content category
Moisture saturation Estimated relative moisture saturation of the cellulose
insulation
Bubbling inception temp. Estimated temperature where the bubbling effect is possible

12.1.6 Comparison
With Primary Test Manager, you can compare any number of measurements. By comparing different
measurements, for example, the measurements on the same asset at different times, you can diagnose
the insulation condition of the asset under test where the moisture assessment is not applicable.
To compare measurements:
1. In the Measurements area, click the Comparison tab.
2. Optionally, click the Assign unique colors check box to change the colors of added measurements
to unique colors in the comparison.
3. In the Test selector, select the measurement you want to add to the comparison, and then click Add
next to the measurement.
Note: You can select measurements from all tests currently available in Primary Test Manager.
4. Repeat step 3 for all measurements you want to compare.

OMICRON 95
DIRANA PTM User Manual

5. Optimize the chart for the visual assessment by using the display settings (see "Display settings" on
page 92).

Figure 12-6: Example of a measurement comparison

6. Compare the measurements visually.

Advanced data processing


With Primary Test Manager, you can further process the measurement data in the comparison view. You
can:
• Simulate a measurement at another temperature than the measurement was done for comparison
Note: The moisture assessment and the assessment of the oil should only be performed on the
original measurement.
• Filter the measured polarization current
• Re-calculate the part of the FDS curve calculated from the PDC measurement to smooth the curve
for comparison
• Update moisture analysis after the advanced data processing
Note: The advanced data processing addresses expert users. Use this feature only in well-founded
cases.

96 OMICRON
Application

To access the advanced data processing options, click next to the measurement you want to process.

Figure 12-7: Advanced data processing window

Table 12-10: Advanced data processing options

Option Description
Temperature correction (FDS)
Actual temperature Temperature at which the measurement was done
Simulated temperature Temperature at which you want to simulate the measurement
Temperature change Difference between the simulated temperature and the actual
temperature
Pressboard activation energy Activation energy of the asset’s insulation
Noise filter
Polarization meas. (current) Noise filtering of the measured polarization current
Miscellaneous options
Re-calculate calculated part of the Select this option to re-calculate the part of the FDS curve
curve calculated from the PDC measurement, for example, to smooth
the curve for comparison. This option is only available for
combined FDS and PDC measurements made with Primary
Test Manager or the DIRANA software version 1.5 or later.
Update moisture analysis Select this option if you want to update the moisture analysis
after the advanced data processing.
► To create a modified copy of the selected measurement after the advanced data processing, click
Create a modified copy.
► To update the selected measurement after the advanced data processing, click
Update existing measurement.

OMICRON 97
DIRANA PTM User Manual

12.1.7 Disconnection
To disconnect DIRANA from the test object:

WARNING
Death or severe injury caused by high voltage or current possible
► Before disconnecting DIRANA from the test object, observe the five safety rules (see
1.2.2 "Safety rules" on page 7) and all additional relevant laws and internal safety
standards.
► Do not touch the OUTPUT connector or any parts of the test setup when the red LED
on the DIRANA front panel lights continuously or blinks.
► Always ensure that the device is safely switched off and the sample is discharged
before touching any parts of the test setup.
1. Switch off DIRANA.
2. Disconnect all clamps and cables from the test object’s terminals.
3. Disconnect all cables from DIRANA.

98 OMICRON
Application

12.2 Oil analysis


The Oil analysis is used to add the results of oil analyses performed by an oil laboratory or using a mobile
DGA test instrument. The values can be entered directly or imported from an Excel file.
For the dissolved gas in oil values the standard assessments and visualization according to
IEEE C57.104-2008 and IEC 60599-2007-05 Edition 2.1. are performed.
The following table describes the Oil analysis settings.

Table 12-11: Oil analysis settings

Setting Description
Asset
Asset Asset under test – set in the asset data (see 11 "Asset data" on
page 71)
Tank type Type of transformer tank
Insulation medium Insulation medium of the transformer – set in the asset data (see
11 "Asset data" on page 71)
Note: The DGA is only valid for the insulation medium Mineral oil.
Oil type Type of transformer oil
Test conditions
Sample date Date of sample collection
Oil sample temperature Oil temperature at the time of sampling
Measurement
Analyzed by Information on how the sample was analyzed
• Oil lab: The sample was analyzed by a laboratory.
After selecting Oil lab, you can enter the Name and Address of the
laboratory.
• Mobile DGA: The sample was analyzed using a mobile DGA device.
After selecting Mobile DGA, you can enter the device
Manufacturer/Type and its Serial number.
• Online DGA: The sample was analyzed using a permanently
installed monitoring device.
After selecting Online DGA, you can enter the device
Manufacturer/Type and its Serial number.
Use C3 hydrocarbons Activate the Use C3 hydrocarbons check box to add C3H6 and C3H8
to the list of Gas in oil values, and to activate ratio assessment
according to the MSS scheme.
Sampling point Sampling point on the transformer tank:
• Top
• Middle
• Bottom

OMICRON 99
DIRANA PTM User Manual

The following table describes the gas-in-oil values.

