Sunteți pe pagina 1din 67

Total Sheet  67

Vendor’s name :  BENTINI CONSTRUCTION S.pA.
Owner’s Name : SH/ E&P/DP/ HRM
Purchaser          : JGC CORPORATION, JGC ALGERIA
P / Order No.    : 0‐7577‐2‐P‐2140‐001‐A
Equipment/Material name : FIRE ALARM SYSTEM ‐ VENDOR DATA BOOK AND
INSTALLATION, OPERATION & MAINTENANCE MANUAL
SYSTÉME DÉTECTION D'INCENDIE ‐ MANUEL
D'INSTALLATION, D'UTILISATION ET DE MAINTENANCE
Item number : BC2129‐000‐000‐FPR‐MAN‐00001
Vendor Doc No. : V‐2140‐001‐A‐811
Document title : FIRE ALARM SYSTEM ‐ VENDOR DATA BOOK AND
INSTALLATION, OPERATION & MAINTENANCE MANUAL
SYSTÉME DÉTECTION D'INCENDIE ‐ MANUEL
D'INSTALLATION, D'UTILISATION ET DE MAINTENANCE

HASSI R’MEL BOOSTING PHASE III PROJECT
(JOB No. : 0‐7577‐20)
ISSUE PURPOSE(FA,FI,FC,AB)                            (                           FA                          )
A
RESULT CODE(A,B,R,N,F)                                    (                                                           )
N/A
NEXT STATUS(FA,FI,FC,AB)                                (                                                           )
RESUBMISSION DATE                                           (                                                           )
BLD/K.I
RESPONSIBLE DEPT./PERSON                           (                                                           )
6-Dec-2018
Review Date                                                            (                                                          )
A: Approved without Comment                B: Approved with Minor Comment
R: Resubmit Incorporating Comments     N: Not Approved F: Not Subject to Review
Approval or review hereunder shall not be construed to relieve Supplier / Subcontractor of his 
responsibilities and liabilities under the Contract.
JGC DOC.  ORIG. PURCHASE ORDER NO. SERIAL REV.
NO. V ‐ 2140‐001‐A 811 1

3
2
1 ISSUED FOR APPROVAL CEU A.S. M.S.
0 ISSUED FOR APPROVAL CEU A.S. M.S.
REV DESCRIPTION PREP’D CHK’D APP’D

D R A
IN
10-D
E C - 2 018
PRINT
ED
WHEN 1 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1


Installation,Operationand
MaintenanceManual

FIREDETECTIONSystem





Manueld'installation,
d'utilisationetdemaintenance

SystèmeDÉTECTIOND'INCENDIE



D R A
IN
10-D
E C - 2 018
PRINT
ED
WHEN Page 2 of 67 2 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

INDEX/INDICE:


           Page/Page

1) ManualUserFCP………………..…………..………….……………………………..005
ManuelUtilisateurdeFCP………………..…………..………….………………..005

2) ManualUserSmokeDetector……………....…….……………………………..040
ManuelUtilisateurdeDétecteurdefuméeaddressable……………..040

3) ManualUserAirDuctSmokeDetector……….…….………………………..042
ManuelUtilisateurdeDétecteurdefuméedeconduitd'air………..042

4) ManualUserHeatDetector………………….…….……………..……………….049
ManuelUtilisateurdeDétecteurdechaleuradressable………………049

5) ManualUserCableSpaceHeatDetector…………………….………………051
ManuelUtilisateurdeDétecteurdechaleurmécanique……………...051

6) ManualUserIntrinsicallySafeDetector..…….………………………………054
ManuelUtilisateurdeDétecteuràsécuritéintrinsèque………………054

7) ManualUserFAASTͲLTAirSamplingSystem……………………………….057
ManuelUtilisateurdeDétecteurdefuméed'aspiration………………057

D R A
IN
10-D
E C - 2 018
PRINT
ED
WHEN Page 3 of 67 3 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1





ManualUserFCP:
AMͲ8000.2







ManuelUtilisateurdeFCP:
AMͲ8000.2





D R A
IN
10-D
E C - 2 018
PRINT
ED
WHEN Page 4 of 67 4 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

D
AM-8000
R A
Installation
manual
IN E C - 018
10-DIntelligent Addressable Fire detection
2
PRINT
ED
WHEN Page 5 of 67 5 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

INDEX
Limits of Fire Detection Systems 1
EN 54 : Informations – Option with Requirements 2
General Description 3
INSTALLATION: Dimensions for wall assembly 4
Front Panel indications 5
Electrical features 6
Earthing 6
Mains power supply 6
Power Supply 6
Battery Charger section 6
Batteries 6
Power supply and battery operation 7
Mains and Batteries connection 8
User power supply output 9
Fuse list 9
Relay Outputs 10
Sounder Output 11
System Components 12
Black-Box 12
AM-8000 CPU card 12
CNU – CNU terminal block 13
DIP SWITCH on CPU CARD 14
AM-8000 Front Panel LCD 14
DIP SWITCH on LCD CARD 16
LCD-8000 installation 16
CAN-LCD-8000 card 17
System Wiring 19
System Wiring example 21
CAN Bus Wiring: Cables 22
LIB-8000 card 23
LIB-8000 CNU terminal Block 23
Communication lines with Detectors / Modules 24
Technical specifications of analogue line connection cables 24
SENSORS & MODULES Connection 25
Test procedure for analogue system lines 26
System Test and Commissioning 27
SYSTEM PERIODICAL MAINTENANCE 28
Power Supply : Current and Battery calculation 29
Summary of Current consumption of Loop devices 31

AAM8000 Installation Manual INDEX

INDCR
AM8000_ind Doc. 160.1-AM8000-ENG Rev A.1 NOTIFIER ITALIA
-2018
E
10-D PRINT
ED
WHEN Page 6 of 67 6 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

NOTE: Do not try to install the control unit and devices connected without reading this manual.
.

DETECTION SYSTEM LIMITS


An alarm or fire detection system can be very useful for the prompt warning of any dangerous event, such as fire, a
robbery or a simple burglary, in some cases it can automatically manage events (transmission of messages for
room evacuation, automatic fire-extinguishing, TVCC system interface, access route or door blockage, automatic
warning to authorities, etc.), but in any case, it does not ensure protection against damages to propriety or
damages caused by fires or robberies).
Moreover, each system may not properly operate if it is not installed and maintained according to the
manufacturer’s instructions.

PRECAUTIONS
x These instructions contain procedures to be followed in order to avoid damages to
equipment. It is assumed that the user of this manual has performed a training
course and that he knows the applicable rules in force.
x The system and all its components must be installed in an environment having the
following features:
x Temperature: -5 °C ¸ +40 °C.
x Humidity: 10 % - 93 % (without condensation).
x Peripheral devices (sensors, etc.) which are not perfectly compatible with the
control unit may cause damages to the same control unit, and a bad operation of
the system in any moment. Therefore, it is essential to only use material which is
guaranteed by NOTIFIER and is compatible with its own control units.
Please consult NOTIFIER Technical Service for any doubt.

x This system, like all solid state components, may be damaged by induced
electrostatic voltages: handles the boards keeping them among the edges and
avoid to touch the electronic components.
x An appropriate earthing connection ensures, in any case, a sensitivity reduction to
disturbances.
x Please consult NOTIFIER Technical Service if you cannot solve installation
problems.
x Any electronic system does not operate if it is not powered.
If power supply from the mains fails, the system ensures its operation through
battery, but only for a limited period of time.
x During the system planning phase, take into account the autonomy required to
appropriately dimension the power supply and batteries.
x Skilled personnel shall periodically check the state of batteries.
x Disconnect the MAINS and the batteries BEFORE removing or inserting any board.
x Disconnect ALL power supply sources from the control unit, BEFORE performing
any servicing.
x The control unit and the connected devices (sensors, modules, repeaters, etc.)
may be damaged, if a new board is inserted or removed, or if the powered cables
are connected.
x The most common cause for malfunctioning is inappropriate maintenance.
x Take special care of these aspects since you start the system planning phase; this
will facilitate future servicing and will reduce cost.

This panel is market with the CE label to comply with the following European Directives :
Electromagnetic Compatibility Directive 2004/108/EC and 2006/95/CE

Nazional Rules Compliants

This device must be installed and must operate in accordance with these instructions

D R A and to the rules in force in the installation place.

IN
10-D
E C - 2 018
AM-8000
PRINT
ED PAGE - 1
L WHEN
EDAM8000_manu-inst Page 7 of 67 7 / 67
NOTIFIER ITALIA
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

EN 54 : Informations
x The AM-8000 control unit has a maximum capacity of : 636 sensors
EN54-2 13.7 and 636 addressable modules .
EN54
! Max 512 If this function is not appropriately used, it can contravene the EN54
Sensors / Manual requirements.
Call Points per This limit includes the possible conventional sensors and buttons
microprocessor. connected to the system with zone modules.
Therefore, check the number of installed devices and ensure their types
are in conformity with the rule
.

x This fire detection control unit is in accordance with the requirements of rule
EN54 EN54-2/4 .
9 In addition to the basic EN 54 requirements, the control unit is in conformity with the
following optional operation requirements

Optional Functions EN 54.2 reference


Output to fire alarm devices 7.8
Output to fire protection equipment 7.10
Fault monitoring of fire protection equipment 7.10
Delays to outputs 7.11
Dependencies on more than one alarm signal 7.12 ( type A )
Fault signals from point 8.3
Total loss of power supply 8.4
Disablement of addressable points 9.5
Test Condition 10
Indication of the test condition 10.2
Indication of zones in the test state 10.3

x The power supply section of the AM-8000 control unit is in conformity with the
EN54 following EN54-4 requirements.
9
Function EN 54.4 reference
Power supply from main source 5.1
Power supply from battery source in standby 5.2
Re-charging and check of the battery source 5.3
Power supply fault detection and signalling 5.4

D R A
IN
10-D
E C - 2 018
PAGE P-R2INTED AM-8000
L WHEN
EDNOTIFIER ITALIA Page 8 of 67 8 / 67
AM8000_manu-inst
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

GENERAL DESCRIPTION
AM-8000 control unit is a fire detection control unit manufactured in conformity with the EN.54.2 and EN.54.4 rules.

Technical features :
x Multi-microprocessor system
LCD-8000-L / LCD-8000-F with display TFT 7” (800 x 480 with backlit ) and 256 colors and touch-screen with
keyboard simulation to program and configure the system.
x Keys dedicated to specific functions : Evacuation, Reset delays, Buzzer Silencing, Silencing / Siren Reset,
System Reset.

x LINES:
2 analogue lines programmable to closed or open loop for the connection of the field elements
Each line can drive 159 sensors + 159 input and output modules
max 4 loop each panel using the optional 2 loop LIB-8000 card.

x SERIAL INTERFACES:

- 1 x RS.485 to drive remote LCD repeaters.


- 2 x Can-Bus lines to connect to closed loop ring for a network of up to 8 panels and 8 LCD-8000 terminals

x POWER SUPPLY:
Standard 27,6 Vdc - 4A total.
Battery charger 27,6 Vdc - 1A (with temperature compensation).
User output 27,6 Vdc - 1.5A, to power external loads such as sirens, bells, etc. .

x OUTPUTS:
1 Supervised Siren Output
1 General Alarm Output with contacts free from voltage
1 General Fault Output with contacts free from voltage

x Mechanics
The control unit mechanics is suitable for wall installations
Sizes 334mm (L) x 408mm (H) x 193mm (P)
Protection grade : IP 30
Operation temperature : -5 °C a +40 °C
Stockage temperature: -10 °C a +50 °C
Weight: 7.5 Kg

x
Main Functions
3 password levels (Operator - Maintenance – Configuration)
4 total access levels in conformity with the EN.54 rules
Programmable text : point description through 32 characters; zone description through 32 characters
500 physical zones and 400 logical groups
CBE Control Equations (Control-by event) for activation with logical operators (And,Or, Xor , etc.).
Event historical file with the last 2000 events in non-volatile memory
Real time clock
Line self-programming with automatic recognition of the type of the connected devices.
Automatic recognition of points having the same address.
Decision algorithms for the alarm and fault criteria.
Automatic sensitivity change Daytime /Night.
Signaling of need for sensor cleaning
Signaling of poor sensor sensitivity
Programmable alarm threshold for sensors
Pre-defined software function programming for the various devices used
Walk-Test function for zones.

D R A
IN
10-D
E C - 2 018
AM-8000
PRINT
ED PAGE - 3
L WHEN
EDAM8000_manu-inst Page 9 of 67 9 / 67
NOTIFIER ITALIA
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

Installation
Dimensions for wall assembly

SIDE display

View from High

View from back

View from low View from back

Moreover, if the control unit must


The control unit must be installed to the be installed to the wall beside a
wall so as to allow a clear view of the corner wall, the minimum distance
display and easy access by the from the latter must be at least
operator. For example, it allows an 280 mm, so as to avoid the
optimal view of the display at 1.5 m opening of the front panel.
height ,
.

The control unit is designed to be


installed to the wall through self-
blocking cleats (masonry walls) or self-
tapping screws (pre-fabricated panels).
It is recommended not to install the
panel near heat sources (radiators,
etc.)
Use screws of max 5 mm.

It is recommended not to install the control unit near heat sources (radiators, etc.).
The control unit can be opened by unscrewing the two cover fixing screws.

D R A
IN
10-D
E C - 2 018
PAGE P-R4INTED AM-8000
L WHEN
EDNOTIFIER ITALIA Page 10 of 67 10 / 67
AM8000_manu-inst
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

Extractable labels on the front panel

AM-8000 control unit is provided with extractable labels to indicate


the functions Status via LED and some function buttons.

D R A
IN
10-D
E C - 2 018
AM-8000
PRINT
ED PAGE - 5
L WHEN
EDAM8000_manu-inst Page 11 of 67 11 / 67
NOTIFIER ITALIA
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

ELECTRICAL FEATURES
x Operation temperature: - 5° C ÷ + 40°C.
x Relative humidity: 10 % ÷ 93 % (without condensation).
x Storage temperature: - 10°C÷ + 50°C.

Earthing
The earthling system must be performed in conformity with CEI and ISPELS rules or rules valid in the country
where the panel is installed.
In any case, must have a resistance lower than 10 Ohm (measured at the well with disconnected users). This
complies the CEI 68-12 rule for TN installations.
The earth connection to the control unit is compulsory and it must be performed on the CNAL terminal block. (refer
to basic board topography).

Main power supply


The control unit is powered by the mains voltage and, in case of mains breakdown it can continue to normally
operate due to the re-chargeable battery contained in the same control unit.
The required features for the mains supply are:
ŶŶŶ
Voltage: 230 Vac single-phase -15% ÷ +10%.
ŶŶŶ
Frequency: 50 / 60 Hz.
ŶŶŶ
Current 1.5 A.
¾ N.B.: particular care must be taken when the installation is performed near powerful electromagnetic
sources (ex. repeaters, radio relays, motors, etc.).

Power supply
The power supply has the following output: 28 Vdc -8 % ÷ +2 % , 4 A ripple max. 500mVpp
(Power supply for control unit, user output, external load power supply).

Battery charger section

x Output voltage = 27.6 Vdc.


x Output current = 1.5 A ca 500mVpp max (temperature compensation).
x Number of batteries that can be connected = 2 x 12 V – min.7Ah max.18Ah max.
x The battery charger section has the following signalling thresholds
Exhausted battery threshold = 21.5 Vdc.
Re-charge Fault threshold = 3.4 Vdc (voltage difference between the two batteries).
Battery release threshold = 19.5 Vdc

Batteries
Average duration declared by the manufacturer - 3-5 years at an ambient temperature of 20 C°
N.B. Life decreases in accordance with a higher operating temperature and possible discharging-recharging cycles

Recommended Batteries:

Capacity 7 Ah ( Min. stand-by capacity )


Yuasa tipo NP7-12B o NP7-12FR (UL94) Faston - Capacity (20hr) = 12V 7Ah – Dimensions: 151 x 65 x 98.
Fiamm tipo FG20721 o FGV20721 (UL94) Faston- Capacity (20hr) = 12V 7Ah – Dimensions: 151 x 65 x 98.

Capacity 17-18 Ah ( max. stand-by capacity )


Yuasa tipo NP18-12B o NP7-12FR (UL94) Bullone - Capacity (20hr) = 12V 17.2Ah – Dimensions: 181 x 77 x 167.
Fiamm tipo FG21803 o FGV21803 (UL94) Bullone- Capacity (20hr) = 12V 18Ah – Dimensions: 181 x 77 x 167.

These are respectively the Min. and the Max battery capacity compatible with the Battery Charger.
Depending from the Stand-by time required in the System and from Loads calculation, the user can select an intermediate
value.

D R A
IN
10-D
E C - 2 018
PAGE P-R6INTED AM-8000
L WHEN
EDNOTIFIER ITALIA Page 12 of 67 12 / 67
AM8000_manu-inst
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

BATTERIES Installation

Power supply and battery operation


The main microprocessor of the control unit periodically checks the state of the main AC power supply source, batteries and
the recharging circuit. The control unit will automatically switch on the stand-by battery source when AC mains fails.

When the control unit operates through AC mains, the main microprocessor controls the battery charger output and the
presence of them. To perform this test, the output battery charger is temporarily switched off and the battery voltage is read
(signalling of missing batteries<15.0V).

When the control unit operates as a battery (in the absence of the AC mains) “Low Battery” breakdown will be
indicated when their voltage is <21.5V and, to prevent irreversible damages the voltage will be automatically
switched off, by disconnecting the batteries, when the voltage is < 19,5V.
All wirings MUST be checked BEFORE they are connected to the control unit.
It is recommended to perform at least the following checks:

x Check the continuity of all cables used (including the shield )


x Ensure that, in alarm conditions, any possible voltage drops do not compromise the
operations of the various devices.
x Ensure that the electrical characteristics of all cables used come within the
manufacturer’s specifications (refer to the various sections of this manual)
x Check the insulation between all cables and between cables and shield and the
earthing. minimum of 2Mȍ insulation is required.
x Check that the screen of all signal cables is not earthed in positions other than the
prescribed ones.
x Check that the signal cables do not travel together with the power lines..

D R A
IN
10-D
E C - 2 018
AM-8000
PRINT
ED PAGE - 7
L WHEN
EDAM8000_manu-inst Page 13 of 67 13 / 67
NOTIFIER ITALIA
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

Mains and Batteries connection

The 230 Vac mains power supply cable must preferably pass near the relevant terminal block.
The connection to the 230 Vac power supply mains must be performed through three-conductor cable (phase-
neuter- earth).
The identification of the earth conductor coming from the mains must be performed on the CNAL terminal block
(refer to basic board topography) and must be fixed at the cabinet by means of cable –tightening strip so that it
cannot be accidentally stripped off from the terminal block.
The 230 Vac power supply cable must be fixed inside the control unit by means of an appropriate cable fixing
device.

NOTE: The cable fixing collars must be HB flammability class.


The mains supply conductors shall not be consolidated by means of a soft welding..

