Documente Academic
Documente Profesional
Documente Cultură
Produced by:
PLANNING GUIDE
Disclaimer:
This publication was made possible through support of the American people provided by the U.S.
Agency for International Development (USAID). The opinions expressed herein are those of
International Resources Group and do not necessarily reflect the views of USAID or the United
States Government.
Table of Contents
1. Distribution System 1
1.1. Distribution System Planning 1
1.1.1. Planning Criteria 2
Amps Amperes
HT High Tension
IT Information Technology
KV Kilo Volt
KW Kilowatt
KWh Kilowatt-hour
LT Low Tension
MW Megawatt
ACRONYMS
P&D Planning and Design
PF Power Factor
T/F Transformer
VAR Volt-Amps-Reactive
LIST OF TABELS
Table 1: Planning Criteria.............................................................................................3
Table 2: Sample Calculation of Different Factors (HT)..............................................30
Table 3: Economic Conductor Size for Replacement (HT)........................................36
Table 4: Economic Conductor Sizes for New HT line................................................39
Table 5: Economic Conductor Sizes for Replacement in LT......................................44
Table 6: Maximum Allowable Service Cable Length.................................................44
Table 7: Economic Conductor Size for New LT Line................................................46
Table 8: Permissible Limits........................................................................................49
Table 9: Prioritization of HT Proposals......................................................................49
Table 10: Growth Factors...........................................................................................53
Table 11: Prioritization of LT Proposals.....................................................................55
Table 12: Maximum Span Lengths for the New HT Line.............................................1
Table 13: Maximum Span Lengths for the New Composite Line.................................1
Table 14: Maximum Span Lengths for the New LT Line.............................................1
Table 15: Secondary Loading Number of Spans (60 m Each)......................................2
Table 16: Typical Core and Winding Losses in Distribution Transformers..................1
Table 17: Fuse Rating for Distribution Transformer.....................................................4
Table 18: Current Carrying Capacity (HT Cables).......................................................1
Table 19: Current Carrying Capacity (LT Cables)........................................................2
Table 20: Characteristics of Conductors (Aluminum and ASCR)................................3
Table 21: Characteristics of Conductors (Copper)........................................................4
Table 22: Capacitor Judgment Factors........................................................................14
Table 23: Corrected Power Factor Selection Table.....................................................20
Table 24: Fuse Rating for HT Capacitor.....................................................................27
Table 25: Fuse Rating for LT Capacitor.....................................................................27
LIST OF FIGURES
Figure 1: Components of Electricity Distribution System 1
Figure 2: Network Risk Assessment 4
Figure 3: Annual Feeder Load 15
Figure 4: Bifurcation of 11 KV Feeders 39
Figure 5: Maximum Allowable Service Cable Length 45
1. DISTRIBUTION SYSTEM
Power distribution is the final stage in the delivery of electricity to end users – the
distribution system carries electricity from the transmission system and delivers it to
consumers. Typically, in Pakistan the distribution network comprises of
mediumvoltage (mostly 11KV& rarely 33 KV)feeders commonly known as high
tension (HT), network distribution transformers, lowvoltage lines (0.415 KV) referred
to as low tension(LT) network,service drops and energy meters at the consumer’send.
Distribution networks are typically of two types, radial and looped or interconnected.
A radial network originates from the grid station and passes through the network area
with no normal connection to any other power source. An interconnected network will
have multiple connections to other points of the power supply. These points of
connection are normally open, but allow various configurations by the operating
utility through closing and opening switches. Operation of these switches may be
performed automatically from a control center or manually by a lineman. The benefit
of the interconnected model is that in the event of a fault or required maintenance, a
small area of the network can be isolated while the remaining portion is kept
energized;however, the distribution networks constructed in Pakistan aremostly radial.
3. PLANNING CRITERIA
These planning criteria are the principles and prescribed limits on the basis of which
the system is planned, designed, and operated. Fundamental or primary planning
criteria applicable to distribution network are voltage, power factor, capacity,
reliability, and technical losses, etc. In effect they define what should or should not be
considered a problem with respect to system loading, voltage profile, and reliability.
These are the parameters that define the threshold (limits) of acceptable distribution
performance. If the system is planned and designed to operate within prescribed
limits, normally the technical losses remain within acceptable limits. The planner of
the distribution system is guided by the following general principles:
Under normal operating conditions, i.e. with no system component fault, all
equipment will operate within normal ratings and the system voltages will remain
within permissible limits when the system is operating anywhere from the
minimum load to forecasted maximum peak load.
Under system emergency condition i.e. with the system or the equipment at
fault, the power equipment may be operated with overloaded and / or under
voltage for the limit and for a specific period. Planning is based on normal and
emergency power equipment ratings. Emergency ratings are those which the
equipment can safely withstand for a specified period.
There are many types of limits for electrical equipment; one of them is thermal
capability which is the demand-carrying ability of all the elements of an electrical
device. Various distribution items have nameplate ratings that denote maximum
loading they were designed to handle. For example, conductors have given current
carrying capabilities that vary greatly over different ambient temperatures/ loading
conditions.
The overall process employs the evaluation of existing system with existing load and
subsequently the existing distribution system is analyzed with forecasted/projected
load. These two methods are sometimes referred to as EXI-EXI; and EXI-PRO
analysis. Based on the results of these two analyses a new distribution system is
proposed and evaluated against the projected load. It is called PRO-PRO analysis
model. In order to properly model and analyze the existing system and its load, it is
essential to have sufficient historical records. A typical work flow for analysis is as
shown in Figure 2:
EXI-EXI
Network Risk Assessment
Load Allocation, Load Flow
Calculation of plant
ratings based on
predefined
Yes/No standards condition
Pass and load profiles
EXI-PRO
Load Forecasting
Calculation Medium to long range
of plant
ratings Network Risk Assessment
based on Load Allocation, Load Flow
predefined
standards
No
condition
and
Pass
Projected
Yes
load.
PRO-PRO
Network Rehabilitation
Calculation of proposed
No Capacitor installation (Fixed/Shunt) plant ratings based on
Reconductoring predefined standards
Action
condition and Projected
load.
Network Risk Assessment
Load Allocation, Load Flow
Yes
Pass
Network Rehabilitation with
Benefit to
Cost No Augmentation
The analysis mainly involved in network risk assessment is conducted through load
allocation and load flow studies. Load flow analysis studies are used to determine
expected circuit overloads and to evaluate alternatives for system reinforcements
based on the results of the load flows.These studies then determine whether the
network requires rehabilitation measures or not.
Normally when an existing system is extended it also undergoes such studies like
network risk assessment etc. However, to meet with the increasing demand, the power
distribution network is extended without proper analysis and augmentation. This
result in increased energy losses and a voltage drop beyond permissible limits. The
engineering economics and finance both indicate toward their reduction in the
existing as well as future extensions. For the reduction in energy losses and voltage
drops some means are adopted to augment and rehabilitate the existing distribution
system.
The ELR is an iterative process to reduce the annual energy loess incurred by the
distribution company. Major factors affecting energy losses are voltage drop in
distribution network are listed below.
Impedance of line conductor
Loading of line conductor
Power factor
Poor maintenance
Defective/Sluggish meters
Theft of electricity
Thus the distribution network must be constantly monitored to reduce these factors
and the cost of rehabilitation should be justified against the benefits. The major
activities that are performed under ELR are:
Area planningwith or without network augmentation
Capacitor installation (Fixed/Shunt)
Reconductoring
Transformer Relocation
Replacement of Sluggish equipment
Feeder Bifurcation
Transformer Augmentation
These programs deal with projects where the distribution of power or continuity of
services is the main objective instead of feasibility. Major activities performed under
this program are:
Construction of feeders due to addition of a 132 KV new transformer, new
132 KV grid station, conversion from 66 KV to 132 KV, and augmentation of
power transformer to relieve a nearby overloaded grid station.
Rehabilitation of feeder by replacement of conductor, pole, structure or the
introduction of new ones by mid spanning (to reduce span length).
Deteriorated conductor (with broken strands) or a conductor with more /
unacceptable number of joints may be replaced on top priority basis. This holds
for conductors of any size.
The following techniques reduce the unit receipt and hence, reduce the energy losses
and voltage drops.
