Model: AC45
Powered by CUMMINS
Generator Specification
Performance Data
Service PRP(1) ESP(2)
Model AC45
Power (kVA) 50 55
Engine brand Cummins
Power (kW) 40 44
Engine model 4BT3.9G2
Rated speed ( r.p.m) 1800
Speed control type Electronic
Standard voltage (V) 400/230V
Phase 3
Rated at power factor(cos phi) 0.8
Control system Digital
Starter motor voltage 24V
AU V ER
ISO 9001 E T
R A
I
Frequency 60HZ
U
BUREAU VERITAS B
Certification
1 82 8
380/220 55 44 50 40 83.6
220/127 55 44 50 40 144.3
Engine Specification: 4BT3.9G2
-1%
Winding Connections (standard) Star-serie 352
Terminals 12 296
IP rating IP23
50
-1%
46
38
30
0 1 2 3 4 5 6 7 8 9 10 1 1 1 2
δf%: -10.64 Benchmark phase: A Min. frequency: 44.68Hz Recovery time: 1.95s
Three phase Reliable Single phase
δf%: 7.74 Benchmark phase: A Max. frequency: 53.87Hz Recovery time: 0.54s
Options
· Water Jacket · Winding Temp measuring · Tools with the machine · Low fuel level alarm
Pre-heater Instrument · Extended range fuel tank · Automatic fuel
· Fuel heater · Alternator Pre-heater · Bunded fuel tank feeding system
· PMG · Fuel T-valves
· Anti-damp and anti-corrosion
treatment
· Anti-condensation heater
· Winding and bearing RTD
· Rental type · Oil Pre-heater · Front heat protection · Remote control panel
Canopy · Oil temp sensor · ATS
· Trailer · Synchronizing controller
· Adjustable earth leakage
relay
Control Panel
Configuration Benefits
Operation conditions
Features
· Operation temp: -20 ˚C to + 70 ˚C
· 3 phase generator set monitoring
· Support of engines equipped with electronic control unit · Storage temp: -30 ˚C to + 80 ˚C
· Operating humidity: 95% w/o condensation
· Vibration 5-25Hz, ±1.6 mm
· Comprehensive diagnostic message
5-100Hz, a= 4g
· Automatic or manual start/ stop of the gensets
· Shocks: a= 500m/s²
· Push buttons for simple control, lamp test
· Graphic back- lit LCD display
Options
· Parameters adjustable via keyboard or PC
· Mains measurements ( 50HZ/ 60HZ) · Ethernet interface (Remote monitoring and control)
· Generator measurements ( 50HZ/ 60HZ) · GSM modem/wireless internet (Remote monitoring and control)
· Comprehensive shutdown or warning on fault condition · RS232-RS485 Dual port interface
· 3 phase Generator protections · Synchronizing control panel
· Distribution board with sockets kit and power busbar
- Over- / under voltage
· Battery trickle charge ammeter
- Over- / under frequency
· Earth leakage protection
- Current/ voltage asymmetry
· Earth fault protection
- Over current/ overload · Low fuel level alarm
· 3 phase AMF function · Low fuel level shutdown
- Over-/under frequency · High fuel level alarm
- Over-/under voltage · Fuel transfer system control
- Voltage asymmetry · Low coolant level shutdown
· Configurable analog inputs · High lube oil temp shutdown
· Battery voltage, engine speed (pick-up) measurement · Overload via alarm switch on breaker
· Configurable programmable binary inputs and outputs · Engine coolant heater controls
· Warm-up and cooling functions · Control panel heater
· Generator C.B. and Mains C.B. control with feedback and · Speed adjust switch
return timer
· Oil temp displayed on LCD screen
· RS232 interface
· Additional 8 inputs and outputs
· Modem communication support
· Hours counter
· Sealed to Ip65
· Event log
ISSUE 1 @ AGG
All information in the document is substantially correct at time of printing but may be subsequently altered by the company.