A sectioning device external to the control unit must be provided for the 230 Vac power cable (contact separation: 3
mm min.) The sectioning device must be omni-polar or must disconnect the line phase
Power Supply connection must be done following this procedure: (Refer to Base Board)

1 – Turn off the main power switch of the 230 Vac mains.
2 – Disconnect the CNAL terminal block from the control unit.
3 – Connect the mains cable.
4 – Re-connect the CNAL terminal block
5 – Turn on the mains switch
6 – Install and connect the batteries as indicated in this manual.

¾ N.B.: Once the control unit has been powered, it will automatically start operating.
However, in accordance with the battery storage period, it is necessary to wait some hours before the
batteries are completely re-charged.

7 – Check the operation of the LED indicators on the panel, according to the paragraph “TEST AND STARTING
OPERATION”.
8 – Close the control unit.

D R A
IN
10-D
E C - 2 018
PAGE P-R8INTED AM-8000
L WHEN
EDNOTIFIER ITALIA Page 14 of 67 14 / 67
AM8000_manu-inst
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

Current consumption from battery

x Current from battery in Normal Condition in the absence of mains voltage 230 Vac:
x CPU-8000 Card : 115 mA
x 1x LIB-8000 : 80 mA
x LCD-8000-L: 125 mA @ 24Vcc
x LCD-8000-F: 165 mA @ 24Vcc
x + current of external loads ( Detectors+Modules, external loads connected to the User Output)
x Current from battery in Alarm Condition in the absence of mains voltage 230 Vac:
x CPU-8000 Card : 135 mA
x 1x LIB-8000 : 90 mA
x LCD-8000-L: 230 mA @ 24Vcc
x LCD-8000-F: 270 mA @ 24Vcc
x + current of external loads in Alarm Condition ( Detectors+Modules, external loads connected to
the User Output)

See the appendix at the end of this manual for proper battery calculation in Stand-by and in Alarm
condition.

User power supply output

The AM-8000 control unit has one 24 Vdc fixed


CNU
output

The output is protected by 4 A FAST fuse


Use the fixed voltage output to power external
loads such as, for example, LCD repeaters
01 02
displays.
24V GND

User Output + Sounder Output:


x 28Vdc +2% -8% User power supply output connection
x 1.5 A dc ~500mVppmax
(refer to basic board topography)

Fuse list
230 V mains voltage 3,15 AL
Battery Output 7 A RESETTABLE
User power supply output 4 A RESETTABLE
Sounder output 1,35 A RESETTABLE

D R A
IN
10-D
E C - 2 018
AM-8000
PRINT
ED PAGE - 9
L WHEN
EDAM8000_manu-inst Page 15 of 67 15 / 67
NOTIFIER ITALIA
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

Relay outputs
FUNCTION CHARACTERISTICS

Siren 1 contact controlled by 24Vcc / 2A resistive

General Alarm Max 2A resistive 30 Vdc, NA-NC selectable through Jumper JALL
(refer to basic board topography)
General Fault Max 2A resistive 30 Vdc, NA-NC selectable through Jumper JGST
(refer to basic board topography)
USR1
Max 2A resistive 30 Vdc, NA-NC selectable through Jumper JUSR1
USR2 (refer to basic board topography)
Max 2A resistive 30 Vdc, NA-NC selectable through Jumper JUSR2
(refer to basic board topography)

EN54-2 8.8 x The General Fault relay is usually in energized state. It is de-energized in Fault
condition.
EN54
! General Fault Output x NOTE: do not connect to this output any alarm remote control, such as a
telephone dial (EN 54.2. 7.7) because the output line is not controlled
Contact range: max 30 VAC/DC, 2A,
Non-inductive loads CNU
Selection of type of contact (Normally open or
Normally closed) through JGST Jumper on
board (refer to basic board topography)
19 20
NC/ NO COM

Main Fault output connections


(refer to basic board topography)

EN54-2 7.7 x The main Alarm relay is available in free voltage contacts
EN54
General Alarm Output x NOTE: do not connect to this output any alarm remote control, such as a telephone
! dial (EN 54. 2. 7.7) because the output line is not controlled.

Contact range: max 30 VAC/DC, 2A,


Non-inductive loads CNU
Selection of type of contact (Normally open or
Normally closed) through JALL Jumper on board
(refer to basic board topography)

21 22
NC/ NO COM

Main Alarm output connections


(refer to basic board topography)

EN54-2 7.7
x The USR1 and USR2 relays are available in free voltage contacts
EN54
! Outputs x NOTE: do not connect to this output any alarm remote control, such as a telephone
USR1and USR2 dial (EN 54. 2. 7.7) because the output line is not controlled.

Contact range: max 30 VAC/DC, 2A,


Non-inductive loads
Selection of type of contact (Normally open or
Normally closed) through JURS1 e JUSR2
CNU CNU
Jumpers on board (refer to basic board
topography) USR1 USR2

NOTE:
To program the activation of these outputs refer 23 24 25 26
to “Am-8000 Programming Manual” NC/ NO COM NC/ NO COM

A
IN0-DDECR
URS1 e USR2 output connections
-2018 (refer to basic board topography)

1 PAGE P-R10
INTED AM-8000
L WHEN
EDNOTIFIER ITALIA Page 16 of 67 16 / 67
AM8000_manu-inst
O L
NCO NTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

Sounder connection - controlled output

CNU Siren output connections


(refer to basic board topography)

3 4

Polarized devices (electronic sirens, etc.)


4
47 K
¼W
3
NOTE:
Connect the 47K , ¼ W EOL
resistor only on last sounder
of the line
Non-polarized devices (Bells, relays, etc.)
4
ATTENTION:
47 K
¼W Polarity displayed are in
3 Alarm condition, at idle
2 x 1N 4004 condition, they are inverted

Sounder output operation window

SHORTCIRCUIT IDLE CUT

21K 61K

D R A
IN
10-D
E C - 2 018
AM-8000
PRINT
ED PAGE - 11
L WHEN
EDAM8000_manu-inst Page 17 of 67 17 / 67
NOTIFIER ITALIA
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

SYSTEM COMPONENTS
Black Box

x Each Black Box is equipped of one CPU card and can contain up to 2 Loop Interface cards ( LIB-8000 )
x Each LIB card can drive up to 2 ADV loop
x Each ADV Loop line can connect up to 159 detector and 159 Modules in Advanced protocol or 99+99 in
CLIP mode.

AM-8000 CPU card

D R A
IN
10-D
E C - 2 018
PAGE P-R12
INTED AM-8000
L WHEN
EDNOTIFIER ITALIA Page 18 of 67 18 / 67
AM8000_manu-inst
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

CNA terminal block


N° description Function Note
1 Phase
230Vac mains Power
2 Eatrh
Fused with 3,15 AL
3 Neutral

CNU terminal block

N° Name description Note


1 +24V USR Fused with 4 A fuse
2 GND USR
Sounder/ Siren (positive in
3
non alarm) Fused with 1,35A resettable fuse (this is a
EOL resistor = 47Kȍ
4
Sounder/ Siren (Negative in (polarity inversion output).
non alarm)
5 Not used
6 LIN +
NO EOL Internal resistor
7 GNDIS RS.485 Opto-insulated
8 LIN -
9 VPPLA POWER supply line Can-Bus (Output Line)
10 GNDP for LCD CAN bus devices with internal EOL resistor
11 CDAHA Power Supply line is
Communication line (side A) protected with a 4° Fuse
12 GND
for CAN BUS NETWORK
13 CDALA
14 VPPL1 POWER supply line AUDIO 1 Line
15 GND1 for CAN bus AUDIO devices Can-Bus with internal EOL
16 CDAH1 Communication line (side A) resistor
17 GND for AUDIO CAN bus devices Power Supply line is
18 CDAL1 protected with a 4° Fuse
19 General Fault : NO-NC Contacts : 2A 30V
General Fault Relay Normally-Open or Closed
20 General Fault : C
selectable via JGST Jumper
21 General Alarm : NO-NC Contacts : 2A 30V
General Alarm Relay Normally-Open or Closed
22 General Alarm : C
selectable via JALL Jumper
23 User1 : NO-NC Contacts : 2A 30V
User 1 Relay Normally-Open or Closed
24 User1 : C
selectable via JUSR1
25 User2 : NO-NC Contacts : 2A 30V
User 2 Relay Normally-Open or Closed
26 User2 : C
selectable via JUSR2
27 VPPLB POWER supply line
for CAN bus LCD devices Can-Bus (Input Line)
28 GNDP
with internal EOL resistor
29 CDAHB
Communication line (side B) Power Supply line is
30 GND
for CAN BUS NETWORK protected with a 4° Fuse
31 CDALB
32 VPPL2 POWER supply line AUDIO 2 Line
33 GND1 for AUDIO CAN bus devices Can-Bus with internal EOL
34 CDAH2 Communication line (side A) resistor
35 GND for AUDIO CAN bus 2 Power Supply line is
36 CDAL2 protected with a 4° Fuse

D R A
IN
10-D
E C - 2 018
AM-8000
PRINT
ED PAGE - 13
L WHEN
EDAM8000_manu-inst Page 19 of 67 19 / 67
NOTIFIER ITALIA
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

DIP SWITCH on CPU CARD

1 2 3 4 5 6 7 8
Download Tech SW
ADDRESS config. Load conf. use only Upgrade

ON off off off Black Box n.1


off ON off off Black Box n.2
ON ON off off Black Box n.3
off off ON off Black Box n.4
off off off off
ON off ON off Black Box n.5
off ON ON off Black Box n.6
ON ON ON off Black Box n.7
off off off ON Black Box n.8
Box ID
= Dip 5 = ON
proper from USB key loads configuration
configuration ON off off off previously prepared by PK-8000 SW Tool
Dip 6= ON
Box ID copy the configuration in the USB
= memory key
proper configuration off ON off off
Box ID
= Dip 8= ON
proper Use only by authorized Technician
configuration off off off ON

Note : Set the dip-SW 5-6-8 in ON for the time necessary to perform the function. Restore it in OFF position for
Normal operations.

AM-8000 Front Panel LCD


187 mm

31 mm

247 mm

D R A
IN
10-D
E C - 2 018
PAGE P-R14
INTED AM-8000
L WHEN
EDNOTIFIER ITALIA Page 20 of 67 20 / 67
AM8000_manu-inst
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

NOTE:
The two CPU cards of the two available LCD models ( LCD-800-F and LCD-8000-L differs in the component and in the software, but
maintain all end-user Connectors and Dip Switches in the same positions and with the same pin-out.

D R A
IN
10-D
E C - 2 018
AM-8000
PRINT
ED PAGE - 15
L WHEN
EDAM8000_manu-inst Page 21 of 67 21 / 67
NOTIFIER ITALIA
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

DIP SWITCH settings on LCD CARD

1 2 3 4 5 6 7 8
SW
ADDRESS OFF only Upgrade

ON off off off off LCD n.1 Normal Operation


off ON off off off LCD n.2 Normal Operation
ON ON off off off LCD n.3 Normal Operation
off off ON off off LCD n.4 Normal Operation
off
ON off ON off off LCD n.5 Normal Operation
off ON ON off off LCD n.6 Normal Operation
ON ON ON off off LCD n.7 Normal Operation
off off off ON off LCD n.8 Normal Operation

ID: proper configuration Off Off Off ON LCD n. ID Use only


under manufacturer autorization

LCD-8000-L /F installed in the Black-Box front door


To install the LCD on the Front Panel door:
x Open the door
x Take-off the plastic cover removing the front Label and cutting the 4 plastic connection
x Fit the LCD in the square hole and fix it using 4 screw as illustrated
x Connect the Flat Cable as schow in the picture.

D R A
IN
10-D
E C - 2 018
PAGE P-R16
INTED AM-8000
L WHEN
EDNOTIFIER ITALIA Page 22 of 67 22 / 67
AM8000_manu-inst
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

LCD-8000-L /F installed along the CAN-Bus Network : use CAN-LCD-8000 CARD


This card is necessary when the LCD is not installed in the same cabinet with the AM-8000 CPU

D R A
IN
10-D
E C - 2 018
AM-8000
PRINT
ED PAGE - 17
L WHEN
EDAM8000_manu-inst Page 23 of 67 23 / 67
NOTIFIER ITALIA
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

Display -Si TFT 7”wide (800x3rgbx480) with resistive touch screen. Antiglare surface.
LED Backlite software controlled.
Keyboard Matrix 2 columns by 3 lines ( 6 keys maximum )
Buzzer .
Real Time Clock Internal RTC with replaceable battery
Power Supply When installed inside the Black Box, the LCD-8000 is powered from the Panel with a flat Cable (max 2 mt))
When installed outside the Black Box , the CAN-LCD-8000 card must be used and an external power ( min
18Vcc a - max 40Vcc ) must be provided
Operating Temperature –5°C a +40°C
Humidity Max 95% no condensation
Stockage temperature –10°C a +50°C

Current consumption

LCD-8000-L Normal Condition 125mA @ 24Vcc – Alarm Condition 230mA @ 24Vcc


LCD-8000-F Normal Condition 165mA @ 24Vcc - Alarm Condition 270mA @ 24Vcc
CAN-LCD-8000 25mA @ 24Vcc

CAN-LCD-8000 card

CNFR : 10 pins connector to connect the LCD in a remote mode


1 VPP LA External Power supply for side A : min.18 Vdc – max.40 Vdc.
2 GNDP Protected with a 1A35 Fuse.
3 CDA HA
4 GND CanBus side A Communication
5 CDA LA
6 VPP LB External Power supply for side B : min.18 Vdc – max.40 Vdc.
7 GNDP Protected with a 1A35 Fuse.
8 CDA HB
9 GND CanBus side B Communication
10 CDA LB

D R A
IN
10-D
E C - 2 018
PAGE P-R18
INTED AM-8000
L WHEN
EDNOTIFIER ITALIA Page 24 of 67 24 / 67
AM8000_manu-inst
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

D R A
IN
10-D
E C - 2 018
AM-8000
PRINT
ED PAGE - 19
L WHEN
EDAM8000_manu-inst Page 25 of 67 25 / 67
NOTIFIER ITALIA
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

System Network Wiring


Power Power Power
230 Vac 230 Vac 230 Vac
AM-8000BB 1 AM-8000BB 2 AM-8000BB 3

CAN BUS
CAN BUS CAN BUS
Data Communication ring

7
Analogue Analogue Analogue Analogue
Power 24 Vdc

Power 24 Vdc

Power 24 Vdc

Power 24 Vdc

Power 24 Vdc

Power 24 Vdc
Optional Module for:
CAN BUS

Loop 1,2 Loop 3,4 Loop 1,2 Loop 1,2 - printing driver
- extension storage data

4 5 6

side A side B side A side B side A side B

CAN BUS
CAN BUS CAN BUS

LCD-8F LCD-8L LCD-8L


(Full) (Light) (Light)

™ Both LCD-8000-F and LCD-8000-L units are integral part of the AM-
EN54-2 8000 system. This implies that are “not only” events repeaters, but
EN54 also enable the operator to perform all EN 54.2 mandatory
! 8.2.6 - 12.5.3
functions like configuration, test, disabling etc.
Panels with ™ What said, implies that the connection to the AM-8000 CAN-Bus
components in MUST BE wired in Class A ( Loop ) configuration.
separate cabinet:
™ And also the Power supply connection MUST BE in the same
Fault condition & configuration.
indication. If this function is not appropriately followed, it can contravene the EN54
requirements.
Here are some samples of the power supply and CAN bus wiring.
Note that :
x Each LCD have TWO connections for the CAN Network
x Each LCD have TWO connections for the Power Supply
x CAN-Bus IN-OUT connections must be wired in separated path
x LCD Power IN-OUT connections must be wired in separated
path
Power source for the LCD-8000L and LCD-8000F can be :
x One Black Box for all LCDs , or….
x Each LCD can be powered from the nearest Black Box , or….
x One LCD can use a local EN 54.4 certified Power Supply unit but
in this case the Power line must be splitted and the two
connection path must be physically separated.

D R A
IN
10-D
E C - 2 018
PAGE P-R20
INTED AM-8000
L WHEN
EDNOTIFIER ITALIA Page 26 of 67 AM8000_manu-inst 26 / 67
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

System Wiring Example

D R A
IN
10-D
E C - 2 018
AM-8000
PRINT
ED PAGE - 21
L WHEN
EDAM8000_manu-inst Page 27 of 67 27 / 67
NOTIFIER ITALIA
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

CAN Bus wiring : CABLES

Communication Cable
Cable used for CAN Bus connection must be : Twisted pair – Shielded – Impedance: 120 Ohm

Shield wire have to be connected to the negative terminal on both side to guarantee the reference continuity.

Suggested cables are :

Double pair for both CAN-Bus + Power supply:


Belden 3082 A Multi-Conductor (18 AWG for CAN-Bus + 15 AWG for Power supply)
Using this cable, maximum distance from first to last equipment is: 800 mt at maximum transmission
speed of 31250 bit/sec

Belden 3086 A Multi-Conductor (20 AWG for CAN-Bus + 16 AWG for Power supply)
Using this cable, maximum distance from first to last equipment is: 400 mt at maximum transmission
speed of 31250 bit/sec

Single pair for CAN-Bus:


Belden 3105 A Twisted pair (22 AWG for Can-Bus only)
Using this cable, maximum distance from first to last equipment is: 300 mt at maximum transmission
speed of 31250 bit/sec

Power Supply Cable

Power supply cable can be a twisted pair with copper section proportional to :
o the distance from first and last equipment,
o Number and current consumption of all devices along the line.
o must guarantee the minimum voltage need to the properly functionality of all peripherals at
maximum current.

Can Bus Typology

Similary to all RS-485 communication line, the CAN Bus is a Point-to-Point sequential serie connection.
The wire must have a 120 Ohm resistor at each end.

The typology used is a Class A ( closed line – Loop ) .

It’s not necessary to follow the sequential serie on the peripherals addresses.

T-taps are not permitted.

Cable must be wired in conduits separated by the mains power line and anyway wiring must be compliant to laws
and rules valid in the country of the installation.