Area planning without the addition of new feeders, i.e. shifting load from
heavily loaded feeders to the adjoining lightly loaded feeders in the vicinity.
Installation of HT shunt capacitors (fixed/switched):
Reconductoring, i.e. replacement of existing conductor with higher capacity
conductor.
Bifurcation of feeder i.e. addition of new feeder to shift some of the load of
the existing feeder.
Area planning with the addition of new feeders.
Area planning at the grid station level is sometimes required to provide relief
to the overloaded grid stations by shifting its load to nearby under-loaded or
newly constructed grid stations. Area planning may or may not involve new
feeders.
Load balancing of distribution transformers.
Relocation of distribution transformer i.e. shifting of transformer to the load
center.
The following measures can be taken to improve the units sold and reduce the overall
loss.
Shifting of meters outside the customer’s premises.
Proper vigilance by the officers/officials to avoid theft of electricity.
Detection of units through checking/surveillance by officers.
Combing of feeders.
Installation of check meters.
Replacement of old and defective/sluggish meters.
Note: Reduction in theft of electricity and its measures are not in the scope of this
guideline.
In case of SynerGEE, sections are the basic building blocks of the electricity
distribution system model. A section represents an electrical path between two end
points (nodes), and can use vertices primarily to form the geographic path of the line.
Thus a single data layer is used to represent a section and its vertices and a node or a
vertex cannot exist without a section. A data layer is a digital representation of real
world objects, into a series of data themes, which can be integrated using geographic
location. Each section, in SynerGEE, is composed of an overhead or underground
conductor segment and a group of devices and/or loads. All the elements in the
distribution model are inter-connected through conductor segments and thus have
their association with some particular Section. All the equipment/devices can only be
associated with existing section and cannot exist without a section.
Node
2 3
Vertex A
D
B C
1
The GIS created works on relational database model in which the storage objects are
tables which store data in rows and columns.A simplified E-R diagram of SynerGEE
model is as shown below.
ESRI’s ArcGIS works with geographic information in numerous file formats, but it is
specially designed to work with and leverage the capabilities of the geodatabase. It is
the primary data format used for editing and performing other data management tasks.
An ArcGIS geodatabase is a collection of geographic and tabular datasets of various
types held in a common file system folder. It is a container of geographic and tabular
datasets which may reside as stand-alone or related to each other.The following figure
indicates the core elements of a typical geodatabase.
There are three types of geodatabases namely File, personal and ArcSDE geodatabase.
The File geodatabase is used due to its improved versatility, optimized performance
and almost no size limitation.
Feature datasets provides a way to group feature classes with the same spatial
reference.Feature datasets also have a natural organizational quality, much like a
folder on a file system. Since for many geographic information system (GIS)
applications the majority of the data for a particular database has the same spatial
reference, it is possible to use feature datasets as organizational containers. The grid
station names are used to group feeders as shown;
A feature class is a collection of features that have the same spatial representation (for
example, point, line or polygon) and share a common set of descriptive attributes. The
GIS is mainly composed of three feature classes Substation, Pole and Lines.
The substation feature class contains one single point to represent the location of the
facility.
All the nodes, vertices and devices such as transformer, capacitor and fuses etc.
present in the distribution system are represented in one layer. Due to the fact that
largely nodes and vertices are formed at poles assemblies the layer is named as
“Pole”.
Line is the feature class used to store sections in ArcGIS environment. The layer is
named keeping in view the common nomenclature as sections are generally referred
to as electrical lines.
18. TABLE
In the geodatabase, attributes that are not associated directly with geographical
element are managed in tables based on a series of simple relational data concepts.
Tables can be joined to a feature class based on an item or can reside as stand-alone.
The substation and feeder names are assigned three character unique text codes; so
that the feeder line and pole feature classes can be properly named. These codes along
with full names are stored separately in Substation and Feeder tables. A sample of
these tables is shown below.
The field survey is conducted with the help of Global Positioning System (GPS). The
GPS has changed the way GIS users collect and manage spatial data. The technology
is offering a very high accuracy even with a navigator class GPS device. The GPS
device particularly used is Garmin GPS 78s and was selected due to its ruggedness.
The device is quite simple in operation and is equipped to handle different projection
systems.
The projection system employed for GIS is “Universal Transverse Mercator (UTM)”,
which is a conformal projection. The UTM system is not a single map projection. The
The DISCOs falling within multiple zones must develop and maintain independent
data for each zone. The coordinate system must be selected on the GPS device prior to
commencing the field survey. The settings are available under the Setup menu and
Position format Sub menu. Following indicate the system setting on the GPS.
Another important factor that must be considered during the field survey is the time
provided to GPS device to lock the satellite signals as the GPS technology works on
the basis of time. A GPS receiver listens to multiple satellites and solves equations to
determine its exact position. At a minimum, four satellites must be in view of the
receiverfor a reasonable amount of time so that the GPS can estimate the location
within accuracy of the location within ±5m. The Following indicate the system setting
and a representative coordinate marked after surveying.
Theattribute information is collected with the help of survey forms. The design of the
survey form is kept very simple and all the details regarding the electrical line such as
conductor type and regarding the equipment such as its capacity/size make and other
related information is collected from the site. The field surveyors also mark a unique
number on the poles. This number is generated by combining various fieldsas shown:
Device Date Of Survey GPS
Number Waypoint
d d m m y y
2 4 1 5 0 5 1 5 1 2 5
Table 2; Unique Survey Code Detail
SynerGEE Electric is a software product for modeling, simulating, and analyzing the
power distribution systems. It provides a modelling environment that facilitate user to
perform various analysis and simulate different network arrangement. The network
intelligence that has been built in SynerGEE Electric is managed mainly by two types
of datatypes.
Model Data
Model data is used to build the topology of a model. Model data includes information
on sections, nodes and equipment location. In other words Model data includes the
instance data associated with the spatial construction of electric distribution network.
Equipment Data
Equipment data can be thought of as a “virtual warehouse” of power system devices.
Equipment data refers to the nameplate equipment data that is mostly invisible in the
map display but plays a critical role during SynerGEE analysis. Most devices have
some sort of equipment data associated with them that describes the type of device
and related operational parameters. Equipment data also includes “zone” data, such as
the definitions of customer zones etc. The equipment data is stored in a warehouse.
Data Entry
Schema
SynerGEE Schema
The loading profile provides a better understanding of the system’s behavior under
different loading conditions. If one peak value of the load is used to calculate energy
loss for the entire year, it will result in an approximate value.This generalization,
however, is unavoidable in the absence of detailed data.
Analysis of EXI-EXI model is performed in SynerGEE to view a complete and
comprehensive detail of existing model and to observe whether any rehabilitation is
required in the existing model or whether a shift to the EXI-PRO model is
possible.The steps listed below are required to perform EXI-EXI analysis in
SynerGEE:
III. In order to run the load flow analysis it is essential to allocate the loads.
IV. In the “Planning” ribbon group, select the arrow under load allocation.
V. A submenu will appear.
The “Feeder/ Station Summary” contains information regarding the loading of the
feeder as shown below.
XI. The above window indicates the summary of the load flow analysis results:
The tab on the right contains various chapters of the report that will help us
analyze various aspects of distribution network. The relevant chapters are
discussed in detail below.
XII. The chapter “Feeder Summary” provides information regarding line loss,
transformation loss and total feeder KWloss. The transformation losses include
the no-load loss and the copper loss. Feeder losses include line loss and
transformation loss of distributed transformers.
XIII. The detailed losses both in KW and KVAR in each section/equipment are
available in the “Losses” chapter.
XV. In order to determine that the voltage received by the customer at each node is
within permissible limits, please see the “Balance Results” chapter. The
balance results will display voltage out values on each section. One can use the
filter on top of the column to identify all sections where the voltage does not
satisfy the conditions.
III. After adding these groups, the percentage growth rate in section records must
be edited. The default settings are at 2% as shown.
IV. The software is flexible and can have different growth rates at different
sections. This procedure is very useful because it is not necessary to increase
growth on all sections of a feeder. It is more appropriate to assign different
VI. After selecting “Query”, draw a rectangle around the parameter of the feeder to
select all equipment as shown.
VII. Once the selection is complete and the right click is released, a small window
will appear along with the cursor for launching the “Multiple Editor”. Select
the load selection button as shown below.
