Documente Academic
Documente Profesional
Documente Cultură
Magnum DS metal-enclosed
low-voltage switchgear
Contents
Description Page
Ratings
Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Voltage transformers . . . . . . . . . . . . . . . . . . . . . . 13
Control power transformers . . . . . . . . . . . . . . . . 13
Application
Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
System voltage/frequency . . . . . . . . . . . . . . . . . . 13
Continuous current ratings . . . . . . . . . . . . . . . . . 13
Ambient temperature . . . . . . . . . . . . . . . . . . . . . 13
Altitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Unusual environments and
operating conditions . . . . . . . . . . . . . . . . . . . . . . 14
Types of systems . . . . . . . . . . . . . . . . . . . . . . . . 14
System application . . . . . . . . . . . . . . . . . . . . . . . 15
Transformer main secondary breakers . . . . . . . . 16
Bus sectionalizing (tie) breakers . . . . . . . . . . . . . 16
Automatic transfer schemes
and intelligent control . . . . . . . . . . . . . . . . . . . . . 16
Generator breakers . . . . . . . . . . . . . . . . . . . . . . . 16
Feeder breakers—general . . . . . . . . . . . . . . . . . . 17
Motor starting feeder breakers . . . . . . . . . . . . . . 17
Group motor feeder breakers . . . . . . . . . . . . . . . 17
Ground fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Sequence of operation . . . . . . . . . . . . . . . . . . . . 21
Features
Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Instrumentation/metering . . . . . . . . . . . . . . . . . . 35
Instrumentation—door mounted . . . . . . . . . . . . . 36
Accessories and options . . . . . . . . . . . . . . . . . . . 36
Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Typical specification . . . . . . . . . . . . . . . . . . . . . . . 39
Technical Data TD01901001E Magnum DS metal-enclosed
Effective November 2017 low-voltage switchgear
• Better metering accuracy 2000 2000 100 kA, 150 kA, 200 kA
• Higher quality and reliability 3200 3200 100 kA, 150 kA, 200 kA
4000 4000 100 kA, 150 kA, 200 kA
• State-of-the-art monitoring and communications
5000 5000 100 kA, 150 kA, 200 kA
Magnum DS switchgear can meet the needs for general 6000 — 100 kA, 150 kA, 200 kA
applications, service entrance, harsh environments, multiple 8000 — 100 kA, 150 kA, 200 kA
source transfer, special grounding systems and many others.
10,000 — 100 kA, 150 kA, 200 kA
Modern designed Magnum DS metal-enclosed low-voltage
switchgear and power circuit breakers provide: Note: In addition to the available bus bracings shown above, the bus has
been tested for short-circuit values of 85,000 A for a full 60 cycles.
• 100% rated, fully selective protection
• Integral microprocessor-based breaker tripping systems
• Two-step stored-energy breaker closing Standards and certifications
• 100 kA short-circuit bus bracing standard Standards
• Optional 150 kA and 200 kA short-circuit bus bracing, without Magnum DS switchgear conforms to the following standards: NEMA
preceding current limiting fuses SG3 and SG5, CSA, ANSI C37.20.1, C37.51, and UL Standard 1558.
2 EATON www.eaton.com
Magnum DS metal-enclosed Technical Data TD01901001E
low-voltage switchgear Effective November 2017
EATON www.eaton.com 3
Technical Data TD01901001E Magnum DS metal-enclosed
Effective November 2017 low-voltage switchgear
Table 4. Magnum DS breaker control voltages and currents The narrow-band characteristic curve graphically illustrates the
Control voltage 24 dc 48 dc 125 dc 120 ac 240 ac close coordination obtainable in breaker systems with Digitrip RMS
tripping devices. Repeatability is within 2%.
Close current (SR), ampere 2.70 1.30 0.67 0.59 0.34
Shunt trip current, ampere 2.70 1.30 0.67 0.59 0.34 The maximum breaker current rating for any breaker frame size is
determined by the rating of the sensor used.
Spring charge motor, ampere:
N/A 4.00 3.00 3.00 N/A The breaker current rating for any frame size can be changed by
(9 seconds)
simply changing the sensors and associated rating plug, which are
(5 seconds) 14.00 7.50 3.00 3.00 1.50 easily removed from the breaker drawout element. The wide range
Control voltage range: of long-delay pickup makes one set of sensors more flexible on a
Close – 18–26 38–56 100–140 104–127 208–254 wider range of loads. The Digitrip RMS itself need not be changed
when the associated sensors and rating plugs are changed.
Trip – 18–26 28–56 70–140 60–127 208–254
Motor currents are running currents. Inrush is approximately 400%. Digitrip RMS can be supplied in various combinations of four
Motor running time to charge spring approximately 5 seconds. independent, overcurrent protection functions:
• Long delay (L)
• Instantaneous (I)
Maximum voltages at which the interrupting ratings in Table 1
apply are: • Short delay (S)
• Ground (G)
Table 5. Voltages
System voltage Maximum voltage
• Ground alarm only (A)
208 or 240 254 Every Magnum DS trip unit comes standard with LSI characteristics.
480 508 Optional ground (G) or ground alarm (GA) may also be provided.
600 635 These trip units also provide the ability to defeat instantaneous
protection. In addition, short delay protection may be set to the
maximum instantaneous level, effectively disabling short delay
protection. Under no condition is it possible to set the trip unit
These interrupting ratings are based on the standard duty cycle beyond the capabilities of the circuit breaker.
consisting of an opening operation, a 15-second interval and a
close-open operation, in succession, with delayed tripping in case
of short-delay devices. Table 7. Digitrip RMS adjustable trip settings
Time/current Pickup Pickup point Time band,
The standard duty cycle for short-time ratings consists of characteristics setting (see note) seconds
maintaining the rated current for two periods of 1/2 second each, Long delay 0.4, 0.5, 0.6, 0.7, 0.8 In times 2, 4, 7, 10, 12, 15, 20, 24
with a 15-second interval of zero current between the two periods. 0.9, 0.95, 1.0 long delay (at 6 times pickup value)
setting
Table 6. Available sensor ratings and rating plugs Instantaneous Off, 2, 3, 4, 6, 8, 10 In times —
for Digitrip RMS M1 short delay
setting
Breaker frame Available ratings
Short delay 2, 2.5, 3, 4, 6, 8, 10 In times 0.1, 0.2, 0.3, 0.4, 0.5
800 200, 250, 300, 400, 600, 800 M1 long delay (flat response)
1600 200, 250, 300, 400, 600, 800, 1000, 1200, 1600 setting 0.1 , 0.3 , 0.5
2000 200, 250, 300, 400, 600, 800, 1000, 1200, 1600, 2000 Ground fault 0.25, 0.3, 0.35, 0.4, In times 0.1, 0.2, 0.3, 0.4, 0.5
0.5, 0.6, 0.75, 1.00 ground fault (flat response)
3200 200, 250, 300, 400, 600, 800, 1000, 1200, 1600, 2000, (1200 A maximum) setting 0.1 , 0.3 , 0.5
2500, 3000, 3200
I2t response.
4000 2000, 2500, 3200, 4000
5000 2000, 2500, 3200, 4000, 5000 Note:
6000 2000, 2500, 3200, 4000, 5000 In = Rating plug valve
Ir = Long delay pickup setting times In
The rating plug is for 50 and 60 Hz applications. Rating plugs are not interchangeable with 60 Hz
or 50 Hz only rating plugs.
4 EATON www.eaton.com
Magnum DS metal-enclosed Technical Data TD01901001E
low-voltage switchgear Effective November 2017
Table 9. Digitrip ground fault pickup values for secondary injection test kit amperes
Pickup (dial) setting values in secondary amperes
Installed Sensor
rating plug rating 25% 30% 35% 40% 50% 60% 75% 100%
200 200 1.25 1.50 1.75 2.00 2.50 3.00 3.75 5.00
250 250 1.25 1.50 1.75 2.00 2.50 3.00 3.75 5.00
300 300 1.25 1.50 1.75 2.00 2.50 3.00 3.75 5.00
400 400 1.25 1.50 1.75 2.00 2.50 3.00 3.75 5.00
600 600 1.25 1.50 1.75 2.00 2.50 3.00 3.75 5.00
800 800 1.25 1.50 1.75 2.00 2.50 3.00 3.75 5.00
1000 1000 1.25 1.50 1.75 2.00 2.50 3.00 3.75 5.00
1200 1200 1.25 1.50 1.75 2.00 2.50 3.00 3.75 5.00
1600 1600 1.25 1.50 1.75 2.00 2.50 3.00 3.75 3.75
2000 2000 1.25 1.50 1.75 2.00 2.50 3.00 3.00 3.00
2500 2500 1.25 1.50 1.75 2.00 2.40 2.40 2.40 2.40
3000 3000 1.25 1.50 1.75 2.00 2.00 2.00 2.00 2.00
3200 3200 1.25 1.50 1.50 1.88 1.88 1.88 1.88 1.88
4000 4000 1.25 1.50 1.50 1.50 1.50 1.50 1.50 1.50
5000 5000 1.20 1.20 1.20 1.20 1.20 1.20 1.20 1.20
6000 6000 1.20 1.20 1.20 1.20 1.20 1.20 1.20 1.20
Tolerance on pickup levels are ±10% of values shown in chart.
For testing purposes only: When using an external single-phase current source to test low level ground fault current settings, it is advisable to use the auxiliary power module (APM). Especially when the
single-phase current is low, without the APM it may appear as if the trip unit does not respond until the current is well above the set value, leading the tester to believe there is an error in the trip unit when
there is none. The reason this occurs is that the single-phase test current is not a good simulation of the normal three-phase circuit. If three-phase had been flowing, the trip unit would have performed
correctly. Use the APM for correct trip unit performance when single-phase tests are made.
