INSTRUCTIONS   FOR   LC2030  
 
 
 
Contents  of  this  manual:  
 
 
 
 
IMPORTANT  INFORMATION  ..............................................................................................................................  3  

INSTRUCTIONS  FOR  LC2030  ............................................................................................................................  4  

ELECTRIC  SUPPLY  ..........................................................................................................................................  10  

ELECTRIC  SUPPLY  AND  HEATING  ROD  .............................................................................................................................  10  


LEVEL  SWITCH  AND  TEMPERATURE  SENSOR  .....................................................................................................................  10  

FEATURES  ........................................................................................................................................................  11  

LEVEL  CONTROL  ........................................................................................................................................................  11  


FLOW  CONTROL  F1  ...................................................................................................................................................  12  
FLOW  CONTROL  WITH  VALVE  F2  ..................................................................................................................................  13  
TEMPERATURE  CONTROL  ............................................................................................................................................  14  

DESCRIPTION  OF  THE  CONTROL  PANEL  ............................................................................................................  15  

LEVEL  SENSOR  CONNECTOR  .........................................................................................................................................  15  


LAMPS  ..................................................................................................................................................................  15  
SWITCHES  ............................................................................................................................................................  16  
BINARY  SIGNALS  (DIGITAL)  .......................................................................................................................................  16  
ANALOG  SIGNALS  .....................................................................................................................................................  17  
VOLTAGE  SUPPLY  (E.G.  FOR  CONNECTION  OF  PROCESS  INTERFACE  ELECTRONIC  OF         I/O-­‐BOARDS  4488  BZW.  8816)  ..................  17  

EMPTY  WORKSTATION  ....................................................................................................................................  18  

REPLACING  THE  FUSE  ....................................................................................................................................   18  

CONNECTING  OF  LC2030  TO  I/O-­‐BOARD  4488  ...............................................................................................   19  

IP-­‐ADDRESS  FOR  BUS  COUPLER  BK9050  (I/O-­‐BOARD  4488)  AND  PC  ................................................................  19  
 
 
 
 
 
 
   
 
     
     
     
     
INSTRUCTIONS   FOR   LC2030  
 
 
 
IMPORTANT   INFORMATION  
 
 
 
When  temperature  is  to   be  controlled,  it  is  important  that  the  water  level  is  
above  the  medium  level   switch  and  the  marking  on  the  heating  rod.  
 
To  prevent   damage  to  the   heating   rod   it  is   necessary   to  cool  it  down  (i.e.  leave  it  
in   the  water   tank)   for  at  least  30  minutes.  
 
• Do  not  heat  the  water  in  the  tank  to  more  than  45°C.    
 
• The  pumps  must  not  run  dry,  i.e.  without  water.  
 
• Do  not  close  the  valves  completely  as  this  can  damage  the  pumps.  
 
The  input  signal  FC1  is  an  analog  input  and  shall  not  exceed  a  maximum  of  10V  DC.    
 
The  lamps  L1,  L2  and  L3  are  binary  inputs  with  a  maximum  of  24V  DC.  
 
Make  sure,  all  level  switch  plugs  and  the  temperature  probe  plug  are  fully  
connected.  

  3
     
     
     
     
INSTRUCTIONS   FOR   LC2030  
 
 
 
INSTRUCTIONS   FOR   LC2030  
 
The   workstation   LC2030   can   be   used   to   work   on   open-­‐loop   control   tasks   (binary)   and   closed-­‐loop  
control  tasks  (analog).  The  following  closed-­‐loop  control  systems  are  available:  
• liquid  level  control  
• flow  control  
• temperature  control  
 
The   workstation   is   equipped   with  an   adjustable   pump   for  flow   and  level   control   and   with   a  heating  
rod  and  a  circulation  pump  for  temperature  control.  
 
Level  switches  and  a  pressure  sensor  give  information  about  the  level  in  on  tank.  A  Pt100  resistance  
thermometer   and   a   flow   meter   measure   temperature   and   flow   rate.  The   workstation   is   shown  
below.  
 