VIII. A window will appear for the load setting. Select the growth option from the
menu on the left as shown (below) and apply the settings below.
X. The reports can be analyzed one by one as discussed in the EXI-EXI model or
the analyst can turn directly to the warning chapter under the reports section.
These warnings help to determine system reliability and loading status of
equipment. This analysis provides a guideline to decide what sort of
rehabilitation measure is required.
The SynerGEE software does not automatically store the report generated during
analysis. To retrieve reports at a later stage they must be saved manually. The process
for saving reports in Adobe Acrobat’s PDF format is explained below.
I. There is a command available for printing multiple chapters available in the
“Control” ribbon as shown.
III. After selectingthe desired report chapters,click the “Finish” button at the
bottom of the screen and the “Print” window will appear.
IV. Select the Adobe printer and check the “Print to File” option to save the output
as a PDF.
The remaining settings regarding the page layout can be performed in the “Page
Setup” dialogue box. “Page Setup” can also be accessed by pressing the pole icon on
the extreme right and selecting page setup as shown.
III. Select the Data Source Alias(DSA) for the Model as the window above does
not require the location of where to save the version; rather it requires the DSA
of the base model. This will enable the software to compare Base Model to
Version for changes. Click Next.
IV. Another window will appear. The DSA for the version to be saved should be
selected. It is recommended that the same DSA as the model is selected to keep
the data of one feeder at one place. The button can be used to add the
source model DSA as shown.
V. After selection of the DSA click “Next”,the following window will appear. The
name and description of “Versions”are entered as shown below.
VIII. Select the DSA of the versioned data sources listed. Select “Next”.
IX. All the version regarding that feeder will be listed and can be loaded by using
the combo box. Click “Finish” to load the version. Similarly, various other
versions can be saved and loaded accordingy for analysis purposes.
The following table illustrates the use ofannual data to calculate different factors
NAME HT FEEDER = ABC CIRCUIT CONNECTED KVA = 5300
INPUT SECTION + OUTPUT SECTION
MONTH
II. A window will appear listing all capacitors in one place.The capacitor
placement settings can be accessed by pressing the “Settings” button as shown.
IV. SynerGEE will also encircle the recommended location of capacitors on the
feeder map. Click the button in the SynerGEE placement tool. The
software also enables users to mark the selected capacitor on the map by a
circle as shown.
VI. The placed capacitor is temporary untilit is made permanent after reviewing its
impact through the “Report” button.
VII. The capacitor can be made permanent by pressing the “Permanent” buton and
similarly can be removed by pressing the “Remove” button.
The following table presents the economic loading in Amp for replacing a conductor
with agreater size. This table should be used for all conductor replacement on existing
HT feeders for energy loss reduction and renovation. A conductor of higher than
economic size may only be used if the voltage drops of the feeder exceed the 5%
limits in the case of rural feeders and 3% in the case of urban feeders.
Existing New Loading level above which new
Conductor Conductor conductor is economical(Amps)
Gopher Rabbit 41
Gopher Dog 42
Gopher Panther 63
Gopher Osprey 77
Rabbit Dog 74
Rabbit Panther 96
Rabbit Osprey 106
Dog Panther 164
Dog Osprey 168
II. A subsequent series of windows will appear for entering the selection criteria
which in this case, is based on the results shown below:
III. Check the selection criteria based on which the query will be built. Multiple
criteria can be selected simultaneously.
IV. The next screen contains details regarding the source of the query i.e. at what
data set the query should be applied.
VI. A list of selected objects is displayed as shown and thus they can be edited one
by one or by clicking the “Launch Multiple Editor” button.
This table presents lower and upper economic loading limits for distribution
conductor, in Amperes and should be used for planning of the new HT Feeders.
Lower Limit Upper Limit
Conductor
(Amps) (Amps)
Gopher Not to be used in the future
Rabbit 0 41
Dog 42 103
Panther 104 Above 104
Osprey 104 Above 104
IV. Select one of the recommended options and place it;the selected load balancing
option will be moved to second place.
III. The section can be connected anywhere without giving consideration to its
orientation because it has zero value for length. Thus multiple load flow
analysis can be executed to identify an optimal location.
Ant wasp 85
The following chart must be read in conjunction with the above table.
Wasp 74 Above 74
The main criteria for proposal selection is the Benefit to Cost ratio, however, the
following table can be used where needed for the prioritization of proposals.
% AEL % VD B/C Ratio
Share: 50 % Share: 30 % Share: 20 %
Value Weight Value Weight Value Weight
3–4 1 5 – 10 1 1–2 1
4–5 2 10 – 15 2 2–3 2
5–6 3 15 – 20 3 3–4 3
6–7 4 20 – 25 4 4–5 4
7–8 5 25 – 30 5 5–6 5
8–9 6 30 – 35 6 6–7 6
9 – 10 7 35 – 40 7 7–8 7
Operation formation will develop the HT proposal and submit to Planning and Design
(P&D) directorate along with following information/documents for further
scrutiny/approval.
c. Input data sheet (stacking sheet) of existing and proposed feeders as per Format-IV.
d. Data by month of the max/min load of grid station power transformers involved in
the proposal for the last three years as per Format-V.
e. Monthly technical data of 11 KV feeders involved in the proposal for last three
years as per Format-VI.
f. Indicate the category of 11KV feeder i.e. according to the following:
Urban / Rural / Industrial / Dedicated.
g. Availability of 11KV outgoing panels at grid stations and the identification of right-
of-way problems.
56. TECHNICAL ANALYSIS AND OTHER IMPORTANT PARAMETERS KEPT IN VIEW FOR
TECHNICAL ANALYSIS
a. Load flow studies of existing and proposed situation of feeders (with and without
capacitor) should be carried at peak load (without growth) by using SynerGEE or PSS-
adept software (already available in each DISCO).
b. The results of existing and proposed conditions (with and without growth) at zero
year study should be compiled as per Formats-VIII (A&B) & IX (A&B)respectively.
c. Net benefits/savings in losses that would be achieved (with and without growth)
should be calculated as per Formats-X (A&B).
d. The average power factor of 11KV feeder may be calculated by taking the reading
of KWh and KVARh meters installed at grid stations or power factor meter, if available. If
power factor reading is not available, then assume the power factor as under:
Benefit to Cost calculation shall be carried out (as per Format-XIII) as follows:
Benefit to Cost Ratio = Annual Benefits (Rs) – 0.04 (NFC)
– (0.60 x 0.143) (RFC) with Growth/0.143 (NFC)
Where,
NFC stands for New Facility Cost (Rs)
RFC stands for Replaced Facility Cost (Rs)
0.04 O&M charges (4% per annum)
0.60 Depreciation Factor for Replaced Facility
0.143 Capital Recovery Factor (CRF) is the
calculated @ 14% opportunity cost of capital for
equipment life of 30 years
CRF = (1 - i)n x i/(1 + i)n – i
n is the period of study (here 30 years)
Manager Project Construction will be bound to complete the whole work within 60
days of issue of Work Order and to intimate to all the concerned.
After completion of work, Manager Project Construction will energize/shift the load
as per the approved plan in coordination with Grid Station Operation
(GSO)/Operation formation within 10 days and hand over the work to Operations
formation. After energizing/shifting the load, Manager Project Construction will
submit the completion report to P&D Directorate for inspection as per Format-XIV.
All completed works will be finally checked/inspected 100% for all technical
parameters quality and quantity of ELR and DOP by Director (P&E).
65. DATA/INFORMATIONCOLLECTION
Single-phase customers falling in urban areas have been divided into the following
categories:
Posh Localities: Load per S/Phase customers is considered as 4 KVA.
Benefit to Cost Ratio may be calculated (as per Format-X) by using the following
sheet:
I. Annual Energy Loss after 5 years
a) Existing system = _______________KWh
Where EPR stands for Electricity Purchase Rate (Rs / KWh) of the DISCO.
II.
a. Loading of existing ____KVA
transformer at present = __________% KVA
b. Loading of existing ____KVA
Manager Project Construction will be bound to complete the whole work within 30
days of issuance of the Work Order, and to intimate to all the concerned.
