MANUAL
LC2030
UK
Technical
Solutions
International
Hawthorn
house
Romans
Business
Park
Farnham
GU9
7SX
United
Kingdom
Tel:
+44
1252
718
710
By
Email:
info@tsi-‐london.com
www.tsi-‐london.com
INSTRUCTIONS
FOR
LC2030
Contents
of
this
manual:
IMPORTANT
INFORMATION
..............................................................................................................................
3
IP-‐ADDRESS
FOR
BUS
COUPLER
BK9050
(I/O-‐BOARD
4488)
AND
PC
................................................................
19
INSTRUCTIONS
FOR
LC2030
IMPORTANT
INFORMATION
When
temperature
is
to
be
controlled,
it
is
important
that
the
water
level
is
above
the
medium
level
switch
and
the
marking
on
the
heating
rod.
To
prevent
damage
to
the
heating
rod
it
is
necessary
to
cool
it
down
(i.e.
leave
it
in
the
water
tank)
for
at
least
30
minutes.
• Do
not
heat
the
water
in
the
tank
to
more
than
45°C.
• The
pumps
must
not
run
dry,
i.e.
without
water.
• Do
not
close
the
valves
completely
as
this
can
damage
the
pumps.
The
input
signal
FC1
is
an
analog
input
and
shall
not
exceed
a
maximum
of
10V
DC.
The
lamps
L1,
L2
and
L3
are
binary
inputs
with
a
maximum
of
24V
DC.
Make
sure,
all
level
switch
plugs
and
the
temperature
probe
plug
are
fully
connected.
3
INSTRUCTIONS
FOR
LC2030
INSTRUCTIONS
FOR
LC2030
The
workstation
LC2030
can
be
used
to
work
on
open-‐loop
control
tasks
(binary)
and
closed-‐loop
control
tasks
(analog).
The
following
closed-‐loop
control
systems
are
available:
• liquid
level
control
• flow
control
• temperature
control
The
workstation
is
equipped
with
an
adjustable
pump
for
flow
and
level
control
and
with
a
heating
rod
and
a
circulation
pump
for
temperature
control.
Level
switches
and
a
pressure
sensor
give
information
about
the
level
in
on
tank.
A
Pt100
resistance
thermometer
and
a
flow
meter
measure
temperature
and
flow
rate.
The
workstation
is
shown
below.
Fig.
1:
Flow
chart
LC2030
4
INSTRUCTIONS
FOR
LC2030
5
INSTRUCTIONS
FOR
LC2030
Heating
rod
Level
drain
B1
B2
LS1
V3
LS2
F1
Operator
panel
230V
socket
for
heating
rod
Power
supply
with
fuse
6
INSTRUCTIONS
FOR
LC2030
7
INSTRUCTIONS
FOR
LC2030
V2
230V
socket
P1
P2
for
heating
rod
Power
supply
with
fuse
P1
P3
8
INSTRUCTIONS
FOR
LC2030
P4
Tank 1 Tank 2
9
INSTRUCTIONS
FOR
LC2030
ELECTRIC
SUPPLY
POWER
SUPPLY
AND
HEATING
ROD
On
the
left
side
of
the
control
panel
you
can
find
the
power
supply
for
230V
and
a
230V
socket
for
heating
rod
plug
(Fig.
7).
Fig.
7:
Electrical
control
and
230V
socket
for
heating
rod
LEVEL
SWITCH
AND
TEMPERATURE
SENSOR
In
Fig.
8
you
can
see
the
connector
for
level
switches
LS1,
LS2,
LS3
and
temperature
sensor
T1.
10
INSTRUCTIONS
FOR
LC2030
FEATURES
LEVEL
CONTROL
Level
control
exercises
are
performed
in
tank
B1.
The
level
is
measured
with
three
level
switches
LS1,
LS2
and
LS3
and
pressure
sensor
L1.
The
analog
signal
of
level
in
tank
B1
is
provided
at
socket
L1
in
a
range
of
2..10V
DC
for
0..45cm.
Tank
B1
is
being
filled
by
pumps
P1
and
P2.
Pump
P3
pumps
the
water
into
Tank
B2.
For
level
control
the
flow
LS1
rate
of
pump
P3
is
adjustable
by
an
analog
signal
FC1
(0...10V).
To
influence
the
control
system
it
is
possible
to
switch
pumps
P1
and
P2
on
and
off.