 
 
Fig.  1:  Flow  chart  LC2030    

  4
     
     
     
     
INSTRUCTIONS   FOR   LC2030  
 

  5
     
     
     
     
INSTRUCTIONS   FOR   LC2030  
 

 
Heating  rod  
Level  drain  

B1  
B2  

LS1  
V3  

LS2  

F1  

LS3   Aluminium  rack  

Operator  panel  
 

230V  socket  
for  heating  rod  

Power  supply  
with  fuse  

  6
     
     
     
     
INSTRUCTIONS   FOR   LC2030  
 

Fig.  2:  Front  side  of  LC2030  

  7
     
     
     
     
INSTRUCTIONS   FOR   LC2030  
 

V2  

230V  socket  
P1   P2  
for  heating  rod  
 
 

Power  supply  
with  fuse  

Fig.  3:  Left  side  

P1  

 
P3  

Fig.  4:  Right  side  

  8
     
     
     
     
INSTRUCTIONS   FOR   LC2030  
 

   

P4  
 

Fig.  5:  Back  side  view  

Tank  1   Tank  2  

Fig.  6a:  Simplified  flow  chart  of  LC2030  

  9
     
     
     
     
INSTRUCTIONS   FOR   LC2030  
 
 
 
 
ELECTRIC   SUPPLY  
 
 
POWER   SUPPLY   AND   HEATING   ROD  
 
 
On  the  left  side  of  the  control  panel  you  can  find  the  power  supply  for  230V  and  a  230V  socket  for  
heating  rod  plug  (Fig.  7).  

 
Fig.  7:  Electrical  control  and  230V  socket  for  heating  rod  
 
LEVEL   SWITCH   AND   TEMPERATURE   SENSOR  
 
 
In   Fig.   8   you   can   see   the   connector  
for   level   switches   LS1,   LS2,   LS3   and  
temperature   sensor   T1.  
 
 
 
 
 

Fig.  8:  Connector  for  level  switches  and  temperature  sensor  

  10
     
     
     
     
INSTRUCTIONS   FOR   LC2030  
 
 
 
 
FEATURES  
LEVEL   CONTROL  
 
 
  Level  control  exercises  are  performed  in  tank  B1.  The  level  
 
is  measured  with  three  level  switches  LS1,  LS2  and  LS3  and  
 
  pressure  sensor  L1.  The  analog  signal  of  level  in  tank  B1  is  
  provided  at  socket  L1  in  a  range  of  2..10V  DC  for  0..45cm.  
   
 
   
  Tank   B1   is   being   filled   by   pumps   P1   and   P2.   Pump   P3  
  pumps   the   water   into   Tank   B2.   For   level   control   the   flow  
LS1   rate   of   pump   P3   is   adjustable   by   an   analog   signal   FC1  
 
 
(0...10V).   To   influence   the   control   system   it   is   possible   to  
  switch  pumps  P1  and  P2  on  and  off.  With  the   hand  valves  
  flow   rate   of   pumps   P1   and   P2   can   be   adjusted   or  
  influenced  (see  also  Fig.  1).  
  LS2  
 
The  level  sensor  can  also  be  connected  to  tank  B2  for   level  
 
  control  by  input.  
   
   
   
   
   
  LS3  
   
   
   
   
   
   
   
   
   
 
 
Fig.    9:  Level  control  in  B1  
 

  11
     
     
     
     
INSTRUCTIONS   FOR   LC2030  
 
 
 
 
FLOW   CONTROL   F1  
 
 
  The   flow   control   is   influenced   by   the   signal   FC1  
  (revolution   speed,   pump   P3).   By   using   the   hand  
  valve,   the   flow   rate   can   be   varied.   The   analog  
 
signal   of   the   flow   rate   is   provided   at   socket   F1  
 
 
with  a  range  of  0..10V  DC  for  0..6L/min.  
 
 
 
 
 
 
 
 
 
 
 
 
   
 
 
 
   
 
  V3  
   
   
   
   
   
   
   
   
   
   
 
 
F1  
 
 
 
 
 
 
 
 
 
Fig.   10:  Sensor  of  flow  control  F1  and  hand  valve  V3    

  12
 

INSTRUCTIONS   FOR   LC2030  

FLOW   CONTROL   WITH   VALVE   F2  


 
  The  flow     control     with     the     valve     V1     and     flow  
 
sensor  F2  is  influenced  by  the  signal  FC2.  
 
 
 
 
 
   
  V1  
   
   
   
   
   
   
   
   
   
   
   
   
   
 
 
 
  F2  
 
 
 
 
 
 
 
 
 
 
Fig.   11:  Flow  sensor  F2  and   control  valve  V1    

  13
     
   
INSTRUCTIONS   FOR   LC2030  
 

TEMPERATURE   CONTROL  
 
The  heating  rod  has  to  be  connected  to  the  230V  socket  at  the  left  side  of  the  control  panel  and  the  
Pt100  thermometer  to  the  socket  “Temp.“  on  the  top  of  the  control  panel.  
 