D R A
IN
10-D
E C - 2 018
PAGE P-R22
INTED AM-8000
L WHEN
EDNOTIFIER ITALIA Page 28 of 67 28 / 67
AM8000_manu-inst
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

LIB-8000 Card

DIP SWTCHES TO PROGRAM LIB NUMBER

DIP SWITCH SW1


1 2 3 4
LIB1 ON OFF OFF OFF
LIB2 OFF ON OFF OFF

LIB-8000 CNU terminal Block


N° Description Characteristics Note
12 Fault relay “Common” Max 30V 1A Select N.O./N.C. with
11 Fault relay N.C./ N.O. JGST Jumper
10 Alarm Relay “Common” Max 30V 1A Select N.O./N.C. with
9 Alarm Relay N.C./N.O. JALL Jumper
8 Line 2 B-
7 Line 2 B+
Detection LINE 2
6 Line 2 A-
5 Line 2 A+
4 Line 1 B-
3 Line 1 B+
Detection LINE 1
2 Line 1 A-
1 Line 1 A+

D R A
IN
10-D
E C - 2 018
AM-8000
PRINT
ED PAGE - 23
L WHEN
EDAM8000_manu-inst Page 29 of 67 29 / 67
NOTIFIER ITALIA
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

Communication lines with Detectors / Modules


The AM-8000 control unit communicates with intelligent detection and control devices which are addressable
through a 2 wire line.
The line can be connected to respect the specifications relevant to the signalling circuit lines of the STYLE 4 (open
line) and STYLE 6 (closed line).
The peripheral devices are powered by using the same line which is used to communicate with them.

x If more than 32 devices (ref. EN54.2) are installed on a line, this must be
configured as closed Loop ( style 6 ).
EN54
x If a connection is performed with a T-branch in a closed loop, not more than 32
! devices must be installed on this branch and these devices must be separated by
In case of short line insulators.
circuit cannot be lost x If the line is in Style 6 (Loop) an appropriate number of insulators devices must be
more than 32 alarm provided, in such way to don’t lost more than 32 points in case of short circuit.
points

The detection circuit must be separated by other cables to minimize the risk of interferences
Use twisted cable according to the specifications.
The detection Loop circuit is supervised and current-limited

The connection cables fitted with detectors, the auxiliary devices and the power mains, can be introduced into the
control unit by making some appropriate holes, by running cables along the side walls of the box, and appropriately
providing for those which are located near the terminal block.

Technical specifications of analogue line connection cables


Type of cable: 2 conductors ( for their section refer to the table below )
x Twisted narrow pitch (5 /10 cm.)
x Shielded pair cable
x Max. admitted capacity : 0,5 uF

Cable section
The sections are referred to the total length of the line (in case of “STYLE 6” loop and therefore when the loop is
closed, it is considered the loop length) which, however, must not be longer than 3000 meters and the total
resistance of the line must be lower than 40 Ohm.
Minimum Cable Section
Up to 500 mt. cable 2 x 0,5 mm²
Up to 1.000 mt. cable 2 x 1 mm²
Up to 1.500 mt. cable 2 x 1,5 mm²
Up to 3.000 mt. cable 2 x 2,5 mm²

Number of installed devices for line


The maximum number of devices that can be installed for each of the four detection lines is the following:
159 Detectors using Advanced Protocol
159 input and/or output modules
Isolator modules
The insulator modules allow to electrically insulate on the loop a series of devices from the remaining ones,
allowing loop critical components to continue operating even in case of the communication line short circuit.
Input Modules
The addressable inputs modules allow the AM-8000 system to monitor contacts, manual alarm call points, 4 wires
conventional detectors, and several other devices with alarm contact outputs.
Output modules
Through addressable output modules, the AM-8000 system, by means of the programmable CBE equations, can
activate the indication circuits or output relays through voltage free contacts or supervised class A controls.
Intelligent detectors
The AM-8000 control unit can communicate only with analogue detectors declared as compatible by NOTIFIER
ITALIA. In particular, all Advanced protocols devices of the NFX series will enable to use the maximum address

D R A
capability of 159 detectors each line.
IN
10-D
E C - 2 018
PAGE P-R24
INTED AM-8000
L WHEN
EDNOTIFIER ITALIA Page 30 of 67 30 / 67
AM8000_manu-inst
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

MODULE AND SENSOR CONNECTION

For the specific device connections , please refer to :


“Analogue system device installation manual”
document : M-199.1-SCH-ITA or M-199.1-SCH-ENG
by Notifier Italia.

Example of closed line (style 6 or Loop)

MCP
M700KI

MCP
MCP
M700KI
M700KI

- “B” SIDE -
“A” SIDE
+ +

The total length of the loop couple (from the Panel Loop output and input) SHALL NOT exceed 3.000 mt.

D R A
IN
10-D
E C - 2 018
AM-8000
PRINT
ED PAGE - 25
L WHEN
EDAM8000_manu-inst Page 31 of 67 31 / 67
NOTIFIER ITALIA
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

Test procedure for analogue system lines


Before powering the control unit lines, check the following values:
NOTE: A DIGITAL MULTI METER IS REQUIRED

Line resistance
Positive

Side B

Negative

Side A

The direct current resistance of the negative wire of the loop SHALL NOT exceed 20 Ohm.
The measurement must be performed by disconnecting the channels “A” and “B” from the LIB
Multi meter points are to be connected to the Negative wire terminals.
To have the total loop wire resistance, multiply by 2 the value read on the Negative side.

Line insulaton

Place between (+) and (-) of line through a tester, with sensors or modules installed and check the following:

OR

OPEN CLOSED

Test 1:
Connect : Tester (+) / Line (+) and Tester (-) / Line (-)
Check : Resistance: 1 - 1.3 MOhm
Test 2:
Connect : Tester (+) / Line (-) and Tester (-) / Line(+)
Check : Resistance: 0.7 - 0.9 MOhm

Screen shield insulation from the cable/line


Place a test prod of the tester on the line cable screen and the other test prod on the positive cable (+) of the
same line. The resistance measured must be higher than 15-20 MOhm, better if “infinitive”.

Perform the same operation between the line screen and negative cable (-). Check that also in this case the
resistance is higher than 15-20 MOhm.

Earthing /lines insulation


Place a test prod of the tester on the system earthing and the other test prod on the positive cable (+) of the line;
the resistance measured must be higher than 15-20 MOhm, better if “infinitive”.

Perform the same operation between the earthing and negative cable (-) of the line. Check that also in this case the
resistance is higher than 15-20 MOhm.

Earthing /cable screen insulation


Place a test prod of the tester on the system earthing and the other test prod on the cable braid; the resistance
measured must be higher than 15-20 MOhm, better if it is “infinitive”.

Line voltage
With the sensors/modules line connected, the line output voltage must be 24 Vcc without the device query (no

IN D RAprogrammed Point)
018 much lower than 14 Vcc indicates a connection inversion of sensors or modules.
CA-2voltage
E
10-D PAGE P-R26
INTED AM-8000
L WHEN
EDNOTIFIER ITALIA Page 32 of 67 32 / 67
AM8000_manu-inst
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

System Test and Commissioning


The Control unit installation must be performed after having carefully read the instructions contained in the
installation manual and the programming manual.

Once mechanical installation of the control unit has been completed, perform the following operations:

x Check the correct detection line wiring through a multi-meter (refer to chapter Test Procedure for the
analogue system lines in this manual).

x Connect the detection lines to the control unit.

x Connect the main alarm siren (fitted with 47 KW ¼ W balance resistance) on the CNU-03 and 04 terminals
(refer to basic board topography )

x To correctly dimension the batteries to be used, check the autonomy that the system must guarantee in case
of 230 Vac. mains breakdown.

Connect the control unit to the 230 Vca mains by means of a three-pole cables: phase, earth, neuter (the earth
cable must be longer than the phase and neuter ones) on the CNAL terminal block (the earthing connection
is compulsory) and must be fixed to the cabinet by means of a cable fixing device so that it cannot be
accidentally stripped off.

The power supply connection must be performed through the following phases
(refer to basic board topography):

x Turn off the main switch of the 230 Vca mains which powers the control unit;
x Disconnect the CNAL terminal block from the control unit
x Connect the 230 Vca mains to the CNAL terminal block;
x Connect the CNAL terminal block to the control unit ;
x Turn on the main switch of the 230 Vac mains
x Install and connect the batteries as indicated in this manual

When the control unit is powered check the following conditions on the front panel:

x Green led “POWER OK” = on


x Yellow led ” FAULTS” = flashing;
x Buzzer = continuous sound

By pressing the Buzzer Silencing key, the buzzer is switched off and the “POWER UP” fault indication is displayed

By Pressing the “RESET” key the request to enter the level 2 password is displayed
(default = 22222) .

Enter the password and check the following conditions:

x green led “POWER OK” = on


x yellow led “FAULTS” = off
x no faults signalling on the display

To program the control unit consult the chapter “RECOMMENDED SEQUENCE TO PERFORM THE CONTROL
UNIT PROGRAMMING” in the Operator and Programming manual.

D R A
IN
10-D
E C - 2 018
AM-8000
PRINT
ED PAGE - 27
L WHEN
EDAM8000_manu-inst Page 33 of 67 33 / 67
NOTIFIER ITALIA
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

SYSTEM PERIODICAL MAINTENANCE


Check that the green led “POWER OK” is on
Check that all other control unit leds are off

Press the function TEST key on the LCD and enter the level 2 password to access the “TEST” menu.

Use the arrow keys  to select the item “Led” (lamp test function), press the enter key
to perform the test, check that all light indications are on for some seconds.

1. Disconnect the 230 Vca mains supply from the AM-8000 control unit and check the following conditions:
x The indication of “MAINS LOSS” on the display
x Yellow led “FAULTS” flashing.
x Yellow led “POWER OK” on
x Yellow led “MAINS” on
x General Fault relay active
x After at least 15 minutes, check the battery voltage.
If the sum of the two battery voltages is lower than 20.5 V replace them.

2. Connect the 230 Vca mains power supply to the control unit, press the “SILENCE ALARM/FAULT” key and
check the following conditions:
x There is no indication of Alarm in progress on the display
x Yellow led “FAULTS” off
x Yellow led “POWER OK” on.
x Yellow led “MAINS” off
x General Fault relay deactivated

3. Disconnect both batteries; wait (not more than 2-3 minutes) for the control unit to signal:
x The indication of “BATTERIES NOT CONNECTED” on the display
x Yellow led “FAULTS” flashing.
x Yellow led “POWER OK” on.
x Yellow led “MAINS” on
x General Fault relay active

Re-connect the batteries and press the “SILENCE ALARM/FAULT” key and check:
x No breakdown signalling on the display
x Yellow led “FAULT” off
x Yellow led “POWER OK” off
x Yellow led “MAINS” off
x General Fault relay deactivated

4. Alarm a line 1 device and check the following conditions:


x Red led “ALARM” flashing.
x Siren output active.
x Alarm display

Press the “SILENCE ALARM/FAULT “ key and subsequently the “SILENCE / RESOUND SIREN” key; the
request to enter the level 2 password is displayed ( default = 22222 ).
Enter ths password and check the following conditions:
x yellow led SILENCE SOUNDER off
x red led “ALARM” on.
x Siren output deactivated

By pressing the “RESET” key, the request to enter the level 2 password is displayed (default = 22222).
Enter the password and check the following conditions:
x yellow led SILENCE SOUNDER off
x red led “ALARM” off
x Siren output deactivated
x No alarm signalling on the display

At the end of the maintenance leave the control unit in the idle condition (without alarm and breakdown

D R A
signalling) and check that the led “POWER OK” is on.

IN
10-D
E C - 2 018
PAGE P-R28
INTED AM-8000
L WHEN
EDNOTIFIER ITALIA Page 34 of 67 34 / 67
AM8000_manu-inst
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

POWER SUPPLY – Current calculation


The power supply must be able to continuously power all the internal system devices (and all external devices)
during the stand-by period, that is in NON-alarm conditions.
- Use the table A to calculate the load in stand-by conditions.
- Use the table B to calculate the additional current which is necessary in Alarm conditions
A 24 Vcc internal power supply for a total of 4 Ampere is available on the power supply for the system operation

NORMALcondition ALARM condition


A B
Item Q Current each Total Current Current each Total Current
(dev x Q) (dev x Q)
AM-8000
CPU- 8000 115 mA 135 mA
LIB-8000 80 mA 90 mA
CAN-LCD-8000 25 mA 25 mA
LCD-8000-L 125 mA 230 mA

LCD-8000-F 165 mA 270 mA

Devices connected to Sounder 0 0 |_________| |_________|


1
Output

Loops 2 Current
Refer to Table 2
Loop 1 |_________| |_________|
Loop 2 |_________| |_________|
Loop 3 |_________| |_________|
Loop 4 |_________| |_________|
User Output current 3 (Max 1.5A ) (Max 1.5A)
LCD-6000
Bells 0 0 |_________| |_________|
Sounders 0 0 |_________| |_________|
Strobes 0 0 |_________| |_________|
Other devices |_________| |_________| |_________| |_________|

4
Total = Total =

(x24h) or (x72h) = x 0.5 h =

Stand-by (A) Ah Alarm (B) Ah


5
Ah Battery = (A + B) x 1.2 = Ah

1 Check the load for each output is within admitted limits

2 Current from loops: Refer to the device manufacturer data sheet for the current necessary in normal mode.
Calculate the total current required for each loop by using the table 2 (refer to the following).
Alarm current: Refer to the devices manufacturer’ data sheet for the current necessary in alarm mode.
Calculate the total current required for each loop by using the table 2 (refer to the following) taking into account that the control unit controls
the activation only of the first 6 sensor and input module LED in alarm
Check that the total current for each loop is lower than 500 mA.

3 Refer to the device manufacturer data sheet for the current necessary in normal and alarm mode. Check that the total current is lower than
1,5 Ampere.

4 The current request for the stand-by or alarm conditions cannot, in any case, exceed the power supply capacity. If the calculated current
exceeds the value of 4 Ampere, available at the power supply, the exceeding current, necessary during the Alarm condition, is drawn from the
batteries.

5 The sum of currents obtained must be multiplied by a 1,2 factor to take account of the battery manufacturing tolerances.

D R A
IN
10-D
E C - 2 018
AM-8000
PRINT
ED PAGE - 29
L WHEN
EDAM8000_manu-inst Page 35 of 67 35 / 67
NOTIFIER ITALIA
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

Table 2
PERIPHERALS POWERD BY LOOPS
Device type Quantity Current Total in Current Total in
normal condition Alarm condition
Detectors serie NFX
Detectors serie 700
MCP
Single Modules serie 700
Double Modules serie 700
Modules serie MA
MMX-10 N
CMX-10 R
Isolation modules
Addressable Sounders
(Power from loop)
Other devices

N.B. Total must be less than 0,500 A Total (loop N.1) : Total (loop N.1) :
Detectors serie NFX
Detectors serie 700
MCP
Single Modules serie 700
Double Modules serie 700
Modules serie MA
MMX-10 N
CMX-10 R
Isolation modules
Addressable Sounders
(Power from loop)
Other devices

N.B. Total must be less than 0,500 A Total (loop N.2) : Total (loop N.2) :
Detectors serie NFX
Detectors serie 700
MCP
Single Modules serie 700
Double Modules serie 700
Modules serie MA
MMX-10 N
CMX-10 R
Isolation modules
Addressable Sounders
(Power from loop)
Other devices

N.B. Total must be less than 0,500 A Total (loop N.3) : Total (loop N.3) :
Detectors serie NFX
Detectors serie 700
MCP
Single Modules serie 700
Double Modules serie 700
Modules serie MA
MMX-10 N
CMX-10 R
Isolation modules
Addressable Sounders
(Power from loop)
Other devices

N.B. Total must be less than 0,500 A Total (loop N.4) : Total (loop N.4) :

D R A
IN
10-D
E C - 2 018
PAGE P-R30
INTED AM-8000
L WHEN
EDNOTIFIER ITALIA Page 36 of 67 36 / 67
AM8000_manu-inst
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

Summary of Current consumption of Loop devices:

Device Current NOTE

Normal Alarm

SDX-751ME 300 ȝA 6,5 mA


SDX-751TEM 300 ȝA 7 mA
FDX-551E 300 ȝA 7 mA
FDX-551HTE 300 ȝA 7 mA
NFXI-OPT 300 ȝA 4 mA
NFXI-TDIFF 300 ȝA 4 mA
NFXI-TFIX 58/78 300 ȝA 4 mA
NFXI-SMT2 300 ȝA 4 mA
PINNACLE 330 ȝA 6,5 mA
HPX-751 300 ȝA 5 mA
SMART 3 200 ȝA 7mA
SMART 4 200 ȝA 7mA
LPB-700 / 400 2 mA 8,5mA Loop Power
LPB-700T 2 mA 8,5mA 24 Vcc external
MMX-102E 100 ȝA 5 mA
M710E-CZ 288 ȝA 8.8mA External Power
M710E-CZ 1.5 mA 8.8mA Loop Power
M710E-CZR 500 ȝA 8.8 mA External Power
M710E-CZR 6,5 mA 8,8 mA Loop Power
ZMX-1E 200 ȝA 9 mA External Power
IMX-1 200 ȝA 4 mA
M710-E 310 ȝA 5 mA
MMA1-I 400 ȝA 5 mA
MCX-3 450 ȝA 5 mA
M701E 310 ȝA 5 mA
CMA1-I 410 ȝA 5 mA
M500KA 200 ȝA 5 mA
M700K 260 ȝA 5 mA
M700KI 360 ȝA 5 mA
NBG-12LX 100 ȝA 5 mA
P700 390 ȝA 5 mA
M720 340 ȝA 5 mA
M721 340 ȝA 5 mA
M701E-240 275 ȝA 8,8 mA
CMA-11 340 ȝA 6 mA
CMA22 700 ȝA. 7 mA
MCX-55M 2.7 mA 30mA
MMX-10M 2,7 mA 30mA
CMX-10R 4mA 30mA
AWS32/R-I 220ȝA 6.5mA Maximum Volume
AWS32/R/RD-I 220ȝA 9.7mA Maximum Volume
AWB/RD-I 220ȝA 2,2 mA
ABS32/PW-I 220ȝA 6,5 mA
ABSB32/PW/RD-I 220ȝA 9,8 mA
DNRE 300 ȝA 4 mA Depends from Detector installed
WL-NTM 20 mA 25 mA

D R A
IN
10-D
E C - 2 018
AM-8000
PRINT
ED PAGE - 31
L WHEN
EDAM8000_manu-inst Page 37 of 67 37 / 67
NOTIFIER ITALIA
O L
NCONTR
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

20097 Tel: 02/518971


San Donato Milanese Fax: 02/5189730
(MILANO) www.notifier.it
Via Grandi, 22 E-mail: notifier@notifier.it
A Honeywell company

Every care has been taken in the preparation of this data sheet but no liability can be accepted for the use of the information therein. Design features may be changed or amended without prior notice.

NOTIFIER ITALIA S.r.l.