EATON www.eaton.com 5
Technical Data TD01901001E Magnum DS metal-enclosed
Effective November 2017 low-voltage switchgear
1
.9
7
8
3
2
30
50
20
40
60
.7
10
70
80
90
100
6
7
9
.5
.6
40
10
30
20
.8
90
80
50
60
70
10 0
10000 10000
2 HOURS
9000 9000
2 HOURS
8000
7000
Circuit Breaker Time/Current Curves (Phase Current) 8000
Magnum Power Circuit Breakers 7000
6000
Available long delay Response: Long Delay and Short Delay Trip (FLAT and I2T) 6000
5000
setting This curve is for 50 Hz or 60 Hz applications. 5000
0.4 to 1x In = Ir
1 HOUR
1 HOUR
4000
Available Sensors and Matching Rating Plug in Amperes 4000
in 0.1 increments 200 A 800 A 2500 A
3000 250 A 1000 A 3000 A 3000
300 A 1200 A 3200 A
400 A 1250 A 4000 A
2000 2000
600 A 1600 A 5000 A
630 A 2000 A 6300 A
Notes:
1. There is a memory effect that can act to shorten the long delay. The memory effect
1000 1000
comes into play if a current above the long delay pick up value exists for a time and
900 900
800
then is cleared by the tripping of a downstream device or the circuit breaker itself. A 800
700
subsequent overload will cause the circuit breaker to trip in shorter time than normal. 700
The amount of time delay reduction is inverse to the amount of time that has elapsed
600 since the previous overload. Approximately five minutes is required between 600
500 overloads to completely reset memory. 500
2. The end of the curve is determined by the interrupting rating of the circuit breaker.
400 3. For the ground fault time/current curve see curve 70C1008. For the instantaneous see 400
curve 70C1007.
300 4. The long delay pickup point (indicated by rapid flashing of unit status LED on the 300
Maximum total product) occurs at 110%, with a ± 5% tolerance. The instantaneous settings have
conventional 100% ±10% at the pick up points.
200
clearing time 5. With zone interlocking on short delay utilized and no restraining signal, the minimum 200
time band applies regardless of the setting.
6. This curve is shown as a multiple of the long delay setting.
7. Breakpoint back to FLAT response indicated by dots occurs at 8x Ir for upper line of
I2T curve.
8. Total clearing times show include the response times of the trip unit, the breaker
100 100
90
opening and the interruption of the current. 90
9. Additional available max M1 settings
80 Long delay time curves 80
1 MINUTE
70 Narrow Frame 70
60
can extend down to M1 200 A through 1250 A M1 = 14x In
60
(max. short delay setting) 1600 A, 2000 A M1 = 12x In
50 Standard Frame: 50
See Note 9. 200 A through 1250 A M1 = 14x In
40 1600 A, 2000 A, 2500 A M1 = 12x In 40
3000 A, 3200 A, M1 = 10x In
30 Double Wide Frame: 30
24
. 2000 A, 2500 A
3200 A, 4000 A, 5000 A
M1 = 14x In
M1 = 12x In
20 6300 A (IEC only) M1 = 10x In 20
Minimum 10. Curve applies from –20 °C to +55 °C ambient. Temperatures above +85 °C cause
total .
15
automatic trip. Breaker must be applied according to “Continuous Rating at
Different Ambient” table.
clearing
10 time Available long 10
9 9
delay time
8
7
7
. shown at 6x Ir
2 2.5 3
8
7
6 2,4,7,10,12,15,20,24 6
5 seconds +0/–30% 5
4
4
. 4
3 3
2
2
. 2
TIME IN SECONDS
TIME IN SECONDS
.9
1 Available short 1
.9
.8 10 delay settings .8
.7 2.5 8
2 to 10x Ir ± 5% .7
.6
See Note 9. .6
2 3 4 6
.5 .5
.5 .5*
.4 .4
.4
.3 .3
.3 .3*
.2 .2
.2
.1
.1 Application .1*
.1
.09 determines .09
.08
.08
.07 end of curve .07
.06 .06
.05 .05
.01 .01
1
.9
7
8
3
2
9
.7
6
7
9
.5
.6
30
50
5
20
40
60
10
70
80
90
.8
100
40
10
30
20
90
80
50
60
70
100
70C1006
Figure 1. Magnum DS circuit breakers with Digitrip RMS 520/520M/520MC/520i/520Mi/520MCi trip unit typical long delay
and short delay time/phase current characteristic curve (LS)
6 EATON www.eaton.com
Magnum DS metal-enclosed Technical Data TD01901001E
low-voltage switchgear Effective November 2017
.5
.7
.8
.6
.9
7
8
1
30
50
2
20
40
60
80 0
10
70
80
90
20 0
40 0
60 0
70 0
90 0
900 0
10 0
30 0
50 0
400 0
500 0
800 0
100 0
200 0
300 0
600 0
700 0
1000 0
10000 10000
2 HOURS
2 HOURS
9000 9000
8000 Circuit Breaker Time/Current Curves (Phase Current) 8000
7000 7000
6000 Magnum and Magnum DS Circuit Breakers 6000
5000 Response: Instantaneous Trip
5000
This curve is for 50 Hz and 60 Hz applications.
1 HOUR
1 HOUR
4000 4000
Notes:
3000 1. There is a memory effect that can act to shorten the long delay. The 3000
memory effect comes into play if a current above the long delay pick up
value exists for a time and then is cleared by the tripping of a down stream
2000 device or the circuit breaker itself. A subsequent overload will cause the 2000
circuit breaker to trip in shorter time than normal. The amount of time
delay reduction is inverse to the amount of time that has elapsed since
the previous overload. Approximately five minutes is required between
overloads to completely reset memory.
1000 2. The end of the curve is determined by the interrupting rating of the
1000
900 circuit breaker. 900
800 3. For the ground fault time/current curve see curve 70C1008. 800
700 4. This curve is shown as a multiple of the Rating Plug (I). 700
600 5. The Instantaneous settings have conventional 100% ± 10% as the 600
pickup points.
500 500
6. Total clearing times shown include the response times of the trip unit,
400 the breaker opening and the interruption of the current. 400
7. Additional settings of OFF and M1 are also available with:
300
Narrow Frame:
300
200 A through 1250 A M1 = 14x In
1600 A M1 = 12x In
200 2000 A (IEC only) M1 = 12x In
Standard Frame: 200
200 A through 1250 A M1 = 14x In
1600 A, 2000 A, 2500 A M1 = 12x In
3000 A, 3200 A M1 = 10x In
4000 A (IEC only) M1 = 10x In
100 100
90
Double Wide Frame:
90
80 2000 A, 2500 A M1 = 14x In
80
1 MINUTE
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
3 3
TIME IN SECONDS
3 6
2 10
2 2
TIME IN SECONDS
8
1 4
1
.9
.8
Available instantaneous .9
.3 .3
.2 .2
.1 Instantaneous trip at .1
.09 high fault currents .09
.08 .08
.07 .07
.06 .06
.05 .05
.04 .04
.01 .01
.5
.7
.8
.6
.9
7
8
1
9
2
30
50
20
40
60
10
70
80
90
800
200
400
600
700
900
100
300
500
30
50
20
40
60
70
80
90
9000
4000
5000
8000
1000
2000
3000
6000
7000
100
KA 70C1007
Figure 2. Magnum DS circuit breakers with Digitrip RMS 520/520M/520MC/520i/520Mi/520MCi trip unit typical instantaneous
time/phase current characteristic curve (I)
EATON www.eaton.com 7
Technical Data TD01901001E Magnum DS metal-enclosed
Effective November 2017 low-voltage switchgear
.06
.0 7
.08
.0 5
.0 9
.1
.4
.5
.7
.8
.3
.6
.2
.9
.8
.2
.4
.6
.7
.9
3
5
6
2
.3
.5
1
7
8
9
2
10
9
4
8
3
5
6
7
10
10000 10000
2 HOURS
9000 9000
2 HOURS
8000 8000
7000
Circuit Breaker Time/Current Curves (Ground Current) 7000
6000 6000
Magnum and Magnum DS Circuit Breakers
5000 Response: Ground Trip (FLAT & I 2T) 5000
1 HOUR
This curve is for 50 Hz or 60 Hz applications.
1 HOUR
4000 4000
Notes:
3000 3000
1. The end of the curve is determined by the interrupting rating of the
circuit breaker.
2000 2. For phase current time/current curves, see 70C1006 and 70C1007. 2000
3. The curve is shown as a multiple of the Rating Plug (I).
4. The ground fault settings have conventional 100% ± 10% as the
pickup points.
5. Except as noted tolerances on current level are ±10% of values
1000 shown in chart. 1000
900 6. The ground fault pick up is limited to 1200A setting for non- 900
800 international styles. 800
700 7. The rating plug is for 50 Hz and 60 Hz applications. 700
600 8. With zone interlocking on ground fault utilized and no restraining 600
500 signal, the minimum time band applies regardless of setting. 500
9. For additional curve tolerances contact Eaton.
400 10. Total clearing times shown include the response time for the trip unit, 400
the breaker opening and the current interruption.
300 11. Transition point from I2T back to FLAT response indicated by dot 300
occurs at 0.625x In for upper boundary of I2T curve.
200 200
100 100
90 90
80 80
1 MINUTE
70 70
60 60
50 50
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6
.25 .5 1.0 Available 6
5 ground setting 5
0.25 to 1.0x In ±10%
4 4
See Note 6.