After completion of the work, Manager Project Construction will energize/shift the
load as per the approved plan in coordination with operation formation within 10 days
and hand over the work to the Operations formation. After energizing/shifting the
load, Manager Project Construction will submit the completion report to P&D
Directorate for inspection as per Format-XI.
All completed works will be finally checked/inspected 100% for all technical
parameters quality and quantity of ELR and DOP by Director (P&E).
He will check/inspect the completed work within 15 days of receipt of completion
report from Manager Project Construction and issue completion certificate as per
Format-XII, if the work has been executed according to the approved plan and as per
WAPDA SDI. The check should not ignore even a single missing bolt.
Representatives of Chief Engineer (ELR), WAPDA & Director (Distribution
Planning), WAPDA may also check/inspect any work.
Total time will be restricted to 62 working days (i.e. from approval of proposal to
inspection/completion certificate); the officer mentioned above, will share any delay
beyond this.
MAXIMUM DEMAND
The maximum demand of an installation or system is the largest of all the demands,
occurringover a specified period of time (most severe condition imposed on system
either in terms of thermal loading or voltage drop).This is the sum total of all demands
of all circuits that occur simultaneously during that period.
COINCIDENT FACTOR
It is a ratio of maximum coincident demand of a composite group of customers
(occurring in the same time interval), to the sum of the maximum demands of
individual customers comprising the group (occurring at different time intervals). It is
reciprocal of diversity factor.
NON-COINCIDENT DEMAND
It is sum of the demands of a group of loads irrespective of the time interval to which
each demand is applicable. The maximum non-coincident demand is indicative of
(sum total of) average individual maximum demands.
DEMAND FACTOR
This is the ratio of maximum demand to the connected load of the system.It indicates
the degree to which the total connected load is served simultaneously.
LOAD FACTOR
It is the ratio of average load over a specified period of time to peak load occurring in
that period. In fact, load factor indicates the degree to which the peak load is sustained
during the period.
LOAD DIVERSITY
It is the difference between the sum of peaks of two or more individual loads
(occurring in different time intervals) and the peak of the combined load (occurring in
the same time interval).
DIVERSITY FACTOR
It is the ratio of the sum of the individual maximum demands of various subdivisions
of a system (occurring at any/ different time intervals) to the actual maximum demand
(occurring at the same time interval) of the whole system (it is greater than 1). It is
reciprocal of coincident demand.
OR
It is the ratio of the sum total of all maximum demands of the various circuits to the
actual maximum demand of the system.It is, generally, of the order of 1.25.
LOSS FACTOR
It is the ratio of the average power loss to the peak power loss during a specified
period of time.
POWER FACTOR
It is the ratio of the active power to the apparent power.
MAXIMUM VOLTAGE
It is the largest five-minute average or mean voltage.
MINIMUM VOLTAGE
It is the least five-minute average or mean voltage.
VOLTAGE LIMIT
The permissible voltage values which define the extremities of a range, generally
expressed as plus and minus percentage variations from the nominal value.
NOMINAL VOLTAGE
Nominal voltage of a circuit or system is the nominal value assigned for the purpose
of convenient designation. (Its value lies a little above the midpoint of the band of
voltage that falls within the same general class).
RATED VOLTAGE
It is the voltage at which the operating and performance characteristics of equipment
are referred (or the nameplate voltage).
DISTRIBUTION SYSTEM
It consists of all electrical power equipment and facilities used to transfer electrical
energy from the grid station to the customer.
UTILIZATION VOLTAGE
It is the voltage measured at the terminals of the machine or device.
BASE VOLTAGE
It is the reference value which is a common denominator to the nominal voltage
ratings of transmission and distribution lines, equipment, and utilizing equipment.
VOLTAGE REGULATION
It is the percentage of the voltage drop of a line with reference to the receiving end
voltage.
CONSUMER INTERFACE
It is thepoint at which the customer’s load is connected to the utility’s power system.
This is normally the point of metering installation.
CONNECTED LOAD
This is the sum total of the entire nameplate-rated loads of electrical equipment
installed by a customer.
DEMAND FACTOR
LOAD FACTOR
LOSS FACTOR
= a (load factor) + (1-a) (load factor )2
= 0.3 (load factor) + 0.7 (load factor )2
Where, a = 0.3 for distribution system
Another empirical approximation is:
Loss factor = (load factor )3
KVA
Where, Es = 11000 / 3 V,
= 11000 / 1.732 V is the line to neutral (or phase
voltage whereas 11000 V is line to line voltage.
This formula is applicable for calculation of iron as well as copper losses if losses of a
T/F of any capacity are known.
VALUATION FACTOR
= Loss Factor x 8760 x EPR
Where, EPR stands for Electricity Purchase Rate is
in Rs/KWh of the respective DISCO, and
8760 are number of hours in a year,
SPAN LENGTH
The following are the broad guidelines for maintaining span lengths in different
scenarios.
HT Line (11 kV)
Conductor Single Circuit Double Circuit Triple Circuit
36 Ft Lattice Steel 40 Ft Lattice Steel 45 Ft Lattice Steel
Structure, & PC Pole Structure, & PC Structure, & PC Pole
Pole
Urban Rural Urban Rural Urban Rural
Osprey
200 Ft 300 Ft 200 Ft 300 Ft 200 Ft 300 Ft
Panther
Dog
200 Ft 400 Ft 200 Ft 400 Ft 200 Ft 400 Ft
Rabbit
1
Power Distribution Planning Reference Book, Second Edition By H. Lee Willis
This table presents the number of LT spans possible for each conductor for different
loadings. The table is not intended to be a replacement for circuit analysis and is only
to be used to determine the LT circuits which require renovation. This table is not a
replacement of voltage measurement at different points on the system to check losses.
This table is only an indicator of areas requiring renovation.
Transformer
Size 630 KVA 400 KVA 200 KVA 100 KVA 50 KVA 25 KVA
Conductor Size
Gnat - - 2 4 10 20
Ant - - 4 9 19 40
Wasp 2 4 8 17 34 68
Ratio of mixture: 1 : 2 : 4 = 7
Cement = 100.65 cft x 1/7 = 14.38 (cft) ÷ 1.25 (cft per bag) = 11.50 bags
VOLUME OF MIXTURE
FOR
HT (40 FEET) STEEL STRUCTURE FOUNDATION
Size of Foundation = 2 ½’ x 2 ½’ x 7 ½’ = 46.875 cft
Wet mixture required = 46.875 cft x1.5 = 70.31 cft
CEMENTSAND CRUSH
Ratio of mixture: 1 : 2 4 = 7
Quantity of Material Required
Cement = 39 cft x 1/7 = 5.57 (cft) ÷ 1.25 (cft per bag) = 4.45 bags
VOLUME OF MIXTURE
FOR
LT (31 FEET) STEEL STRUCTURE FOUNDATION
CEMENTSANDCRUSH
Ratio of mixture: 1 : 2 : 4 = 7
losses at low power, can be reduced by improving core materials and by reducing
harmonics.
Copper losses, which become more important at high power levels, can be
management.
The following table represents typical core and winding losses in distribution
transformers.
TRANSFORMER SIZE CORE LOSS*/IRON WINDING LOSS**/
(KVA) LOSSES(KW) COPPER LOSSES(KW)
Three Phase
10 0.065 0.320
15 0.085 0.435
25 0.123 0.640
50 0.175 1.170
Single Phase
63 0.205 1.280
Formula:
Losses of a Transformer "A" =KVA rating of transformer "A" x 0.75 x Losses of transformer "B"
KVA rating of transformer "B"
whose losses are known
Step-II
Growth Rate Determine the annual load growth rate. The following are the
recommended values for per customer growth:
Recommended Per
Load Type Customer Growth
Rate of Demand of
Existing Customers
(%)
Rural 3
Urban Low Income 5
Urban High Income 9
Step-III
n = No. of Years
(200/108) = (1.09)n
ln (200/108) = ln (1.09)n
ln (1.852) = n x ln (1.09)
For Operation: Loading of distribution transformer under normal conditions should not
exceed 100 % of its KVA rating.
The following table represents the fuse rating against the transformer rating.