M-0160.1-AM-8000-ENG Rev A.1

A socio unico - 20097 San Donato Milanese (Ml) - Via Grandi, 22 - Tel.: 02/518971 - Fax: 02/5189730 - Capitale Sociale
€ 2.700.000,00 i.v. - C.C.A.A. 1456164 - Trib. Milano Reg. Soc. 348608 - Vol. 8549 Fasc. 8 - Partita IVA IT
11319700156 (informativa privacy art. 3 Digs 196/03).
UFFICI REGIONALI:
10151 Torino - Via Pianezza, 181 - Tel.: 011/4531193 - Fax: 011/4531183 - E-mail: notifier.torino@notifier.it - 35010
Limena (PD) Via IV Novembre, 6/c int.9 - Tel.: 049/7663511 - Fax: 049/7663550 - E-mail: notifier.padova@notifier.it -
40050 Funo di Argelato (BO) - Asta Servizi, Bl. 3B, Gall. B n. 85, Centergross - Tel.: 051/864855 - Fax: 051/6647638 - E-
mail: notifier.bologna@notifier.it – 50136 Firenze - Via Telesio, 15 - Tel.: 055/696706 – Fax: 055/6529294 - 00118
Roma - Via Del Casale Santarelli, 51 - Tel.: 06/7988021 - Fax: 06/79880250 - E-mail: notifier.roma@notifier.it - 80143
Napoli – Via G.Porzio,4 Centro Direzionale. Isola E2, Scala B, Piano 5°, int.19 - Tel.: 081/7879398 - Fax: 081/7879159-

D R A
E-mail: notifier.napoli@notifier.it - 70125 Bari - Via Della Costituente, 29 - Tel.: 080/5013247 - Fax: 080/5648114 - E-
mail: notifier.bari@notifier.it - 95126 Catania - Via Alcide De Gasperi, 187 - Tel.: 095/7128993 - Fax: 095/7120753 -
IN
10-D
E C - 2 018
PRINT
ED
WHEN Page 38 of 67 38 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1





ManualUserSmokeDetector:
NFXIͲOPT







ManuelUtilisateurdeDétecteurde
fuméeaddressable:
NFXIͲOPT




D R A
IN
10-D
E C - 2 018
PRINT
ED
WHEN Page 39 of 67 39 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

EN54-7: 2000 Pittway Tecnologica S.r.l.


0786 DOP-IFD140 NFX-OPT
EN54-17: 2005 (NFXI only) Via Caboto 19/3, 34147
09 DOP-IFD141 NFXI-OPT
NFX(I)-OPT Trieste, Italy

Figure 2: Cleaning the Sensor

102 mm
Sensor Cover

B501AP 70°C
52 mm

I56-3388-004
-30°C 97 g Cover Removal Tabs

Sensing Chamber Cover


and Screen

Sensing Chamber
INSTALLATION AND MAINTENANCE INSTRUCTIONS
ENGLISH FOR MODEL NFX-OPT / NFXI-OPT PHOTO
ELECTRONIC SMOKE SENSOR
GENERAL DESCRIPTION
0RGHOV1);237DQG1);,237DUHLQWHOOLJHQWSOXJLQW\SHVPRNHVHQVRUVWKDWFRPELQH
DSKRWRHOHFWURQLFVHQVLQJFKDPEHUZLWKDGGUHVVDEOHFRPPXQLFDWLRQV7KHVHVHQVRUVDUH
GHVLJQHGIRURSHQDUHDSURWHFWLRQDQGPXVWRQO\EHFRQQHFWHGWRFRQWUROSDQHOVWKDWXVHD
FRPSDWLEOHSURSULHWDU\FRPPXQLFDWLRQSURWRFROIRUPRQLWRULQJDQGFRQWURO MAINTENANCE
%HIRUHFOHDQLQJGLVDEOHWKHV\VWHPWRSUHYHQWXQZDQWHGDODUPV
7KH1);,237VHQVRUFRQWDLQVDQLVRODWRULILQVWDOOLQJWKLVYHUVLRQFKHFNWKHSDQHOGRFX-
PHQWDWLRQIRUGHWDLOVRIKRZPDQ\LVRODWRUVFDQEHXVHGRQDORRS  5HPRYHWKHVHQVRUWREHFOHDQHGIURPWKHV\VWHP
 *HQWO\UHOHDVHHDFKRIWKHIRXUFRYHUUHPRYDOWDEVWKDWKROGWKHFRYHULQSODFH VHHÀJXUH
7ZR/('VRQHDFKVHQVRUOLJKWWRSURYLGHDORFDOo YLVLEOHVHQVRULQGLFDWLRQ RSHUDWLRQRI
 DQGUHPRYHWKHVHQVRUFRYHU
/('VDUHGHSHQGHQWRQSDQHO 5HPRWH/('LQGLFDWRUFDSDELOLW\LVDYDLODEOHDVDQRSWLRQDO
 9DFXXPWKHRXWVLGHRIWKHVFUHHQFKDPEHUFRYHUFDUHIXOO\ZLWKRXWUHPRYLQJLW
DFFHVVRU\ZLUHGWRWKHVWDQGDUGEDVHWHUPLQDOV DJDLQGHSHQGHQWRQSDQHO 
 5HPRYHWKHVFUHHQFKDPEHUFRYHUDVVHPEO\E\SXOOLQJLWVWUDLJKWRXW
SPECIFICATIONS  8VHDYDFXXPFOHDQHUDQGRUFOHDQFRPSUHVVHGDLUWRUHPRYHGXVWDQGGHEULVIURPWKH
2SHUDWLQJ9ROWDJH5DQJH WR9'& WRIRU1);,LVRODWHG VHQVLQJFKDPEHUDQGVHQVLQJFKDPEHUFRYHU
0D[6WDQGE\&XUUHQW QRFRPP  —$#9DQGoC  5HLQVWDOOWKHVHQVLQJFKDPEHUFRYHUE\DOLJQLQJWKHVTXDUHDQGURXQGKROHVRQWKH
FRPP/('EOLQNHQDEOHGVHF  —$#9DQGoC FRYHUZLWKWKHVTXDUHDQGURXQGSLQVDURXQGWKHVHQVLQJFKDPEHUJHQWO\SUHVVLQJLW
5HDGVHF/('EOLQNVHF  —$#9DQGoC KRPHXQWLOLWVOLSVLQWRSODFH
 DGG—$IRU1);,,VRODWHG  5HLQVWDOOWKHVHQVRUFRYHU8VHWKHFRYHUUHPRYDOWDEVDQG/('VWRDOLJQWKHFRYHUZLWK
0D[$ODUP&XUUHQW /('RQ  DGGP$#9DQGoC WKHVHQVRU6QDSWKHFRYHULQWRSODFH
2SHUDWLQJ+XPLGLW\5DQJH WR5HODWLYH+XPLGLW\1RQ&RQGHQVLQJ :KHQDOOVHQVRUVKDYHEHHQFOHDQHGUHVWRUHSRZHUWRWKHORRSDQGWHVWWKHVHQVRU V 
Isolator Characteristics (NFXI Only) DVGHVFULEHGXQGHUTESTING.
0D[LPXPUDWHGFRQWLQXRXVFXUUHQWZLWKWKHLVRODWRUFORVHG ,FPD[ $ TESTING
0D[LPXPUDWHGLVRODWRUFXUUHQW XQGHUVKRUWFLUFXLW  ,VPD[ $ 6HQVRUVPXVWEHWHVWHGDIWHULQVWDOODWLRQDQGIROORZLQJSHULRGLFPDLQWHQDQFH'LVDEOHWKH
0D[OHDNDJHFXUUHQW ,/PD[ ZLWKWKHLVRODWRURSHQ LVRODWHGVWDWH P$ ]RQHRUV\VWHPXQGHUJRLQJPDLQWHQDQFHWRSUHYHQWXQZDQWHGDODUPV
0D[VHULHVLPSHGDQFHZLWKWKHLVRODWRUFORVHG =FPD[ PRKPDW9GF
7HVWWKHVHQVRUVDVIROORZV
,QGHSHQGHQWO\WHVWHGDQGFHUWLÀHGWR(1 DQG(1IRU1);,
Magnet Method
WIRING GUIDE  7HVWWKHVHQVRUE\SRVLWLRQLQJWKHWHVWPDJQHW PRGHO0RSWLRQDO DJDLQVWWKH
5HIHUWRWKHLQVWDOODWLRQLQVWUXFWLRQVVXSSOLHGZLWKWKHSOXJLQVHQVRUEDVHVIRUZLULQJGHWDLOV VHQVRUERG\DSSUR[LPDWHO\FPIURP/('LQGLFDWHGE\DPDUNRQWKHVHQVRUFRYHUDV
$OOEDVHVDUHSURYLGHGZLWKWHUPLQDOVIRUSRZHUDQGDQRSWLRQDO5HPRWH,QGLFDWRU VKRZQLQÀJXUH
Note 1:$OOZLULQJPXVWFRQIRUPWRDSSOLFDEOHORFDODQGQDWLRQDOFRGHVDQGUHJXODWLRQV  %RWK/('·VRQWKHVHQVRUVKRXOGODWFKLQWRDODUPZLWKLQVHFRQGVDFWLYDWLQJWKHFRQWURO
Note 2:9HULI\WKDWDOOVHQVRUEDVHVDUHLQVWDOOHGDQGWKDWSRODULW\RIWKHZLULQJLVFRUUHFWDW SDQHO
HDFKEDVH
WARNING
Figure 3: Test Magnet Position
Disconnect loop power before installing sensors. Notify proper authorities.
Test Magnet
SENSOR INSTALLATION
 6HWWKHVHQVRUDGGUHVV VHHÀJXUH E\WXUQLQJWKHWZRURWDU\VZLWFKHVRQWKHXQGHUVLGH
RIWKHVHQVRUVHOHFWLQJDQXPEHUEHWZHHQDQG 1RWH7KHQXPEHURIDGGUHVVHV
DYDLODEOHZLOOEHGHSHQGHQWRQSDQHOFDSDELOLW\FKHFNWKHSDQHOGRFXPHQWDWLRQIRU
LQIRUPDWLRQRQWKLV 5HFRUGWKHDGGUHVVRQWKHODEHODWWDFKHGWRWKHEDVH
Mark on Cover
LED 2
Figure 1: Rotary Address Switches LED 1

Smoke Method
 8VLQJJHQHUDWHGVPRNHRUV\QWKHWLFVPRNHDHURVROIURPDQDSSURYHGPDQXIDFWXUHU
VXFKDV1R&OLPE3URGXFWV/WGVXEMHFWWKHVHQVRUWRFRQWUROOHGDPRXQWVRIVPRNHLQ
DFFRUGDQFHZLWKORFDOFRGHVRISUDFWLFHDQGPDQXIDFWXUHUUHFRPPHQGDWLRQV
X 10 X1  %RWK/('·VRQWKHVHQVRUVKRXOGODWFKLQWRDODUPZLWKLQVHFRQGVDFWLYDWLQJWKHFRQWURO
SDQHO
 ,QVHUWWKHVHQVRULQWRWKHEDVHDQGURWDWHLWFORFNZLVHXQWLOLWORFNVLQWRSODFH $IWHUFRPSOHWLRQRIWKHWHVWQRWLI\WKHSURSHUDXWKRULWLHVWKDWWKHV\VWHPLVRSHUDWLRQDO
 $IWHUDOOWKHVHQVRUVKDYHEHHQLQVWDOOHGDSSO\SRZHUWRWKHV\VWHP
 7HVWWKHVHQVRUDVGHVFULEHGXQGHUTESTING. WARNING
 5HVHWWKHVHQVRUE\FRPPXQLFDWLRQFRPPDQGIURPWKHSDQHO LIMITATIONS OF SMOKE SENSORS
Tamper-Resistance. 6PRNHVHQVRUVPXVWEHXVHGLQFRQMXQFWLRQZLWKFRPSDWLEOHHTXLSPHQW
7KHVHVHQVRUVLQFOXGHVDIHDWXUHWKDWZKHQDFWLYDWHGSUHYHQWVUHPRYDORIWKHVHQVRUIURP 6PRNHVHQVRUVZLOOQRWVHQVHÀUHVZKLFKVWDUWZKHUHVPRNHGRHVQRWUHDFKWKHVHQVRUV
WKHEDVHZLWKRXWWKHXVHRIDWRRO5HIHUWRWKHLQVWDOODWLRQLQVWUXFWLRQVIRUWKHVHQVRUEDVH $VHQVRUPD\QRWGHWHFWDÀUHGHYHORSLQJRQDQRWKHUOHYHORIDEXLOGLQJ
IRUGHWDLOVRIKRZWRXVHWKLVIHDWXUH 6PRNHVHQVRUVDOVRKDYHVHQVLQJOLPLWDWLRQV&RQVLGHUDWLRQPXVWEHPDGHRIWKHHQYLURQ-
CAUTION PHQWZKHQVHOHFWLQJÀUHVHQVRUV
Dust covers help to protect units during shipping and when first installed. Smoke sensors cannot last forever.6PRNHVHQVRUVFRQWDLQHOHFWURQLFSDUWV(YHQ
They are not intended to provide complete protection against contamination WKRXJKVHQVRUVDUHPDGHWRODVWRYHU\HDUVDQ\RIWKHVHSDUWVFRXOGIDLODWDQ\WLPH
therefore sensors should be removed before construction, major re-decoration 7KHUHIRUHWHVW\RXUVPRNHGHWHFWLRQV\VWHPDWOHDVWVHPLDQQXDOO\&OHDQDQGWDNHFDUH
or other dust producing work is started. Dust covers must be removed before RI\RXUVPRNHVHQVRUVUHJXODUO\7DNLQJFDUHRIWKHÀUHGHWHFWLRQV\VWHP\RXKDYHLQVWDOOHG
system can be made operational. ZLOOVLJQLÀFDQWO\UHGXFH\RXUSURGXFWOLDELOLW\ULVNV

D R A
IN
10-D
E C - 2 018
INTED
EN PR
NTR O L L ED WH
N200-200-00 Page 40 of 67 40 / 67
I56-3388-004
NCO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1





ManualUserAirDuctSmokeDetector:
DNRE







ManuelUtilisateurdeDétecteurde
fuméedeconduitd'air:
DNRE




D R A
IN
10-D
E C - 2 018
PRINT
ED
WHEN Page 41 of 67 41 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

INSTALLATION AND MAINTENANCE INSTRUCTIONS

DNR Duct Smoke Detector


SPECIFICATIONS
Operating Temperature: –4° to 158° F (–20° to 70° C);
32° F to 120° F (0° C to 49° C) with module installed in the DNR
Storage Temperature: –22° to 158° F (–30° to 70° C)
Humidity: 0% to 93% Relative Humidity Non-condensing
Air Velocity: 100 to 4000 ft./min. (0.5 to 20.3 m/sec.)
Rectangular Footprint Dimensions: 14.38 in L × 5 in W × 2.5 in D (37 cm L × 12.7 cm W × 6.36 cm D)
Square Footprint Dimensions: 7.75 in L × 9 in W × 2.5 in D (19.7 cm L × 22.9 cm W × 6.35 cm D)
Weight: 1.6 pounds; 0.73 kg
Electrical (See applicable detector head installation manual for electrical specifications. Use the Base/Sensor Cross Reference chart at http:\\www.systemsensor.com
to determine applicable sensor head.)

Table of Contents Page ACCESSORY CURRENT LOADS AT 24 VDC


[1] Limitations of Duct Smoke Detectors . . . . . . . . . . . . . . . . . . . . . . . . .1
DEVICE STANDBY ALARM
[2] General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 RA100Z 0mA 12mA Max.
[3] Contents of the Duct Smoke Detector Kit . . . . . . . . . . . . . . . . . . . . . .1 RTS451/RTS151 0mA 12mA Max.
[4] Detector Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 RTS451KEY/RTS151KEY 0mA 12mA Max.
[5] Sampling Tube Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 [2] GENERAL DESCRIPTION
[6] Measurement Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Smoke introduced into this air duct system will be distributed throughout the
[7] Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 entire building. Smoke detectors designed for use in air duct systems are used
to sense the presence of smoke in the duct.
[8] Verification of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Model DNR Air Duct Smoke Detector utilizes photoelectric technology for the
[9] Dectector Cleaning Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
detection of smoke. This detection method, when combined with an efficient
[10] Sensor Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 housing design, samples air passing through the duct and allows detection of
[11] Optional Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 a developing hazardous condition. When sufficient smoke is sensed, an alarm
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 signal is initiated at the fire control panel monitoring the detector, and appro-
BEFORE INSTALLING priate action can be taken to shut off fans, blowers, change over air handling
Read System Sensor’s Applications Guide for Duct Smoke Detectors (HVAG53), systems, etc. These actions can facilitate the management of toxic smoke and
which provides detailed information on detector spacing, placement, zoning, fire gases throughout the areas served by the duct system.
wiring, and special applications. This manual is available online at www.sys- The DNR incorporates a sensor cover tamper feature that provides a trouble
temsensor.com. NFPA Standards 72 and 90A should also be referenced for signal at the panel immediately if the cover is removed or improperly in-
detailed information. stalled. Proper installation of the sensor cover removes the trouble condition.
NOTICE: This manual shall be left with the owner/user of this equipment. When programmed with the system control panel, two LEDs on each duct
IMPORTANT: This detector must be testeds and maintained regularly follow- smoke detector light to provide local visible indication.
ing NFPA 72 requirements. The detector must be tested an maintained regularly The DNR provides a remote alarm output for use with auxiliary devices, such
following NFPA 72 requirements. According to NFPA, the detector should be as the RA100Z remote LED annunciator, as well as remote test capability with
visually inspected semiannually and functionally tested at least once a year. This the RTS451/RTS151 or RTS451KEY/RTS151KEY Remote Test Stations.
may need to be more frequent depending on the air quality of the duct supply air.
[2.1] DETECTOR FEATURE SET
[1] LIMITATIONS OF DUCT SMOKE DETECTORS – Utilizes plug-in head
– Sampling tubes install from front and rear
WARNING – Compatible with existing accessories
The National Fire Protection Association has established that DUCT DETEC- – Able to address detector per code switches on sensor head.
TORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR [3] CONTENTS OF THE DUCT SMOKE DETECTOR KIT
PROTECTION as a means of providing life safety. Nor are they a substitute for 1. Sensor/power side and covers (use appropriate sensor per the system
early warning in a building’s regular fire detection system. control panel)
System Sensor supports this position and strongly recommends that the user 2. Three #10 sheet metal screws for mounting
read NFPA Standards 90A, 72, and 101. The DNR Air Duct Smoke Detectors 3. Drilling template
are listed per UL 268A. 4. One sampling tube end cap
5. One plastic exhaust tube
This device will not operate without electrical power. Fire situations may
NOTE: A DST sampling tube must be ordered to complete the installation. It
cause an interruption of power. The system safeguards should be discussed
must be the correct length for the width of the duct where it will be installed. See
with your local fire protection specialist.
Table 1 on page 3 to determine the inlet tube required for different duct widths.
This device will not sense smoke unless the ventilation system is operating
[4] DETECTOR INSTALLATION
and the cover is installed.
[4.1] VERIFY DUCT AIR FLOW DIRECTION AND VELOCITY
For this detector to function properly, it MUST be installed according to the Model DNR detectors are designed to be used in air handling systems having
instructions in this manual. Furthermore, the detector MUST be operated within air velocities of 100 to 4000 feet per minute. Duct widths from 6 inches to 12
ALL electrical and environmental specifications listed in this manual and the feet can be accommodated. Be sure to check engineering specifications to
sensor head installation manual. Failure to comply with these requirements may ensure that the air velocity in the duct falls within these parameters. If neces-
prevent the detector from activating when smoke is present in the air duct. sary, use a velocity meter (anemometer) to check the air velocity in the duct.