3 3
2 2
.6
.3 .4
TIME IN SECONDS
TIME IN SECONDS
1 1
.9 .9
.8 .25
.8
.7 .7
.5 .75
.6 .6
.5 .5
.5 0.5*
.4 .4
.4
.35
.3 Available flat response .3
.3 ground time 0.3*
.2
0.1 to 0.5 seconds
.2
.2
.1 0.1*
.1 .1
.09 .09
.08 I2t
slope for .08
.07 ground time .07
.06 .06
.05
Available .05
I2t response
.04 .04
Flat shape for ground time
.03 ground time 0.1*, 0.3*, .03
0.5* seconds
.02 .02
.01 .01
.09
.07
.06
.08
.05
.4
.5
.7
.8
.1
.3
.6
.2
.9
.8
6
2
.2
.4
.6
.7
.9
.5
1
7
8
9
.3
2
10
9
4
8
3
5
6
7
10
70C1008
Figure 3. Magnum DS circuit breakers with Digitrip RMS 520/520M/520MC/520i/520Mi/520MCi trip unit typical ground fault
time/phase current characteristic curve (G)
8 EATON www.eaton.com
Magnum DS metal-enclosed Technical Data TD01901001E
low-voltage switchgear Effective November 2017
.9
.7
1
.5
.6
7
8
3
2
30
50
.8
20
40
60
10
70
80
90
8
100
6
7
9
3
40
10
30
20
90
80
50
60
70
100
10000
9000
2 HOURS
8000 Circuit Breaker Time/Current Curves (Phase Current)
7000
6000 Magnum and Magnum DS Circuit Breakers
Response: Long Delay (I2T) and Short Delay Trip (FLAT and I2T)
5000
This curve is for 50 Hz or 60 Hz applications.
1 HOUR
70
4. SHORT PU (Max M1 setting) is a additional setting, based on In (Plug), that can
extend out where the SHORT PU will function.
60
Standard Breaker: Double Wide Breaker:
50
Adjustable 200 A through 1250 A M1=14x In 2000 A, 2500 A M1=14x In
1600 A, 2000 A, 2500 A M1=12x In 3200 A, 4000 A, 5000 A M1=12x In
40 LONG TIME 3000 A, 3200 A M1=10x In 6300 A M1=10x In
2–24 seconds 5. The SHORT PU points have 100% ± 5% tolerance.
30 6. SHORT SLOPE: FLAT
(+0 –30%) at 6x Ir
24 Tolerance is +0/ –80 ms for all settings except
With 0.5s 0.10s setting is 0.06 to 0.13
20 increments. 0.20s setting is 0.15 to 0.22
See Note 7. 7. SHORT SLOPE: I2T
I2T slope flattens out at 8 x Ir for top of band with FLAT time minimum value
prevailing for bottom of band.
See Note 4. Curve Trip Equation: Trip = SHORT TIME * 64/ I2, where I is a multiple of Ir (top)
10 10 Curve Trip Equation: Trip = SHORT TIME * 64/ I2 * 0.70 (bottom)
9 The above equations indicate tolerance is +0/ –30% for all settings except
8 Adjustable 0.10s is +30%–25%
7 SHORT PU 0.20s is +10%–25%
6
1.5x to 10x or For all curves the lower flat response time value projected to I2T line will
determine the other Break Point and shape of the curve.
5 12x or 14x Ir 8. The end of the curve is determined by the interrupting rating of the circuit breaker.
4 4 With 0.5 9. Curve applies from –20 °C to +55 °C ambient. Temperatures above +85 °C cause
increments. automatic trip. Breaker must be applied according to “Continuous Rating
3 See Note 4. at Different Ambient” table.
2 2
Adjustable
TIME IN SECONDS
SHORT TIME
1 0.10s to 0.50s Break point
.9
.8 With 0.05 steps. at 8x Ir to FLAT
.7 See Note 6.
.6 Max clearing time
.5 0.50s 0.50s
.4
.3
.2
0.10s
.1
.09
.08
.07
.06
.05
Adjustable I2T
.04
response
Minimum SHORT TIME Minimum
.03
clearing time 0.10 to 0.50 clearing time
seconds
.02 with 0.05s
increments.
See Note 7.
.01
1
.9
7
8
3
2
9
.7
6
7
9
.5
.6
30
50
5
20
40
60
10
70
80
90
.8
100
40
10
30
20
90
80
50
60
70
100
70C1034
Figure 4. Magnum DS circuit breakers with Digitrip RMS 1150/1150i—I2T trip unit typical long delay and short delay time/phase
current characteristic curve (LS)
EATON www.eaton.com 9
Technical Data TD01901001E Magnum DS metal-enclosed
Effective November 2017 low-voltage switchgear
1
.9
7
8
3
2
30
50
20
40
60
.7
10
70
80
90
.6
100
6
7
9
.5
40
10
30
20
.8
90
80
50
60
70
10 0
10000
9000
2 HOURS
4000
Available Sensors and Matching Rating Plug in Amperes
3000 200 A 800 A 2500 A
250 A 1000 A 3000 A
2000 300 A 1200 A 3200 A
400 A 1250 A 4000 A
600 A 1600 A 5000 A
630 A 2000 A 6300 A
1000
900
800 Notes:
700
600 1. There is a Long MEMORY (if enabled) effect that can act to shorten the long
delay. The memory effect comes into play if a current above the LONG PU
500
value exists for a time and then is cleared by the tripping of a downstream
400 device or the circuit breaker itself. A subsequent overload will cause the
circuit breaker to trip in shorter time than normal. The amount of time delay
reduction is inverse to the amount of time that has elapsed since the previous
300
overload. Approximately five minutes is required between overloads to
completely reset memory.
2. This curve is shown as a multiple of LONG PU Setting (Ir).
200 The actual pickup point occurs at 110% of the Ir, current,
with a ±5% tolerance.
Long TIME Curve Equation: Trip = Long TIME *1296/I4,where I is a multiple of Ir.
3. In this time region £ 0.5 seconds the I4 T Long TIME function will flatten out
and be no faster than the Short TIME setting. This is to avoid a notch in graph.
100 4. SHORT PU (Max M1 setting) is an additional setting.
90 Standard Breaker:
80 200 A through 1250 A M1=14x In
1 MINUTE
2
TIME IN SECONDS
1 1
.9
.8
Adjustable
.7 SHORT PU
.6 1.5x to 10x or
.5 12x or 14x Ir 0.50s
.4
With 0.5
increments.
.3 See Note 4.
See Note 3.
.2
0.10s
.1
.09
.08
.07
.06
.05
.04
Minimum
.03 clearing time
See Notes 6, 7.
.02
.01
1
.9
7
8
3
2
9
.7
.6
6
7
9
.5
30
50
5
20
40
60
10
70
80
90
.8
100
40
10
30
20
90
80
50
60
70
100
70C1035
Figure 5. Magnum DS circuit breakers with Digitrip RMS 1150/1150i—I4T trip unit typical long delay and short delay time/phase
current characteristic curve (LS)
10 EATON www.eaton.com
Magnum DS metal-enclosed Technical Data TD01901001E
low-voltage switchgear Effective November 2017
1
.9
7
8
3
9
2
.7
6
7
9
.6
5
.5
30
50
20
40
60
10
70
80
90
.8
100
40
10
30
20
90
80
50
60
70
100
10000
9000
2 HOURS
8000 Circuit Breaker Time/Current Curves (Phase Current)
7000
6000 Magnum and Magnum DS Circuit Breakers
Response: instantaneous trip
5000
This curve is for 50 Hz or 60 Hz applications.
1 HOUR
4000
Notes:
3000 1. There is a memory effect that can act to shorten the long delay.
The memory effect comes into play if a current above the long delay
pickup value exists for a time and then is cleared by the tripping of a
2000
downstream device or the circuit breaker itself. A subsequent overload
will cause the circuit breaker to trip in shorter time than normal. The
amount of time delay reduction is inverse to the amount of time that
has elapsed since the previous overload. Approximately five minutes
is required between overloads to completely reset memory.
1000 2. The end of the curve is determined by the interrupting rating of the
900 circuit breaker.
800 3. This curve is shown as a multiple of the rating plug (In).
700 4. The instantaneous settings have conventional 100% ± 10% as their
600 pick up points.
5. Total clearing times shown include the response times of the trip unit,
500 the breaker opening and the interruption of the current.
400 6. Additional settings of OFF and M1 are also available with
Standard Frame: Double Wide Frame:
200 A through 1250 A M1=14x In 2000 A, 2500 A M1=14x In
300
1600 A, 2000 A, 2500 A M1=12x In 3200 A, 4000 A, 5000 A M1=12x In
3000 A, 3200 A M1=10x In 6300 A M1=10x In
200
7. For breakers rated 3200A and less having a 100 kA rms interruption
rating, an additional high instantaneous trip module is provided in the
breaker set to trip at a 170 kA ± 10% instantaneous peak current level.
This protection is functional even when the Instantaneous is set to the
OFF position.
100
90
80
1 MINUTE
70
60
50
40
30
20
10
9
8
7
6
5
Available INST PU
TIME IN SECONDS
.5
.4
.3
.2
Instantaneous trip
.1
.09
at high fault currents
.08
.07
.06
.05
.04
.03
Application and
breaker ratings
determine end
.02 of curve
.01
1
.9
7
8
3
2
9
.7
.6
.5
30
50
30
50
20
40
60
20
40
60
10
70
80
90
70
80
90
.8
100
100
40
30
20
90
80
50
60
70
100
kA 70C1043
Figure 6. Magnum DS circuit breakers with Digitrip RMS 1150/1150i trip unit typical instantaneous
time/phase current characteristic curve (I)
EATON www.eaton.com 11
Technical Data TD01901001E Magnum DS metal-enclosed
Effective November 2017 low-voltage switchgear
.06
.0 7
.08
.0 5
.0 9
.1
.4
.5
.7
.8
.3
.6
.2
.9
.8
.2
.4
.6
.7
.9
.3
.5
3
5
6
2
4
1
7
8
9
2
10
9
4
8
3
5
6
7
10
10000 10000
2 HOURS
9000 9000
2 HOURS
1 HOUR
1 HOUR
4000 4000
Notes:
1. The end of the curve is determined by the interrupting rating of the
3000 3000
circuit breaker.