Fuse
Rating T/F Rating KVA Color
1K 10 & 15 Black
3K 25 & 50 Green
6K 75 Brown
10K 100 & 150 Blue
15K 200 & 250 Orange
20K 300 Yellow
30K 400 White
40K 630 Gray
In case of bare conductors the technical data provided in the following table is based
on conductor temperature of 75 degrees C and 40 degrees C ambient, 35 degree rise,
air at 0.61 m/s (2FPS). The conductor data complies with British Standards (BS 215 :
1970 &. BS 3242 : 1970.
Using thePythagorean Theorem, the relationship among real, reactive and apparent
power is:
(apparent power)2 = (real power)2 + (reactive power)2
S =(P² + Q²)
P= 3 VI Cos Ø
Q= 3 VI Sin Ø
S = 3 VI
In transmission/distribution lines, only the active component of the current is useful.
When power factor is low, the phase (active) component is small but the reactive
component is large. Therefore,the large supply (of apparent) current is required for the
same amount of active (load) current. Large reactive component means a large voltage
drop, resulting in greater copper losses requiring voltage regulation equipment, and
decreasing the power equipment efficiency.
If the voltage and current are both sinusoidal then
Power Factor =KW/KVAor
KVA = KW/ Cos Ø
Where, Ø is phase (angle) difference between voltage and current.
In case of three phase system
KVA = 3 VI or
I = KVA/3 V
Therefore, I KVA
The above reveals that KVA is directly proportional to current. Hence, the major
disadvantage of low power factor is that current required for a given useful (KW)
power will be high.
Suppose a three phase balanced system is supplying a load W at voltage V and power
factor Cos Ø, then the current flowing through the conductor is
A few utilities offer reduced billing demand if the actual power factor exceeds the
desired power factor.
Ø2
Ø1
S2 (
KVA
) Q2 (KVAR)
S1 Q1
(K
VA
)
QC (KVAR)
low motor power factor and efficiency, as well as in the reduction of losses in service
cables, LT lines, transformers and HT lines as explained by the figure above.After
capacitor installation,KVAR is reduced from Q 1 to Q2, due to leading KVAR (Qc)
supplied by capacitor, to partially neutralize the lagging KVAR of the system.
Qc = Q1 – Q2
Qc = P (tan Ø1 – tan Ø2)
The capacitor is a static source of reactive power (i.e. leading to reactive current). It
compensates the lagging current of load, but care must be taken while estimating the
maximum capacity of distribution capacitors that can be installed without resulting in
leading power factor.
CAPACITOR TYPES
There are two types of capacitors according to their mode of installation:
Series Capacitors have some drawbacks. First, all load current has to flow
through capacitors, so, when the load increases, larger capacitors are needed.
Second, it boosts the voltage up at the point of installation only.
The effect of series capacitor application on voltage profile of a feeder with uniformly
distributed load is illustrated in the figure below:
Series Capacitor
Rise produced
by Series Cap
Volts
Reference Feeder Profile
with series
Cap
Feeder Profile
without series
Capacitor
Distance
The series capacitor produces no voltage effect between the supply source and the
capacitor location and its entire boost effect is between the capacitor location and the
remote end of the feeder.
EFFECT OF SHUNT CAPACITORS ON FEEDER VOLTAGE PROFILE
The effect of shunt capacitor application on voltage profile of feeder with uniformly
distributed load is illustrated in the figure below:
Capacitors produce a voltage rise as it supplies leading current that
compensates the inductive reactance of the feeder.
As is seen in the above figure, this “voltage rise” increases linearly from zero
at substation to its maximum value at the capacitor location.
Between the capacitor location and the remote end (i.e. load end) of the
feeder, the voltage rise due to capacitor is at its maximum value.
Capacitor
Rise produced by
Capacitor
Volts
Reference Feeder Profile with
Capacitor
When the capacitor voltage-rise profile is combined with the original feeder
voltage profile, the resulting net voltage profile is obtained.
The capacitor increases the voltage level all along the feeder, resulting also in
improved voltage spread.
Proposed permanently connected capacitor application should be checked to
make sure that voltage to some customers near the capacitor location should not
exceed the permissible limits during light load periods.
Switched capacitor application should be checked to minimize the voltage
flicker caused by the switching of the capacitor bank.
BENEFITS OF SHUNT CAPACITORS ON DISTRIBUTION SYSTEM
There are numerous benefits to be gained through Power Factor correction. These
benefits range from reduced demand on power system to increased load carrying
capabilities in existing circuits and overall reduced power system losses.The benefits
of power factor correction aren’t just limited to the balance sheet; there are also huge
environmental benefits associated with power factor correction, which means
reducing thecarbon footprint and helping the environment.
DEMAND REDUCTION
We cannot change the load requirement but can serve load VAR requirement through
an inexpensive source (capacitor) and relieve the power plant system from supplying
unnecessary reactive power, which de-rates the active power production capability of
the generator.
There are different combinations of MW & MVAR that can be employed to have the
same utilization of generator capacity.
Generator is fully loaded with a load having 70% power factor. Note that the MW
supplied are less than 50 MW, rated output, but 100% of the generation capacity
(MVA) has been utilized. Meaning, the MW component of the Generator has been de-
rated with low power factor.
In another scenario, if a capacitor is added in the system.it can be seen that the system
is released from 42 MVAR to 25.5 MVAR so the system capacity released due to
demand reduction can now be used to serve the additional loads thus increasing
revenue.
In the above example, the same load which earlier loaded the generator to 100% is
now being served through thegenerator in addition to a capacitor. This relieved the
capacity of the power plant and hence the generator observed a demand reduction on
its terminals.By supplying VARs right at the load, the capacitors relieve the system
burden of carrying extra VARs. The generator is now loaded up to 82.5% and can still
The above charts show the savings due to the application of capacitors on the feeder.
RELEASE OF SYSTEM CAPACITY
Although the financial return from conductor loss reduction alone is seldom
sufficient to justify the installation of capacitors, it is sometimes an attractive
additional benefit; especially for overloaded andlong rural feeders with
predominant pumping load.
System Transformation & Conductor Losses are proportional to the current
squared and, since the current is reduced with the power factor improvement, the
losses are reduced considerably.
REDUCED CARBON FOOTPRINT
A lower power factor causes a higher current flow for a given load. As the line
current increases, the voltage drop in the conductor increases, which result in a
lower voltage.
With an improved power factor, the voltage drop in the conductor is reduced,
improving the voltage at the equipment and on the feeder. The overall voltage
improvement has perpetual effect on the performance of other connected loads
SHUNT CAPACITOR TYPES
There are two types of shunt capacitors:
i. Fixed capacitors designed at light load.
Fixed capacitors are quite cheap as compared to switched capacitors. Therefore, more
often, these are used (in the distribution network) than switched capacitors.
Fixed capacitor banks are usually applied (if economical) to improve the power factor
to bring it close to (or less than but not greater than) unity at light load, and are
permanently connected to the system through fuses.
Proposed permanently connected capacitor application should be checked to make
sure that the voltage to some customers should not rise too high during light load
periods.
The capacitor selection discussed so far has dealt only with applying capacitors to
correct power factor at minimum load. In order to correct power factor during heavier
loading periods, it is necessary to use switched capacitors. Switching of capacitors
may be done manually or automatically. Automatic controls can become cost
effective due to the cost incurred by personnel sent to manually switch them, and
because of the additional line losses incurred if not done in a timely manner.
Automatic controls can track various parameters and switch the capacitor banks as
needed to optimize the system power factor. The additional capacitors should be
switched either as an entire bank or in steps in order to keep the power factor from
becoming significantly leading at any time. In addition, proper switching prevents
overvoltage, undesirable voltage flicker and helps the capacitors perform the task they
were installed to do.
Capacitor bank size and location should be selected and designed in a manner that
limits voltage change to 3 volts (on a 120-volt base) to eliminate customer complaints.
For situations where limited switching is expected, customers on long, lightly loaded
feeders may accept up to a 6 volt change.
Since switched capacitors are generally installed to supplement un-switched
capacitors, they are located in the same manner as unstitched units. Results of
computer load flow studies should be used to determine the optimum sizes and
locations for capacitors. Fixed capacitor installations should be designed to
appropriately accommodate the system's inductive reactance expected during
expected minimum loading. The augmenting switched capacitor installations need to
be designed such that they appropriately accommodate the system's inductive
reactance expected during peak loading periods.