Table 12-12: Gas-in-oil values

Data Description
TDCG Total dissolved combustible gas
TDG Total dissolved gas
TCGe Estimation of the percentage of total combustible gas in the gas space.
It will only correspond to the actually measured value if there is a
balance between the gas blanket and the oil.
Lab. result Assessment result of the laboratory according to the IEEE or IEC
standard.
Assessment Manual Gas-in-oil analysis assessment:
• Manual pass
• Manual fail
• Manual investigate
• Not assessed

Assessment summary
The results are assessed using the following interpretation methods:
• Duval’s triangles (see Table 12-13)
• IEC basic gas ratios
• Roger’s ratios
• Doernenburg’s ratios
• Key gases according to IEEE C57.104 and IEC60599 (see Table 12-13)
• MSS scheme

100 OMICRON
Application

Table 12-13: Examples of result visualization in the Assessment Summary section

Condition 4

Condition 3

Key gas ranges and conditions


according to IEEE C57.104
Condition 2

Condition 1

Indicator

Assumed fault –
see Assessment Summary
table

Duval’s triangle 1

Indicator

Indicator

Key gas ranges and conditions


according to IEC 60599,
visualized in 3D

OMICRON 101
DIRANA PTM User Manual

Assessment details
• The Table contains condition ranges and states for individual gases.
• The Ratio Table lists all used gas ratios, depending on the selected standard, and provides an
Interpretation of the recorded values.

Table 12-14: Assessment Details

Data Description
Table
Standard Standard used for the condition assessment
Overall assessment Condition fulfilled by the measured value of an individual gas
TDCG ppm/day Increase in TDCG per day since the last measurement
Recommendation Recommended interval for future measurements
Ratio Table
Sample Date Date of the sampling

Duval triangle
Duval’s triangles visualize faults in a triangular coordinate system (see Table 12-13).
• Triangle 1: gases formed by faults of low to high energy
• Triangle 4: gases formed more specifically by faults of low energy or temperature
• Triangle 5: gases formed more specifically by faults of high temperature

Pattern
The key gas results are visually compared to four reference patterns. If a reference graph matches the
measured value, it is highlighted.

Physico-chemical oil analysis


The following table describes the physico-chemical oil analysis data.

Table 12-15: Physico-chemical oil analysis data

Data Description
Water content
H2O meas. Measured water content in oil
H2O @ 20 ºC Calculated water content in oil
Relative saturation Relative water saturation
Assessment Water content assessment
DC conductivity
Meas. value Measured DC conductivity
Test temperature Temperature of the oil during DC conductivity test
Field strength Field strength

102 OMICRON
Application

Table 12-15: Physico-chemical oil analysis data (continued)

Data Description
Assessment DC conductivity assessment
Power factor
Standard Standard underlying the power factor analysis
Meas. value @ 25 ºC Power factor measured at 25 ºC
Meas. value @ 100 ºC Power factor measured at 100 ºC
Assessment Power factor assessment
Dielectric breakdown voltage
Standard Standard underlying the dielectric breakdown voltage analysis
Meas. value Measured dielectric breakdown voltage
Test temperature Oil temperature during dielectric breakdown voltage test
Assessment Dielectric breakdown voltage assessment
Chemical
Interfacial tension Interfacial tension of the oil
Neutralization value Neutralization value of the oil
Particle count Particle count of the oil
Color Color of the oil
Assessment Chemical assessment
The following table describes the test status.

Table 12-16: Test status

Status Description
Prepared
Partially executed See Table 6-1: "Job statuses" on page 37.
Executed

Note: The test status set in the Oil analysis is displayed in the job overview (see 6.2 "Job overview" on
page 39) under Tests.

OMICRON 103
DIRANA PTM User Manual

12.3 Insulation Resistance test


The Insulation Resistance test is used to import or enter data from an insulation testing device.