2. For phase current time/current curves, see curves 70C1031 through
70C1040.
2000 2000
3. The curve is shown as a multiple of the Rating Plug (In).
4. The ground fault settings have conventional 100% ± 10% as their
pick-up points.
5. Except as noted, tolerances on current levels are ±10% of values shown
in chart.
1000 6. The ground fault pickup is limited to 1200 A setting for the Digitrip 1150 1000
900 900
unit. The Digitrip 1150i unit only has a minimum earth pickup setting
800 800
700
starting at 0.1 x In. 700
7. With zone interlocking on ground fault utilized and no restraining signal,
600 the minimum time band (FLAT) applies regardless of setting. 600
500 8. Total clearing times shown include the response time of the trip unit, 500
the breaker opening, and the interruption of the current.
400 400
9. Ground Slope: FLAT
Tolerance is +0 / –80 ms except
300 0.10s setting band is 0.06 to 0.13 300
0.20s setting band is 0.15 to 0.22
10. Ground Slope: I2T
200 I2T slope flattens out at 0.625x In for top of band with FLAT time 200
minimum value prevailing for bottom of band.
Curve Trip Equation: Trip = (GROUND TIME) x 0.39 / I2 (top)
Curve Trip Equation: Trip = (GROUND TIME) x 0.39 / In2) * 0.70 (bottom)
The above equations indicate tolerance is +0 / –30% for all
100 settings except: 100
90 0.10s is +30% –25% 90
80 80
1 MINUTE
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 Available GND PU setting Available GND 6
5 0.25to 1. 0x In ±10% PU Setting 0.25 to 5
with steps of 0.01. 1.0x In ±10% with
4 4
See Note 6. steps of 0.01.
3
See Note 6. 3
2 2
Break point at
TIME IN SECONDS
TIME IN SECONDS
0.625x In to FLAT
1 1
.9 .9
.8 Max clearing .8
.7 time .7
.6 .6
.5 0.50s 0.50s
See Notes .5
9 and 10.
.4 .4
.3 .3
.2 .2
Available FLAT response
GROUND TIME
0.1 to 0.5 seconds 0.10s
with 0.05s increments
.1 .1
.09 .09
.08 .08
.07 Available .07
.06 I2T response .06
.05 GROUND TIME .05
See Notes 7, 9.
.02 .02
.01 .01
.09
.07
.06
.08
.05
.4
.5
.7
.8
.1
.3
.6
.2
.9
5
6
.8
2
.2
.4
.6
.7
.9
1
7
8
9
.3
.5
2
10
9
4
8
3
5
6
7
10
70C1041
Figure 7. Magnum DS circuit breakers with Digitrip RMS 1150/1150i trip unit typical ground time/phase current
characteristic curve (G)
12 EATON www.eaton.com
Magnum DS metal-enclosed Technical Data TD01901001E
low-voltage switchgear Effective November 2017
EATON www.eaton.com 13
Technical Data TD01901001E Magnum DS metal-enclosed
Effective November 2017 low-voltage switchgear
14 EATON www.eaton.com
Magnum DS metal-enclosed Technical Data TD01901001E
low-voltage switchgear Effective November 2017
EATON www.eaton.com 15
Technical Data TD01901001E Magnum DS metal-enclosed
Effective November 2017 low-voltage switchgear
16 EATON www.eaton.com
Magnum DS metal-enclosed Technical Data TD01901001E
low-voltage switchgear Effective November 2017
EATON www.eaton.com 17
Technical Data TD01901001E Magnum DS metal-enclosed
Effective November 2017 low-voltage switchgear
Blown fuse
18 EATON www.eaton.com
Magnum DS metal-enclosed Technical Data TD01901001E
low-voltage switchgear Effective November 2017
Need for ground fault protection Ground fault protection application and coordination
If the magnitude of all ground currents would be large enough to In all power systems, continuity of service is very important. For
operate the short delay or instantaneous elements of the phase reliable service continuity, selective tripping is applied between
overcurrent trip devices, there would be no need for separate main, tie, and feeder breakers, and downstream protecting devices,
ground fault protection on solidly grounded systems. Unfortunately, for phase-to-phase faults. Similar selective tripping is desirable when
because low magnitude ground currents are quite common, this is breakers trip on grounds. The application of ground protection only to
not the case. Low level ground currents can exist if the ground is in main breakers may ensure good ground protection. However, it will
the winding of a motor or a transformer, or if it is a high impedance not provide good service continuity because the main breaker will
ground. Low level ground currents may also be due to an arcing trip on grounds that should have been cleared by feeder breakers.
type ground. The arcing type grounds are the source of the most For proper protection and for good service continuity, main, tie and
severe damages to electrical equipment. The lower limit of the feeder breakers all should be equipped with ground fault protection.
arcing ground currents is unpredictable and the magnitude may be In view of the above, it is evident that properly applied ground
considerably below the setting of the breaker phase overcurrent protection requires ground elements as far down the system to
trip devices. It is for this reason that the National Electrical Code, the loads as practical. For best results, downstream molded case
and UL, require ground fault protection for all service disconnect breakers should have individual ground protection. This would result
breakers rated 1000 A and greater, applied on systems with greater in excellent ground protection because ground elements of Magnum
than 150 V line-to-ground. DS and downstream breakers having similar tripping characteristics
Because the breaker phase overcurrent trip devices cannot provide can be coordinated.
sensitive enough protection against low magnitude ground faults, Depending on the sensitivity of the ground fault protection method
there is a need for an additional protective device. This additional applied, coordination between Magnum DS breaker ground
device is not to operate on normal overloads and it is to be sensitive elements and downstream branch circuit fuses is sometimes
and fast enough to protect against low magnitude grounds. It is also impractical. This is due to the basic fact that the blowing of one
important that this additional ground protecting device be simple phase fuse will not clear a ground on a three-phase system. The
and reliable. If the Magnum DS breaker solid-state tripping system other two-phase fuses will let the load “single-phase,” and also
including an optional “ground element” is selected, good ground continue to feed the ground through the load, as shown in
fault protection will be ensured. Diagram 5 in Figure 12.
The ground element High resistance grounding
The ground element of the solid-state trip unit is in addition to Where continuity of service is a high priority, high resistance
the usual phase protection. The ground element has adjustable grounding can add the safety of a grounded system while minimizing
pickup with calibrated marks as shown in Table 8 and Table 9 and the risk of service interruptions due to grounds. The concept is a
adjustable time delay. The input current to the trip unit can simple one: provide a path for ground current via a resistance that
be provided by: limits the current magnitude, and monitor to determine when an
A. Residual connection of phase sensors, with the residual circuit abnormal condition exists.
connected to the ground element terminals. This is the Magnum The ground current path is provided at the point where the service
DS low-voltage switchgear standard ground protection system begins, by placing resistance in the connection from system neutral
for three-wire systems. On four-wire systems, standard ground to ground. Control equipment continuously measures ground
fault protection includes a fourth “neutral sensor.” It is connected current. A relay detects when the current exceeds a predetermined
to vectorally subtract from the residual current of the phase level. An alarm alerts building personnel that a ground exists. The
sensors. Its only function is to sense neutral currents. It does system has built-in fault tracing means to assist in finding the source
not sense ground current. These systems produce pickup values of the ground. An integral transformer provides control power from
as shown in Table 8. the primary source.
B. External ground sensing current transformers connected to
600 V (maximum) delta systems
the ground element terminals. This means that this external
ground sensor will trip the breaker whenever its secondary To add high resistance grounding to an ungrounded delta-connected
output current exceeds the values shown in Table 9. Tripping system, a neutral point must be created. Three single-phase
is independent of phase currents. The lower the CT ratio, the transformers can be interconnected in a zigzag or wye-broken delta
more sensitive the ground fault protection. configuration to provide such a neutral point. The transformers and
grounding resistors are chosen to limit the ground current to a
maximum value of 5 A.
Note: The neutral point may not be used to serve phase-to-neutral loads. Also,
this technique may be applied on wye-connected sources when the neutral
point is not conveniently accessible from the service entrance location.