To   prevent   damage   to   the   heating   rod   and   the   workstation,   it   is   only   possible   to   switch   on   the  
heater,   when   the   water   level   in   tank   B1   is   above   LS2.   All   level   switches   need   to   be   connected.  
Additional  to  level  switch  LS2  the  marking  on  the  heating  rod  has  to  be  below  the  water  surface.  
 
Pump  P4  should  be  running  to  mix  the  water  in  tank  B1.  
 
 

 
 
 
 
 
 
 
 
 
 
 
 
Mark  for  minimum
Immersion  depth  

Fig.  12:  Heating  rod  and  Pt100  temperature  sensor  

  14
     
     
INSTRUCTIONS   FOR   LC2030  
 

DESCRIPTION   OF   THE   CONTROL   PANEL  

The   workstation’s   control   panel   provides   all   signals   for   level,   flow   rate,   temperature   and   level  
switches  and  also  provides  plugs  for  pumps  and  the  heater.  For  various  tasks  switches  and  lamps  on  
the  control  panel   may  be  used    (e.g.  traffic  light).  
 
The  control  panel  provides  a  24V  DC  supply    for  process  hardware  (e.g.  Beckhoff  hardware).  
 
The   analog   signals   of   level,   flow   rate   and   temperature   are   provided   as   0(2)...10V   DC.   The   control  
signal  for  pump  P3  is  also  in  a  range  of  0...10V  DC.  
The   heating   rod   socket,   the   power   inlet   and   the   main   switch   are   located   on   the   left   side   of   the  
control   panel.  There  is  a  fuse   inside  the   power  switch,   in  case  of   damage  it  has  to   be  replaced  by  a  
250VAC  6.3A  medium  time  lag  fuse  (20mm  x  5mm).  
 

 
 
Fig.  13:  Control  panel    
 
LEVEL   SENSOR   CONNECTOR  
 
 
Connector  for  level  switches  LS1,  LS2,  LS3:   M8-­‐Sensor  socket  
Pt100-­‐Thermometer  connector:   M12-­‐Sensor  socket  
Connector  for  signals:   4mm-­‐Sockets  
 
LAMPS  
 
The   lamps   can   be   used   for  different   tasks:   e.g.   to   show   status   or   alarm.   The   lamps   need   a   24V   DC  
input  signal,  which  has  to  be  connected  to  the  socket.  
 
LAMPS  
LAMP1   Red  LED   24V  DC  
LAMP2   Yellow  LED   24V  DC  
LAMP3   Green  LED   24V  DC  

  15
     
     
     
INSTRUCTIONS   FOR   LC2030  
 

SWITCHES  
 
The   switches   provide   24V   DC   at   the   corresponding   socket.   The   voltage   may   be   used   to   run   e.g.  
pumps,  lamps  or  the  heating  rod.  
 
 
 

SWITCHES  
HS1   Standard  switch   24V  DC  
HS2   Standard  switch   24V  DC  
HS3   Standard  switch   24V  DC  
HS4   Push  button   24V  DC  
HS5   Push  button   24VDC  
 
BINARY   SIGNALS   (DIGITAL)  
 
 
Three  binary  inputs  for  level  switches  and  five  binary  outputs  for  the  pumps  and  heating  rod  are  
provided.  
 
Binary  input  
LS1   Level  switch  1   24V  DC  
LS2   Level  switch  2   24V  DC  
LS3   Level  switch   3   24V  DC  
 
Binäre  output  
P1   Pump  P1   24V  DC  
P2   Pump  P2   24V  DC  
P3   Pump  P3   24V  DC  
P4   Pump  P4   24V  DC  
TC1   Heating  rod   24VDC  
 
Pump  4  mixes  the  water  in  tank  B1  (circulation  pump).  Pump  P4  should  run  while  using  temperature  
control.  
 
TC1   is  a   binary  signal  of   24V   DC   for   switching  on   the   heating   rod.   (The   heating   rod   is  only  switched  
on,  when  the  level  is  above  LS2).  The  marking  on  the  heating  rod  should  be  below  water  surface  to  
prevent  overheating.  

  16
     
     
     
  INSTRUCTIONS   FOR   LC2030  
 

ANALOG   SIGNALS  
 
Analog  input  signals  for  reading  level,  flow  and  temperature   and  analog  output  signals  for  controlling  
level   and  flow  are  provided.  
 
