Documente Academic
Documente Profesional
Documente Cultură
©istockphoto.com/allkindza
By Krishnanjan Gubba Ravikumar,
Brandon Bosley, Ty Clark, and Julio Garcia
GTGs
9.42 MW
9.42 MW
9.42 MW
13.8 kV
13.8 kV (60 Hz) 13.8 kV 13.8 kV
(60 Hz) Bus A Bus B (60 Hz) Bus D (60 Hz) Bus C
61
95
The regulation at each unit is performed by biasing
60 the speed governor using a control signal (typically an
94
93 Electric Power 59 analog bias). This bias adds into or subtracts from the
Mechanical Power 58 speed reference (nominal speed) of the governor con-
92 Speed = Frequency
trol itself. The response of the bias signal is defined
91 57
0 5 10 15 20 by a proportional-integral-derivative (PID) control that
Time (s) exists within the GCS controller.
Figure 4 shows the integration of the bias signal into
FIGURE 3. A small-load synchronous machine step response. a typical governor-controlled block diagram. The con-
ditioner block is used to limit and
scale the bias for use in the gover-
Valve/Gate nor control system. The speed bias
Pm
Turbine Pe integrator time constant, limits, and
Steam Wr gain are field-tunable parameters
∆Y – that obtain the desired response
+ + from the machine.
Integrator –K Σ Σ Speed
∆Wr Reference W0 A high-level block diagram of the
+
frequency control function within
Integrator the distributed controller is shown
in Figure 5. Depending on the type
Conditioner of control selected, different logic is
activated along with the PID loop.
Speed Bias Figure 6 shows single-unit iso-
(Analog Signal) chronous governor regulation for
different bias conditions. During a
FIGURE 4. The block diagram of an isochronous governor with integrated speed bias (analog control situation, the GCS dynami-
bias input). cally calculates the bias set points
65,000 65
Generator Active Power
5–60 MW
Generator Frequency (Hz)
60
Generator Frequency
15–5 MW
Load
Reference
0 55
0 4.7 9.4 14.1 18.8 23.5 28.2 32.9 37.6 42.3 47
Time (min)
FIGURE 7. The base load tests on a single STG model using real GCS controller equipment.
FIGURE 11. Simulation data showing the effect of a three-phase fault on a helper motor.
135
53 trolled lab testing.