In lieu of load flow studies and computer calculated placement schemes, meter
readings should be taken at load centers in the same manner as un-switched units, but
now peak conditions should be investigated instead of minimum load conditions.
Readings should be taken so that peak KVA and KW loading can be determined.
Since Power Factor = KW/KVA,
Rise produced by
regulator
Volts
Reference Feeder Profile with
regulator
Like series capacitor, voltage regulator also produces no voltage effect between the
supply source and the regulator location and its entire boost effect is between the
regulator location and the remote end of the feeder.
COMMON METHODS OF CONNECTING CAPACITORS
Most common methods of connecting capacitors are as under:
3-Phase Grounded Wye
3-Phase Ungrounded Wye
3-Phase Delta
Single Phase
HT LT
Fuse
Gnd
S/P Ground to
Grounded wye Ungrounded wye Delta Neutral
Grounded wye and ungrounded wye connections are usually made on high
voltage (HT) circuits; whereas delta and single-phase connections are usually
made on low voltage (LT) circuits.
50 m
0 3 4
150 m 150 m 150 m 150 m
1 2 75 m 50 m
200 KVA
substation 40 KVA
at 0.70 PF
5 KVA 20 KVAR 8
at 0.95 PF 7 capacitor
POWER TRIANGLE
This means that when one phase of a capacitor bank is out of service; take the entire
bank out of service. Capacitors should be inspected regularly, at least before and after
peak seasons.
CAPACITOR INSTALLATION DRAWINGS
An installation drawing for shunt capacitors on three-phase lines is given below.
This type responds to local air temperature for tracking such temperature-sensitive
loads as air conditioning and electric heat. Controls include both wide range and
narrow range settings.
Wide range controls can be set to switch capacitors “ON” and “OFF” for various
temperature ranges, for example, “ON” between 85 and 90 degrees F and “OFF” for
temperatures between 75 and 80 degrees F. This feature allows a second tier of
capacitors to act as fixed units during a long spell of hot or cold weather. Other
capacitor banks can be controlled with narrow-range controls and be set to turn ”ON”
This type responds to inductive loading and is used where load voltage is regulated
and load power factor varies in an unpredictable manner with variation in kilowatt
loading. KVAR type controls use an induction-directional or solid state relay for
single-phase indication. KVAR control presents a better approach to capacitor
switching control but it has been rarely used in the past, due to its high cost. In recent
years, electronic control costs have lowered making KVAR control now a
consideration. KVAR control has been useful for improving system power factor in
situations where one large industrial customer is served and the customer does not
provide its own power factor correction.
POWER FACTOR MASTER ELEMENT CONTROL
This type responds to changes in power factor and is similar to KVAR control where
that it uses an induction-directional or solid state relay with a desensitizing adjustment
to prevent hunting at light loads. The desensitizing adjustment is needed to account
for the possible occurrence of the power factor bandwidth being less than the change
in sensing caused by switching the capacitor. Like kilovar control, power factor
control has been rarely used because of its high cost. However, costs have been
declining in recent years and several manufacturers offer good power factor controls,
making this type of control also a consideration.
TIME SWITCHING MASTER ELEMENT CONTROL
This type responds by using a simple clock device to switch capacitors at some
predetermined time. It is primarily used where the load characteristics are predictable
and reasonably constant, as with industrial loads. Desirable added features are
weekend and holiday blocking. This can be a low cost method. It is also
recommended that the clock be capable of remaining accurate in case of a power
outage.
CAPACITOR FUSING
Capacitor fuse protection has to be coordinated with any line sectionalizing devices
that will be operated on the feeder. Fuses should be designed to blow before the
capacitor case ruptures, in order to prevent personal injury, damage to adjacent
equipment, or capacitor dielectric fluid leaks.
Fuse Rating 11 KV Capacitor Color
Capacitor current protection devices should have a nominal rating of 135% to 140%
of the capacitor line current. Capacitor jumpers and switches need to have adequate
capacity to handle capacitive currents at full rating of capacitors on a continuous
basis.
Fuse Rating LT Capacitor Fuse Type
Rating (KVAR)
5A 2 NH 00
10 A 5 NH 00
20 A 10 NH 00
40 A 20 NH 00
75 A 40 NH 00
150 A 80 NH 00
Properly designed fuse protection is necessary for each shunt capacitor installation,
mainly to disconnect a faulted capacitor from the line before the capacitor causes
other current protective devices to operate. Capacitor units are not normally fused
individually, but by phase in a bank of one or more capacitors per phase. Banks
should always contain the same amount of KVARs in each phase. Capacitor fusing is
normally designed to operate at 120 to 135 percent of the capacitor's nameplate
current rating, though such fusing is occasionally de-rated to no less than 108% for
multiple units per phase.
In high lightning areas, fuses should be larger but no greater than 140% of the
capacitor's nameplate current rating. The choice of fuse rating for a capacitor
installation should always be based on a particular fuse's time-current characteristics.
This individual design attention is needed because of the wide variation in fuse time-
current characteristics and the different types and brands of fuses available.
If lightning causes excessive fuse blowing but there is no capacitor damage, fuses
should be replaced with the next larger size.
Added precautions should be taken when working with delta and non-grounded, wye-
connected, capacitors. A hazardous voltage may be present on a capacitor even when
the phase conductor to which the capacitor is connected is open-circuited for work.
Line voltage can feed back through the capacitor via the capacitor's common
connection with capacitors connected to other phase conductors that are still
energized. That is why, it is important for line crews to always check phase
conductors for the presence of voltage. Before working on any part of a capacitor
bank, completely de-energize the bank, and disconnect all line conductors from all
terminals. It is not good practice to rely on a capacitor's internal discharging resistors
to reduce the terminal voltage to a safe value after being disconnected from a power
line. After disconnecting a capacitor and waiting for the discharging resistors to bleed
voltage down, short-circuit the capacitor terminals and connect the shorted terminals
and the cases to ground. Leave the capacitor shorted until all work is completed.
OUT OF SERVICE REPAIR/STORAGE
Prior to capacitors being removed from their racks, and waiting several minutes,
during which the discharging resistors should have reduced the capacitor terminal
voltage practically to zero, the terminals should be simultaneously short-circuited and
solidly connected to their cases. Permanent shorting connections should then be
installed because capacitors tend to accumulate a residual charge, even when not
connected to a power source, if not short-circuited. Copper wire can be used to make
the capacitor terminal-to-terminal-to-case shorting connections. The connection
should not be removed until the unit is re-installed.
Node Distance Conductor Transformer CAPS/ Node Distance Conductor Transformer CAPS/
From To (km) Size (kVA) Switches From To (km) Size (kVA) Switches
Note: For PSS/Adept Software, columns for X & Y Coordinates should be incorportaed in the format.
January
February
March
April
May
June
July
August
September
October
November
December
N
ote*Any Unusual/abnormal maximum/minimum loading of Power T/Fs should also be explained with reasons behind.
* ** ***
Month off Peak Load (Amps) Peak Load (Amps) Max Hour KWH Units Sent Units Sold Losses Demand Power Load
Reading in Year-3 in Year-3 in Year-3 Factor Factor Factor
Year-1 Year-2 Year-3 Year-1 Year-2 Year-3 (kWH) (kWH) (kWH) kWH %age (%age) (%age) (%age)
January
February
March
April
May
June
July
August
September
October
November
December
Average
Total
Note: Any Unusual/abnormal maximum/minimum loading of 11 KV Feeder should also be explained with reasons behind.
* Demand Factor = (1.732 x I max x 11kV) / Circuit's connected kVA
** Power Factor = Max Hour kWh reading / (1.732 x I max x 11 kV)
*** Load Factor (monthly) = kWh Units sent per month / (24 x 30 x Max Hour kWh reading)
Note: Refer to Annexure-III, for calculation of Demand, Power, and Load Factors
Certified that I have personally checked the site and found that the Node to Node
Length, Conductor size & Capacity of Transformers shown on the site sketch and all
other data related to proposal are correct. The proposal has been checked at site and
found as per actual requirement of the area. It has not been prepared to benefit to any
individual, especially industrial consumer and is in the interest of maximum Nos. of
consumers of the area. After execution it will definitely reduce energy loss. The
proposal has not been prepared in any Private Housing Scheme/Colonies where the
sponsors are required to deposit full amount for its electrification.