Table 12-17: Insulation Resistance test settings

Setting Description
Test conditions
Test object temperature Temperature of the test object
Custom test conditions Activate the Custom test conditions check box to set test conditions
differing from the global test conditions.
Ambient temperature Ambient temperature on site
Humidity Relative ambient humidity
Calculations
PI calculation Calculation of polarization index
Time 1 In the standard PI calculation, the testing device is applied and insulation
resistance measurements are taken after 60 seconds (Time 1) and 600
Time 2
seconds (Time 2).
The polarization index (PI) is calculated as follows:
R 600
PI = -----------
R 60

DAR calculation Calculation of dielectric absorption ratio


Time 1 In the standard DAR calculation, the testing device is applied and
insulation resistance measurements are taken after 30 seconds (Time 1)
Time 2
and 60 seconds (Time 2).
The dielectric absorption ratio (DAR) is calculated as follows:
R 60
DAR = --------
R 30

Correction factors
Temperature correction Select the Temperature correction check box to activate temperature
correction.
Correction temp. Temperature correction factor

104 OMICRON
Application

Table 12-18: Insulation Resistance measurement data

Setting Description
Test data To import a file containing test data:
► Press Add to browse your computer and add data from a file.
To directly import data from a measurement file:
► Open the file on your computer.
► In the file press CTRL+A to mark all content, and then press CTRL+C
to copy.
► In Primary Test Manager press Paste from clipboard.
The results may take a few seconds to load.
Measurement Name or number of the measurement
PI Polarization index
DAR Dielectric absorption ratio
Time Time at which the given values were recorded
Voltage
Voltage and current values recorded at the Time specified in the first
V DC
column
I DC

OMICRON 105
DIRANA PTM User Manual

13 Technical data
Table 13-1: DIRANA specifications

Characteristic Rating
Test modes
UST, GST, GSTg
Voltage source
Measurement voltage ±200 Vpeak
Max. continuous output 50 mApeak
current
PDC
Current measurement
Range ±10 mA
Resolution 0.1 pA
Input resistance 2 kΩ
Accuracy 0.5 % ± 1 pA
FDS
Measurement voltage 200 Vpeak
Measurement current ±50 mApeak
Dissipation factor
Range 0…10
Accuracy1
1 mHz < f < 100 Hz 1 % + 3×10–4
f < 1 mHz 2 % + 5×10–4
and f > 100 Hz
Capacitance
Range 10 pF…100 μF
Accuracy 0.5 % + 1 pF
Ranges for combined FDS and PDC measurements
Frequency 10 μHz…5 kHz
1. For capacitances > 100 pF and using default settings

Table 13-2: Power requirements

Characteristic Rating
Input voltage/power 10 V…24 V DC/24 W

106 OMICRON
Technical data

Table 13-3: Power supply specifications

Characteristic Rating
Input
Voltage 85 V…264 V
Frequency 50 Hz/60 Hz
Power 40 W max.
Output
Voltage 12 VDC
Current 3.34 A max.

Table 13-4: Climate

Characteristic Rating
Operating –10 ºC…+55 ºC/+14 ºF…+131 ºF
Temperature
Storage –35 ºC…+65 ºC/–31 ºF…+149 ºF
Max. altitude Operating 70 kPa…106 kPa
(air pressure) Storage 70 kPa…106 kPa

Table 13-5: Mechanical data

Characteristic Rating
Dimensions (w × h × d) 260 mm × 50 mm × 265 mm/10.25 inch × 2 inch × 10.5 inch
Weight of instrument <2.3 kg/5 lb (without measuring cables)

OMICRON 107
DIRANA PTM User Manual

Table 13-6: Standards conformity

EMC, safety

IEC/EN 61326-1 (industrial electromagnetic environment)


EMC
FCC subpart B of part 15, class A

IEC/EN/UL 61010-1,
Safety
IEC/EN/UL 61010-2-30

Other
IEC/EN 60068-2-27
Shock
(15 g/11 ms, half-sinusoid, 3 shocks in each axis)
IEC/EN 60068-2-6
Vibration (frequency range 10 Hz…150 Hz, acceleration 2 g continuous
(20 m/s2/65 ft/s2), 20 cycles per axis)
IEC/EN 60068-2-78
Humidity (20%…95% relative humidity, no condensation),
tested at 40 ºC/104 ºF for 48 hours

108 OMICRON
TMDRA 100

14 TMDRA 100
14.1 Designated use
The TMDRA 100 is an accessory to the DIRANA test system for performing two-channel measurements
in the laboratory, delivering typical dielectric response characteristics of transformers as shown later in
this chapter. The moisture analysis can be done as for real measurements. The TMDRA 100 is a demo
box used for demo and training purposes. It can also be used to verify the integrity of the device and
measurement cables.