EATON www.eaton.com 19
Technical Data TD01901001E Magnum DS metal-enclosed
Effective November 2017 low-voltage switchgear
20 EATON www.eaton.com
Magnum DS metal-enclosed Technical Data TD01901001E
low-voltage switchgear Effective November 2017
EATON www.eaton.com 21
Technical Data TD01901001E Magnum DS metal-enclosed
Effective November 2017 low-voltage switchgear
To distribution equipment
To distribution equipment
A B C
N A B C 1 2 3 G R W
CLF
Control
CLF
circuit
N 1 2 3 G R W CLF
CLF
AM Control
CLF Zigzag
circuit connected
CLF grounding
transformers
AM Artificial
neutral
59N Pulser Grounding Test
resistor resistor resistor
59N
High-resistance
G grounding assembly High-resistance
G grounding assembly
Figure 13. Four-wire system—fault detection via current relay Figure 16. Three-wire system—zig-zag grounding transformers
fault detection via voltmeter relay
A B C
N A B C 1 2 3 G R W
CLF
N 1 2 3 G R W Control
CLF
circuit
CLF
CLF
AM Control
CLF circuit
CLF
Grounding
Wye-broken
delta
resistor
resistor
Pulser
connected
grounding
59N Pulser Grounding Test transformers
resistor resistor resistor
Artificial Test
AM 51N neutral resistor
High-resistance
G grounding assembly High-resistance
G grounding assembly
Figure 14. Four-wire system—fault detection via voltmeter relay Figure 17. Three-wire system—wye-broken delta grounding
transformers fault detection via current relay
To distribution equipment
To distribution equipment
A B C
A B C
1 2 3 G R W
1 2 3 G R W
CLF
Control
CLF
circuit CLF
CLF Control
CLF
circuit
CLF
Zigzag
connected
grounding
transformers
Grounding
Wye-broken
delta
resistor
resistor
Pulser
High-resistance
High-resistance G grounding assembly
G grounding assembly
Figure 15. Three-wire system—zig-zag grounding transformers Figure 18. Three-wire system—wye-broken delta grounding
fault detection via current relay transformers fault detection via voltmeter relay
22 EATON www.eaton.com
Magnum DS metal-enclosed Technical Data TD01901001E
low-voltage switchgear Effective November 2017
Source Jumper
ØA ØB ØC ØN
ØA ØB ØC ØN
BKR
Trip secondary
BKR unit block
Trip secondary
unit block SGF B6
SGF B6 ZC B7
ZC B7 A
S ensors B
A
C
S ensors B
C N1 N1 B5
N1 N1 B5 N2 N2 B4
N2 N2 B4
X
X
Neutral
in four-wire system
Neutral sensor only
in four-wire system (Zero sequence sensor polarity arbitrary)
Load
Figure 19. Residual main and feeder breaker Figure 20. Zero sequence feeder breaker
Apply in four-wire systems for main breaker only when no other grounded sources are connected to
the same system.
Jumper
Note: For double-ended secondary unit substations, ground fault protection
should be as indicated in Figure 21 and Figure 22; however, for this type ØA ØB ØC
of application, the Eaton business should be consulted for the actual bill of
materials to be used. The application becomes rather complex if single-phase BKR
to neutral loads are being served. Trip secondary
unit block
SGF B6
ZC B7
A
S ensors B
C
N1 N1 B5
N2 N2 B4
Neutral
EATON www.eaton.com 23
Technical Data TD01901001E Magnum DS metal-enclosed
Effective November 2017 low-voltage switchgear
B B
B B
T1 T2
T1 T2
A C A C A A
C C
C C
C C
52-2 52-1 52-2
52-1
B B
B B A A
A A
N1 N1 N1 N1
N2 N2
N2 N2
52-T
Bu s
#1 Bus # 2
52-T
A
B
Bus #1 Bus # 2
N2
neutral neutral
B
N1
N1
A
C
connection connectio n
N2
C * *
52-T 52-T
B C
* 33T
A
N1 B
A
N2
X
X
N1
N2
Figure 22. Three-wire double-ended unit substation Figure 23. Four-wire double-ended unit substation
0.35 Sec.
GF trip unit
TI E
GF trip unit
24 EATON www.eaton.com
Magnum DS metal-enclosed Technical Data TD01901001E
low-voltage switchgear Effective November 2017
Table 13. Application of Magnum DS power circuit breakers with standard three-phase transformers—
fluid filled and ventilated dry types
Secondary short-circuit currents Minimum size breakers
Transformer base (100%) rating rms symmetrical amperes for selective trip systems
kVA and Maximum short- Through
percent circuit kVA available transformer Motor Main breaker Feeder breaker Feeder breaker
impedance Amperes from primary system only contribution Combined short delay trip short delay trip instantaneous trip
208 V three-phase—50% motor load
300 83 50,000 14,900 1700 16,600 MDS-616 MDS-408 MDS-408
5.0% 100,000 15,700 17,400 MDS-408 MDS-408
150,000 16,000 17,700 MDS-408 MDS-408
250,000 16,300 18,000 MDS-408 MDS-408
500,000 16,500 18,200 MDS-408 MDS-408
Unlimited 16,700 18,400 MDS-408 MDS-408
500 1389 50,000 23,100 2800 25,900 MDS-616 MDS-408 MDS-408
5.0% 100,000 25,200 28,000 MDS-408 MDS-408
150,000 26,000 28,800 MDS-408 MDS-408
250,000 26,700 29,500 MDS-408 MDS-408
500,000 27,200 30,000 MDS-408 MDS-408
Unlimited 27,800 30,600 MDS-408 MDS-408
750 2083 50,000 28,700 4200 32,900 MDS-632 MDS-408 MDS-408
5.75% 100,000 32,000 36,200 MDS-408 MDS-408
150,000 33,300 37,500 MDS-408 MDS-408
250,000 34,400 38,600 MDS-608 MDS-408
500,000 35,200 39,400 MDS-608 MDS-408
Unlimited 36,200 40,400 MDS-608 MDS-408
1000 2778 50,000 35,900 5600 41,500 MDS-632 MDS-408 MDS-408
5.75% 100,000 41,200 46,800 MDS-608 MDS-608
150,000 43,300 48,900 MDS-608 MDS-608
250,000 45,200 50,800 MDS-608 MDS-608
500,000 46,700 52,300 MDS-608 MDS-608
Unlimited 48,300 53,900 MDS-608 MDS-608
240 V three-phase—100% motor load
300 722 50,000 12,900 2900 15,800 MDS-408 MDS-408 MDS-408
5.0% 100,000 13,600 16,500 MDS-408 MDS-408
150,000 13,900 16,800 MDS-408 MDS-408
250,000 14,100 17,000 MDS-408 MDS-408
500,000 14,300 17,200 MDS-408 MDS-408
Unlimited 14,400 17,300 MDS-408 MDS-408
500 1203 50,000 20,000 4800 24,800 MDS-616 MDS-408 MDS-08
5.0% 100,000 21,900 26,700 MDS-408 MDS-408
150,000 22,500 27,300 MDS-408 MDS-408
250,000 23,100 27,900 MDS-408 MDS-408
500,000 23,600 28,400 MDS-408 MDS-408
Unlimited 24,100 28,900 MDS-408 MDS-408
750 1804 50,000 24,900 7200 32,100 MDS-620 MDS-408 MDS-408
5.75% 100,000 27,800 35,000 MDS-408 MDS-408
150,000 28,900 36,100 MDS-408 MDS-408
250,000 29,800 37,000 MDS-408 MDS-408
500,000 30,600 37,800 MDS-408 MDS-408
Unlimited 31,400 38,600 MDS-408 MDS-408
1000 2406 50,000 31,000 9600 40,600 MDS-632 MDS-408 MDS-408
5.75% 100,000 35,600 45,200 MDS-608 MDS-608
150,000 37,500 47,100 MDS-608 MDS-608
250,000 39,100 48,700 MDS-608 MDS-608
500,000 40,400 50,000 MDS-608 MDS-608
Unlimited 41,800 51,400 MDS-608 MDS-608
At transformer self-cooled rating.
Next larger frame size main breaker may be required for 55/65 °C rise and/or forced air-cooled (FA) transformer. Check transformer secondary ampere rating.
EATON www.eaton.com 25
Technical Data TD01901001E Magnum DS metal-enclosed
Effective November 2017 low-voltage switchgear
Table 13. Application of Magnum DS power circuit breakers with standard three-phase transformers—
fluid filled and ventilated dry types (continued)
Secondary short-circuit currents Minimum size breakers
Transformer base (100%) rating rms symmetrical amperes for selective trip systems
kVA and Maximum short- Through
percent circuit kVA available transformer Motor Main breaker Feeder breaker Feeder breaker
impedance Amperes from primary system only contribution Combined short delay trip short delay trip instantaneous trip
480 V three-phase—100% motor load
500 601 50,000 10,000 2400 12,400 MDS-408 MDS-408 MDS-408
5–0% 100,000 10,900 13,300 MDS-408 MDS-408
150,000 11,300 13,700 MDS-408 MDS-408
250,000 11,600 14,000 MDS-408 MDS-408
500,000 11,800 14,200 MDS-408 MDS-408
Unlimited 12,000 14,400 MDS-408 MDS-408
750 902 50,000 12,400 3600 16,000 MDS-616 MDS-408 MDS-408
5.75% 100,000 13,900 17,500 MDS-408 MDS-408
150,000 14,400 18,000 MDS-408 MDS-408
250,000 14,900 18,500 MDS-408 MDS-408
500,000 15,300 18,900 MDS-408 MDS-408
Unlimited 15,700 19,300 MDS-408 MDS-408
1000 1203 50,000 15,500 4800 20,300 MDS-616 MDS-408 MDS-408
5.75% 100,000 17,800 22,600 MDS-408 MDS-408
150,000 18,700 23,500 MDS-408 MDS-408
250,000 19,600 24,400 MDS-408 MDS-408
500,000 20,200 25,000 MDS-408 MDS-408
Unlimited 20,900 25,700 MDS-408 MDS-408
1500 1804 50,000 20,600 7200 27,800 MDS-620 MDS-408 MDS-408
5.75% 100,000 24,900 32,100 MDS-408 MDS-408
150,000 26,700 33,900 MDS-408 MDS-408
250,000 28,400 35,600 MDS-408 MDS-408
500,000 29,800 37,000 MDS-408 MDS-408
Unlimited 31,400 38,600 MDS-408 MDS-408
2000 2406 50,000 24,700 9600 34,300 MDS-632 MDS-408 MDS-408
5.75% 100,000 31,000 40,600 MDS-408 MDS-408
150,000 34,000 43,600 MDS-608 MDS-608
250,000 36,700 46,300 MDS-608 MDS-608
500,000 39,100 48,700 MDS-608 MDS-608
Unlimited 41,800 51,400 MDS-608 MDS-608
2500 3008 50,000 28,000 12000 40,000 MDS-632 MDS-408 MDS-408
5.75% 100,000 36,500 48,500 MDS-608 MDS-608
150,000 40,500 52,500 MDS-608 MDS-608
250,000 44,600 56,600 MDS-608 MDS-608
500,000 48,100 60,100 MDS-608 MDS-608
Unlimited 52,300 64,300 MDS-608 MDS-608
3000 3609 50,000 30,700 14000 44,700 MDS-840 MDS-608 MDS-608
5.75% 100,000 41,200 55,200 MDS-608 MDS-608
150,000 46,600 60,600 MDS-608 MDS-608
250,000 51,900 65,900 MDS-808 MDS-808
500,000 56,800 70,800 MDS-808 MDS-808
Unlimited 62,800 76,800 MDS-808 MDS-808
3750 4511 50,000 34,000 18000 52,000 MDS-850 MDS-608 MDS-608
5.75% 100,000 47,500 65,500 MDS-808 MDS-808
150,000 54,700 72,700 MDS-808 MDS-808
250,000 62,200 80,200 MDS-808 MDS-808
500,000 69,400 87,400 MDS-L08 MDS-C08
Unlimited 78,500 96,500 MDS-L08 MDS-C08
At transformer self-cooled rating.
