Sunteți pe pagina 1din 2

Pt C, Ch 2, Sec 5

SECTION 5 TRANSFORMERS

1 Constructional and operational For transformers with a power lower than 5 kVA per phase,
this voltage drop is not to exceed 5%.
requirements
An exception is made for special transformers, such as start-
ing and instrument transformers, for which a different volt-
1.1 Construction age variation may be considered.
1.1.1 Transformers, except those for motor starting, are to 1.3.2 In determining the voltage ratio and the impedance
be double wound (two or more separate windings). voltage of transformers, account is to be taken of the total
permitted voltage drop from the main switchboard’s busbars
1.1.2 Transformers are normally to be of the dry, air-cooled
to the consumers (see Ch 2, Sec 3, [9.11.4]).
type.
1.3.3 Transformers are to be constructed to withstand,
1.1.3 When a forced air cooling system is used, an alarm is
without damage, the thermal and mechanical effects of a
to be activated in the event of its failure.
secondary terminal short-circuit for 2 s, with rated primary
1.1.4 Liquid-cooled transformers may be used provided voltage and frequency.
that: For transformers of 1 MVA and over, this is to be justified
with appropriate tests or documentation.
• the liquid is non-toxic and of a type which does not
readily support combustion 1.3.4 When transformers are so arranged that their second-
• the construction is such that the liquid is not spilled in ary windings may be connected in parallel, their winding
inclined position connections are to be compatible, their rated voltage ratios
• temperature and pressure relief devices with an alarm are to be equal (with tolerances allowed) and their short-cir-
are installed cuit impedance values, expressed as a percentage, are to
have a ratio within 0,9 to 1,1.
• drip trays or other suitable arrangements for collecting
the liquid from leakages are provided When transformers are intended for operation in parallel,
the rated power of the smallest transformer in the group is to
• a liquid gauge indicating the normal liquid level range
be not less than half of the rated power of the largest trans-
is fitted.
former in the group.
1.1.5 Transformers are to have enclosures with a degree of
protection in accordance with Ch 2, Sec 3, Tab 2. 1.4 Electrical insulation and temperature
rise
1.2 Terminals 1.4.1 Insulating materials for windings and other current
1.2.1 Suitable fixed terminal connections are to be pro- carrying parts are to comply with the requirements of Ch 2,
vided in an accessible position with sufficient space for Sec 2.
convenient connection of the external cables. 1.4.2 All windings of air-cooled transformers are to be suit-
ably treated to resist moisture, air salt mist and oil vapours.
1.2.2 Terminals are to be clearly identified.
1.4.3 The permissible limits of temperature rise with an
1.3 Voltage variation, short-circuit condi- ambient air temperature of 45°C for (natural or forced) air-
tions and parallel operation cooled transformers are given in Tab 1. The temperature
rises shown for windings refer to measurement by the resis-
1.3.1 Under resistive load (cos  = 1), the voltage drop tance method while those for the core refer to the thermom-
from no load to full load is not to exceed 2,5%. eter method.

Table 1 : Temperature rise limits for transformers

Temperature rise by class of insulation, in °C


N° Part of machine
A E B F H
1 Windings 55 70 75 95 120
2 Cores and other parts: a) the same values as for the windings
a) in contact with the windings b) in no case is the temperature to reach values such as to damage
b) not in contact with the windings either the core itself or other adjacent parts or materials

58 Bureau Veritas April 2009


Pt C, Ch 2, Sec 5

1.4.4 For dry-type transformers cooled with an external liq- 2 Testing


uid cooling system, the permissible limits of temperature
rise with a sea water temperature of 32°C are 13°C higher
than those specified in Tab 1. 2.1 General
1.4.5 For liquid-cooled transformers, the following temper-
2.1.1 On new transformers intended for essential services
ature rises measured by the resistance method apply:
the tests specified in [2.2] are to be carried out.
• 55°C where the fluid is cooled by air
• 68°C where the fluid is cooled by water. 2.1.2 The manufacturer is to issue a test report giving, inter
alia, information concerning the construction, type, serial
1.5 Insulation tests number, insulation class and all other technical data rele-
vant to the transformer, as well as the results of the tests
1.5.1 Transformers are to be subjected to a high voltage test required.
in accordance with the procedure defined in IEC publica-
tion 60076-3. Such test reports are to be made available to the Society.

1.5.2 The test voltage is to be applied between each wind-


2.1.3 In the case of transformers which are completely
ing under test and the other windings not under test, core
identical in rating and in all other constructional details, it
and enclosure all connected together.
will be acceptable for the temperature rise test to be per-
Single-phase transformers for use in a polyphase group are formed on only one transformer.
to be tested in accordance with the requirements applicable
to that group. The results of this test and the serial number of the tested
transformer are to be inserted in the test reports for the other
1.5.3 The r.m.s. value of the test voltage is to be equal to transformers.
2 U + 1000 V, with a minimum of 2500 V, where U is the
rated voltage of the winding. The full voltage is to be main-
2.1.4 Where the test procedure is not specified, the
tained for 1 minute.
requirements of IEC 60076 apply.
1.5.4 Partially rewound windings are to be tested at 80% of
the test voltage required for new machines. 2.1.5 The tests and, if appropriate, manufacture of trans-
formers of 100 kVA and over (60 kVA when single phase)
1.5.5 The insulation resistance of a new, clean and dry intended for essential services are to be attended by a Sur-
transformer, measured after the temperature rise test has veyor of the Society.
been carried out (at or near operating temperature) at a volt-
age equal to 500 V d.c., is to be not less than 5 M. Transformers of 5 kVA up to the limit specified above are
approved on a case by case basis, at the discretion of the
1.5.6 Transformers are to be subjected to an induced volt- Society, subject to the submission of adequate documenta-
age insulation test by applying to the terminals of the wind- tion and routine tests.
ing under test a voltage equal to twice the rated voltage. The
duration of the test is to be 60 s for any test frequency fp up
to and including twice the rated frequency fn. 2.2 Tests on transformers
If the test frequency exceeds twice the rated frequency, the
test time in seconds will be 120 fn / fp with a minimum of 2.2.1 Tests to be carried out on transformers are specified
15 s. in Tab 2.

Table 2 : Tests to be carried out on transformers

N° Tests Type test (1) Routine test (2)


1 Examination of the technical documentation, as appropriate, and visual inspection (3) X X
2 Insulation resistance measurement X X
3 Voltage drop X X
4 High voltage test X X
5 Temperature rise measurement X
6 Induced voltage test X X
7 Voltage ratio X X
(1) Type test on prototype transformer or test on at least the first batch of transformers.
(2) The certificates of transformers routine tested are to contain the manufacturer’s serial number of the transformer which has been
type tested and the test result.
(3) A visual examination is to be made of the transformer to ensure, as far as practicable, that it complies with technical
documentation.

April 2009 Bureau Veritas 59

S-ar putea să vă placă și