Figure 14-1: Typical dielectric response characteristics measured with the TMDRA 100

OMICRON 109
DIRANA PTM User Manual

14.2 Interfaces

CH 1
connector

CH 2 INPUT
connector connector

Figure 14-2: TMDRA 100

Table 14-1: TMDRA 100 interfaces

Interface Description
CH 1 connector Channel 1 output (connect to the channel 1 of DIRANA)
CH 2 connector Channel 2 output (connect to the channel 2 of DIRANA)
INPUT connector Signal source input (connect to the output of DIRANA)

14.3 Application
This section describes the application of the TMDRA 100 demo box.

14.3.1 Connection
To connect the TMDRA 100 to the DIRANA test system:
1. Connect the CH 2 connector of the TMDRA 100 to the CH 2 connector of DIRANA by using the blue
triaxial cable.
2. Connect the CH 1 connector of the TMDRA 100 to the CH 1 connector of DIRANA by using the red
triaxial cable.
3. Connect the INPUT connector of the TMDRA 100 to the OUTPUT connector of DIRANA by using the
yellow triaxial cable.
4. Connect DIRANA to your computer (see 4.1 "Connect DIRANA to the computer" on page 18).
5. Power up DIRANA (see 4.2 "Power up DIRANA" on page 18).

14.3.2 Measurement
The TMDRA 100 can be used as a one-winding or a two-winding transformer for both single-phase and
three-phase configuration.

110 OMICRON
TMDRA 100

► Perform dielectric response analysis measurements as described in 12.1 "DIRANA test" on page 84.

14.3.3 Disconnection
1. Switch off DIRANA by pressing the power switch on the DIRANA rear panel.

WARNING
Death or severe injury caused by high voltage or current
► Do not touch the DIRANA connectors and the connected cables while the red LED on
the DIRANA front panel is on or flashing.
► Wait until the red LED is off before disconnecting the cables.
2. Disconnect the color-codes triaxial cables from the CH 1, CH 2 and INPUT connectors of the
TMDRA 100.

OMICRON 111
DIRANA PTM User Manual

14.4 Technical data

Table 14-2: TMDRA 100 specifications

Characteristic Rating
Input voltage ±200 Vpeak

CH 11
@ 0.1 Hz 0.409
Tan(δ)
@ 50 Hz 0.004
@ 0.1 Hz 21.0 nF
Capacitance
@ 50 Hz 20.3 nF
CH 21
@ 0.1 Hz 1.026
Tan(δ)
@ 50 Hz 0.007
@ 0.1 Hz 30.1 nF
Capacitance
@ 50 Hz 20.4 nF
1. Typical ratings at +25 ºC/+77 ºF

Table 14-3: Climate

Characteristic Rating
Operating –10 ºC…+55 ºC/+14 ºF…+131 ºF
Temperature
Storage –20 ºC…+70 ºC/–4 ºF…+158 ºF
Max. altitude 2000 m

Table 14-4: Mechanical data

Characteristic Rating
Dimensions (w × h × d) 115 mm × 70 mm × 30 mm/4.5 inch × 2.8 inch × 1.2 inch
Weight 177 g/0.4 lb

112 OMICRON
TMDRA 100

Table 14-5: Standards conformity

EMC, safety

IEC/EN 61326-1 (industrial electromagnetic environment)


EMC
FCC subpart B of part 15, class A

IEC/EN/UL 61010-1,
Safety
IEC/EN/UL 61010-2-30

Other
IEC/EN 60068-2-27
Shock
(15 g/11 ms, half-sinusoid, 3 shocks in each axis)
IEC/EN 60068-2-6
Vibration (frequency range 10 Hz…150 Hz, acceleration 2 g continuous
(20 m/s2/65 ft/s2), 20 cycles per axis)
IEC/EN 60068-2-78
Humidity (20%…95% relative humidity, no condensation),
tested at 40 ºC/104 ºF for 48 hours

OMICRON 113
DIRANA PTM User Manual

Support
When you are working with our products we want to provide you with the greatest
possible benefits. If you need any support, we are here to assist you!

24/7 Technical support – get support


www.omicronenergy.com/support
At our technical support hotline, you can reach well-educated technicians for all
of your questions. Around the clock – competent and free of charge.
Make use of our 24/7 technical support hotlines:
Americas: +1 713 830-4660 or +1 800-OMICRON
Asia-Pacific: +852 3767 5500
Europe / Middle East / Africa: +43 59495 4444
Additionally, you can find our Service Center or Sales Partner closest to you at
www.omicronenergy.com.

Customer area – stay informed


www.omicronenergy.com/customer
The customer area on our website is an international knowledge exchange
platform. Download the latest software updates for all products and share your
own experiences in our user forum.
Browse through the knowledge library and find application notes, conference
papers, articles about daily working experiences, user manuals and much more.

OMICRON Academy – learn more


www.omicronenergy.com/academy