__________________
1 Feeder-1
2 Feeder-2
3 Feeder-3
4 Feeder-4
5 Feeder-5
10
Total
1 Feeder-1
2 Feeder-2
3 Feeder-3
T otal
Feeder-1
Feeder-2
1 Feeder-1 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
2 Feeder-2 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
3 Feeder-3 (EM)
Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
4 Feeder-4 (P)
Feeder-3
New Line
Sub Total
Total
Sr. Feeder Grid Station Line /Load/Connected KVA Shifted From Nodes Where %VD is not within prescribed Limit Max kW % Annual kWh %
Nodes Where
Total %VD is within Power Load
Length of Connected Peak Off Peak Nodes prescribed Factor Factor
No. Feeder Limit 5-10% 10-15% 15-20% 20-25% >25% % VD Loss KW Loss Loss A.E. Loss
Line (km) kVA Load (A) Load (A)
Feeder-1
Feeder-2
1 Feeder-1 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
2 Feeder-2 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
3 Feeder-3 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
4 Feeder-4 (P) Feeder-3
New Line
Sub Total
Total
Feeder-2
1 Feeder-1 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
2 Feeder-2 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
3 Feeder-3 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
4 Feeder-4 (P) Feeder-3
New Line
Sub Total
Total
Feeder-1
Feeder-2
1 Feeder-1 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
2 Feeder-2 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
3 Feeder-3 (EM)
Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
4 Feeder-4 (P)
Feeder-3
New Line
Sub Total
Total
Feeder-1
Feeder-2
1 Feeder-1 (EM)
Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
2 Feeder-2 (EM)
Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
3 Feeder-3 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
4 Feeder-4 (P) Feeder-3
New Line
Sub Total
Total
Feeder-1
Feeder-2
1 Feeder-1 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
2 Feeder-2 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
3 Feeder-3 (EM)
Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
4 Feeder-4 (P)
Feeder-3
New Line
Sub Total
Total
Feeder-1
Feeder-2
1 Feeder-1 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
2 Feeder-2 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
3 Feeder-3 (EM)
Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
4 Feeder-4 (P)
Feeder-3
New Line
Sub Total
Total
Feeder-1
Feeder-2
1 Feeder-1 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
2 Feeder-2 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
3 Feeder-3 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
4 Feeder-4 (P)
Feeder-3
New Line
Sub Total
Total
Feeder-1
Feeder-2
1 Feeder-1 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
2 Feeder-2 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
3 Feeder-3 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
4 Feeder-4 (P) Feeder-3
New Line
Sub Total
Total
Feeder-1
Feeder-2
1 Feeder-1 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
2 Feeder-2 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
3 Feeder-3 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
4 Feeder-4 (P) Feeder-3
New Line
Sub Total
Total
Feeder-1
Feeder-2
1 Feeder-1 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
2 Feeder-2 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
3 Feeder-3 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
4 Feeder-4 (P) Feeder-3
New Line
Sub Total
Total
Feeder-1
Feeder-2
1 Feeder-1 (EM) Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
2 Feeder-2 (EM)
Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
3 Feeder-3 (EM)
Feeder-3
New Line
Sub Total
Feeder-1
Feeder-2
4 Feeder-4 (P) Feeder-3
New Line
Sub Total
Total
Proposed Facilities:
450 KVAR 900 KVAR
No. Node Nos. No. Node Nos.
Fixed Capacitors (Relocation From ____ From ____
____ ____
of Existing Cap) to_____ to_____
Attachments:
Planning Proposals Estimate Summary/BOQ
Cost Benefit Analysis Single Line Diagrams
Others: Sketch Showing Scope of Work
Total
COST SUMMARY
1
2
3
4
5
Sub Total
1
2
3
4
5
Sub Total
3
4
5
Sub Total
1
2
Sub Total
Sub Total
Total
1-LD,R
2-LD,R
7-LD,R
10-LD,R
23-LD,R
15-L D,R
16-L D, R
Sub Total
1-LO, P, L
2-LO, P, L
7-LO, P, L
10-LO, P, L
23-LO, P, L
15-L O,P, L
16-L O,P, L
Sub Total
TOTAL
1-LD,R
2-LD,R
7-LD,R
10-LD,R
23-LD,R
15-L D,R
16-L D, R
Sub Total
1-LO, P, L
2-LO, P, L
7-LO, P, L
10-LO, P, L
23-LO, P, L
15-L O,P, L
16-L O,P, L
Sub Total
TOTAL
Without Growth
Total Saving in Losses without Growth (S1 +S2 +S3 + S4) S5 = _______ kW
With Growth
Where, VF = Valuation Factor = Loss Factor x 8760 x Electricity Purchase Rate * = Rs. _________ / kW / Annum
Quantity
Sr.
MATERIAL UNIT As per Actual Variation From
No. Issued
W/O Installed W/O Issued
1 2 3 4 5 6 7=4-6 8=5-6
A. NEW WORK
1 PC/SPUN POLES
31 FEET NO.
36 FEET NO.
40 FEET NO.
45 FEET NO.
55 FEET NO.
2 LATICE STEEL STRUCTURES
31 FEET NO.
36 FEET NO.
40 FEET NO.
45 FEET NO.
55 FEET NO.
3 WOODEN/STEEL CROSS ARM
11 KV WOODEN NO.
11 KV STEEL NO.
4 INSULATORS
11 KV PIN TYPE NO.
11 KV DISC TYPE NO.
L.T. SPOOL TYPE NO.
5 PINS
11 KV INSULATOR PINS NO.
6 CROSS ARM BRACES
11 KV KNEE BRACE NO.
11 KV STEP BRACE NO.
7 NEW HT LINE
GOPHER KM.
RABBIT KM.
DOG KM.
LYNX KM.
PANTHER KM.
OSPREY KM.
8 RECONDUCTORING OF HT LINE WITH
GOPHER KM.
RABBIT KM.
DOG KM.
LYNX KM.
PANTHER KM.
OSPREY KM.
9 AAC CONDUCTOR
GNAT KM.
ANT KM.
WASP KM.
10 ALUMINIUM TIE WIRE M
STAY RODS COMPLETE SET WITH
11
ANCHOR ASSEMBLY NO.
12 STAY WIRE (10MM, 7/3,22) KG
13 EYE NUT NO.
14 EARTHING SETS COMPLETE NO.
15 DANGER PLATES NO.
16 BARBED WIRE KG
Material Quantity
Sr.
Description Unit As per
No. As per B.O.Q Variations
MRN
1 2 3 4 5 6=4-5
44 AAC Wasp MR
45 AAC Ant MR
46 S/C 500 MCM Cable MR
47 3/Core 4-AWG Cable MR
48 4/C 37/.083 Cable MR
49 4/C 19/.083 Cable MR
50 Drop Out Cut Out Set
51 Plateform Double Structure EA
50 Drop Out Cut Out Set
52 Plateform Double Structure EA
G Attachments:
Copies of S.Rs Copies of M.R.Ns
As Built Drawing/Sketch
Construction Construction
Division:- _____________ S/Division:- ________________
Material Quantity
Sr. As per Actual at Site Variations
Description Unit
No. As per B.O.Q C/ Report (Checked by
From B.O.Q From C/Report
Submitted by Committee)
1 2 3 4 5 6 7=4-6 8=5- 6
A NEW WORK
1 -H.T Structures
36' No.
40' No.
45' No.
2 -H.T P.C/Spun Poles
36' No.
40' No.
3 New H.T Line
ACSR Osprey Conductor Meter
ACSR Panther Conductor Meter
ACSR Dog Conductor Meter
ACSR Rabbit Conductor Meter
ASCR Gopher Conductor Meter
4 Reconductoring of H.T Line
ACSR Osprey Conductor Meter
ACSR Panther Conductor Meter
ACSR Dog Conductor Meter
ACSR Rabbit Conductor Meter
ASCR Gopher Conductor Meter
5 H.T Capacitors (Fixed)
- Relocation of Existing Cap No.
- Installation of New Cap No.