Next larger frame size main breaker may be required for 55/65 °C rise and/or forced air-cooled (FA) transformer. Check transformer secondary ampere rating.
26 EATON www.eaton.com
Magnum DS metal-enclosed Technical Data TD01901001E
low-voltage switchgear Effective November 2017
Table 13. Application of Magnum DS power circuit breakers with standard three-phase transformers—
fluid filled and ventilated dry types (continued)
Secondary short-circuit currents Minimum size breakers
Transformer base (100%) rating rms symmetrical amperes for selective trip systems
kVA and Maximum short- Through
percent circuit kVA available transformer Motor Main breaker Feeder breaker Feeder breaker
impedance Amperes from primary system only contribution Combined short delay trip short delay trip instantaneous trip
600 V three-phase—100% motor load
500 481 50,000 8,000 1900 9,900 MDS-408 MDS-408 MDS-408
5.0% 100,000 8,700 10,600 MDS-408 MDS-408
150,000 9,000 10,900 MDS-408 MDS-408
250,000 9,300 11,200 MDS-408 MDS-408
500,000 9,400 11,300 MDS-408 MDS-408
Unlimited 9,600 11,500 MDS-408 MDS-408
750 722 50,000 10,000 2900 12,900 MDS-408 MDS-408 MDS-408
5.75% 100,000 11,100 14,000 MDS-408 MDS-408
150,000 11,600 14,500 MDS-408 MDS-408
250,000 11,900 14,800 MDS-408 MDS-408
500,000 12,200 15,100 MDS-408 MDS-408
Unlimited 12,600 15,500 MDS-408 MDS-408
1000 962 50,000 12,400 3900 16,300 MDS-616 MDS-408 MDS-408
5.75% 100,000 14,300 18,200 MDS-408 MDS-408
150,000 15,000 18,900 MDS-408 MDS-408
250,000 15,600 19,500 MDS-408 MDS-408
500,000 16,200 20,100 MDS-408 MDS-408
Unlimited 16,700 20,600 MDS-408 MDS-408
1500 1443 50,000 16,500 5800 22,300 MDS-616 MDS-408 MDS-408
5.75% 100,000 20,000 25,800 MDS-408 MDS-408
150,000 21,400 27,200 MDS-408 MDS-408
250,000 22,700 28,500 MDS-408 MDS-408
500,000 23,900 29,700 MDS-408 MDS-408
Unlimited 25,100 30,900 MDS-408 MDS-408
2000 1924 50,000 19,700 7700 27,400 MDS-620 MDS-408 MDS-408
5.75% 100,000 24,800 32,500 MDS-408 MDS-408
150,000 27,200 34,900 MDS-408 MDS-408
250,000 29,400 37,100 MDS-408 MDS-408
500,000 31,300 39,000 MDS-408 MDS-408
Unlimited 33,500 41,200 MDS-408 MDS-408
2500 2406 50,000 22,400 9600 32,000 MDS-632 MDS-408 MDS-408
5.75% 100,000 29,200 38,800 MDS-408 MDS-408
150,000 32,400 42,000 MDS-408 MDS-408
250,000 35,600 45,200 MDS-608 MDS-608
500,000 38,500 48,100 MDS-608 MDS-608
Unlimited 41,800 51,400 MDS-608 MDS-608
3000 2886 50,000 24,600 11500 36,100 MDS-632 MDS-408 MDS-408
5.75% 100,000 33,000 44,500 MDS-608 MDS-608
150,000 37,300 48,800 MDS-608 MDS-608
250,000 41,500 53,000 MDS-608 MDS-608
500,000 45,500 57,000 MDS-608 MDS-608
Unlimited 50,200 61,700 MDS-608 MDS-608
3750 3608 50,000 27,200 14400 41,600 MDS-840 MDS-408 MDS-408
5.75% 100,000 38,000 52,400 MDS-608 MDS-608
150,000 43,700 58,100 MDS-608 MDS-608
250,000 49,800 64,200 MDS-608 MDS-608
500,000 55,500 69,900 MDS-808 MDS-808
Unlimited 62,800 77,200 MDS-808 MDS-808
At transformer self-cooled rating.
Next larger frame size main breaker may be required for 55/65 °C rise and/or forced air-cooled (FA) transformer. Check transformer secondary ampere rating.
EATON www.eaton.com 27
Technical Data TD01901001E Magnum DS metal-enclosed
Effective November 2017 low-voltage switchgear
Lifting plate
Metal-enclosed “shipping
split” terminal blocks
Optional “top-of-gear”
breaker lifter
4.10 (104)
99
(2515)
92
(2337)
Horizontal cross bus area
Ground
bus
20.28
(515)
ì Dî 25.63
(651)
2A97855
28 EATON www.eaton.com
Magnum DS metal-enclosed Technical Data TD01901001E
low-voltage switchgear Effective November 2017
44.00
(1117.6)
W 3.00 16.00 16.00
3.00 3.00 Provisions (76.2) (406.4) (406.4)
FC (76.2) (76.2) for 0.50 F FC
hardware Provisions 3.38
for .50 hardware 4.63 (85.9)
3.38
Front (85.9) Front Front (117.6)
5.38 5.38
(136.7) (136.7) Bottom
Bottom control Bottom
control 3.50 4.25
3.50 conduit control (108.0)
(88.9) conduit (88.9) conduit area
21.50 area 21.50
21.50 area
(546.1) 0.65 (546.1)
(546.1) 0.65 0.65
(16.5) 3.50 3.50 (16.5)
(16.5) 3.50 (88.9) (88.9)
(88.9) 3.60 3.60 31.18
3.60 31.18 (91.4) (91.4) (792.0)
(91.4) (792.0)
6.00
(152.4)
Top 1.03 1.03
(26.2) Top Top (26.2)
1.03 control 3.60 control 3.60
(26.2) control
3.60 conduit (91.4) 3.00 conduit conduit 3.00 (91.4)
(91.4) 3.00 area (76.2) area area (76.2)
(76.2) D
3.00 D 1.50 1.50
1.50 (76.2) (38.1) (38.1)
(38.1) 3.00
1.50 (76.2)
(38.1)
6.00
(152.4)
Power A
conduit A
area Power conduit area
CC
CC
1.38
(35.1)
1.38
(35.1) 3.00 16.00 16.00 3.00
(76.2) (406.4) (406.4) (76.2)
3.00 3.00
(76.2) (76.2) 6.00
(152.4)
Floor plan—22-inch (559 mm) and Floor plan—44-inch (1118 mm) wide structures
30-inch (762 mm) wide structures
EATON www.eaton.com 29
Technical Data TD01901001E Magnum DS metal-enclosed
Effective November 2017 low-voltage switchgear
Center of gravity location Table 18. Magnum DS indoor switchgear structure approximate
weights (less breakers)
For seismic calculations, the following dimensions should be used to
locate the center of gravity for indoor Magnum DS switchgear. Structure depth in inches (mm)
60 66 72 78 84 90
Structure (1524.0) (1676.4) (1828.8) (1981.2) (2133.6) (2286.0)
Table 15. Center of gravity location type
inches (mm) Lb (kg)
Axis Position
22 (558.8) 1250 1300 1350 1400 1450 1500
X (vertical) 60 inches (1524 mm) (Breaker (568) (590) (613) (636) (658) (681)
Y (left-to-right) Center of lineup structure)
Z (from the front) 26 inches (660 mm) 30 (762.0) 1700 1770 1840 1900 1980 2050
(Breaker (772) (804) (835) (863) (899) (931)
structure)
44 (1117.6) 2500 2600 2700 2800 2900 3000
Table 16. Heat loss data (Breaker (1135) (1180) (1226) (1271) (1317) 1362)
Estimated heat loss per breaker (watts)
structure)
Breaker frame Fixed mounting Drawout mounting 22 (558.8) 950 1000 1050 1100 1150 1200
(Auxiliary (431) (454) (477) (499) (522) 545)
800 60 150 structure)
1600 150 329 12 (304.8) 475 500 525 550 575 600
2000 172 374 (Transition) (216) (227) (238) (250) (261) 272)
3200 359 719 22 (558.8) 950 1000 1050 1100 1150 1200
(Transition) (431) (454) (477) (499) (522) 545)
4000 374 749
38 (965.2) 1600 1625 1650 1675 1700 1725
5000 400 1000 (Utility) (726) (738) (749) (760) (772) 783)
6000
50 (1270.0) 1650 1675 1700 1725 1750 1775
For lower than maximum load currents, watt loss may be estimated by reducing the full load loss
(Utility) (749) (760) (772) (783) (795) (806)
by the following:
WL = (IL/IFL)2 WFL
Where:
WL = Load watts Table 19. Magnum DS breaker weights—lb (kg)
WF = Full load watts Breaker Fixed Drawout
IL = Actual load current
IFL = Full load current MDS-408 110 (50) 130 (59)
Contact Eaton. MDS-608 110 (50) 130 (59)
MDS-808 120 (55) 145 (66)
Table 17. Estimated heat loss (watts) per structure MDS-C08 120 (55) 145 (66)
Loss is based on fully loaded vertical and cross bus rating MDS-616 110 (50) 130 (59)
in a structure as given below. MDS-816 120 (55) 145 (66)
Rating Vertical bus Cross bus MDS-C16 120 (55) 145 (66)
2000 410 288 MDS-620 120 (55) 145 (66)
3200 1623 1163 MDS-820 120 (55) 145 (66)
4000 1097 1169 MDS-C20 120 (55) 145 (66)
5000 1410 886 MDS-632 135 (61) 175 (80)
6000 1265 MDS-832 135 (61) 175 (80)
8000 — MDS-C32 135 (61) 175 (80)
10,000 — MDS-840 250 (114) 310 (141)
For lower than maximum load currents, watt loss may be estimated by reducing the full load loss
MDS-C40 250 (114) 310 (141)
by the following: MDS-850 250 (114) 310 (141)
WL = (IL/IFL)2 WFL MDS-C50 250 (114) 310 (141)
Where:
WL = Load watts MDS-860 250 (114) 310 (141)
WF = Full load watts MDS-C60 250 (114) 310 (141)
IL = Actual load current
IFL = Full load current Manually or electrically operated. For approximate impact weight, add 50% of breaker weight.