Analog  Inputs  
L1   Level  signal   2…10V  DC   0…45  cm  
F1   Flow  signal  P3   0…10V  DC   0…6,0  L/min  
F2   Flow  signal  V1   0…10V  DC   0…2,0  L/min  
T1   Temperature   0…10V  DC   -­‐30…70  °C  
 
Analog  Outputs  
FC1   Control  signal  pump  P3   0…10V  DC   0…100%  
FC2   Control  signal   valve  V1   0…10V  DC   0…100  %  
 
Information  for  signal  range:  
The  pressure/level  sensor  provides  a  4...20mA  signal  for  a  range  of  0...45mbar/0...45cm.  This  signal  is  
converted  to  a  2...10V  DC  signal.  For  exact  level  information  an  individual  calibration  is  necessary.  
 
The  0...10V  DC  temperature  signal  corresponds  to  a  range  from  -­‐30  to  70  °C.  
 
The  0...10V  DC  flow  rate  signal  F1  corresponds  to  a  range  from  0.0  to  6.0  L/min.  
The  0...10V  DC  flow  rate  signal  F2  corresponds  to  a  range  from  0.0  to  2.0  L/min.  
 
 
Information  for  pump  3:  
Due  to  technical  requirements  pump  P3  has  a  minimum  flow  rate,  when  the  pump  is  activated.  
 
 
 

VOLTAGE   SUPPLY   (E.G.   FOR   CONNECTION   OF   PROCESS   INTERFACE   ELECTRONIC   OF  


I/O-­‐BOARDS   4488   BZW.   8816)  
 
 
Spannungsversorgung  
24V   24V  DC  
GND   0V  DC  

  17
     
     
     
INSTRUCTIONS   FOR   LC2030  
 
 
 
 
EMPTY   WORKSTATION  
 
 
To  drain  the  water  from  the  workstation,  use  the  water  hose  in  one  of  the  hose  couplings.  
 
 
 
REPLACING   THE   FUSE  
 
 
The  fuse  is  situated  inside  the  power  switch,  in  case  of  damage  it  has  to  be  replaced  by  a  250VAC  
6.3A  medium  time  lag  fuse  (20mm  x  5mm).   Disconnect  the  power  supply  cable.  Open  the  fuse  cover  
carefully  and  exchange  the  fuse,  then  close  the  cover.  

  18
     
     
     
INSTRUCTIONS   FOR   LC2030  
 
 
 
CONNECTING   OF   LC2030   TO   I/O-­‐BOARD   4488  
 
 
 
I/O-­‐Board   LC2030   Signalbeschreibung  
Analog  Input  
AIN1   L1   Level  
AIN2   T1   Temperature  
AIN3   F1   Flow  rate,  controlled  pump  
AIN4   F2   Flow  rate,  controlled  valve  
Analog  Output  
AOUT1   FC1   Controller  output  for  pump  P3  
AOUT2   FC2   Controller  output  for  valve  V1  
AOUT3   /    
AOUT4   /    
Binary  Input  
DIN1   LS1   Level  switch  tank  1,  full  
DIN2   LS2   Level  switch  tank  1,  medium  full  
DIN3   LS3   Level  switch  tank  1,  empty  
DIN4   HS1   Switch  1  
DIN5   HS2   Switch  2  
DIN6   HS3   Switch  3  
DIN7   HS4   Push  button  4  
DIN8   HS5   Push  button  5  
Binary  Output  
DOUT1   P1   Pump  1  
DOUT2   P2   Pump  2  
DOUT3   P3   Pump  3  
DOUT4   TC1   Heating  rod  
DOUT5   P4   Pump  4  
DOUT6   LAMP1   Lamp  1  
DOUT7   LAMP2   Lamp  2  
DOUT8   LAMP3   Lamp  3  
 
 
 
IP-­‐ADDRESS   FOR   BUS   COUPLER   BK9050   (I/O-­‐BOARD   4488)   AND   PC  
 
 
The  bus  coupler  has  the  IP-­‐Address  172.16.17.1,  Subnet  Mask  255.255.0.0  
 
For  communication  with  the  PC  the  PCs  IP-­‐Address  has  to  be  set  to  172.16.17.2  or  higher.  
Subnet  Mask  needs  also  to  be  set  to  255.255.0.0  
 
Use  a  CAT5e  crossover  cable  for  direct  connection  between  PC  and  BK9050  or  use  a  standard  
CAT5e  cable  when  using  a  network  switch.  