D R A
IN
10-D
E C - 2 018
PRINT
ED
WHEN Page 42 of 67 42 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

FIGURE 1. EXPLODED VIEW OF DUCT SMOKE DETECTOR COMPONENTS:

EXHAUST TUBE

WIRING COMPARTMENT

WIRING COMPARTMENT COVER

SAMPLING
TUBE
SOLD
SEPERATELY

SENSOR MODULE
SENSOR HEAD

NOTE: SENSOR HEAD IS ONLY


INCLUDED ON SPECIFIED MODELS. SENSOR MODULE COVER
H0569-06

[4.3.1] FOR RECTANGULAR SIDE-BY-SIDE MOUNTING CONFIGURATION:


[4.2] DETERMINE MOUNTING LOCATION AND CONFIGURATION
Center punch at (4) target centers: (2) “A” for sampling tubes and (2) “B” for
On ducts wider than 18 inches it is recommended that the detector be
the rectangular configuration mounting tabs as shown on mounting template.
mounted downstream of a bend, obstruction in the duct, or the supply or
Drill pilot holes at target “A” centers and cut two 1.375 inch diameter holes
return air inlet.
using a 13⁄8-inch hole saw or punch. Drill .156 inch diameter holes using a 5⁄32
Exception: Installation of duct detectors can be on or within a commercial inch drill at target “B” centers.
packaged rooftop heating and air-conditioning system, fire/smoke dampers
and economizers. They may be mounted in either the supply and/or return [4.3.2] FOR SQUARE TOP-OVER-BOTTOM MOUNTING CONFIGURATION:
Center punch at (4) target centers: (2) “A” for sampling tubes and (2) “C” for
air section as determined by local code.
the square configuration mounting tabs as shown on mounting template. Drill
Once a suitable location is selected, determine if the detector is to be mounted pilot holes at target “A” centers and cut two 1.375 inch diameter holes using
in a side-by-side “rectangular” configuration or a top-over-bottom “square” a 13⁄8-inch hole saw or punch. Drill .156 inch diameter holes using a 5⁄32 inch
configuration as shown in Figure 2. If mounting in the square configuration, drill at target “C” centers. If desired, drill an additional .156 inch hole at the
remove the rear attachment screw, rotate the unit at hinge, and replace the location of one of the mounting tabs on the lower housing.
screw into the new attachment hole as shown in Figure 2. Do NOT remove
[4.4] SECURE THE DUCT DETECTOR TO THE DUCT
the hinge screw during this process. Final installation approval shall be based
upon passing differential pressure and smoke entry tests described in the Use two (rectangular configuration) or three (square configuration) of the pro-
Measurement Tests section. vided sheet metal screws to screw the duct detector to the duct.
FIGURE 2: CAUTION: Do not overtighten the screws.
REMOVE SCREW AND PIVOT REPLACE SCREW [5] SAMPLING TUBE INSTALLATION
DETECTOR AS SHOWN BELOW. TO SECURE DETECTOR [5.1] SAMPLING TUBE SELECTION
IN PLACE.
The sampling tube must be purchased separately. Order the correct length,
as specified in Table 1, for width of the duct where it will be installed. The
sampling tube length must extend at least 2/3 across the duct width for optimal
performance.
The sampling tube is always installed with the air inlet holes facing into the
air flow. To assist proper installation, the tube’s connector is marked with an
arrow. Make sure the sampling tube is mounted so that the arrow points into
the airflow as shown in Figure 3. Mounting the detector housing in a vertical
orientation is acceptable provided that the air flows directly into the sam-
pling tube holes as indicated in Figure 3. The sampling tube and exhaust tube
can be mounted in either housing connection as long as the exhaust tube is
H0550-00 mounted downstream from the sampling tube.
[4.3] DRILL THE MOUNTING HOLES
Remove the paper backing from the mounting template supplied. Affix the
template to the duct at the desired mounting location. Make sure the template
lies flat and smooth on the duct.

D R A
IN
10-D
E C - 2 018
PRINT
ED
WHEN Page 43 of 67 43 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

TABLE 1. SAMPLING TUBES RECOMMENDED FOR FIGURE 4.


DIFFERENT DUCT WIDTHS:
Outside Duct Width Sampling Tube Recommended*
12˝
Up to 1 ft. DST1 1 4

1 to 2 ft. DST1.5
2 to 4 ft. DST3
4 to 8 ft. DST5 2˝
8 to 12 ft. DST10 (2-piece)

*Must extend a minimum of 2⁄3 the duct width


3 4
/˝ DETECTOR
HOLE
FIGURE 3. AIR DUCT DETECTOR SAMPLING TUBE:
H0215-00

SAMPLING TUBE ENDCAP NOTE: Air currents inside the duct may cause excessive vibration, especially
when the longer sampling tubes are used. In these cases, a 3 inch floor flange
(available at most plumbing supply stores) may be used to fasten the sam-
pling tube to the other side of the duct. When using the flange/connector
mounting technique, drill a 1 to 1 ¼ inch hole where the flange will be used
[5.3] MODIFICATIONS OF SAMPLING TUBES
There may be applications where duct widths are not what is specified for the
installation. In such cases, it is permissible to modify a sampling tube that is
ARROW MUST FACE AIR FLOW longer than necessary to span the duct width.
INTO AIR FLOW DIRECTION
Use a 0.193-inch diameter (#10) drill and add the appropriate number of holes
H0551-00
so that the total number of holes exposed to the air flow in the duct is 10 to 12.
Space the additional holes as evenly as possible over the length of the tube.
CAUTION: The sampling tube end cap, included with the detector, is critical CAUTION: This procedure should only be used as a temporary fix. It is not
to proper operation of the duct smoke detector. The end cap is needed to intended as a permanent substitute for ordering the correct length tubes.
create the proper air flow to the sensor of the duct smoke detector. Once any
sampling tube length adjustments are made, plug the end of the sampling [5.4] REMOTE SAMPLING TUBE INSTALLATION
tube with the provided end cap. The detector arrangement can also incorporate the remote mounting of the
sampling tube and/or exhaust tube. In this case both the detector, sampling
A plastic exhaust tube is included with the unit to be installed if needed. In- tube and exhaust tube (if included) should be rigidly mounted to withstand
stall into the housing connection that is downstream from the sampling tube the pressure and vibrations caused by the air velocity. The location of the
connection. The exhaust tube can be installed from the front of the detector detector’s sampling tube should be such that there is uniform airflow in the
or the back. A longer 1 foot exhaust tube, model ETX, is available as an acces- cross section area.
sory in cases where the molded exhaust tube does not extend at least 2 inches
into the duct. Pressure differential across the sampling and exhaust ports in the detector hous-
ing shall be verified to be between 0.01 and 1.11 inches of water. Do so by mea-
[5.2] SAMPLING TUBE INSTALLATION suring the pressure difference between the inlet and outlet ports on the detector
1. For tubes shorter than the width of the duct, slide the sampling tube, housing using a manometer as described in the Measurement Tests sectiont of
with installed end cap, into the housing connection that meets the air- this manual.
flow first. Position the tube so that the arrow points into the airflow as
shown in Figure 3. Per NFPA sampling tubes over 3 feet long should be [6] MEASUREMENT TESTS
supported at the end opposite of the duct detector. In ducts wider than 8 [6.1] AIR FLOW
feet, work must be performed inside the duct to couple the other section The DNR is designed to operate over an extended air speed range of 100 to
of the sampling tube to the section already installed using the ½ inch 4000 FPM. To verify sufficient sampling of ducted air, turn the air handler on
conduit fitting supplied. Make sure that the holes on both sections of the and use a manometer to measure the differential pressure between the two
air inlet sampling tube are lined up and facing into the airflow. sampling tubes. The differential pressure should measure at least 0.01 inches
of water and no more than 1.11 inches of water. Because most commercially
2. For tubes longer than the width of the air duct, the tube should extend
available manometers cannot accurately measure very low pressure differen-
out of the opposite side of the duct. Drill a ¾ inch hole in the duct op-
tials, applications with less than 500 FPM of duct air speed may require one
posite the hole already cut for the sampling tube. Ensure that the sam-
of the following: 1) the use of a current-sourcing pressure transmitter (Dwyer
pling tube is angled downward from the duct smoke detector to allow for
Series 607) or 2) the use of aerosol smoke, see below for test descriptions.
moisture drainage away from the detector. The sampling tube should
FIGURE 5. PROCEDURE FOR VERIFYING AIR FLOW:
be angled at least 1⁄4” downward for every 12” of duct width per Figure
TO SAMPLING TUBE
4.There should be 10 to 12 holes spaced as evenly as possible across the TO EXHAUST TUBE
width of the duct. If there are more than 2 holes in the section of the tube
extending out of the duct, select a shorter tube using Table 1. Otherwise,
HIGH LOW
trim the tube to leave approximately 1 to 2 inches extending outside the DIFFERENTIAL
PRESSURE
duct. Plug the end with the end cap and tape closed any holes in the TRANSMITTER
MODEL #607-01
protruding section of the tube. Be sure to seal the duct where the tube
15 TO 36
protrudes. VDC SUPPLY
9 VOLT
BATTERY
1000 OHM 5% 9 VOLT
BATTERY
1 WATT RESISTOR 9 VOLT
BATTERY

VOLT METER FLUKE


MODEL 87 OR
EQUIVALENT
H0163-01
+ –

D R A
IN
10-D
E C - 2 018
PRINT
ED
WHEN Page 44 of 67 44 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

[6.2] LOW FLOW AIR FLOW TEST USING DWYER SERIES 607 [8] VERIFICATION OF OPERATION
DIFFERENTIAL PRESSURE TRANSMITTER [8.1] INSTALL THE COVER
Verify the air speed of the duct using an anemometer. Air speed must be at Install the covers making sure that the cover fits into the base groove. Tighten
least 100 FPM. Wire the Dwyer transmitter as shown in Figure 5. Connect the the seven screws that are captured in the covers. Note that the cover must be
leads of the meter to either side of the 1000: resistor. Allow unit to warm up properly installed for proper operation of the sensor.
for 15 seconds. With both HIGH and LOW pressure ports open to ambient air,
[8.2] POWER THE UNIT
measure and record the voltage drop across the 1000: resistor (measurement
Activate the communication line on terminals COM + and COM –.
1), 4.00 volts is typical. Using flexible tubing and rubber stoppers, connect the
HIGH side of the transmitter to the sampling tube of the duct smoke detec- [8.3] DETECTOR CHECK
tor housing, and the LOW side of the transmitter to the exhaust tube of the Standby – If programmed by the system control panel, look for the presence of
duct smoke detector housing. Measure and record the voltage drop across the the flashing LEDs through the transparent housing cover. The LED will flash
1000: resistor (measurement 2). Subtract the voltage recorded in measure- with each communication.
ment 1 from the voltage recorded in measurement 2. If the difference is greater Trouble – If programmed by the system control panel and the detector LEDs
than 0.15 volts, there is enough air flow through the duct smoke detector for do not flash, then the detector lacks power (check wiring, missing or improp-
proper operation. erly placed cover, panel programming, or power supply), the sensor head is
[7] FIELD WIRING; INSTALLATION GUIDELINES missing (replace), or the unit is defective (return for repair).
All wiring must be installed in compliance with the National Electrical Code [8.4] DUCT SMOKE DETECTOR TEST & MAINTENANCE PROCEDURES
and the local codes having jurisdiction. Proper wire gauges should be used. Test and maintain duct smoke detectors as recommended in NFPA 72. The
The conductors used to connect smoke detectors to control panels and acces- tests contained in this manual were devised to assist maintenance personnel
sory devices should be color-coded to prevent wiring mistakes. Improper con- in verification of proper detector operation.
nections can prevent a system from responding properly in the event of a fire.
Before conducting these tests, notify the proper authorities that the smoke
For signal wiring (the wiring between detectors or from detector to auxiliary detection system will be temporarily out of service. Disable the zone or system
devices), it is usually recommended that single conductor wire be no smaller under test to prevent unwanted alarms.
than 18 gauge. The duct smoke detector terminals accommodate wire sizes up
to 12 gauge. Flexible conduit is recommended for the last foot of conduit; solid [8.4.1] TEST THE UNIT
conduit connections may be used if desired. 1. M02-04-00 Magnet Test (not included) – This sensor can be function-
ally tested with a test magnet. The test magnet electronically simulates
Duct smoke detectors and alarm system control panels have specifications for smoke in the sensing chamber, testing the sensor electronics and connec-
Signaling Line Circuit (SLC) wiring. Consult the control panel manufacturer’s tions to the control panel.
specifications for wiring requirements before wiring the detector loop.
2. Remote Test Accessory – The use of a remote accessory for visible indica-
[7.1] WIRING INSTRUCTIONS tion of power and alarm is recommended.
Disconnect power from the communication line before installing the DNR Verify system control panel alarm status and control panel execution of all
duct smoke detector. intended auxiliary functions (i.e. fan shutdown, damper control, etc.).
The DNR detectors are designed for easy wiring. The housing provides a ter- Two LEDs on the sensor are controlled by the panel to indicate sensor
minal strip with clamping plates. Wiring connections are made by sliding the status. Coded signals, transmitted from the panel, can cause the LEDs
bare end under the plate, and tightening the clamping plate screw. See Figure to blink, latch on, or latch off. Refer to the control panel technical docu-
6 on below for system wiring. mentation for sensor LED operation and expected delay to alarm.
FIGURE 6. SYSTEM WIRING DIAGRAM FOR DNR: [8.4.2] THE DETECTOR MUST BE RESET BY THE SYSTEM CONTROL PANEL
[8.4.3] SMOKE RESPONSE TEST
To determine if smoke is capable of entering the sensing chamber, visually
identify any obstructions. Close cover tamper terminals on sensor side of
COMM. housing to ensure communication to panel. Plug the exhaust and sampling
LINE (+)
tube holes to prevent ducted air from carrying smoke away from the detector
COMM.
LINE head, then blow smoke such as cigarette, cotton wick, or punk directly at the
COMM. head to cause an alarm. REMEMBER TO REMOVE THE PLUGS AFTER THIS
LINE (–) TEST, OR THE DETECTOR WILL NOT FUNCTION PROPERLY.
[8.4.4] SMOKE ENTRY TEST USING AEROSOL SMOKE
This test is intended for low-flow systems (100-500 FPM). If the air speed is
UL/FM LISTED 1ST 2ND greater than 500 FPM, use a conventional manometer to measure differential
CONTROL DETECTOR DETECTOR pressure between the sampling tubes, as described under Measurement Tests
PANEL IN LOOP IN LOOP on Page 3.
HO572-00
[7.2] SET THE ADDRESS Drill a ¼-inch hole 3 feet upstream from the duct smoke detector. With the air
Set the desired address on the sensor head code wheel switches. on the back handler on, measure the air velocity with an anemometer. Air speed must be
of the sensor head. at least 100 FPM. Spray aerosol smoke* into the duct through the ¼-inch hole
FIGURE 7. ROTARY ADDRESS SWITCHES for five seconds. Wait two minutes for the duct smoke detector to alarm. If the
BREAKAWAY STOP duct smoke detector alarms, air is flowing through the detector. Remove the
duct smoke detector cover and blow out the residual aerosol smoke from the
chamber and reset the duct smoke detector at the panel. Use duct tape to seal
the aerosol smoke entry hole. Remember to replace the cover after the test or
the detector will not function properly.
*Aerosol smoke can be purchased from Home Safeguard Industries at home-
safeguard.com, model 25S Smoke Detector Tester, and Chekkit Smoke Detector
HO112-00 Tester model CHEK02 and CHEK06 available from SDi. When used properly,
the canned smoke agent will cause the smoke detector to go into alarm. Re-
Note: Some panels support extended addressing. In order to set the sensor fer to the manufacturer’s published instructions for proper use of the canned
above the address number 99 on compatible systems, carefully remove the smoke agent.
stop on the left hand rotary switch with pliers as shown in Figure 7.
NOTE: Verify sensor cover gasket is properly seated on cover prior to cover
installation

D R A
IN
10-D
E C - 2 018
PRINT
ED
WHEN Page 45 of 67 45 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

The RTS451/RTS151/RTS451KEY/RTS151KEY Remote Test Station facilitates


CAUTION test of the alarm capability of the duct smoke detector. These accessories pro-
Canned aerosol simulated smoke (canned smoke agent) formulas will vary by vide the stimulus to initiate an alarm condition at the detector. The DNR duct
manufacturer. Misuse or overuse to these products may have long term adverse smoke detector must be reset by the system control panel.
effects on the smoke detector. Consult the canned smoke agent manufacturer’s
[11.1] OPTION 1:
published instructions for any further warnings or caution statements.
REMOTE TEST USING SENSOR WITH REMOTE TEST CAPABILITY
(WITHOUT A TEST COIL):
[9] DETECTOR CLEANING PROCEDURES
A sensor with suffix "R" is available for use inside the DNR. Suffix "R"
Notify the proper authorities that the smoke detector system is undergoing
represents a head with Remote Test Capability. Using this head inside the
maintenance, and that the system will temporarily be out of service. Disable
DNR eliminates the need for a test coil when wired to a RTS451/RTS151/
the zone or system undergoing maintenance to prevent unwanted alarms and
RTS451KEY/RTS151KEY Remote Test Station.
possible dispatch of the fire department.
To install the RTS451/RTS151/RTS451KEY/RTS151KEY, using the sensor with
[9.1] DETECTOR SENSOR
remote test capability connect the device as shown in Figure 9; wire runs must
1. Remove the sensor to be cleaned from the system.
be limited to 25 ohms or less per interconnecting wire.
2. Remove the sensor cover by pressing firmly on each of the four removal
tabs that hold the cover in place. NOTE: Resistor assembly must be in place between RA+ and OUT+
3. Vacuum the screen carefully without removing it. If further cleaning is inside the DNR for Remote Test function to operate.
required continue with Step 4, otherwise skip to Step 7. FIGURE 9. RTS451/RTS451KEY/RTS151/RTS151KEY USING
4. Remove the chamber cover/screen assembly by pulling it straight out. SENSOR WITH REMOTE TEST CAPABILITY
5. Use a vacuum cleaner or compressed air to remove dust and debris from
the sensing chamber. TEST COIL +
6. Reinstall the chamber cover/screen assembly by sliding the edge over the RTS451/RTS451KEY
TEST COIL – RTS151/RTS151KEY
sensing chamber. Turn until it is firmly in place.
7. Replace the cover using the LEDs to align the cover and then gently COMM +
1
pushing it until it locks into place.
OUT (CONV ONLY) +
8. Reinstall the detector. 2
COMM –
[9.2] REINSTALLATION 3 JUMPER
1. Reinstall the detector in its housing. RA/RTS –
2. Restore system power.
RA + 4
3. Perform Detector Check.
4. Notify the proper authorities testing has been completed and the smoke RTS + 5
detector system is back in operation.
[10] SENSOR REPLACEMENT H0633-00
1. Remove the sensor head by rotating counterclockwise.
2. Pull gently to remove it. [11.2] OPTION 2:
3. To replace the sensor head, align the mounting features and rotate clock- REMOTE TEST USING A TEST COIL:
wise into place. The use of a remote test station requires the installation of an accessory
[11] OPTIONAL ACCESSORIES coil, part number DCOIL, sold separately.
Optional accessories include RA100Z, RTS451/RTS151 and RTS451KEY/
RTS151KEY. 1) Install DCOIL in housing pocket insuring that arrow is pointing toward detector
2) Install DCOIL mounting screw
NOTE: Ensure blue wire always remains connected to RA+ on the field 3) Connect each DCOIL lead to a Test Coil Terminal
connector side of the terminal block. See Figure 10 below for reference.