Contact Eaton.
30 EATON www.eaton.com
Magnum DS metal-enclosed Technical Data TD01901001E
low-voltage switchgear Effective November 2017
17.13 Structure
(435.1) width 109.03
5.03 Roof Rear of (2769.4)
4.00 20.00 20.00 45.66 (127.8) C 0.95
2.50 (508.0) (508.0) (1159.8) Rear of base inner to floor
(63.5) (101.6) (24.1)
B structure
( )
119.98 22.00-inch width = 21.4 to rear frame (543.6)
(3047.5) O.S. of outdoor 30.00-inch width = 29.4 to rear frame (746.8)
Overall depth end sheet A 38.00-inch width = 37.4 to rear frame (950.0)
See Figure 1 above for 50.00-inch width = 49.4 to rear frame (1254.8)
18.44 Bus opening (from base) Transformer
bus duct orientation info. (468.4) 55.00-inch width = 54.4 to rear frame (1381.8)
flange
3.89 Outdoor 36.00
0.61 (914.4)
(98.8) (15.5) roof sheet
2.30 22.00 14.00
(58.4) 28.59 111.48 A
(726.2) 30.21 (558.8) (355.6)
109.03 (767.3) (2831.6)
(From base) Overall
(2769.4) (Opening 20.74
width) height 30.89 26.97 (526.8)
105.06 5.75 5.75 (784.6) (685.0) CL
CL
(2668.5) (146.1) (146.1) CL
Throat 72.00
(1828.8) Front of
CL opening CL
B 33.45 & TXF Switchgear outdoor
(849.6) See base
depth Figure 1
(Door Switchgear yhroat
width) 4.00 (shipped disassembled) Door
2.00
(50.8) (101.6) Door swing swing
26.00 43.38 42.00
(660.4) 33.45 33.45
(1101.9) (849.6) (1066.8)
(Aisle width) 39.66 (clear (849.6)
117.08 (1007.4)
(2973.8) width)
Side view
Top view
Front view
EATON www.eaton.com 31
Technical Data TD01901001E Magnum DS metal-enclosed
Effective November 2017 low-voltage switchgear
17.13 Structure
(435.1) width 109.03
Roof Rear of (2769.4)
4.00 20.00 20.00 0.95
2.50 (508.0) (508.0) Rear of base C inner to Floor
(63.5) (101.6) (24.1)
B structure
3.06 Control wire 2.00 18.44 16.85
(77.7) 26.94 opening (50.8) 30.00 (468.4) (428.0) 25.52
(684.3) (762.0) (648.2)
3.50 x 3.50 C
Opening Unit A A L
(88.9 x 88.9)
0.95
3.06 17.83 B (24.1)
(77.7) 25.44 (452.9) Section B-B
(646.2) Bottom
40.94 44.00 CL Structure
conduit (1117.6) B C
(1039.9) width
Opening space Unit
3.93 Top View 18.00 13.35 9.00
(99.8) (457.2) (339.1) (228.6)
Bus duct
chimney and cover 22.00 17.35 11.00
3.06 18.94 22.00 (558.8) (440.7) (279.4)
(77.7) (481.1) (558.8) 0.95 0.95 30.00 25.35 15.00
Opening Unit (24.1) (24.1) (762.0) (644.0) (381.0)
B 38.00 33.35 19.00
1.50 Section A-A (965.2) (847.1) (482.6)
Lifting angle (38.1) 44.00 39.35 22.00
Foundation tie down (1117.6) (999.5) (558.8)
(for seismic only) 50.00 45.35 25.00
Floor plan Figure 1 (1270.0) (1151.9) (635.0)
Front view
32 EATON www.eaton.com
Magnum DS metal-enclosed Technical Data TD01901001E
low-voltage switchgear Effective November 2017
Integral base
The rugged formed base greatly increases the rigidity of the
structure and reduces the possibility of damage during the
installation of the equipment and is suitable for rolling, jacking
and handling. A lifting angle is permanently welded into the bus
compartment structure for increased strength.
Rear cover/doors
In Magnum DS switchgear standard rear covers with captive
Through the door design
hardware are the bolt-on type. They are split into two sections to
facilitate handling during removal and installation. Optional rear doors
are also available. Four-position drawout
Breakers can be in connected, test, disconnected or removed
Through-the-door design position. The breaker compartment door can be closed in the
The following functions may be performed without the need to open connected, test and disconnected positions.
the circuit breaker door: levering the breaker between positions,
operate manual charging system and view the spring charge status Closing spring automatic discharge
flag, close and open breaker, view and adjust trip unit and read the Mechanical interlocking automatically discharges the closing springs
breaker rating nameplate. when the breaker is removed from its compartment.
Breaker inspection
When withdrawn on the rails, breaker is completely accessible for
visual inspection; tilting is not necessary. The rails are permanent
parts of every breaker compartment. Interference interlocks are
supplied on breakers and in compartments where the compartments
are of the same physical size to ensure an incorrect breaker cannot
be inserted.
EATON www.eaton.com 33
Technical Data TD01901001E Magnum DS metal-enclosed
Effective November 2017 low-voltage switchgear
Bus bracing
Unique vertical bus configuration provides an optional industry
leading short circuit withstand rating of 200,000 A without the need
for preceding current limiting fuses. Standard bracing is 100,000 A.
The “U” shaped bar is the heart of the Magnum DS vertical bus.
This configuration provides a much higher mechanical strength. To
further demonstrate the strength and rigidity of this bus system, it
has been verified through testing to withstand 85,000 A short circuit
for a full 60 cycles.
Silver plating
Bolted, silver-plated copper main buses are standard. The plating
is over the entire length of the bar, not just at the joints. Optional
tin-plated copper buses are available.
Bus joints
All joints are bolted and secured with Belleville-type spring washers
for maximum joint integrity. These washers reduce the potential
of joint hardware loosening during the change of joint temperature Optional insulated bus
associated with variations of the loads.
Barriers
Full neutral
Optional grounded metal barriers isolate the main bus and
For four-wire applications, the neutral bus is rated 100% of main bus connections from the cable compartment providing added safety to
rating as a standard, up to a maximum ampere rating of 6000 A. the workers while reducing the potential of objects falling into the
bus compartment.
Ground
A ground bus is furnished the full length of the switchgear assembly Wiring
and is fitted with terminals for purchaser’s connections. Cable Compartment
Glass reinforced polyester and The cable compartment gives ample room for terminating the
Ultramid姞 stand-off insulation system power cables. Removable top roof sheets allow for easy conduit
hub installation. The floor of the cable compartment is open to allow
Glass reinforced polyester has been used on both low- and cable entry from underground duct banks. Optional floor plates are
medium-voltage switchgear for decades. By combining this industry available.
proven material with Ultramid insulation, a total system providing
exceptional mechanical and dielectric withstand strength, as well Optional grounded metal barriers isolate the main bus and
as high resistance to heat, flame, and moisture, is produced. connections from the cable compartment, as well as optional
Substantial testing to demonstrate accelerated effects of heating barriers to separate adjacent cable compartments.
and cooling on the mechanical and dielectric properties of this In addition to cable, Pow-R-Way busway and nonsegregated bus
system prove it to provide superior performance for decades of duct can be terminated in the compartment.
trouble-free operation.
Lug pad
The lugs are located on the breaker run-backs to accommodate lug
orientations at a 45° angle to reduce the bending radius of the cable
needed for making the connections, thus reducing installation and
maintenance time. Mechanical setscrew type lugs are standard.
Optional NEMA 2-hole compression lugs are available as an option.
