Sunteți pe pagina 1din 1

Network Protection & Automation Guide

In many cases, it is not feasible to protect against all hazards section between the current transformers and the circuit
with a relay that responds to a single power system quantity. breaker A is not completely protected against faults. A fault at
An arrangement using several quantities may be required. In F would cause the busbar protection to operate and open the
this case, either several relays, each responding to a single circuit breaker but the fault may continue to be fed through the
quantity, or, more commonly, a single relay containing several feeder. If the feeder protection is of the type that responds
elements, each responding independently to a different only to faults within its own zone (see section 2.5.2), it would
quantity may be used. not operate, since the fault is outside its zone. This problem is
dealt with by intertripping or some form of zone extension, to
The terminology used in describing protection systems and
ensure that the remote end of the feeder is also tripped. These
relays is provided in Appendix A. Different symbols for
methods are explained extensively in chapters 11 and 12.
describing relay functions in diagrams of protection schemes
are used, the three most common methods (IEC, IEEE/ANSI Busbar
and IEC61850) are provided in Appendix B. protection

2.3 ZONES OF PROTECTION


To limit the extent of the power system that is disconnected
when a fault occurs, protection is arranged in zones. The
principle is shown in Figure 2.5. Ideally, the zones of
Feeder
protection should overlap, so that no part of the power system protection
is left unprotected. This is shown in Figure 2.6(a), the circuit
(a) CTs on both sides of circuit breaker
breaker being included in both zones.
A Busbar
protection
GS Zone 1
F

Feeder
Zone 2 protection
(b)CTs on circuit side of circuit breaker
Figure 2.6: CT locations
The point of connection of the protection with the power
system usually defines the zone and corresponds to the
location of the current transformers. Unit type protection
Zone 3
results in the boundary being a clearly defined closed loop.
Figure 2.7 shows a typical arrangement of overlapping zones.

Zone 4

Zone 5 Zone 7

Feeder 1 Feeder 2 Feeder 3


Zone 6 Figure 2.7: Overlapping zones of protection systems

Figure 2.5: Division of power systems into protection zones Alternatively, the zone may be unrestricted; the start will be
defined but the extent (or ‘reach’) will depend on
For practical physical and economic reasons, this ideal is not
measurement of the system quantities and will therefore be
always achieved, accommodation for current transformers
subject to variation, owing to changes in system conditions
being in some cases available only on one side of the circuit
and measurement errors.
breakers, as shown in Figure 2.6(b). In this example, the

2-4 © 2011 Alstom Grid. Single copies of this document may be filed or printed for personal non-commercial use and must include this
copyright notice but may not be copied or displayed for commercial purposes without the prior written permission of Alstom Grid.

S-ar putea să vă placă și