FIGURE 8. WIRING DIAGRAM FOR DNR TO RA100Z:


FIGURE 10. DNR USING A TEST COIL
+ RA
(+)
RA100Z

– RA
(-)

REMOTE ALARM LED


OPTION 1 PER UNIT

H0570-05

Note: If using RA100Z, ensure that jumper is removed.

DCOIL
TEST COIL SCREW
H0561-01
TEST COIL TERMINALS

D R A
IN
10-D
E C - 2 018
PRINT
ED
WHEN Page 46 of 67 46 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

FIGURE 11. WIRING DIAGRAM FROM DNR TO RTS451/RTS151/


RTS451KEY/RTS151KEY USING A TEST COIL:

TEST COIL +
4 5
* EXTERNAL
TEST COIL – (-) POWER (+)
SUPPLY

COMM + 1 2 3

OUT (CONV ONLY) +


RTS451/151,
RTS451/151KEY
COMM –
REMOTE TEST STATION
RA/RTS –
LED OPTION
RA + 1 PER UNIT
10mA CURRENT DRAW
RTS +
TEST COIL OPTION
1 PER UNIT
95mA CURRENT DRAW

H0571-07

NOTE: The RTS451/151, RTS451/151KEY test coil circuit requires an


external 24 VDC power supply which must be UL listed.

[11.3] ADDITIONAL MODULE OPTION


The DNR can also accommodate a relay or control module (sold separately)
within the power board side of the housing. The relay or control module must
be listed as compatible to the fire alarm control panel.
Physical Module Mounting
1) Remove the breakaway tabs at the four corners of the module
2) Locate the module at right most corner of the power board. The upper
left corner mounting hole of the module will align with a screw boss in
the housing.
3) Install a #8×3⁄8˝ Plastite screw at the screw boss location

Note: See the corresponding module Installation Instructions for general


description, control panel compatibility, wiring and ratings.

Please refer to insert for the Limitations of Fire Alarm Systems


THREE-YEAR LIMITED WARRANTY
System Sensor warrants its enclosed product to be free from defects in materials and TX 79936, USA. Please include a note describing the malfunction and suspected cause
workmanship under normal use and service for a period of three years from date of of failure. The Company shall not be obligated to replace units which are found to be
manufacture. System Sensor makes no other express warranty for the enclosed product. defective because of damage, unreasonable use, modifications, or alterations occurring
No agent, representative, dealer, or employee of the Company has the authority to in- after the date of manufacture. In no case shall the Company be liable for any consequen-
crease or alter the obligations or limitations of this Warranty. The Company’s obligation tial or incidental damages for breach of this or any other Warranty, expressed or implied
of this Warranty shall be limited to the replacement of any part of the product which is whatsoever, even if the loss or damage is caused by the Company’s negligence or fault.
found to be defective in materials or workmanship under normal use and service during Some states do not allow the exclusion or limitation of incidental or consequential dam-
the three year period commencing with the date of manufacture. After phoning System ages, so the above limitation or exclusion may not apply to you. This Warranty gives you
Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, specific legal rights, and you may also have other rights which vary from state to state.
send defective units postage prepaid to: Honeywell, 12220 Rojas Drive, Suite 700, El Paso

D R A
IN
10-D
E C - 2 018
PRINT
ED
WHEN Page 47 of 67 47 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1





ManualUserHeatDetector:
NFXIͲTFIX78







ManuelUtilisateurdeDétecteurde
chaleuradressable:
NFXIͲTFIX78




D R A
IN
10-D
E C - 2 018
PRINT
ED
WHEN Page 48 of 67 48 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

NFX(I)-TDIFF NFX(I)-TFIX58 NFX(I)-TFIX78


DOP-IFD146 NFX-TDIFF EN54-5: 2000 Class A1R
DOP-IFD147 NFXI-TDIFF EN54-5: 2000 Class A1R, EN54-17: 2005
DOP-IFD148 NFX-TFIX58 EN54-5: 2000 Class A1S
102 mm 0786 DOP-IFD149 NFXI-TFIX58 EN54-5: 2000 Class A1S, EN54-17: 2005
09 DOP-IFD150 NFX-TFIX78 EN54-5: 2000 Class BS
DOP-IFD151 NFXI-TFIX78 EN54-5: 2000 Class BS, EN54-17: 2005
B501AP
80°C Pittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy
61 mm

-30°C 88 g I56-3391-004

INSTALLATION AND MAINTENANCE INSTRUCTIONS CAUTION


ENGLISH FOR THE NFX/NFXI THERMAL FIRE SENSORS Dust covers help to protect units during shipping and when first installed.
They are not intended to provide complete protection against contamination
GENERAL DESCRIPTION therefore sensors should be removed before construction, major re-decoration
7KH1);1);,LQWHOOLJHQWWKHUPDOVHQVRUVDUHSOXJLQW\SHÀUHVHQVRUVWKDWXVHDVLQJOH or other dust producing work is started. Dust covers must be removed before
thermistor sensing circuit to provide early warning of developing fires, together with system can be made operational.
DGGUHVVDEOHFRPPXQLFDWLRQZLWKWKHÀUHSDQHO MAINTENANCE
The NFX-TDIFF/NFXI-TDIFF provides fixed 58 oC and rate-of-rise (10 oC/minute) Before cleaning, disable the system to prevent unwanted alarms:
temperature sensing (Class A1R). 1. Remove the sensor to be cleaned from the system.
7KH1);7),;1);,7),;SURYLGHVÀ[HGoC temperature sensing (Class A1S). 2 Use a vacuum cleaner and/or clean, compressed air to remove dust and debris from the
7KH1);7),;1);,7),;SURYLGHVÀ[HGoC high temperature sensing (Class BS). thermistor and sensor cover.
3. Replace the sensor into the base.
7KHVHVHQVRUVDUHGHVLJQHGIRURSHQDUHDSURWHFWLRQDQGPXVWRQO\EHFRQQHFWHGWRÀUH
4. When all sensors have been cleaned, restore power to the loop and test the sensor(s)
panels that use a compatible proprietary communication protocol for monitoring and control.
as described under TESTING.
The NFXI sensors contain an isolator, if installing this version check the panel documentation
for details of how many isolators can be used on a loop. TESTING
Sensors must be tested after installation and following periodic maintenance. Disable the
Two LEDs on each sensor light to provide a local 360o visible sensor indication (operation of
zone or system undergoing maintenance to prevent unwanted alarms.
LEDs are dependent on panel). Remote LED indicator capability is available as an optional
accessory wired to the standard base terminals (again dependent on panel). Test the sensors as follows:
SPECIFICATIONS Magnet Method
Operating Voltage Range: 15 to 32 VDC (15 to 28 for NFXI isolated) 1. Test the sensor by positioning the test magnet (model M02-24-optional) against the
Max. Standby Current (no comm.): 160 —A @24 V and 25oC sensor body approximately 2cm from LED 1, indicated by a mark on the sensor cover
(comm. LED blink enabled - 5 sec) 300 —A @24 V and 25oC DVVKRZQLQÀJXUH
(Read 16 sec. LED blink 8 sec) 190 —A @24 V and 25oC 2. Both LED’s on the sensor should latch into alarm within 30 seconds, activating the control
add 50 —A for NFXI isolated models panel.
Max. Alarm Current (LED on): add 3.5 mA @ 24 V and 25oC
Operating Humidity Range: 10% to 93% Relative Humidity, Non-Condensing
Figure 2: Test Magnet Position Test
Isolator Characteristics (NFXI Versions Only) Magnet
Maximum rated continuous current with the isolator closed (Ic max): 1A
Maximum rated isolator current (under short circuit) (Is max): 1A
Max. leakage current (IL max) with the isolator open (isolated state): 15mA
Max. series impedance with the isolator closed (Zc max): 170 m ohm at 15Vdc
7KHVHVHQVRUVKDYHEHHQ,QGHSHQGHQWO\WHVWHGDQGFHUWLÀHGVHH&(WDEOH
EN54-5 states that Class A1 has a maximum application temperature of 50oC, Class B has Mark on Cover
a maximum application temperature of 65oC. LED 1
LED 2
WIRING GUIDE
Refer to the installation instructions supplied with the plug-in sensor bases for wiring details.
All bases are provided with terminals for power and an optional Remote Indicator.
Note 1: All wiring must conform to applicable local and national codes and regulations.
Note 2: Verify that all sensor bases are installed and that polarity of the wiring is correct at Control Panel Method
each base.
1. Test the sensitivity from the system control panel.
WARNING
Disconnect loop power before installing sensors. Notify proper authorities. Direct Heat Method (Hair dryer of 1000-1500 watts).
1. Direct the heat toward the sensor from its side. Hold the heat source about 15 cm away
SENSOR INSTALLATION
to prevent damage to the cover during testing.
 6HWWKHVHQVRUDGGUHVV VHHÀJXUH E\WXUQLQJWKHWZRURWDU\VZLWFKHVRQWKHXQGHUVLGH 2. The LEDs on the sensor should light when the temperature at the sensor reaches
of the sensor, selecting a number between 01 and 159. (Note: The number of addresses 58°C/78°C (dependent on the model being tested).
available will be dependent on panel capability, check the panel documentation for 3. Reset the sensor at the system control panel.
information on this). Record the address on the label attached to the base. After completion of the test notify the proper authorities that the system is operational.
WARNING
Figure 1: Rotary Address Switches
LIMITATIONS OF THERMAL SENSORS
Fire sensors must be used in conjunction with compatible equipment.
Heat sensors are designed to protect property, not life. They do not provide early
ZDUQLQJRIÀUHDQGFDQQRWGHWHFWVPRNHJDVFRPEXVWLRQSDUWLFOHVRUÁDPH
Heat sensors do not always detect fires because the fire may be a slow smouldering,
ORZKHDWW\SH SURGXFLQJVPRNH RUEHFDXVHWKH\PD\QRWEHQHDUZKHUHWKHÀUHRFFXUV
or because the heat of the fire may bypass them. Consideration must be made of the
; ; environment when selecting heat sensors.
Fire sensors cannot last forever. Fire sensors contain electronic parts. Even though
2. Insert the sensor into the base and rotate it clockwise until it locks into place. sensors are made to last over 10 years, any of these parts could fail at any time. Therefore,
3. After all the sensors have been installed, apply power to the system. WHVW\RXUÀUHGHWHFWLRQV\VWHPDWOHDVWVHPLDQQXDOO\7DNLQJFDUHRIWKHÀUHGHWHFWLRQ
4. Test the sensor as described under TESTING. V\VWHP\RXKDYHLQVWDOOHGZLOOVLJQLÀFDQWO\UHGXFH\RXUSURGXFWOLDELOLW\ULVNV
5. Reset the sensor by communication command from the panel.
Tamper-Resistance.

D R A
These sensors includes a feature that, when activated, prevents removal of the sensor from
the base without the use of a tool. Refer to the installation instructions for the sensor base

IN
10-D
E C 018
for details of how to use this feature.
- 2
INTED
EN PR
NTR O L L ED WH
N200-203-00 Page 49 of 67 49 / 67
I56-3391-004
NCO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1





ManualUserCableSpaceHeatDetector:
TMP2ͲDͲCͲRͲ1A







ManuelUtilisateurdeDétecteurde
chaleurmécanique:
TMP2ͲDͲCͲRͲ1A




D R A
IN
10-D
E C - 2 018
PRINT
ED
WHEN Page 50 of 67 50 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

NOTIFIER by Honeywell HEAT DETECTOR TMP2 Rev. 1.0 Del 20/07/07

HEAT DETECTOR TMP

ISTRUZIONI D’USO OPERATING INSTRUCTIONS

Descrizione Description
I rilevatori termovelocimetrici serie TMP sono costituiti da un
circuito elettronico per il condizionamento del segnale generato dal The TMP2 series of overheat detectors, includes an electronic
trasduttore. circuit for signal conditioning generated by the transducer.
The electrical signal of the transducer is transformed into an
Il segnale elettrico del trasduttore è trasformato in un’uscita engineered output with different interface solutions.
ingegnerizzata con differenti possibilità di collegamento. The electronic card, reduced to the minimum size, is made using
La scheda elettronica, di ridotte dimensioni, è realizzata utilizzando SMT technology and placed directly into the unit probe.
la tecnologia SMT, e montata direttamente all’interno della sonda.

Features
Caratteristiche
Di grande affidabilità e lunga durata. High reliability, dependable long-life.
Immune alle interferenze elettromagnetiche, minimizzando la High Immunity to EMI disturbances and virtually eliminate false
possibilità di falsi allarmi. alarms.
E’ dotato di due livelli di allarme nel range da –20° a 110° C. Two temperature set-point levels setting from -20°C to 110°C.
Alimentazione 10-30 Vdc Supply Voltage 10-30 Vdc
Assorbimento 200 uA in condizioni normali Supply current 200 uA in normal condition
20 mA in condizioni normali 20 mA in alarm condition
Fusibile 63 mA Supply fuse 63 mA
Cavo 2 conduttori. Cable Type 2 wires cable.
Test diagnostico automatico Automatic self diagnosis

Typical application
Applicazioni
TMP2 detectors are particularly suitable in commercial and
I rilevatori TMP sono particolarmente adeguati a proteggere industrial plants in presence of flammable or corrosive elements or
ambienti con pericolo di esplosione, come ad esempio quelli con condensing steams.
presenza di elementi corrosivi o vapori di condensazione. Suitable for use in explosive atmospheres.
Impianti commerciali e industriali Hazard material stores.
Atmosfere esplosive Extraction ducts.
Immagazzinaggio di materiali pericolosi
Condotti di estrazione.

TMP detectors are designed according to European


I sensori TMP sono progettati in base alla norma Europea requirements EN54 and ATEX directive.
EN54 e alle direttive ATEX

1
NOTIFIER by Honeywell Via Grandi, 22 – 20097 SAN DONATO MILANESE (MI)
Tel.: +39 02 51897.1 - Fax: +39 02 5189730 - E-mail: notifier.milano@notifier.it

D R A
IN
10-D
E C - 2 018
PRINT
ED
WHEN Page 51 of 67 51 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

NOTIFIER by Honeywell HEAT DETECTOR TMP2 Rev. 1.0 Del 20/07/07

Collegamenti elettrici Interconnecting cable guidelines

Per il collegamento del sensore con l'unità di alimentazione, si consiglia The TMP2 heat detector requires an interconnecting cable having two
l'uso di cavi schermati. conductors. Note that the use of shielded cables is recommended .
Nel caso in cui si usino più spezzoni di filo, per realizzare il cablaggio, Should more than one strand of wire be used in the wiring be sure that
assicurarsi che vi sia continuità anche sulla schermatura dei cavi e le the cable screen is continuous and that the conductors are soldered at
giunzioni tra i conduttori dovranno essere stagnate. the joints.
Sempre in merito alla schermatura si ricorda che questa deve essere Furthermore it must be remembered that the protective shielding must
collegata a terra unicamente dal lato unità di controllo o gruppo di be earthed only on the side of the control unit or power supply, and
alimentazione, mentre non dovrà mai essere collegata sui rilevatori. must never be connected to the detector.
Si sconsiglia l'uso di capicorda, o comunque la realizzazione di The use of terminal leads is recommended, otherwise the joints on the
giunzioni sui cavi di alimentazione mediante dispositivi di serraggio o a power cable must be clamped with flat tab connectors or soldered.
crimpare. It is best to avoid connection, to the same power source used for the
Evitare di collegare, alla stessa fonte di alimentazione utilizzata per i detectors, inductive loads could generate ‘noises’ on the power supply
rilevatori, carichi induttivi o capacitivi in grado di generare transienti to the system.
sull’alimentazione del sistema. In any case the use of auxiliary winding on the main power transformer
Nel caso sia necessaria una fonte di alimentazione di servizio si is recomended for supply suppression devices, actuators, sounders or
consiglia l’utilizzo di un avvolgimento separato sul secondario del other devices.
trasformatore di alimentazione.

Collegamento in loop con resistenza di fine linea Interconnection references for current loop with end of line resistor

Loop +
Loop -

Assicurarsi che l'impianto elettrico disponga di una buona messa a terra. The cable screen must be connected to safety earth in safe area.

Assegnazione cavi sonda TMP2 TMP2 probe cable assignment


Cavo Marrone morsetto + Brown cable Terminal block +
Cavo Bianco morsetto - White cable Terminal block -

Il rilevatore viene calibrato in fabbrica in base ai diversi livelli di The sensor is calibrated in the factory specifically for the
temperatura richiesti dal cliente. temperature levels requested by the client.
L’installazione e il mantenimento devono essere effettuati Installation and maintenance must be carried out by suitably
esclusivamente da personale qualificato. skilled and competent personell only.

Mantenimento Maintenance
Si raccomanda di testare il sensore ogni sei mesi. It is on-the-less good practice to check ever six months the
Prima di iniziare qualsiasi processo di verifica, è necessario response of the sensor.
informare tutto il personale responsabile della sicurezza in modo Before starting any verification procedures all personnell
che tutti i sistemi di allarme che possano essere connessi al responsible for security should be informed and all alarm
sistema, vengano disconnessi. systems which might be connected to the system should be
switched off.