With
the
hand
valves
flow
rate
of
pumps
P1
and
P2
can
be
adjusted
or
influenced
(see
also
Fig.
1).
LS2
The
level
sensor
can
also
be
connected
to
tank
B2
for
level
control
by
input.
LS3
Fig.
9:
Level
control
in
B1
11
INSTRUCTIONS
FOR
LC2030
FLOW
CONTROL
F1
The
flow
control
is
influenced
by
the
signal
FC1
(revolution
speed,
pump
P3).
By
using
the
hand
valve,
the
flow
rate
can
be
varied.
The
analog
signal
of
the
flow
rate
is
provided
at
socket
F1
with
a
range
of
0..10V
DC
for
0..6L/min.
V3
F1
Fig.
10:
Sensor
of
flow
control
F1
and
hand
valve
V3
12
13
INSTRUCTIONS
FOR
LC2030
TEMPERATURE
CONTROL
The
heating
rod
has
to
be
connected
to
the
230V
socket
at
the
left
side
of
the
control
panel
and
the
Pt100
thermometer
to
the
socket
“Temp.“
on
the
top
of
the
control
panel.
To
prevent
damage
to
the
heating
rod
and
the
workstation,
it
is
only
possible
to
switch
on
the
heater,
when
the
water
level
in
tank
B1
is
above
LS2.
All
level
switches
need
to
be
connected.
Additional
to
level
switch
LS2
the
marking
on
the
heating
rod
has
to
be
below
the
water
surface.
Pump
P4
should
be
running
to
mix
the
water
in
tank
B1.
Mark
for
minimum
Immersion
depth
14
INSTRUCTIONS
FOR
LC2030
The
workstation’s
control
panel
provides
all
signals
for
level,
flow
rate,
temperature
and
level
switches
and
also
provides
plugs
for
pumps
and
the
heater.
For
various
tasks
switches
and
lamps
on
the
control
panel
may
be
used
(e.g.
traffic
light).
The
control
panel
provides
a
24V
DC
supply
for
process
hardware
(e.g.
Beckhoff
hardware).
The
analog
signals
of
level,
flow
rate
and
temperature
are
provided
as
0(2)...10V
DC.
The
control
signal
for
pump
P3
is
also
in
a
range
of
0...10V
DC.
The
heating
rod
socket,
the
power
inlet
and
the
main
switch
are
located
on
the
left
side
of
the
control
panel.
There
is
a
fuse
inside
the
power
switch,
in
case
of
damage
it
has
to
be
replaced
by
a
250VAC
6.3A
medium
time
lag
fuse
(20mm
x
5mm).
Fig.
13:
Control
panel
LEVEL
SENSOR
CONNECTOR
Connector
for
level
switches
LS1,
LS2,
LS3:
M8-‐Sensor
socket
Pt100-‐Thermometer
connector:
M12-‐Sensor
socket
Connector
for
signals:
4mm-‐Sockets
LAMPS
The
lamps
can
be
used
for
different
tasks:
e.g.
to
show
status
or
alarm.
The
lamps
need
a
24V
DC
input
signal,
which
has
to
be
connected
to
the
socket.
LAMPS
LAMP1
Red
LED
24V
DC
LAMP2
Yellow
LED
24V
DC
LAMP3
Green
LED
24V
DC
15
INSTRUCTIONS
FOR
LC2030
SWITCHES
The
switches
provide
24V
DC
at
the
corresponding
socket.
The
voltage
may
be
used
to
run
e.g.
pumps,
lamps
or
the
heating
rod.
SWITCHES
HS1
Standard
switch
24V
DC
HS2
Standard
switch
24V
DC
HS3
Standard
switch
24V
DC
HS4
Push
button
24V
DC
HS5
Push
button
24VDC
BINARY
SIGNALS
(DIGITAL)
Three
binary
inputs
for
level
switches
and
five
binary
outputs
for
the
pumps
and
heating
rod
are
provided.
Binary
input
LS1
Level
switch
1
24V
DC
LS2
Level
switch
2
24V
DC
LS3
Level
switch
3
24V
DC
Binäre
output
P1
Pump
P1
24V
DC
P2
Pump
P2
24V
DC
P3
Pump
P3
24V
DC
P4
Pump
P4
24V
DC
TC1
Heating
rod
24VDC
Pump
4
mixes
the
water
in
tank
B1
(circulation
pump).
