PLC and HMI Remote Access via MOXA

OnCell Devices
Page |2

Introduction:
This document was written to provide you with an example configuration that will allow
you to remotely access, program, and control a C-more operator interface and a DirectLogic PLC
using MOXA’s OnCell G3110 Cellular IP Gateways. These procedures can be applied to any
application which requires access to a remote LAN within a cell tower reception zone.

OnCell Setup with C-More and DL06 PLC


This configuration will enable the following features over the cellular network:

1. Web Services on the C-More Panel


2. Remote Access and control on the C-More Panel
3. FTP services on the C-More Panel
4. Application Transfer to C-More Panel
5. PLC programming and monitoring with DirectSoft

System Overview:
Hardware:

1. OnCell G3110 Industrial quad-band GSM Cellular IP gateways


2. EDS-205 5 Port Unmanaged Ethernet Switch
3. EA7-T8C 8” C-More Panel (any size is acceptable)
4. D0-06DR DL06 PLC
5. H0-ECOM100 Ethernet Communication Module
(Please note: This configuration can be used with any AutomationDirect PLC including
DL205 and the Productivity 3000, the DL06 is used here for demonstrative purposes)

www.quantumautomation.com | 4400 East La Palma Ave. Anaheim, CA 92807. | P: 714-854-0800. | F: 714-854-0803


Page |3

Items to Complete before configuration:


1. Program PLC
2. Program C-More (with Remote Access, please see the C-more Remote Access Tutorial)
3. Contact CrossBridge Solutions to setup account and obtain SIM card
4. Install SIM card in OnCell 3110

Addresses for our configuration:

Device Name IP Address


OnCell G3110 192.168.127.254 (default)
EA7-T8C (C-more) 192.168.127.101
DL06 (or other PLC) 192.168.127.100

OnCell Configuration Steps:


1. Setup IP Address – “Basic Network Settings”
2. Configure GPRS APN – “GSM GPRS Settings”
3. Setup Port Forwarding – “Virtual Server Settings”

To configure the OnCell 3110 you must be plugged into the local network. Plug into EDS-
205 to and bring up Internet Explorer. Type in the IP address 192.168.127.254. The Moxa
configuration should appear. If you wish to change the IP address of the OnCell this can be
done in the “Basic Network Settings” as seen below. We left the default IP address for our
application.

www.quantumautomation.com | 4400 East La Palma Ave. Anaheim, CA 92807. | P: 714-854-0800. | F: 714-854-0803


Page |4

CrossBridge Solutions will supply you with an APN name that must be entered into the
OnCell device before it will communicate with CrossBridge. Enter the APN name in the GSM
GPRS Settings as shown below:

Finally setup port forwarding in the Virtual Server Settings as shown here:

www.quantumautomation.com | 4400 East La Palma Ave. Anaheim, CA 92807. | P: 714-854-0800. | F: 714-854-0803


Page |5

Public Port Internal IP Internal Port Uses


8080 192.168.127.101 80 Web Access for the C-more Panel
11102 192.168.127.101 11102 Remote Access for the C-more Panel
2121 192.168.127.101 21 FTP server for the C-more Panel
9999 192.168.127.101 9999 Programming Port for the C-more Panel
7070 192.168.127.100 7070 Programming Port for the DL06 PLC

Save configuration and Restart OnCell unit. After the unit powers up you should now have the
GSM and the GPRS lights “ON”.

Access the different functions:

YOUR_IP_ADDRESS = Address Supplied by CrossBridge


Function Address
Moxa Remote Configuration http://YOUR_IP_ADDRESS
C-More Web Page http://YOUR_IP_ADDRESS:8080/
C-more FTP Services http://YOUR_IP_ADDRESS:2121/
C-More Project Transfer Enter "YOUR_IP_ADDRESS" in Offline Ethernet Connectons
(see image below)
PLC Programming Enter "YOUR_IP_ADDRESS" in Link Editor

www.quantumautomation.com | 4400 East La Palma Ave. Anaheim, CA 92807. | P: 714-854-0800. | F: 714-854-0803


Page |6

PC to CrossBridge servers:
Go to ftp site at: ftp://ftp.crossbridgesolutions.com/get/YOUR-ACCOUNT-Name
Download file: Your-Account.zip
Extract and open file
Double click on application: “CrossBridge Install” to run application.
Restart computer (application changes your registry file so computer must be restarted)
Go to: Start > My network places – then Right click > select properties
You will see an Icon for CrossBridge Host Server – Double click on the Icon
This will ask you for username and password, Enter:
Username: (found in ZIP file)
Password: (found in ZIP file)
Go back to the files you downloaded from the ftp site and double click on Routes, it will do
something very quickly and go away.
You are in!!
Ping 63.84.143.1 to confirm connection to CrossBridge
Ping (IP Address from CrossBridge for your OnCell Device)
Go to Start > Run – Enter: cmd
From the command prompt, enter: ping<space> and the IP you wish to ping

www.quantumautomation.com | 4400 East La Palma Ave. Anaheim, CA 92807. | P: 714-854-0800. | F: 714-854-0803


Page |7

C-More Programming software modification:


To enable the C-More software to transfer the application over this network the ea_.ini
needs to be modified to add three commands. The file is located in the C-More Software
directory and can be found in a location similar to this (Win XP): C:\Program
Files\AutomationDirect\C-more.

Please add the highlighted lines to your .ini file:

Now you are done and you can start communicating to your C-More!