NOTA: Se desiderate ulteriori informazioni su questo NOTE: If you need more information of this product, you
prodotto, visitate il nostro sito internet www.notifier.it can visit our web site: www.notifier.it

2
NOTIFIER by Honeywell Via Grandi, 22 – 20097 SAN DONATO MILANESE (MI)
Tel.: +39 02 51897.1 - Fax: +39 02 5189730 - E-mail: notifier.milano@notifier.it

D R A
IN
10-D
E C - 2 018
PRINT
ED
WHEN Page 52 of 67 52 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1





ManualUserIntrinsicallySafeDetector:
IDXͲ751







ManuelUtilisateurdeDétecteurà
sécuritéintrinsèque:
IDXͲ751




D R A
IN
10-D
E C - 2 018
PRINT
ED
WHEN Page 53 of 67 53 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

IDX-751 AE SENSOR
COVER
0832
0832-CPD-0201

102 mm
COVER
60°C REMOVAL TABS
B501AP 40°C
47 mm SENSOR
SCREEN
112.5g -20°C -20°C
T4 T5

Figure 1: SENSING
CHAMBER
Cleaning the Sensor
INSTALLATION AND MAINTENANCE INSTRUCTIONS
EN FOR MODEL IDX-751 AE INTRINSICALLY SAFE
INTELLIGENT PHOTO ELECTRONIC SMOKE SENSOR

GENERAL DESCRIPTION
Model IDX-751 is an intrinsically safe smoke detector that combines a photo electronic 7. Re-install the sensing chamber cover by aligning the arrow moulded on the cover
sensing chamber with analogue addressable communications and is for use in hazardous with the arrow printed on the circuit board and sliding the cover over the chamber,
areas where potentially explosive atmospheres are likely to arise. The classification of gently pressing it home until it snaps into place.
equipment required must be confirmed with your responsible authority. The sensor 8. Re-install the sensing chamber screen by sliding it over the sensing chamber.
communicates via a dedicated Galvanic Isolator Barrier with an IMX-1 / IST200 Translator Rotate the screen until the locating tabs on the bottom rim locate in the cutouts in
Module which relays the data to the Control Panel. Rotary decade switches are the chamber base, and the top of the screen is flush with the top of the chamber.
provided for setting the sensor address. 9. Re-install the sensor cover. Use the cover removal tabs and LEDs to align the cover
Two LEDs on each sensor provide a local 360° visible sensor indication. with the sensor. Snap the cover into place.
10. When all sensors have been cleaned, restore power to the loop and test the
SPECIFICATIONS sensor(s) as described under TESTING.
Operating Voltage Range: 15 to 24 VDC
Max. Avg. Standby Current: 220 —A @20 VDC (One communication every 5 CAUTION
sec. With LED blink enabled) The Detector has a plastic enclosure that may present an electrostatic risk and
Max. Alarm Current (LED on): 3 mA @ 24 VDC must not be installed in a position where it may be subject to a high dust-laden
Operating Humidity Range: 10% to 93% Relative Humidity, Non-Condensing air flow. Clean only with a damp cloth and do not rub.
Intrinsic Safety Rating: Ex ia IIC T5 (40o to -20oC), T4 (60o to -20 oC) TESTING
This detector has been independently tested and certified to EN54 part 7: 2000 and Sensors must be tested after installation and following periodic maintenance. Disable
BASEEFA approved for intrinsic safety. the zone or system undergoing maintenance to prevent unwanted alarms.
ACCESSORIES (Available Separately from Notifier) IMPORTANT
IMX-1 / IST200 Translator Module May drive up to 15 IDX-751 sensors If testing is carried out using non-intrinsically safe methods, it must be
Pepperl and Fuchs Y72221 Dedicated Galvanic Isolator Barrier for IDX-751 conducted outside the hazardous area.
detector (drives up to 10 IDX-751 sensors). Test the sensors as follows:
WIRING GUIDE Magnet Test Method
Refer to the installation instructions supplied with the IMX-1/ IST200 Translator Module, 1. Test the sensor by positioning the test magnet (model M02-24-optional) against the
and B501AP Base for wiring details. sensor body approximately 2cm from LED 1, indicated by a mark on the detector
Note 1: All wiring must conform to applicable local and national codes and regulations. cover as shown in figure 3.
Note 2:Verify that all sensor bases are installed and that polarity of the wiring is correct 2. Both LED’s on the detector should latch into alarm within 30 seconds, activating the
at each base. control panel.
WARNING
Disconnect loop power before installing sensors. Notify proper authorities. Figure 3: Test Magnet Position
SENSOR INSTALLATION LED 2

1. Set the sensor address (see figure 2) by turning the two rotary switches, selecting
a number between 01and 99. Record the address on the label attached to the base.
2. Insert the sensor into the base and rotate it clockwise until it locks into place.
3. After all the sensors have been installed, apply power to the system.
4. Test the sensor as described under TESTING.
5. Reset the sensor by communication command from the panel. LED 1

Mark on Cover
Figure 2: Rotary Decade Address Switch
Test Magnet

6 7 8 9 6 7 8 9
5 5
4 4 Smoke Method
3 3 1. Using generated smoke, or synthetic smoke aerosol from an approved manufacturer
2 2 such as No Climb Products Ltd, subject the detector to controlled amounts of smoke
1 0 1 0 in accordance with local codes of practice and manufacturer recommendations.
TENS UNITS
2. Both LED’s on the detector should latch into alarm within 30 seconds, activating the
Tamper-Resistance. control panel.
After completion of the test notify the proper authorities that the system is operational.
Model IDX-751 includes a feature that, when activated, prevents removal of the sensor
without the use of a tool. Refer to the installation instructions for the sensor base for WARNING
details of how to use this feature. LIMITATIONS OF SMOKE DETECTORS
CAUTION Smoke detectors must be used in conjunction with compatible equipment.
Dust covers help to protect units during shipping and when first installed. They Smoke detectors will not sense fires which start where smoke does not reach the
are not intended to provide complete protection against contamination therefore detectors.
sensors should be removed before construction, major re-decoration or other A detector may not detect a fire developing on another level of a building.
dust producing work is started. Dust covers must be removed before system Smoke detectors also have sensing limitations. Consideration must be made of the
can be made operational. environment when selecting fire detectors.
MAINTENANCE Smoke detectors cannot last forever. Smoke detectors contain electronic parts. Even
Before cleaning, disable the system to prevent unwanted alarms: though detectors are made to last over 10 years, any of these parts could fail at any
1. Remove the sensor to be cleaned from the system. time. Therefore, test your smoke detector system at least semiannually. Clean and take
2. Gently release each of the four cover removal tabs that hold the cover in place (see care of your smoke detectors regularly. Taking care of the fire detection system you
figure 1) and remove the cover. have installed will significantly reduce your product liability risks.
3. Vacuum the outside of the screen carefully without removing it.
4. Remove the sensor screen. Pull the screen straight away from the sensing chamber until

D R A
it snaps out of place.

IN
5. Remove the chamber cover by pulling it gently away from the sensing chamber until
C - 2 018
it snaps out of place.
E
10-D 6. Use a vacuum cleaner and/or clean, compressed air to remove dust and debris from
the sensing TED
chamber and sensing chamber cover.
WHE N PRIN
LLED
TRON200-51-00 Page 54 of 67 54 / 67
I56-3383-000
NCON
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

IDX-751 System Diagram


Notes:
SAFE AREA HA ARDOUS AREA 1. Any single channel shunt zener diode safety barrier or single channel of a dual channel
shunt zener diode safety barrier certified by Baseefa or any EEC approved certification
body to EEx ia IIC having the following or lower output parameters:
(See Note 2) Uz 28V Imax: out 93.3 mA Wmax: out 0.66 W
To Next In any safety barrier used, the output current must be limited by a resistor R , such that
Shunt ener
IMX-1 / Detector(s) Imax:out Uz/R. Or any of the following isolation barriers may be used:
Diode Safety
Control IST200 Barrier or P F Smart Fire Detector Isolator Type FDO-CS-Ex1.54-Y72221 (BAS00ATEX7087x)
Panel Translator Isolation One channel from: P F Smart Fire Detector Isolator Type FDO-CS-Ex2.54-Y72222
Module Barrier (see (BAS00ATEX7087X)
Note 1.) 2. The capacitance and either inductance or inductance/resistance (L/R) ratio of the cable
connected to the hazardous area terminals of barrier must not exceed the values shown
Safe area apparatus, which is 2( ) in Table 1.
unspecified except that it must not be 3. The installation must comply with the appropriate national installation requirements, e.g.
supplied from or contain under normal 3 1 (-) in the U. . to BSEN60079-14: 1997.
or abnormal conditions a source of 4. The electrical circuit in the hazardous area must be capable of withstanding an A.C. test
potential with respect to earth in excess 501AP voltage of 500 VRMS to earth or frame of the equipment, for a period of one minute without
of 253 Vrms or 253 VDC breakdown. This note does not apply when using an isolation barrier.

IMPORTANT: See IMX-1 IST200 R12-172-00, REV F


Instructions for screening information IDX-751
Smoke Detector CAUTION
II1G Ex ia IIC T5, T4
Terminals 1 and 2 ( 501AP ase) Baseefa08ATEX0278X Please refer to control panel installation instructions for specific barrier control panel
Group Capacitance Inductance L R Ratio compatibility information.
F mH H OHM
501AP Pins Connection
IIC 0.083 4.2 55 1 - Vin, - Vout
IIB 0.65 12.60 165 2 Vin, Vout
IIA 2.15 33.60 444 3 No Connection
Table 1 Table 2

0832
0832-CPD-0201 DECLARATION OF CONFORMITY

Date of Issue: 18/11/2008


Manufacturer: Pittway Tecnologica S.r.l. Via Caboto 19/3, 34147 Trieste, Italy
Product: IDX-751 AE
Mounting Bases: B501, B501AP
Description: Intrinsically safe analogue addressable optical smoke detector
We hereby declare that the product identified above meets the requirements of the of the EMC Directive 89/336/EEC
amended by 92/31/EEC, 93/68/EEC, 93/97/EEC and the directives listed below. It therefore qualifies for free movement
within markets comprising the European Union (EU) and the European Economic Area (EEA).

Directive EU Construction Products ATEX 4 EEC


Directive 106 EEC
Standard EN54-7:2000 EN6007 -0:2006, EN6007 -11:2007 and EN6007 -26:2007
Notified ody RE-LPC ASEEFA Ltd
Address Garston, Watford, WD25 XX Rockhead usiness Park, Staden Lane, u ton,
Derbyshire, SK17 R
Notified ody 0 32 11 0
Certificate 0 32-CPD-0201 aseefa0 ATEX 027 X
Rating --- II 1 G E ia IIC T5 T4Ga (-20°C Ta 40°C 60°C)

Pittway Tecnologica S.r.l.


Via Caboto 19/3

D R A Alfonso Paribelli
34147 Trieste Italy
Telephone: 39 040 9490 111
IN
10-D
E C - 2 018
PRINT
ED
Plant Manager Fax: 39 040 382137

WHEN Page 55 of 67 55 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1





ManualUserFAASTͲLTAirSampling
System:
FL2011EIandFL2022EI







ManuelUtilisateurdeDétecteurde
fuméed'aspiration:
FL2011EIandFL2022EI




D R A
IN
10-D
E C - 2 018
PRINT
ED
WHEN Page 56 of 67 56 / 67
LLED
NCONTRO
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

ENGLISH
FIRE ALARM ASPIRATION SENSING TECHNOLOGY®
QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT
MODELS FL2011EI, FL2012EI FL2022EI

44 mm

403 mm

367 mm
56 mm
DESCRIPTION 356 mm
135 mm
The LT FL20 Series is part of the Fire Alarm Aspiration Sensing
Technology® )$$67 IDPLO\)$$67LVDQDGYDQFHG¿UHGHWHFWLRQ Figure 1: Dimensions and Knock-Outs
system for use where early warning and very early warning are a
requirement. The system continuously draws air from the controlled Mechanical
environment through a series of sampling holes to monitor the
Exterior Dimensions: See Figure 1
environment for smoke particulate. Wiring: 0.5 mm² to 2 mm² max
The FL20 is the addressable version of the FAAST LT range, Maximum Single Pipe Length 100m (Classes A. B & C)
communicating with the CIE (Fire Panel) via a proprietary loop Maximum Number of Holes 18 (10 x 2.5mm, 8 x 3mm + 3mm
protocol. It is available in 3 different models: end hole - Class C)
Pipe Spec (EN54-20 Compliance): Red ABS to EN 61386
FL2011EI - Has single channel capability with one laser smoke (Crush 1, Impact 1, Temp 31)
sensor. Outside Pipe Diameter: 25mm (nom) or 27mm (nom)
Shipping Weight: 6.5kg (inc sensors)
FL2012EI - Has single channel capability with two laser smoke
sensors in a common chamber for coincidence PARTS LIST
detection.
Description Quantity
FL2022EI - Has two channel capability with two laser smoke FAAST LT unit 1
sensors in separate chambers. (one sensor for each Mounting bracket 1
channel). 3-pin Terminal block 6
This guide provides information for mounting and basic installation 4-pin Terminal block 1
using the unit’s default factory settings. For more advanced info 2-pin Terminal block 3
please see the FAAST LT Advanced Setup and Control Guide. 47 k-ohm EOL Resistor 2
Front Panel Labelling Pack 1
SPECIFICATIONS Quick Installation Guide 1
Electrical Characteristics FAAST LT Advanced Setup and Control Guide available via
Voltage Range: 18.5 - 31.5 VDC download from www.systemsensoreurope.com
Supply Current 200mA (avg); 500mA (max)
@ 24 VDC (excluding sounders) Important Note
&RPPXQLFDWLRQ/RRS6XSSO\9ROWDJH ±9'& /RRSFXUUHQW” Aspirating Smoke Detectors supplied and installed within the
900mA) EU must conform to the EU Construction Products Directive
Communication Loop Standby Current @ 24V: 900 —A max. (poll once (89/106/EEC) and the related European Product Standard EN
every 5s)  )$$67 /7 KDV EHHQ WHVWHG DQG FHUWL¿HG WR HQVXUH WKDW LW
Power Reset: 0.5s
conforms to the necessary Standards, but strict adherence to this
&RQ¿JXUDEOH,QSXW$FWLYDWLRQ7LPH V PLQ
Relay Contact Ratings 2.0 A @ 30 VDC, 0.5A @ 30 VAC instruction guide is advised to ensure that the installation meets
the requirements of the CPD Directive
Environmental Ratings
Temperature: -10°C to 55°C
Relative Humidity: 10% to 93% (non-condensing)
IP Rating: 65

D R A
IN
10-D
E C - 2 018
D200-102-00 D
INTEPR
I56-3888-202
HEN
TROL
LED W Page 57 of 67 57 / 67
NCON
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

This equipment and all associated pipe work must be installed in


accordance with all relevant codes and regulations.

PHYSICAL INSTALLATION

Front Panel Labels


7KH /7 )/ LV VKLSSHG ZLWKRXW WKH IURQW SDQHO ODEHOV ¿[HG LQ Figure 4: How to Knock Out Cable
place. This allows the installer to choose the language required Gland Holes
for the installation from the Front Panel Labelling Pack.
Figure 2 shows where the labels need to be placed:

ALARM

PREALARM

Mounting the LT FL01 to the Wall


10 10

9 9

8 8

7 7

5
6

5
INDICATES CENTRE OF ASPIRATING PIPES
4 4

3 3

2 2
SMOKE 1 1 SMOKE
LEVEL 1 LEVEL 2

MODULE 1 MODULE 2

FAULT POWER
FAULT

FAAST LT
HANGING LUGS

A FIXING HOLE FIXING HOLE


USE FOR PLUMB-LINE
FLOW

HIGH

Figure 5: Mounting Bracket


T

FIL
INPU

FLOW
OR
LOW

SOUN

TER
SYSTEM / DISABLE
ASPIRATOR

TEMPERATU
SENS

DER
RE

Figure 2: Placing the Front Panel Labels

When label A is in place, remove the protector from the bottom of


90 mm
the clear cover to stick the cover down, as shown in Figure 3: 99 mm

41 59 mm
mm

Figure 3: Remove Backing to


POSITION OF BRACKET
Stick Cover Down

PLUMB LINE
329 mm

Cable Access
Knock out cable gland holes where required. The
location of the cable gland holes is shown in Figure 1,
represented by the icon: OUTER DIMENSION OF UNIT BASE OUTLINE

212 mm 144 mm

Figure 6: Fasten the mounting bracket to the wall

D R A
IN
10-D
E C - 2 018
D200-102-00 D
INTEPR
I56-3888-202
HEN
TROL
LED W Page 58 of 67 58 / 67
NCON
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

Figure 7: Sequence (1 to 9) to Mount the Detector on the Bracket 3LSH+ROH&RQ¿JXUDWLRQ


Figure 8 below shows the pipe holes available on the unit. Each
7a unit has 2 pipe holes per channel (so if installing a 1 channel unit,
99 mm 1 holes 3 and 4 do not function). Use Table 1 to locate the holes
required for the installation:
41
mm
1 2 3 4

Figure 8: Pipe Holes

7b
4 90 mm
5 6

o
0.00
Table 1: Pipe Holes Used for Each FAAST LT Model
FAASTLTMODEL INLETPIPEHOLE OUTLETPIPEHOLE
5 3 FL2011EI ϭΘϮ͕ŽƌϭŽƌϮ ϱ
FL2012EI ϭΘϮ͕ŽƌϭŽƌϮ ϲ
FL2022EI ŚĂŶŶĞůϭͲϭΘϮ͕ŽƌϭŽƌϮ ϱ
ŚĂŶŶĞůϮʹϯΘϰ͕ŽƌϯŽƌϰ ϲ

Note 1: Pipe holes not used should be kept sealed.


7c Note 2: Do NOT glue pipes into the pipe holes.

6
Pipe Installation

329 mm

1 2 3 4 5 6 7 8 9 10 1112 13 14 1516 17 18

1 2

7d

9 3 4

D R A
IN
10-D
E C - 2 018
D200-102-00 D
INTEPR
I56-3888-202
HEN
TROL
LED W Page 59 of 67 59 / 67
NCON
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

Exhaust Pipe

SAMPLING AREA

5 6

PP

SAMPLING AREA

P
WIRING INSTALLATION

Power, Alarm and Control Connections

CHANNEL 1 FILTER CHANNEL 2 FILTER

EARTH BAR
MOUNT

EARTH BAR
(OPTIONAL)

POWER AND
ALARM
CONNECTIONS Figure 9: Inside the Detector
USB PORT
EARTH BAR
MOUNT

SENSOR COVER

POSITION FOR TEST MAGNET POSITION FOR TEST MAGNET

D R A
IN
10-D
E C
D2
- 2 018
1 2
PRINT
ED
3 2 2
HEN
TROL
LED W Page 60 of 67 60 / 67
NCON
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

Table 2: Wiring Terminal Designations Sensor


( ote er inals arked 2 will onl be available on 2 channel he sensor address is set on rotar decade
odels) switches on the back of the s oke sensing
devices. he s oke sensors are located
No. Function under the sensor cover inside the unit (see
1 E t Power n Pri ar P U 1 igure ). he Smoke Sensors section of
2 E t Power n Pri ar P U Maintenance later in the anual shows
3 u Power n ot used in default how to re ove the sensors. s supplied,
4 u Power n ot used in default the default for channel 1 is ddress 1 in
lar ela 1 2 2 channel units (or when two sensors are
lar ela 1 ¿WWHG WKHVHFRQGGHYLFHLVVHWWR$GGUHVV
lar ela 1
Module
lar ela 2 3
lar ela 2 he odule address is set b eans of rotar
1 lar ela 2 decade address switches located behind the
11 ault ela 1 4 door of the unit. Use a screwdriver to rotate
12 ault ela 1 the wheels to the desired address. he
13 ault ela 1 selected address refers to channel 1 on 2
14 ault ela ( U ) 2 channel units the device assigns the ne t ( 1)
1 ault ela ( U ) 2 odule address to channel 2 auto aticall .
1 ault ela ( U ) 2 ence, address 1 is not valid for channel
1 ounder utput 1 1. ( ote: for control panels that use onl
1 ounder utput 1 addresses, is invalid for channel 1.)
1 ounder utput 2 POWERING UP
2 ounder utput 2
Using Default Settings
21 onfigurable nput ( eset)
22 onfigurable nput ( eset) 1. onnect a suitable 24 D suppl to pins
23 ot Used 1 and 2 on ter inal block 1 ( ee able 2)
24 oop out 2. heck the voltage at the connector.
2 oop switched out o use isolator ake sure it is within the required voltage
2 oop in 1 range.
2 oop in  ,IWKHYROWDJHLVZLWKLQWKHVSHFL¿HGUDQJH
2 oop not switched out nternall connected to 2 connect the power connector to the unit.