6 Cross Arms No.
7 Disc Insulators No.
8 Pin Insulators No.
9 Dead End Clamp No.
10 P.G Connectors No.
11 Earthing of H.T Structures No.
12 Foundation of H.T Structures No.
13
Construction Construction
Division:- _____________ S/Division:- ________________
Material Quantity
Sr.
Description Unit As per
No. As per B.O.Q Variations
MRN Provided by M.P Const:
1 2 3 4 5 6=4- 5
B MATERIAL DISMANTLED & RETURNED TO STORE
1 -H.T Structures
36' No.
40' No.
45' No.
2 L.T Structures (31') No.
3 H.T Conductor
ACSR Osprey Conductor Meter
ACSR Panther Conductor Meter
ACSR Dog Conductor Meter
ACSR Rabbit Conductor Meter
ASCR Gopher Conductor Meter
Copper Conductor Meter
4 Cross Arms No.
5 Disc Insulators No.
6 Pin Insulators No.
7
C S.Rs Nos. & Date
a) b) c)
d) e) f)
D MRNs Nos. & Date
a) b) c)
d) e) f)
E Observations/Recommendations
______________________________________________________________________________________________
______________________________________________________________________________________________
______________________________________________________________________________________________
______________________________________________________________________________________________
______________________________________________________________________________________________
______________________________________________________________________________________________
______________________________________________________________________________________________
G Conclusion:
Conditionally
Cleared Rejected
Accepted
Area Type : Urban (Posh____ /Other___)/Rural____ (Tick one) Avg. Load/SP Consumer______kVA
Node Distance Conductor No. of Connections Node Distance Conductor No. of Connections
(m) Size (km) Size
From To 3-P 1-P From To 3-P 1-P
Note: For PSS/Adept Software, columns for X & Y Coordinates should be incorportaed in the format.
R Y B R Y B R Y B R Y B R Y B R Y B
January
February
March
April
May
June
July
August
September
October
November
December
Certified that I have personally checked the site and found that the Node to
Node Length, Conductor size & Capacity of Transformers shown on the site sketch
and all other data related to proposal are correct. The proposal has been checked at
site and found as per actual requirement of the area. It has not been prepared to benefit
to any individual, especially industrial consumer and is in the interest of maximum
Nos. of consumers of the area. After execution it will definitely reduce energy loss.
The proposal has not been prepared in any Private Housing Scheme/Colonies where
the sponsors are required to deposit full amount for its electrification.
__________________
1 T/F-A
2 T/F-B
3 T/F-C
Total
1 T/F-A
2 T/F-B
3 T/F-C
Total
1 T/F-A (E/A)
2 T/F-B (E/A)
3 T/F-C (E/A)
4 T/F-D (P)
Total
Note:
E/A stands for Existing or Augmented
P stands for Proposed
1 T/F-A (E/A)
2 T/F-B (E/A)
3 T/F-C (E/A)
4 T/F-D (P)
Total
Note:
E/A stands for Existing or Augmented
P stands for Proposed
% Power Loss
% Power Loss
Proposed Facilities:
Capacity Node Nos. Capacity Node Nos. Capacity Node Nos.
From ____ From ____ From ____
Relocation of Existing T/F ____ ____ ____
to_____ to_____ to_____
From ____ From ____ From ____
Augmentation of Existing T/F ________ ________ ________
to_____ to_____ to_____
COST SUMMARY
ESR stands for average Electricity Sale Rate (Rs /KWh) of DISCO
Quantity
Sr.
MATERIAL UNIT As per Actual Variation From
No. Issued
W/O Installed W/O Issued
1 2 3 4 5 6 7=4-6 8=5-6
A. NEW WORK
1 PC/SPUN POLES
31 FEET NO.
36 FEET NO.
2 LATICE STEEL STRUCTURES
31 FEET NO.
36 FEET NO.
3 WOODEN/STEEL CROSS ARM
11 KV WOODEN NO.
11 KV STEEL NO.
4 INSULATORS
11 KV PIN TYPE NO.
11 KV DISC TYPE NO.
L.T. SPOOL TYPE NO.
5 PINS
11 KV INSULATOR PINS NO.
6 CROSS ARM BRACES
11 KV KNEE BRACE NO.
11 KV STEP BRACE NO.
7 NEW HT LINE
RABBIT M
DOG M
8 NEW LT LINE
AAC ANT M
AAC WASP M
INSULATED WASP M
INSULATED ANT M
9 RECONDUCTORING OF LT LINE
AAC ANT M
AAC WASP M
INSULATED WASP M
INSULATED ANT M
9 PVC CABLE
2-C 7/.052 M
4-C 19/.052 M
4-C 19/.083 M
4-C 37/.083 M
10 ALUMINIUM TIE WIRE M
STAY RODS COMPLETE SET WITH
11
ANCHOR ASSEMBLY NO.
12 STAY WIRE (10MM, 7/3,22) KG
13 EYE NUT NO.
14 EARTHING SETS COMPLETE NO.
15 DANGER PLATES NO.
16 BARBED WIRE KG
Quantity
Sr. No. MATERIAL UNIT Actual Variation From
As per W/O Issued
Installed W/O Issued
1 2 3 4 5 6 7=4-6 8=5-6
Material Quantity
Sr. No. Description Unit As per
As per B.O.Q Variations
MRN
1 2 3 4 5 6=4-5
B MATERIAL DISMANTLED & RETURNED TO STORE
1 H.T STR 36' EA
2 H.T P.C.C Poles 36' EA
3 L.T STR 31' EA
4 L.T P.C Pole 31' EA
5 Danger Plate EA
6 Anti Climbing Device EA
7 X - Arms 11 kV Wood EA
8 X - Arms 11 kV Steel EA
9 Knee Braces EA
10 Step Braces EA
11 Pin Insulators EA
12 Disc Insulators EA
13 Spool Insulator EA
14 Insulator Pins EA
15 D-Strap EA
16 Dead End Clamp for Dog, Rab EA
17 Loop Dead End Clamp EA
18 Eye Nut EA
19 Double Arming Bolt EA
20 Anchor Shackles EA
21 P.G Connectors for Dog, Rab EA
22 P.G Connector for Wasp EA
23 P.G Connector for Ant EA
24 Nut & Bolts 3 / 8 x 6" EA
25 Nut & Bolts 5 / 8 x 2" EA
26 Nut & Bolts 5 / 8 x 10" EA
27 Nut & Bolts 5 / 8 x 14" EA
28 Round Warshers EA
29 Square Warshers EA
30 Stay Assembly EA
31 STAY Wire KG
32 MS Clamps EA
33 Tie Wire KG
Quantity
Sr. No. MATERIAL UNIT Actual Variation From
As per W/O Issued
Installed W/O Issued
1 2 3 4 5 6 7=4-6 8=5-6
Material Quantity
Sr. No. Description Unit As per
As per B.O.Q Variations
MRN
1 2 3 4 5 6=4-5
B MATERIAL DISMANTLED & RETURNED TO STORE
34 Earthing Unit EA
35 AAC Gnat MR
36 AAC Wasp MR
37 AAC Ant MR
38 2-C PVC Cable 7/0.052 MR
39 4-C PVC Cable 19/0.052 MR
40 4-C PVC Cable 19/0.083 MR
41 4-C PVC Cable 37/0.083 MR
42 200 kVA T/F NO.
43 100 kVA T/F NO.
44 50 kVA T/F NO.
45 25 kVA T/F NO.
46 Drop Out Cut Out Set
47 Plateform Double Structure EA
48 Plateform Single Structure EA
49 Drop Out Cut Out Set
G Attachments:
Copies of S.Rs Copies of M.R.Ns
As Built Drawing/Sketch
Material Quantity
As per
Sr. Actual at Site Variations
Description Unit C/ Report
No. As per B.O.Q (Checked by
Submitted by M.P
Committee)
Const: From B.O.Q From C/Report
1 2 3 4 5 6 7=4- 6 8=5- 6
A NEW WORK
1 2 3 4 5 6=4- 5
B MARERIAL DISMANTLED & RETURNED TO STORE
F Attachments:
Copies of S.Rs Copies of M.R.Ns
G Conclusion:
Conditionally
Cleared Rejected
Accepted
* Pole Class = PCO , PCS , S , TS; ** Type = Primary Pole (PP), Secondary Pole (SP), Transformer Pole (TR), Feeder (FR)