Pump
P4
should
run
while
using
temperature
control.
TC1
is
a
binary
signal
of
24V
DC
for
switching
on
the
heating
rod.
(The
heating
rod
is
only
switched
on,
when
the
level
is
above
LS2).
The
marking
on
the
heating
rod
should
be
below
water
surface
to
prevent
overheating.
16
INSTRUCTIONS
FOR
LC2030
ANALOG
SIGNALS
Analog
input
signals
for
reading
level,
flow
and
temperature
and
analog
output
signals
for
controlling
level
and
flow
are
provided.
Analog
Inputs
L1
Level
signal
2…10V
DC
0…45
cm
F1
Flow
signal
P3
0…10V
DC
0…6,0
L/min
F2
Flow
signal
V1
0…10V
DC
0…2,0
L/min
T1
Temperature
0…10V
DC
-‐30…70
°C
Analog
Outputs
FC1
Control
signal
pump
P3
0…10V
DC
0…100%
FC2
Control
signal
valve
V1
0…10V
DC
0…100
%
Information
for
signal
range:
The
pressure/level
sensor
provides
a
4...20mA
signal
for
a
range
of
0...45mbar/0...45cm.
This
signal
is
converted
to
a
2...10V
DC
signal.
For
exact
level
information
an
individual
calibration
is
necessary.
The
0...10V
DC
temperature
signal
corresponds
to
a
range
from
-‐30
to
70
°C.
The
0...10V
DC
flow
rate
signal
F1
corresponds
to
a
range
from
0.0
to
6.0
L/min.
The
0...10V
DC
flow
rate
signal
F2
corresponds
to
a
range
from
0.0
to
2.0
L/min.
Information
for
pump
3:
Due
to
technical
requirements
pump
P3
has
a
minimum
flow
rate,
when
the
pump
is
activated.
17
INSTRUCTIONS
FOR
LC2030
EMPTY
WORKSTATION
To
drain
the
water
from
the
workstation,
use
the
water
hose
in
one
of
the
hose
couplings.
REPLACING
THE
FUSE
The
fuse
is
situated
inside
the
power
switch,
in
case
of
damage
it
has
to
be
replaced
by
a
250VAC
6.3A
medium
time
lag
fuse
(20mm
x
5mm).
Disconnect
the
power
supply
cable.
Open
the
fuse
cover
carefully
and
exchange
the
fuse,
then
close
the
cover.
18
INSTRUCTIONS
FOR
LC2030
CONNECTING
OF
LC2030
TO
I/O-‐BOARD
4488
I/O-‐Board
LC2030
Signalbeschreibung
Analog
Input
AIN1
L1
Level
AIN2
T1
Temperature
AIN3
F1
Flow
rate,
controlled
pump
AIN4
F2
Flow
rate,
controlled
valve
Analog
Output
AOUT1
FC1
Controller
output
for
pump
P3
AOUT2
FC2
Controller
output
for
valve
V1
AOUT3
/
AOUT4
/
Binary
Input
DIN1
LS1
Level
switch
tank
1,
full
DIN2
LS2
Level
switch
tank
1,
medium
full
DIN3
LS3
Level
switch
tank
1,
empty
DIN4
HS1
Switch
1
DIN5
HS2
Switch
2
DIN6
HS3
Switch
3
DIN7
HS4
Push
button
4
DIN8
HS5
Push
button
5
Binary
Output
DOUT1
P1
Pump
1
DOUT2
P2
Pump
2
DOUT3
P3
Pump
3
DOUT4
TC1
Heating
rod
DOUT5
P4
Pump
4
DOUT6
LAMP1
Lamp
1
DOUT7
LAMP2
Lamp
2
DOUT8
LAMP3
Lamp
3
IP-‐ADDRESS
FOR
BUS
COUPLER
BK9050
(I/O-‐BOARD
4488)
AND
PC
The
bus
coupler
has
the
IP-‐Address
172.16.17.1,
Subnet
Mask
255.255.0.0
For
communication
with
the
PC
the
PCs
IP-‐Address
has
to
be
set
to
172.16.17.2
or
higher.
Subnet
Mask
needs
also
to
be
set
to
255.255.0.0
Use
a
CAT5e
crossover
cable
for
direct
connection
between
PC
and
BK9050
or
use
a
standard
CAT5e
cable
when
using
a
network
switch.
19