Table 3: Relays
RELAY ACTION: NOTES
1 or 2 ontrolled b panel when it deter ines et and b panel not latched
alar condition has been et.
U 1 or 2 hen U D on h1 or h2 ault state is not latched.
or a E E U is occurs. ault is
also signalled when in ervice ode and
when the device is unpowered.

U DE 1 or 2 et when a channel is in . Default condition set on in .


ounder 1 corresponds to h1 and
ounder 2 corresponds to h2

SETTING THE ADDRESSES 4. lose and secure the housing door verif the fan starts up and
DLUÀRZVRXWRIWKHH[KDXVWSRUW7KHXQLWWDNHVPLQXWHVWR
Each aspiration channel uses loop co unications to report its initialise and stabilise in nor al ode.
status infor ation to the E ( ire Panel). s a factor default,
the unit will report s oke alar and sensor infor ation at an &RQ¿JXULQJ2WKHU2SWLRQV
associated sensor address and general alerts and faults on a o change an of the default options, it will be necessar to
different odule address. connect the detector to a P laptop with the Pipe software
installed see USB connection section later in this guide for
ore infor ation on this (and the dvanced etup and
ontrol uide reference D2 1 ).
EXTERNAL RESET
7KH GHIDXOW VHWWLQJ IRU WKH FRQ¿JXUDEOH H[WHUQDO LQSXW LV 'HYLFH
eset (ter inal block ). short circuit connection between these
ter inals will cause the unit to perfor a reset.

; ;

DR20A
Figure 10: Address Switches

IN
10-D
EC-
D2
18
1 2
PRINT
ED
3 2 2
HEN
TROL
LED W Page 61 of 67 61 / 67
NCON
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

FRONT PANEL

he front panel will be different depending on which of the 3 2


odels is being installed, and each is shown below. ALARM

he following infor ation is displa ed: PREALARM

10
‡ 'HWHFWRU6WDWXV1RUPDO$ODUP)DXOWRU,VRODWH
‡ $ODUP /HYHO $ODUP 3UH$ODUP RQO\ DYDLODEOH ZLWK SDQHOV 9

using dvanced Protocol) 8

‡ 3DUWLFXODWH /HYHOV  RQO\ DYDLODEOH ZLWK SDQHOV XVLQJ 7

dvanced Protocol) 6

‡ )DXOW6WDWXV 5
‡ )ORZ/HYHO 4
‡ 7HVW5HVHWDQG'LVDEOH%XWWRQV 3

2
SMOKE
LEVEL 1

MODULE
Figure 11: Front Panel Display
FAULT POWER
FAULT

ALARM

PREALARM
W

HIG
FLO

10
UT

FIL

HF
SOR
INP
LOW

SOU

TER

LOW
OR

TEMPER
SYSTEM / DISABLE
9
SEN

ASPIRAT

NDE
R
ATURE
8

2
SMOKE
LEVEL 1 11b: FL2012EI 1 Channel Detector (2 Sensors)
MODULE

FAULT POWER
FAULT

ALARM

PREALARM

10 10
W

HIG

9 9
FLO

UT

FIL

HF
SOR
INP
LOW

SOU

TER

LOW

8 8
SYSTEM / DISABLE
OR

TEMPER
SEN

ASPIRAT

NDE

7 7
R
ATURE

6 6

5 5

4 4

3 3

2 2
SMOKE SMOKE
LEVEL 1 1 1 LEVEL 2

MODULE 1 MODULE 2

11a: FL2011EI 1 Channel Detector (1 Sensor) FAULT POWER


FAULT
W

HIG
FLO

UT

FIL

HF
SOR
INP
LOW

SOU

TER

LOW
SYSTEM / DISABLE
OR

TEMPER
SEN

ASPIRAT

NDE
R
ATURE

A
IN0-DDECR
11c: FL2022EI 2 Channel Detector
-2018
D2 1 2 3 2 2
1 PRINT
ED
HEN
TROL
LED W Page 62 of 67 62 / 67
NCON
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

Table 4: Front Panel Indicators and Fault Descriptions

INDICATOR ACTION WARNING OR TROUBLE COMMENT / ACTION


E 12 ed hannel is in alar (rela is ensor alar ode is default setting
( et b panel) set with no dela )
1 reen hen sensor is polled ot when in alar
(Polled b panel)
E 12P E ellow hannel is in pre alar (onl with panels using dvanced Protocol)

E E E 12 ellow ed nu ber indicates sensor nl nu bers 1 used (onl with panels using
( et b panel) alar level reached dvanced Protocol).
E 12 DU E odule h1 h2 output on
odule co unication
U ellow eneral or ultiple faults
P E reen is powered
P E U ellow ow power alert high power heck the power suppl voltage.
fault

E reen he ED indicates the air flow n 2 channel unit:


D 12 for a channel: Upper row h1
- entre nor al flow ower row h2
- eft flow low
(2 at e tre e)
- ight flow high
( 2 at e tre e)

ow flow fault heck filter check pipe network for blockages.


PU 1 E ternal input fault ot used with default settings
E 2 ensor co unication fault heck sensor addresses and installation
replace sensor.
P ir flow sensor fault r to restart device.
1 low initiali ation fault heck filter check pipe network for blockages
tr to restart device.
2 an fault r to restart device.
D E 1 lar s alerts not reported eturns to aintenance then or al operation
after in (default)
E 1 rong configuration lashes all U EDs tr to restart device.
2 EEP fault heck power suppl voltage. r to restart
device
3 eal ti e clock fault is corrupted or ti e reading failed.
E PE U E 1 ow te perature alert heck the air flow te perature
2 igh te perature alert heck the air flow te perature
U DE 1 ounder fault heck the sounder circuit and the E
E 1 ilter alert at set date o date set as default
igh flow fault heck pipe network for breaks or leaks.
n case of si ultaneous alerts faults on the sa e ED, priorit order is: ( ighest), 1 blink, 2 blinks, 3 blinks ( owest)

ote: he channel alar and s oke level EDs are under the
control of the E ( ire Panel).
Front Panel Buttons
he front panel has 3 user buttons: TEST, RESET and DISABLE.
hese buttons are used to enter the pass code which then allows
the user to carr out si ple test functions.
ote: n Remote Maintenance and Service Mode, these buttons
are alwa s disabled.

Figure 12: User Interface Buttons

D R A
IN
10-D
E C
D2
- 2 018
1 2
PRINT
ED
3 2 2
HEN
TROL
LED W Page 63 of 67 63 / 67
NCON
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

Table 5: Front Panel Buttons

BUTTON NORMAL Mode MAINTENANCE Mode


RESET hen pressed for 2 s, starts P D hen pressed for 2 s latched alar s,
P EDU E to enter aintenance faults and sounders (rela s) are reset
ode.
nD E ode, if pressed for 2 s unit
will e it fro D E ode
DISABLE Used to incre ent Password digits in hen pressed for 2 s, device enters
P DP EDU E D E ode for inutes (default).
( lar s, alerts and faults not reported).
( o e it D E ode see E E )
TEST Used to confir password in P D hen pressed for 2 s and released, both
P EDU E. Default Password 3111 sensor will si ulate alar

hen pressed for 4 s and released,


sensor 1 will si ulate alar

hen pressed for s and released,


sensor 2 will si ulate alar
COMBINATIONS
RESET + DISABLE hen pressed for 2 s, shows fan speed hen pressed for 2 s, shows fan speed
(on s oke level scales) for a preset ti e. (on s oke level scales) for preset ti e.
RESET + TEST o action hen pressed for 2 s, turns off sounders
RESET + TEST + DISABLE o action hen pressed for 2 s, unit e its fro
E E ode

Password Sequence to Enter Maintenance Mode SERVICE


Press and hold RESET /HIW ÀRZ LQGLFDWRU ZLOO WXUQ \HOORZ WKHQ WARNING
green. ,solate the aspirating detector Irom the ¿re alarm s\stem to prevent
elease RESET and FAULT indicator will switch on green. he an\ unwanted alarms when opening the Iront door oI the unit.
OHIWÀRZLQGLFDWRUZLOOEOLQNJUHHQLQGLFDWLQJWKHGHYLFHLVUHDG\IRU Make sure all power is removed Irom the s\stem beIore removing
WKH¿UVWGLJLW an\ covers.
Press DISABLE to incre ent the EDs 1 press TEST to select Service Mode
a digit.
pening the cabinet door during nor al operation will cause the
7KH ÀDVKLQJ DLUÀRZ VHJPHQW ZLOO WXUQ VROLG JUHHQ DQG WKH QH[W unit to enter Service ode. he FILTER EDs will blink, the unit
VHJPHQWZLOOEHJLQWRÀDVKLQGLFDWLQJVHWWKHQH[WGLJLW:KHQWKH will switch off power to the fans and stops co unicating with
WK GLJLW LV VHOHFWHG DOO  DLUÀRZ VHJPHQWV DUH WXUQHG RII ,I WKH WKH ¿UH SDQHO :KHQ WKH FDELQHW GRRU LV FORVHG WKH XQLW UHVWDUWV
password is accepted the FAULT indicator will re ain green and auto aticall .
the unit enters Maintenance ode. f the password is incorrect
the FAULTLQGLFDWRUÀDVKHV\HOORZDQGWKHXQLWUHPDLQVLQNormal Filters
ode. he Default password in 3111. 3HULRGLFFOHDQLQJRUUHSODFHPHQWRIWKH¿OWHUVZLOOEHUHTXLUHG
f no button is pressed for 1 s during the password sequence, the 7KH¿OWHUVDUHORFDWHGLQVLGHWKHFDELQHWDWWKHWRSRIWKHXQLW VHH
unit returns to Normal ode. f there is no activit in Maintenance igure displa ed earlier in the guide) and are re oved as shown
ode for inutes (default), the FAULT indicator blinks green for in the sequence below:
1 s and then the unit returns to the Normal state.
TESTING
ote that the sensor EDs, which are under the control of the E
( ire Panel), ust be turned on to activate the front panel alar
indicators.
Magnet Test
he alar signalling can be tested for functionalit b placing a
test agnet in the position shown in igure (displa ed earlier in
WKHJXLGH 7KLVPHWKRGGRHVQRWWHVWWKHDLUÀRZLQWKHSLSHZRUN
Smoke Testing 1 2
he s ste alar response can be tested for functionalit
using s oke. he choice of s oke source is dependant on the
installation but in all cases the s oke ust be present for the
duration of the test. oke pellets or atches can be used close
to the sa pling point to introduce s oke particulates into the
s ste . t is reco ended that s oke with a particulate life c cle
of greater than 12 s should be used standard aerosol spra s for
point detector testing do not work well on aspirated s ste s.
Fault Testing
i ulate a fault on the detector (for e a ple, block the outlet pipe)
3

DR20A
and check that a fault is signalled on both the front panel of the unit
and at the E ( ire Panel).
IN
10-D
EC-
D2
18
1 2
PRINT
ED
3 2 2
HEN
TROL
LED W Page 64 of 67 64 / 67
NCON
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

(LWKHU UHSODFH WKH ¿OWHU DVVHPEO\ RU FDUHIXOO\ EUXVK RII WKH PipeIQ™LT QUICK START INSTRUCTIONS
accu ulated dust.
Overview of PipeIQLT
5H¿W WKH ¿OWHU FORVH DQG VHFXUH WKH FDELQHW GRRU 7KH XQLW ZLOO
he Pipe software progra is a convenient and powerful
initialise and restart.
indows based application that can be used to quickl and
Smoke Sensors DFFXUDWHO\GHVLJQSLSHQHWZRUNVJHQHUDWHFRQ¿JXUDWLRQSDUDPHWHUV
he s oke sensors are located under the sensor cover (see igure for correct set up and operation, and facilitate co issioning and
displa ed earlier in the guide). o access the sensors, follow the onitoring of the perfor ance of spiration devices.
sequence below: Pipe provides a graphical interface on a P to:
‡ 'HYHORSDQGYHULI\WKHSHUIRUPDQFHRISLSHQHWZRUNVROXWLRQV
‡ &RQ¿JXUH WKH GHVLJQ SDUDPHWHUV WR VXLW ORFDO ¿UH FRGHV DQG
standards.
‡ *HQHUDWH 3LSH /D\RXWV %R0V &RQ¿JXUDWLRQ DQG (YHQW /RJ
eports.
‡ &RQWURO7HVWDQG0RQLWRU)$$67/7GHYLFHV
here is a co prehensive Help Menu to guide the user through
the different windows and options. he contents have a detailed
inde and a versatile search facilit to locate relevant topics.
1 2 Minimum System Requirements
icrosoft indows P P3 or indows
1 of .
raphics hardware with 12 of e or and support for
pen 2. or later.
of free hard disc space
Installing PipeIQLT
Pipe is supplied on a ass storage device with each
unit, or it can be accessed as a download fro www.
s ste sensoreurope.co .
3 To install from the mass storage device
nsert and view the re ovable storage device. lick on PipeIQLT
f replacing a sensor, ensure that the address set on the new Setup:
sensor is the sa e as on the sensor being replaced.
LASER SAFETY INFORMATION
he detector contains a lass 1 laser product. adiation e itted
inside the s oke sensor is co pletel contained within its housings
and protective covers during all phases of operation.
USB CONNECTION
P connectivit is provided b an onboard U B socket located
FHQWUDOO\EHWZHHQWKH¿OWHUDQGWKHVHQVRU VHH)LJXUHGLVSOD\HG
earlier in the guide). he U interface allows access to a range lick OK and follow the instructions (see: PipeIQLT Setup and
of additional options, via the Pipe application software, when Installation Wizard section below).
connected to a P . he U connecting cable should be re oved
To install from the website
during nor al operation.
lick on the link to Pipe at www.systemsensoreurope.com.
lick on PipeIQLT download. he download securit warning will
appear. elect Save, then click OK.
hen the download co pletes, click Run to displa the above
dialog bo . lick OK and follow the instructions (see: PipeIQLT
Setup and Installation Wizard section below).
PipeIQLT Setup and Installation Wizard
hen the below dialog bo appears, click Setup to start the wi ard:

D R A
IN
10-D
E C
D2
- 2 018
1 2
PRINT
ED
3 2 2
HEN
TROL
LED W Page 65 of 67 65 / 67
NCON
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

Quitting
E tiing the progra closes the application co pletel .
o quit the Pipe application, click X in the upper right corner
of the window.
r click Exit fro the File enu.
Pipe can be uninstalled fro the co puter in the nor al wa
for our operating s ste .

lick Next and follow the on screen instructions.


8QOHVVFKDQJHGWKHLQVWDOOZL]DUGZLOOFUHDWHDQGVWRUH¿OHVDWWKH
following locations:

hen installation is co plete, the wi ard will


auto aticall create a shortcut icon on the P
desktop.
t will be necessar to re boot the P in order to
run Pipe .
Launching
o launch the Pipe application, double click the PipeIQLT icon
on the desktop.
r
click Start (botto left corner of the indows screen) and then 0832
select PipeIQLT fro the progra s list.
hen the application opens, it is possible to start a new pro ect, or FL2011EI: 0832-CPD-1993 12
to onitor or odif an e isting pro ect. Use the File enu to select FL2012EI: 0832-CPD-1994 12
New or Open. hoose fro the Pipe Design, &RQ¿JXUDWLRQor FL2022EI: 0832-CPD-1995 12
Monitoring tabs to enter the required ode.
E 42 :2
o co unicate with a detector, connect the U port to lass
a P with an appropriate cable. et the detector to Maintenance spirating oke Detectors
ode.
Pittwa ecnologica .r.l.
ia aboto 1 3,

D R A 3414 rieste, tal

IN
10-D
E C
D2
- 2 018
1 2
PRINT
ED
3 2 2
HEN
TROL
LED W Page 66 of 67 66 / 67
NCON
Company Document Identification Sub Contractor’s Document
Identification Contractor's Doc. No: V-2140-001-A-811

Sub Contractor's Doc. No: BC2129-000-000-FPR-MAN-00001

FIRE ALARM SYSTEM - VENDOR DATA BOOK

GEPCO SpA
Doc. Title: AND INSTALLATION, OPERATION &
MAINTENANCE MANUAL

Revision: 1

Aspirating Smoke Detector Pipe Installation

Basic Pipe Network Cleaning


and Maintenance Procedure
Periodic maintenance of the FAAST Fire Alarm Aspiration Sens- t If the low flow condition persists, perform another manual
ing Technology pipe network is recommended in environments check of the pipe network against the pipe layout report
with high amounts of airborne particulate, or cold environments generated by PipeIQ. Also, if the exhaust pipe is not
where condensation may freeze on the sampling port and affect situated in the protected space the low/high flow condition
pipe network performance. Annual maintenance of the pipe could be the result of differences in room pressures that
network is recommended for all installations. have changed do to open doors, windows or upgrades to
ventilation units.
Low flow faults on devices which have been installed and oper-
ating normally for a period of time may signal the need for pipe
network cleaning.
Filter Maintenance
Filter maintenance is required only when a ‘Filter’ fault is indi-
Pipe Network Maintenance cated by the FAAST unit. Perform the following procedure to
replace the filter assembly:
During installation of the pipe network, it is recommended that
a valved tee fitting be installed 6 inches to 1 foot from the pipe 1. Remove power from the system.
inlet so that the pipe entering the detector is not subject to any
flow of air during the pipe network maintenance. Forcing air in 2. Open the door on the right side of the device that covers
to, or out of, the FAAST unit by any means other than the inher- the LED system indicators.
ent fan may cause damage to the device and nullify the device 3. Remove the plastic name card over the LEDs.
warranty. 4. Remove the two screws holding the filter assembly into
the device.
Prior to beginning pipe network maintenance:
5. Remove the filter assembly and replace it with a
t Place the device in isolate or disable mode, or power new assembly.
down. 6. Torque the two Phillips-head screws to 6in-lb (0.7 N-M)
t Remove the pipe network from the device, or switch the or ¼ turn past “lightly snug’. DO NOT OVERTIGHTEN.
valve on a valved tee fitting to ensure that no air can be 7. Replace the plastic name card over the LEDs.
force in to or out of the device 8. Close the door and restore power to the system.

To perform pipe network maintenance:

t Affix a vacuum cleaner, or air compressor, to the end of


the pipe network or the entry in to the valved tee fitting.
t While the vacuum is running, use a dry brush or pipe
cleaner to swab out each sampling port in the pipe net-
work. Leave vacuum running for 2 min following last port
cleaning.

Post pipe network maintenance:

t Reconnect pipe network to the FAAST device or switch


the valved tee tap
t Remove the device from isolate or disable mode, or
reapply power to the FAAST
t Observe the air flow pendulum on the user interface. The
two green indicators should be near center underneath
the device’s power indicator. If a low condition existed
before maintenance, this condition should be clear after
maintenance (NOTE: if the device is set to latch in fault,
the device will need to be reset to clear the fault)

D R A
IN
10-D
E C - 2 018
PRINT
ED
WHEN Page 67 of 67 67 / 67
LLED
NCONTRO

S-ar putea să vă placă și