34 EATON www.eaton.com
Magnum DS metal-enclosed Technical Data TD01901001E
low-voltage switchgear Effective November 2017
Instrumentation/metering
Flexibility
Magnum DS switchgear allows for a variety of metering options:
• Analog switchboard type meters such as ammeters, voltmeters,
watthour, power factor, etc.
• Electronic power metering such as the IQ family of analyzer,
DP-4000, etc.
• Instrument door mounted meters. For feeder circuit
instrumentation, 2% accuracy ammeters and ammeter switches
can be mounted on the secondary contact compartment door
between the breaker compartment doors. The ammeters and
switches are immediately associated with definite breaker
circuits. Other devices, such as control pushbuttons, breaker
control switches, indicating lights, and test switches can be
mounted on these panels, within space limitations.
Voltage transformers
Voltage transformers are rated 10 kV BIL and are protected by both
Control wireway primary and secondary fuses. The primary fuses are of the current
limiting type.
Control wire
Current transformers
Standard wire is Type SIS insulated stranded copper, extra flexible
Current Transformers for metering and instrumentation are mounted
No. 16 AWG minimum.
in the breaker compartments and are front accessible. Secondary
Control wire marking wiring between the current transformer and the standard shorting
terminal block is color-coded for ease of identification.
Each wire is imprinted with ink cured under ultraviolet light for
durability and for easy identification by the user. The enhanced solvent Control power transformers
resistance and durability of the aerospace grade UV cure ink has been
Control transformers are provided when required for AC control of
tested for severe environments. The imprinting is made periodically
circuit breakers, space heaters, and/or transformer fans. Like voltage
along the length of the wire, with the ends being imprinted more
transformers, they are protected by current limiting primary fuses.
frequently. The point of origin, wire designation and point of
Non-current limiting fuses are used on the secondary side to protect
destination are imprinted in the following format: <origin zone/wire
branch circuits.
name/destination zone>. Each device has a uniquely designated zone.
“<” indicates the direction of the wire origination and “>” indicates
the direction of the wire destination. As an option, wire marking can
be made utilizing sleeve type or heat shrink sleeve type.
EATON www.eaton.com 35
Technical Data TD01901001E Magnum DS metal-enclosed
Effective November 2017 low-voltage switchgear
Breaker
Contacts
The Magnum DS has silver tungsten moving contacts and silver
graphite stationary contacts. The contacts provide a long-wearing,
low-resistance joint. The contacts are protected from arcing damage
even after repeated interruptions by the “heel-toe” action which
causes the integral arcing contacts to mate before the main contacts
Devices mounted on instrument compartment door
part. The arcing contacts then part last, striking the arc away from
the main contacts.
Accessories and options
The main contacts are of the butt type and are composed of
Switchgear accessories a multiplicity of fingers to give many points of contact without
alignment being critical.
Standard accessories furnished with each Magnum DS switchgear
assembly include:
• One breaker levering crank
• Insulating covers or “boots” are furnished on live main
stationary disconnecting contacts in compartments equipped
for future breakers
• Removable cover to block opening in the door when the breaker
is temporarily removed from its compartment
36 EATON www.eaton.com
Magnum DS metal-enclosed Technical Data TD01901001E
low-voltage switchgear Effective November 2017
EATON www.eaton.com 37
Technical Data TD01901001E Magnum DS metal-enclosed
Effective November 2017 low-voltage switchgear
A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 A13 A14 A15 B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 B13 B14 B15 C1 C2 C3 C4 C5 C6
COM IN OUT
OTS OTS UVR ATR INCOM ATR INCOM Neg. Neutral Source Zone Shunt Spring Motor Cell switch contacts
close power sensor ground interlocking trip release (shown with breaker in
input input input input withdrawn position)
A16 A17 A18 A19 A20 A21 A22 A23 A24 A25 A26 A27 A28 A29 A30 B16 B17 B18 B19 B20 B21 B22 B23 B24 B25 B26 B27 B28 B29 B30 C7 C8 C9 C10 C11 C12
Spring Accessory Breaker auxiliary contacts Breaker auxiliary contacts Latch Cell switch contacts
charge bus (shown with breaker in open position) (shown with breaker in open position) check (shown with breaker in
status commun- switch withdrawn position)
ications
2A97870
38 EATON www.eaton.com
Magnum DS metal-enclosed Technical Data TD01901001E
low-voltage switchgear Effective November 2017
Typical specifications Terminal blocks with integral-type barriers shall be provided for
circuit breaker secondary circuits. The terminal blocks shall be front
General accessible through a hinged access panel above each circuit breaker.
Magnum DS indoor low-voltage metal-enclosed switchgear shall All control wiring shall be securely fastened to the switchgear
consist of a stationary structure assembly and one or more assembly without the use of adhesive wire anchors. A dedicated
removable Magnum DS power circuit breakers complete with wiring path shall be provided for purchaser’s installed control wiring.
disconnecting devices and other necessary accessories. The Non-adhesive anchors shall also be provided for anchoring
switchgear shall be suitable for 600 V maximum service and of purchaser’s installed wiring.
shall withstand a 2200 Vac dielectric test in accordance with
ANSI standards. It shall be designed, manufactured and tested in Disconnecting devices
accordance with the latest applicable standards of IEEE, NEMA,
ANSI, UL and CSA. Documentation of design testing shall be third- The stationary part of the primary disconnecting devices for each
party certified. circuit breaker shall consist of a set of contacts extending through a
glass polyester insulating base. Buses and outgoing cable terminals
Stationary structure shall be directly connected to them. The corresponding moving
contacts shall consist of a set of contact fingers suitably spaced on
Each steel unit forming part of the stationary assembly shall be a the circuit breaker studs. For ease of inspection and maintenance,
self-contained housing having one or more individual breaker or contact fingers shall not be a permanent part of the stationary
instrument compartments, and a rear compartment for the buses structure. In the “connected” position, these contacts shall form a
and outgoing cable connections. current-carrying bridge. The assembly shall provide a multitude of
Prying slots shall be provided on the base of the structures for ease silver-to-silver high-pressure point contacts. High uniform pressure
of positioning in equipment rooms. on each finger shall be maintained by springs. The entire assembly
shall be full floating and shall provide ample flexibility between the
A rigid integral steel base shall be provided for each section, which stationary and moving elements. Contact engagement shall be
will allow movement of shipping groups directly on rollers without maintained only in the “connected” position.
the need for a separate skid.
The secondary disconnecting devices shall consist of floating
Each circuit breaker compartment shall be equipped with primary fingers mounted on the stationary unit and automatically engages
and secondary contacts, drawout extension rails, stationary levering contacts located at the front of the compartment. The secondary
mechanism parts, and required instrument current transformers. A disconnecting contacts shall be silver-plated to ensure permanence
formed steel door, supported on concealed hinges with removable of contact. Contact engagement shall be maintained in the
pins, shall be provided for each circuit breaker compartment. “connected” and “test” positions.
Access to the integral circuit breaker control panel, including the
trip unit, shall be provided without the need to open the breaker Removable element
compartment door. Closed-door spring charging and levering
operations shall also be accomplished without the need to open The removable element shall consist of a Magnum DS power circuit
the breaker compartment door. breaker equipped with the necessary disconnecting contacts and
interlocks for drawout application. The removable element shall have
The top of the unit shall be enclosed with removable steel sheets, four position features and shall permit closing the compartment door
which include necessary hooded ventilation openings. A separate with the breaker in the “connected,” “test,” and “disconnected”
removable access panel shall be provided for drilling of control positions.
conduit hubs. A metal wireway with removable covers shall be
provided for shipping-split wiring. Pull-apart type terminal blocks Power circuit breakers
shall also be provided for rapid, error-free, shipping split assembly.
A metal-enclosed vertical wireway shall be provided for routing of The circuit breaker shall be Magnum DS, operating on the DE-ION
field installed control wiring. arc interruption principle. These breakers shall incorporate specially
designed circuit-interrupting devices that provide high interrupting
The structure shall be so designed that future additions may readily efficiency and minimize the formation of arc flame and gases.
be made at any time. The steel structure shall be thoroughly cleaned
and phosphatized prior to the application of the ANSI No. 61 finish. The primary contacts shall have an easily accessible wear indicator
to indicate main contact erosion. The breaker closing time shall be
A white, laminated, plastic engraved circuit designation nameplate no more than three cycles. Each breaker shall have three windows
shall be provided on each circuit breaker door. in the front cover to offer clear indication of trip and close electrical
accessories mounted in the breaker. The breaker shall be equipped
Buses and connections
with “DE-ION” arc chutes which effectively enclose the arcing
Each breaker circuit shall include the necessary three-phase copper contacts and confine the arc to reduce the disturbance caused
bus and connections between the source bus and one set of circuit by short-circuit interruption. Each breaker shall be equipped
breaker studs. NEMA 2-hole cable lugs, attached to silver-plated with a position indicator, mechanically connected to the circuit
copper extensions for the outgoing cables, shall be provided on the breaker mechanism.
other set of circuit breaker studs. The buses and connections shall
consist of high-conductivity (silver-plated) (tin-plated) copper bar
mounted on heavy-duty supports, and having bolted joints. All bolted
bus joints shall utilize Belleville type spring washers to maintain
maximum joint integrity through continuous thermal cycling. The
bus system shall be suitable for applications on power systems
requiring a (100) (150) (200) kA short circuit withstand rating without
upstream current limiting fuses.
EATON www.eaton.com 39
Technical Data TD01901001E Magnum DS metal-enclosed
Effective November 2017 low-voltage switchgear
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2017 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. TD01901001E / Z20126 All other trademarks are property
November 2017 of their respective owners.